| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.9 LAccepted-Finance 61 ABHAY GARH SCHEME AIR FORCE JODHPUR 342001 RAJ | JODHPUR | JODHPUR | RAJASTHAN | 342001 | L1 | Accepted-Finance LOWEST | |
| 2 | L2₹6.3 L+₹41,655 (7.03%)Rejected-Finance H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | L2 | Rejected-Finance NOT LOWEST | |
| 3 | L3₹6.4 L+₹50,250 (8.48%)Rejected-Finance | L3 | Rejected-Finance NOT LOWEST | |
| 4 | L4₹6.4 L+₹51,985 (8.77%)Rejected-Finance PAHARGANJ SECOND COLONY LAL SAGAR JODHPUR 342001 RAJ | JODHPUR | JODHPUR | RAJASTHAN | 342001 | L4 | Rejected-Finance NOT LOWEST | |
| 5 | L5₹6.6 L+₹65,630 (11.1%)Rejected-Finance | L5 | Rejected-Finance NOT LOWEST |
Tender Value
₹9.5 L
EMD Value
₹19,000
Closing Date
28 Jun 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
AGE (I) R AND D JODHPUR
AGE (I) R AND D DEFENCE LAB JODHPUR
REPAIR/MAINT AND REPLACEMENT OF LT OH LINE/LT UG CABLES AND OTHER LT RELATED WORKS IN ZONE-A AND ZONE-C AT DEFENCE LAB JODHPUR
2023_MES_601194_1
8551/E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
AGE (I) R AND D JODHPUR
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
AGE (I) R AND D JODHPUR
₹19,000
Yes
22 Mar 2024
5 Jun 2023
30 Jun 2023
5 Jun 2023
28 Jun 2023
14 Jun 2023
6 Jun 2023 - 13 Jun 2023
Amount
Disconnecting/ taking out old unserviceable LT underground cable from trenches/floor/along the pole including recoiling at site of work complete all as directed by Engr-in-charge.
M&L XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 volts grade, cross sectional area 50 sqmm. 3.5 core complete all as specified and directed by Engr-in-charge.
M&L XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 volts grade, cross sectional area 25 sqmm. 4.0 core complete all as specified and directed by Engr-in-charge.
M&L XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured heavy duty electric cable with aluminium stranded conductor 1100 volts grade, cross sectional area 240 sqmm. 3.5 core complete all as specified and directed by Engr-in-charge.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation etc or for shaft, wells, cesspots, manholes, pier holes, taking out cable, etc not exceeding 10 Sqm on plan and getting out in any type soil complete all as specified & directed by Engineer-in-Charge.
M&L sand cushioning to PVC cable with tibba sand and punning to provide required cover complete all as directed by Engineer-in-Charge. (Note:- For the purpose of payment only punned thickness will be measured)
Supply & laying 40 to 50mm thick roughly hammer dressed Jodhpur stone patti cable cover 25cm to 30cm wide and n.exc 60cm long each laid dry abutting with each other with maximum gap between adjacent slabs n.exc 10mm complete all as specified & directed by Engineer-in-Charge.
Returning, filling in, including, spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick in any soil complete all as specified & directed by Engineer-in-Charge.
Removing excavated soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed by Engineer-in-Charge.
M&L PCC (1:3:6) type C-1 using 20mm graded stone aggregate in making good the road surfaces as its original position, n. exc. 10 cm in width and setting in mortar complete all as specified and directed by engineeer-in-charge.
M&L for GI tubing of size 80mm light grade with all fittings laid in ternches for cable protection complete all as specified and directed by Engineer-in-charge.
Design , supply, erection, testing and commissioning of outdoor type LT Bus Bar Chamber box, platform mounted suitable for 3 phase 4 wire, 415 Volts AC supply and having 4 Nos steeped type Aluminium Bus Bar (32mm x 5mm) for looping & branch connection system. The chamber shall be painted with powder coated paint ( Shade- RAL- 7032/7035) after 7 tank pre-treatment of surfaces. The bus bar chamber shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The bus bar chamber shall be made out of 3.00mm thick CRCA mild steel sheet and 3.00mm thick gland plate, front door (01 layer) rear door ( 01 layer) opening facility and 4 sideslaning canopy type roof on top and mild steel channel (75 MC) base frame at bottom. the bus bar chamber shall be provided with ventilation facilty in the form of louvers for better heat dissipation including dismantling of old unserviceable existing bus bar chamber, complete all as specifed and directed. ( Note: The Bus bar chamber Box shall be designed in such a way that adequate workable space is made available inside the compartments and the sizeof the chamber shall not be less than 500mm height without base frame and canopy, 500mm width and 450mm depth)
Supply and fixing in replacement ,415V 10KA 'C' curve miniature circuit breaker (MCB) of TP 63 Amp complete all as specified.
M&L in replacement of old unsv MCCB 3 Pole,, 415Volt, 63 Amp with breaking capacity 16 KA all as specified and directed by Engr-in-charge.
M&L in replacement of old unsv MCCB 3 Pole,, 415 Volt, adjustable type, 100 Amp with breaking capacity 16 KA all as specified and directed by Engr-in-charge.
M&L in replacement of old unsv MCCB 3 Pole,, 415 Volt, adjustable type, 125 Amp with breaking capacity 16 KA all as specified and directed by Engr-in-charge.
M&L in replacement of old unsv MCCB 3 Pole,, 415 Volt, adjustable type, 160 Amp with breaking capacity 25 KA all as specified and directed by Engr-in-charge.
M&L in replacement of old unsv MCCB 3 Pole,, 415 Volt, adjustable type, 200 Amp with breaking capacity 25 KA all as specified and directed by Engr-in-charge.
M&L in replacement of old unsv MCCB 3 Pole,, 415 Volt, Fixed type, 250 Amp with breaking capacity 25 KA all as specified and directed by Engr-in-charge.
Supply and fixing MCCB 4 pole 400 Amp rotary type 415 Volt breaking capacity 36 KA including taking down old UNSV MCCB Complete all as specified and as directed by Engr-in-Charge.
Note:- Availablity of Schedule of credit as per availabilty of site, Contractor is not to claim for it during execution of work.
Shri Electrical Enterprises
vinayandsons
Shree Karni Construction
M/S SUMAN ENTERPRISES
Anil Builders
Sachiyay maa Electricals
S.G.ENGINEERING COMPANY
new india engineers
KAVYA ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .