Electrical works - Merging of class III flats at BSQ
2026_RBI_285205_1
RBI_HYD_23_07_2026
Limited
Electrical Works
Works
RBI Quarters, Begumpet
Please refer Tender documents.
1 document required · 1 mandatory
₹0
Exempted
24 Jul 2026
24 Jul 2026
31 Jul 2026
24 Jul 2026
30 Jul 2026
24 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of double door 6-way TPN MCBDB with necessary neutral link, earth link, including circuit wiring termination, internal wiring, blanking plate etc. Incomer - 63A 4P MCB- 1 nos.
Outgoing - 16A SPMCB- 8 nos.
10A SPMCB- 5 nos.
6A SPMCB- 5 nos.
The DB shall be concealed in wall by chasing with required tools and labor etc. | 3 | Nos | - | - |
| 2 | Wiring for light points using 3 X 1.5 sq. mm. 1100 volt grade multi-stranded copper conductor PVC insulated FRLS wires, partly surface/concealed in suitable size rigid, medium duty PVC conduit with required accessories like bends, tees, junction boxes etc. (concealed in wall/floors and surface on ceiling) with modular plate type switches, sockets with respective make required size mounting plate fixed on same make M.S. box concealed in wall and ceiling rose/ connector/angle holder / junction box etc. Point wiring rate shall also include necessary circuit wiring from MCBDB to main lighting switch boards in all rooms/toilet and from main lighting switch board to sub lighting switchboard in same room with 2 X 2.5 + 1 x 1.5 sq. mm. 1100v grade copper conductors FRLS PVC insulated wire and required blank plate in switchboard as directed by Bank’s Engineer. | - | - | - | - |
| 3 | Wiring as item no.2 but for one light point controlled by one 6 amp. plate type switch. | 75 | pts | - | - |
| 4 | Wiring as item no.2 but for ceiling fan point controlled by one 6 amp. plate type switch with electronic 2 modular step regulator socket type suitable for 48” ceiling fan and chandeliers | 25 | pts | - | - |
| 5 | Wiring as item no. 2 but for exhaust fan point controlled by one 6 amp. plate type switch. | 9 | pts | - | - |
| 6 | Wiring same as item no. 2 but for 6 Amp 5 pin independent plug point with 3 x 1.5 sq mm copper wire. | 18 | pts | - | - |
| 7 | Wiring for half point on lighting switch board with 6-amp switch and 6 Amp 5 pin socket including internal wiring etc. | 60 | nos | - | - |
| 8 | Wiring same as item no.2 but for call bell point with bell push and buzzer. | 3 | nos | - | - |
| 9 | Wiring for power point using 2 X 2.5 sq. mm +1x 1.5 sq. mm 1100-volt grade multi-stranded copper conductor PVC insulated FRLS wire partly surface/concealed in suitable size rigid medium duty PVC conduit with required accessories like bends, tees, junction boxes etc. in concealed manner by chasing the wall/floor with modular plate type switches, sockets with respective make required size mounting plate fixed on G.I. box concealed in wall. The wiring shall be done from MCBDB to each power point. Wiring as above for 6/16Amp socket plug point controlled by one 16 Amp type plate switch. | 42 | pts | - | - |
| 10 | Supply & Providing wiring for telephone point from Telephone tag Block at the entrance of block with two pair 0.5 mm. dia copper conductor PVC insulated FRLS PVC sheathed telephone cable in suitable size rigid, medium duty PVC conduit with required accessories like bends, tees, junction boxes etc. in concealed manner by chasing the wall/floor inside flat and in surface manner on wall inside the duct with required scaffolding / zula. Rate shall include for providing of modular RJ-11 telephone jack (single) with respective make required size mounting plate fixed on respective make GI box concealed in wall including termination of the telephone wire. | 3 | pts | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.26 MB
TenderDocument.pdf
Tender Documents • 0.70 MB
BOQ_332911.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].