Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.9 LAccepted-AOC H NO 199 W NO 6 NEAR OLD SDM OFFICE DISTT HAMIRPUR HP 177001 | HAMIRPUR | HAMIRPUR | HP | 177001 | ₹9.9 L Quoted ₹10.0 L | L1 | Accepted-AOC work awarded to M/s Sharma Elect Co. being L1 firm |
| 2 | L2₹10.5 L+₹46,420 (4.65%)Rejected-Finance | ₹10.5 L+₹46,420 (4.65%) | L2 | Rejected-Finance rejected being L2 firm |
Tender Value
₹9.9 L
EMD Value
₹19,800
Closing Date
19 Jul 2022, 10:00 amClosed
Executive Engineer, Electrical Division, HP.PWD Ma
Executive Engineer, Electrical Division, HP.PWD Mandi
Replacement of damaged cooling coil in 4 Nos. AHU existing in Hospital building at Shri lal bahadur Shastri Government Medical college and Hospital Nerchowk Distt Mandi HP
2022_PWD_62509_1
PW/MED/TA/NIT/ e-notice/22-23-2425-35 dt 30.06.22
Open Tender
Electrical Works
Item Rate
30 days
NERCHOWK
PLEASE REFER TO BID DOC
11 documents required · 11 mandatory
₹350
₹19,800
Yes
23 Nov 2022
12 Jul 2022
19 Jul 2022
12 Jul 2022
19 Jul 2022
12 Jul 2022
Amount
S/F AHU's Heating and cooling coil are generally located in the discharge-air-streem immediately down streem of the mixing plenum and filter to provide heating or cooling coil will also be used to dehumidify the air system.AHRI standared 410-Forced circulation Air- Cooling and air heating coil and ASHRE AE33-Methods of Testing Forced- circulation air-cooling,Air-Heating coils.Cooling coil there are built to be piped in a counter-flow arrangement or the air flow in the opposit direction as the chilled water CHW and/ or the referigent in OX coil for a 4- row coil , the air would pass through row 1-4 at the same time the CHW or refrigerant is flowing through row 4-1 complete with testing commissioning including copper brazing etc. as required by Engineer-in- Charge. Make should be OEM WAVES AIRCON Pvt.Ltd.
Specification of the coil
Coil Type Chilled water type (CHW) Make WAVE AIRCON
Coil Tube material CopperMakeWAVE AIRCON
Coil Tube thickness 0.4 mmss MakeWAVE AIRCON
Coil Tube size 1/2'' OD MakeWAVE AIRCON
Coil Fin material Aluminum/NO coatingMake WAVE AIRCON
Coil Fin thickness 0.13mm MakeWAVE AIRCON
Fin spacing 11-13 FPI MakeWAVE AIRCON
Coil Bonding Hydraulic/Meechanical expansioMake WAVE AIRCON
Coil end plate Galvenized MakeWAVE AIRCON
Coil Header MS Header MakeWAVE AIRCON
Factory test pressure 21 kg/sgcm. MakeWAVE AIRCON
PRICE WITH OPERATING AND PHYSICAL DETAILS OF SUPPLY OF COOLING / HEATING COILS With Drain Tray, Coil Support, Installation, Testing, Commissioning, Removing, Replacement, Header Cutting, Brazing At Site, Civil Work, Unloading & Shifting & all Other Controls)
CHW Type,Unit area flow-8500,Coil FH-24''.FL35MM,Row Deep-4,Section-2, Coil face area 18.33sqft
CHW Type,Unit area flow-16500,Coil FH-24''.FL73MM,Row Deep-4,Section-2, Coil face area 32.95sqft
CHW Type,Unit area flow-14000,Coil FH-32.5''.FL67.5MM,Row Deep-4,Section-2, Coil face area 28.13sqft
CHW Type,Unit area flow-13500,Coil FH-30''.FL65MM,Row Deep-4,Section-2, Coil face area 27.08sqft
PRAGATI ELECTRICAL AND ELECTRONIC CO
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .