Civil Works and Installation of Power Backup System at Santhigiri Ayurveda Siddha Research Centre and Skill Development Training Institute, Saket, New Delhi.
NBCC/NIT/GM-RFM/14~EWf6d186e964411040f37a978d
NBCC/NIT/GM-RFM/14
Open Tender-Domestic
Miscellaneous Services
NBCC Bhawan
₹2,950
₹28,540
28 May 2025
14 May 2025
28 May 2025
14 May 2025
28 May 2025
S. No. Description Amount (Rs.)
1 Compound Wall & Gate Work 1207418.37
2 Rain Water Harvesting System 551040.00
3 Underground Sump 254516.32
4 Power Backup System 841114.00
BOUNDARY WALL & GATE WORK
S.No. DSR No. Item Description Unit Rate Qty. Amount
Demolishing R.C.C. work manually/
by mechanical means including
stacking of steel bars and disposal of
unserviceable material within 50
metres lead as per direction of
Engineer - in- charge. Cum 3657.79 2.80 10241.81
Demolishing brick work manually/ by
mechanical means including stacking
15.7 of serviceable material and disposal
of unserviceable material within 50
metres lead as per direction of
Engineer-in-charge.
Earth work in excavation by
mechanical means (Hydraulic
excavator)/ manualmeans over areas
(exceeding 30 cm in depth, 1.5 m in
width as well as 10 sqm on plan)
including getting out and disposal of
Filling available excavated earth
(excluding rock) in trenches, plinth,
sides of foundations etc. in layers not
4 2.25 exceeding 20cm in depth,
consolidating each deposited layer
by ramming and watering, lead up Cum 201.88 59.636 12039.31568
Centering and shuttering including
strutting, propping etc. and removal
5 5.9.1 Foundations, footings, bases for columns Sqm 403.91 18.48 7464.33996
Lintels, beams, plinth beams, girders,
bressumers and cantilevers Sqm 758.49 31.00 23513.25
7 5.9.6 Columns, piers, abutments, pillars, posts and Sqm
Providing and laying in position
4.1 cement concrete of specified grade
excluding the cost of centering and
1:4:8 (1 Cement : 4 coarse sand
8 4.1.8 (zone-III) derived from natural
sources : 8 graded stone aggregate Cum 7016.36 7.44 52201.7184
Digitally signed by RAJ PAL
Providing and laying in position
machine batched and machine mixed
design mix M-25 grade cement
concrete for reinforced cement
concrete work, using cement content
as per approved design mix,
including pumping of concrete to site
of laying but excluding the cost of
centering, shuttering, finishing and
reinforcement, including admixtures
in recommended proportions as per
IS: 9103 to accelerate, retard setting
of concrete, improve workability
without impairing strength and
durability as per direction of
5.33.1 All works upto plinth level
Concrete of M25 Grade with
minimum cement content of 330 Cum 9789.89 8.04 78740.11
5.33.2 All works above plinth level upto
Concrete of M25 Grade with
minimum cement content of 330 Cum 10156.21 2.97 30163.94964
Steel reinforcement for R.C.C. work
including straightening, cutting,
5.22 bending, placing in position and
binding all complete upto plinth level
Thermo-Mechanically Treated bars
of grade Fe-500D or more Kg 111.09 804.30 89346.07
Steel reinforcement for R.C.C. work
including straightening, cutting,
5.22A bending, placing in position and
binding all complete above plinth
Thermo-Mechanically Treated bars
of grade Fe-500D or more Kg 111.09 356.4 39590.87
Brick work with common burnt clay
machine moulded modular bricks of
class designation 12.5 in exposed
brick work including making
horizontal and vertical grooves 10
mm wide 12 mm deep complete in
13 6.28.1 From ground level upto plinth level Cum 7207.32 12.12 87359.95
14 6.28.2 Above plinth level upto floor V level Cum 9240.23 21.39 197648.58
15 mm cement plaster on the rough
side of single or half brick wall of mix
Finishing walls with Acrylic Smooth
exterior paint of required shade :
New work (Two or more coat applied
16 13.46.1 @ 1.67 ltr/10 sqm over and including
priming coat of exterior primer Sqm 165.42 291.40 48202.8052
17 NS Electric Work & Light Fittings Nos 1120.00 28.00 31360.00
Steel work welded in built up
sections/ framed work, including
cutting, hoisting, fixing in position
and applying a priming coat of
Digitally signed by RAJ PAL
In gratings, frames, guard bar,
ladder, railings, brackets, gates and Kg 177.78 1500.00 266667.00
Rain Water Harvesting Pit
S.No. Item Description Unit Rate Qty. Amount
Construction of Rain Water
harvesting pit (size 5 m dia x 3 m
depth) including all associated civil
works of top slab, backfilling,
disposal of surplus excavated earth
UNDERGROUND SUMP
S.No. DSR No. Item Description Unit Rate Qty. Amount
Earth work in excavation by
mechanical means (Hydraulic
excavator)/ manualmeans over areas
(exceeding 30 cm in depth, 1.5 m in
width as well as 10 sqm on plan)
including getting out and disposal of
excavated earth lead upto 50 m and
lift upto 1.5 m, as directed by
Engineer-in-charge.
1 2.6.1 All kinds of soil Cum 182.83 25.20 4607.19
Centering and shuttering including
strutting, propping etc. and removal
of form work for :
2 5.9.1 Foundations, footings, bases for columns Sqm 403.9145 2.85 1151.156325
Walls (any thickness) including
3 5.9.2 attached pilasters, butteresses,
plinth and string courses etc. Sqm 867.775 34.20 29677.91
4 5.9.3 Suspended floors, roofs, landings,
balconies and access platform Sqm 955.0675 12.00 11460.81
Providing and laying in position
cement concrete of specified grade
4.1 excluding the cost of centering and
shuttering - All work up to plinth
1:4:8 (1 Cement : 4 coarse sand
(zone-III) derived from
natural sources : 8 graded stone
aggregate 40 mm
nominal size derived from natural
Digitally signed by RAJ PAL
Providing and laying in position
machine batched and machine mixed
design mix M-25 grade cement
concrete for reinforced cement
concrete work, using cement content
as per approved design mix,
including pumping of concrete to site
of laying but excluding the cost of
centering, shuttering, finishing and
reinforcement, including admixtures
in recommended proportions as per
IS: 9103 to accelerate, retard setting
of concrete, improve workability
without impairing strength and
durability as per direction of
Engineer-in-charge.
(Note :- Cement content considered
in this item is @ 330 kg/cum. Excess/
less cement used as per design mix is
payable/recoverable separately).
5.33.1 All works upto plinth level
Concrete of M25 Grade with
6 5.33.1.1 minimum cement content of 330
Steel reinforcement for R.C.C. work
5.22 including straightening, cutting,
bending, placing in position and
binding all complete upto plinth level
Thermo-Mechanically Treated bars
of grade Fe-500D or more Kg 111.0855 734.40 81581.19
15 mm cement plaster on the rough
13.2 side of single or half brick wall of mix
Digitally signed by RAJ PAL
Providing and applying integral
crystalline slurry of hydrophilic in
nature for waterproofing treatment
to the RCC structures like retaining
walls of the basement, water tanks,
roof slabs, podiums, reservior,
sewage & water treatment plant,
tunnels / subway and bridge deck
etc., prepared by mixing in the ratio
of 5 : 2 (5 parts integral crystalline
slurry : 2 parts water) for vertical
surfaces and 3 : 1 (3 parts integral
crystalline slurry : 1 part water) for
horizontal surfaces and applying the
same from negative (internal) side
with the help of synthetic fiber
brush. The material shall meet the
requirements as specified in ACI-212-
3R-2010 i.e by reducing permeability
of concrete by more than 90%
compared with control concrete as
per DIN 1048 and resistant to 16 bar
hydrostatic pressure on negative
side. The crystalline slurry shall be
capable of self-healing of cracks up
to a width of 0.50 mm. The work
shall be carried out all complete as
per specification and the direction of
For vertical surface two coats @ 0.70
kg per sqm per coat Sqm 487.09 46.20 22503.4194
Total 254516.32
POWER BACKUP SYSTEM
S. No. Description Unit Qty Rate Amount
Supply, installation, Testing &
Commissioning of 'Silent Type Diesel
Generating set as per CPCB IV + or
better norms along with having
Prime Power Rating of KVA as below,
415 volts at 1500 RPM, 0.8 lagging
power factor at 415 V suitable for 50
Hz, 3 phase system & for 0.85 Load
1 Factor, including testing at factory
and site with fuel, load for test and
other necessary arrangements
Complete as per CPWD
specifications, should
have QR code which should contain
drawing, test report OEM
manual,GeoTag of manufacturing
location, rating plate as per relevant
IS Code etc. and consisting of the
Digitally signed by RAJ PAL
(A) Diesel Engine:
Turbocharged Diesel engine 4 stroke
water cooled, multi cylinder,
dynamically balanced fly wheel,
electric start of suitable BHP at 1500
RPM suitable for above output of
alternator at 40 Degree C, 50% RH &
at 1000 Meter MSL, capable of taking
10% over loading for one hour after
continuous operation. The engine
will be with Electronic governor, Dry
typeAir filter with service indicator,
first filling of engine fuel (after
commissioning) lubricating Oil,
Coolant and other consumables
complete with all the required
accessories, the Electronic governor
shall be as per ISO 8528.The engine
shall comply to the latest CPCB
norms (CPCB IV + or better) and
Conforming to BS 5514, BS 649, IS
10000, IS 10002, IS 13018 and as per
CPWD specifications.
(B) Engine mounted Instrument
Panel fitted with and having digital
display for following:
(i) Start-stop switch with key
(ii) Water temperature indication
(iii) Lubrication oil pressure
(iv) Lubrication oil temperature
(v) Battery charging indication and
Voltage indication
(vi) RPM indication
(vii) Over speed indication
(viii) Low lubricantion Oil trip
(ix) Engine Running Hours indication
Digitally signed by RAJ PAL
(C) Alternator:
Synchronous alternator rated of
appropriate KVA, 415 volts at 1500
RPM, 3 phase 50 Hz, AC supply with
0.8 lagging power factor at 40
Degree C, 50% RH & at 1000 Meter
MSL. The alternator shall be having
Screen ProtectedDrip Proof (SPDP)
enclosure IP23, brushless,
continuous duty, dynamically
balanced rotor, capable of taking
10% over loading for one hour after
12 hours of continuous operation,
self cooled,self-excited and self-
regulated through AVR conforming
to IS13364(Part 2)/IS: 4722/BS 2613
suitable for tropical conditions and
with class- H insulation.
(D) Base Frame & Foundation:
Both the engine and alternator shall
be mounted on suitable base frame
made of MS channel with necessary
reinforcement which shall be
installed on suitable cement
concrete foundation and vibration
isolation arrangement as per
recommendations of manufacturer.
Daily service fuel tank of suitable
liters capacity as per CPWD
Specifications, fabricated out of 3
mm thick M.S. sheet complete with
all standard accessories and fuel
piping between fuel tank and diesel
engine with MS class 'C' pipes of
suitable dia. Complete with valves,
level indications & accessories as
required as per specifications.
(F) Exhaust System:
Dry exhaust manifold with hospital
type exhaust silencer and catalytic
Digitally signed by RAJ PAL
(G) Starting System:
12V/24V DC starting system
comprising of starter motors: voltage
regulator and arrangement for initial
excitation complete with suitable
numbers of batteries (180 AH
capacity lead acid SMF type) as
required as per specifications. The
battery shall be housed inside the
acoustic enclosure
(H) Acoustic and weather proof
enclosure with arrangement for fresh
air intake for cooling of the engine &
alternator, extraction, discharging
hot air in to the atmosphere and the
temperature rise inside the
enclosure, noise level
outside enclosure. The acoustic
enclosure should be suitable for
cable connection/connection
through bus-trunking. Such
arrangements on acoustic enclosure
should be water proof & dust-proof
conforming to IP-65 protection. The
enclosure shall be as per CPCB IV +
or better norms etc. and as per
CPWD specifications.
Free standing floor mounted IP 42
automatic mains failure control
panel including auto by-pass, suitable
for KVA as below for silent type DG
set complete with relays, timers, set
of CTs for metering & protection and
energy analyser to indicate currents,
phase and line voltages, frequency,
power factor, KWH, Kilo Volt Ampere
Reative Hour (KVARH), KVA (Phase &
Total), KW & provision for overload,
short circuit, restricted earth fault,
under frequency, power (aluminum)
and control (copper ) cabling of
suitable size upto 15 meter between
AMF panel, LT Panel and DG Set
including connection interconnection
etc. as required, all complete and
and communication/ Ethernet
/RS485/SNMP port open protocol for
BMS integration including suitable
software, the panel shall be of DG
Set OEM make etc. as per approved
by Engineering in charge and
including the following:
Digitally signed by RAJ PAL
1. Suitable numbers and appropriate
capacity 4 pole motorised
electrically operated draw out with
cradle type 3 position ACB/ MCCB
with electronic release for O/C & E/F
and shunt trip.
2. Auto/Manual/Test/Off selector
3. Protection for under and over
voltage phase reversal (2 nos Over
voltage relay, 2 Nos. reverse power
relay and 2 Nos. under voltage relay).
4. 3 Sets of current transformers 15
P10 accuracy for protection and 15
VAclass-I for metering
5. Energy analyser unit to indicate
current, Voltage( L-N & L-L), kW, kVA
(Phase & Total), Frequency, KWH, PF.
6. LED Indicating lamps for load on
mains and load on set.
7. Fuse/ MCB for instruments.
8. Battery charger, complete with
transformer/ rectifier, D.C. voltmeter
and ammeter, selector switch for
trickle, off and boost and current
9. Main supply failure monitor
10. Supply failure timer.
11. Restoration timer
12. Control unit with three impulse
automatic engine start/stop and
failure to start lockout.
13. Impulse counter with locking and
reset facility.
14. ON/OFF/Control circuit switch
15. Audio/Video annunciation for
(i) High water temperature
(ii) Low lubricating oil pressure
(iii) Engine over speed
(iv) Engine fails to start
(v) Full load/maximum load warning
16. Protection for over/under
Frequency, Loss of AC sensing, Over
Current, Unbalancing load with
suitable number of relays and
17. Maintenance notification based
on Engine Run Hour & due date.
Digitally signed by RAJ PAL
18. Load Management through PLC
to achieve auto opening and closing
of incomer breakers, bus coupler
switching of essential panel ,
interlocking providing signal to AMF
Panel for load status and AMF shall
give command to DG Set to auto
start / auto stop depending upon
load status and requirement etc. and
necessary hardware and software
required to perform the operation
shall be provided by the contractor
including all control wiring.
Digitally signed by RAJ PAL
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.06 MB
NIT IT.pdf
Tender Document
Scope of Work.pdf
Tender Document
APPROVE MAKE.pdf
Tender Document
GCC PMC 2022 with 12 amnd.pdf
Tender Document
BOQ Santhigiri.pdf
Tender Document
corrigendum-3817-corrigendum01.pdf
pdf • 0.17 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .