TENDER ENQUIRY FOR AIAMC OF HEATING VENTILATION AND AIR CONDITIONING HVAC SYSTEM OF INS DEEPAK
2019_NAVY_300951_1
FMU/344/AIAMC/DEEPAK/HVAC
Single
Marine Services
Turn-key
365 days
FMU(MBI) NAVAL DOCKYARD
Please refer Tender documents.
2 documents required · 2 mandatory
₹100
Yes
PCDA NAVY
₹2.5 L
10 Jan 2020
25 Nov 2019
11 Dec 2019
26 Nov 2019
10 Dec 2019
26 Nov 2019
26 Nov 2019 - 5 Dec 2019
Amount
CHARGES FOR 1ST YEAR
SERVICE CHARGES
Quarterly Routines on each ATU, Fan coil unit, Air filtration unit & Ventilation fan
DX Controller
(a). Check Supply voltage and fuse (b). Check Analog input & Output signals (c). Check Communication I/O Module (d). Connect the unit to computer and check through online all input & output of controller. Check I/O Module communication with DX Controller. If there is any error in DX controller then upload the programme and check the same
Proportional Actuator 24 VCA
(a). Check 24 AC Voltage at actuator terminal (b). Fuse check (c). Check actuator function with respect to temp requirement (d). Check feedback at module
Multifunctional Actuator, 24 VCA for Flanged valve
(a). Check 24 AC Voltage at actuator terminal (b). Fuse check (c). Check actuator function with respected input (d). Check feedback at module
Outdoor Temperature Sensor
(a). Check temperature sensor feedback to module (b). Fuse check (c). Check voltage at temp sensor terminal (d). Check current mA (e). Check sensor feedback to controller
Duct Temperature sensor
(a). Check temperature sensor feedback to module (b). Fuse check (c). Check voltage at temp sensor terminal (d). Check current mA (e). Check sensor feedback to controller
Antifreeze Sensor
(a). Disconnect the power supply from terminal box (b). Remove sensor from housing and check for electrical failure using tool kit (c). Repair / replace sensor if required
Relay
(a). Check relay for its functioning (b). Remove and replace the item with a new spare part (c). Open the main switch board front door
Contactor
(a). Check for any loose connection and spark (b). Health checks up of contactor coil (c). Check for any mechanical damage (d). Resistance check of contactors using millimeter
Thermal Protection
(a). Check for any loose connection and spark (b). Health checks up of Thermal Protection (c). Check for any mechanical damage (d). check functioning of Thermal Protection
Automatic Switch
(a). Check for any loose connection (b). Check input of auto switch from its source (c). Check functioning/operation of auto switch
Transformer
(a). Check input voltage to transformer (b). Check for overheating (c). Check output voltage
Dust Filter
(a). Withdraw filters from their seat through guide (b). Clean by compressed air (c). reassemble the filters
Damper (Motorised)
(a). Check electrical supply across damper terminals (b). Check and operate damper (c). Check dampers blade
Fan/Blower
(a). Check belt tension and replace if defective
Half yearly Routines on each ATU, Fan coil unit, Air filtration unit & Ventilation fan
Dust Filter
(a). Withdraw filters from their seat through guide (b). Clean by compressed air (c). reassemble the filters
Damper (Motorised)
(a). Check electrical supply across damper motor terminals (b). Damper functionality Checks (c). Clean damper blade (d). Check Motor damper coil healthiness
Fan System
(a). Check belt tension and replace if defective (b). Check airflow of fan (c). Replace belt if found damage
NBC Inlet Valve
(a). Check functional operation of valve (b). Check Hydraulic oil feed to the system (c). Check associated hydraulic accessories and solenoid valve (d). Check signal from hydraulic panel to valve
NBC Outlet Valve
(a). Check functional operation of valve (b). Check Hydraulic oil feed to the system (c). Check associated hydraulic accessories and solenoid valve (d). Check signal from hydraulic panel to valve
DX Controller
(a). Check Supply voltage and fuse (b). Check all Analog input & Output signals (c). Check Communication between I/O Module and DX Controller (d). Online health checks of DX controller and communication with I/O Module. Fixing of error if found
Proportional Actuator 24 VCA
(a). Check Voltage at actuator terminal (b). Fuse check (c). Check actuator function with respect to temp requirement (d). Check feedback at module
Multifunctional Actuator, 24 VCA for Flanged valve
(a). Check Voltage at actuator terminal (b). Fuse check and replace if required (c). Check actuator function with respected input/feed (d). Check feedback at module
Outdoor Temperature Sensor
(a). Check temperature sensor feedback to module (b). Fuse check (c). Check voltage at temp sensor terminal (d). Check current mA (e). Check temp sensor feedback to controller
Duct Temperature sensor
(a). Check temperature sensor feedback to module (b). Fuse check (c). Check voltage at temp sensor terminal (d). Check sensor current (e). Check temp sensor feedback to controller
Antifreeze Sensor
(a). Disconnect the power supply from terminal box (b). Remove sensor from housing and check for electrical failure using tool kit (c). Repair / replace sensor if required
Hydraulic panel of NBC System
(a). Check hydraulic oil. Replace if required (b). Check solenoid valve operation (c). Check I/O to and from panel (d). Check Hydraulic fittings
ECR panel Board
(a). Check panel board component condition (b). Loop mtesting (c). Online programme check up (d). Cleaning of duct by compressed air
Thermal Protection
(a). Check for any loose connection and spark (b). Health checks up of Thermal Protection (c). Check for any mechanical damage
Automatic Switch
(a). Check for any loose connection (b). Check input of auto switch from its source (c). Check functioning/operation of auto switch
Contactor
(a). Check for any loose connection and spark (b). Health checks up of contactor coil (c). Check for any mechanical damage (d). Resistance check of contactors using millimeter
Relay
(a). Check relay for its functioning (b). Remove and replace the item with a new spare part (c). Open the main switch board front door
Fan Motor
(a). Check for abnormal noise (b). Check all thermal connections (c).Check motor coil thrmister value (to be above 100 ohms) (d). Check Motor bearings with SPM Meter, to be in green zone. Replace if defective. (e). Check motor winding resistance and phase to phase (to be more than 2 Ohm) (f). Check motor starting and running current with load (g). Check motor running current with no load
Transformer
(a). Check input/Output voltage of transformer (b). Check for overheating (c). Health checks of coil (d). Fuse health checks and Cleaning of ducts by compressed air and tools
Yearly Routines on each ATU, Fan coil unit, Air filtration unit & Ventilation fan
DX Controller
(a). Check Supply voltage and fuse (b). Check all Analog input & Output signals (c). Check Communication between I/O Module and DX Controller (d)4. Online health checks of DX controller and communication with I/O Module. Fixing of error if found
Proportional Actuator 24 VCA
(a). Check Voltage at actuator terminal (b). Fuse check (c). Check actuator function with respect to temp requirement (d). Check feedback at module
Multifunctional Actuator, 24 VCA for Flanged valve
(a). Check Voltage at actuator terminal (b). Fuse check and replace if required (c). Check actuator function with respected input/feed (d). Check actuator feedback at module
Outdoor Temperature Sensor
(a). Check temperature sensor feedback to module (b). Fuse check (c). Check voltage at temp sensor terminal (d). Check sensor current (e). Check temp sensor feedback to controller
Duct Temperature sensor
(a). Check temperature sensor feedback to module (b). Fuse check (c). Check voltage at temp sensor terminal (d). Check sensor current (e). Check temp sensor feedback to controller
Antifreeze Sensor
(a). Disconnect the power supply from terminal box (b). Remove sensor from housing and check for electrical failure using tool kit (c). Repair / replace sensor if required
Relay
(a). Disconnect the power supply from terminal box (b). Remove sensor from housing and check for electrical failure using tool kit (c). Repair / replace sensor if required
Contactor
(a). Check for any loose connection and spark (b). Health checks up of contactor coil (c). Check for any mechanical damage (d). Resistance check of contactors using millimeter
Thermal Protection
(a). Check for any loose connection and spark (b). Health checks up of Thermal Protection (c). Check for any mechanical damage
Automatic Switch
(a). Check for any loose connection (b). Check input of auto switch from its source (c). Check functioning/operation of auto switch
Transformer
(a). Check input/Output voltage of transformer (b). Check for overheating (c). Health checks of coil (d). Fuse health checks
Dust Filter
(a). Withdraw filters from their seat through guide (b). Clean by compressed air, replace if defective (c). reassemble the filters
Damper (Motorised)
(a). Check electrical supply across damper motor terminals (b). Damper functionality Checks (c). Clean damper blade (d). Check Motor damper coil healthiness
NBC Inlet Valve
(a). Check functional operation of valve (b). Check Hydraulic oil feed to the system (c). Check associated hydraulic accessories and solenoid valve (d). Check signal from hydraulic panel to valve
NBC Outlet Valve
(a). Check functional operation of valve (b). Check Hydraulic oil feed to the system (c). Check associated hydraulic accessories and solenoid valve (d). Check signal from hydraulic panel to valve
NBC Filter
(a). Check air flow in NBC mode to monitor filter condition (b). Replace if desired flow not achieved . (c). For replacing filter follow safety instructions. (d). Cleaning of ducts by compressed air and some special tools
Hydraulic panel of NBC System
(a). Check hydraulic oil. Replace if required (b). Check solenoid valve operation (c). Check I/O to and from panel (d). Check Hydraulic fittings
ECR panel Board
(a). Check panel board component condition (b). Loop testing (c). Online programme check up (d). Check functional operation of ECR panel (e). Check all system status on monitor panel
Fan Motor
(a). Check for abnormal noise (b). Check all thermal connections (c). Check motor coil thermistor value (to be above 100 ohms) (d). Check Motor bearings with SPM Meter, to be in green zone. Replace if defective. (e). Check motor winding resistance and phase to phase (to be more than 2 Ohm) (f). Check motor starting and running current with load (g). Check motor running current with no load
Fan System
(a). Check belt tension and replace if defective (b). Check airflow of fan (c). Replace belt if found damage.
HVAC System check
(a). Check and monitor all compartment temp (b). Check airflow of all respective compartments (c). Check water flow of ATU & FCU (d). Check complete system functional checks
SPARE CHARGES
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
MOTOR BEARING
MOTOR BEARING
MOTOR BEARING
MOTOR BEARING
MOTOR BEARING
BEARING
MOTOR BEARING
MOTOR BEARING
MOTOR BEARING
MOTOR BEARING
MOTOR BEARING
FAN BEARING
FAN BEARING
FAN BEARING
FAN BEARING
FAN BEARING
FAN BEARING
FUSE 10.3x38 1A GG
FUSE 10.3x38 2A GG
CERAMIC FUSE 4A GT 5x20 UL
FUSE 10.3x38 1A GG, UE, UR & FOR TRANSFORMER A ON UA
FUSE 10x38 2A AM 690 V
FUSE 10x38 4A AM 690 V
FUSE 10x38 6A AM 690 V
FUSE 10x38 10A AM 690 V
FUSE 10x38 16A AM 690 V
FUSE 10x38 20A AM 690 V
FUSE 14x51 25A AM 690 V
FUSE 14x38 32A AM 690 V
FUSE 22x58 40A AM 690 V
FUSE 22x58 63A AM 690 V
3PH 14x51 FUSE HOLDER, 690V R.I.NA.
3PH 22x58 FUSE HOLDER, 690V R.I.NA.
3PH 10x38 FUSE HOLDER, 500V R.I.NA.
DAMPER THERMOELECTRICAL FUSE
THERMOELECTRICAL FUSE 72◦C
THERMOELECTRICAL FUSE 95◦C
THERMOELECTRICAL FUSE 72◦C EEXED SCHICSHEK FIRE SAFE
DAMPER MECHANICAL FUSE
MECHANICAL FUSE 47◦C F47
ANTIFREEZE THERMOSTAT
ANTIFREEZE SENSOR
FILL SOLENOID VALVE KIT
FILL SOLENOID VALVE KIT
A9-30-10 230V 50/60HZ CONTACTOR
A12-30-10 230V 50/60HZ CONTACTOR
A16-30-10 230V 50/60HZ CONTACTOR
A26-30-10 230V 50/60HZ CONTACTOR
A30-30-10 230V 50/60HZ CONTACTOR
A40-30-10 230V 50/60HZ CONTACTOR
CA5-10 AUX CONTACT 1NO
CA5-10 AUX CONTACT 1NC
TA 25DU THERMAL PROTECTION 0, 25÷0,4
TA 25DU THERMAL PROTECTION 0, 63÷2
TA 25DU THERMAL PROTECTION , 1÷1,4
TA 25DU THERMAL PROTECTION 0, 1,3÷1,8
TA 25DU THERMAL PROTECTION 0, 1,7÷2,4
TA 25DU THERMAL PROTECTION 0, 2,2÷3,1
TA 25DU THERMAL PROTECTION 0, 3,5÷5
TA 25DU THERMAL PROTECTION 0, 4,5÷6,5
TA 25DU THERMAL PROTECTION 0,7,5-11A
TA 25DU THERMAL PROTECTION 0,10-14A
TA 25DU THERMAL PROTECTION 0, 13-19A
TA 25DU THERMAL PROTECTION 0, 18÷25
TA 25DU THERMAL PROTECTION 0,24-32A
TA 25DU THERMAL PROTECTION 0,29-42A
4 POINTS MINI-RELAY 24VAC
4 POINTS MINI-RELAY 220VAC
1SFA 616400R1001 RED LIGHT
1SFA 616400R1002 GREEN LIGHT
S202M D 3A AUTOM SWITCH 10KA
S202M C 2A AUTOM SWITCH 10KA
S202M C 4A AUTOM SWITCH 10KA
S202M C 6A AUTOM SWITCH 10KA
S202M D 6A AUTOM SWITCH 10KA
1SFA 616400R1003 YELLOW LIGHT
1SFA 616400R1005 WHITE LIGHT
MULTILED BA9S DC 8 CH24V RED
MULTILED BA9S DC 8 CH24V GREEN
MULTILED BA9S DC 8 CH24V YELLOW
MULTILED BA9S DC 8 CH24V WHITE
N/O CONTACT
N/C CONTACT
COMMUNICATION MODULE
EXPANSION MODULE (8 BO)
EXPANSION MODULE (8 BI)
ELECTRIC ACTUATOR FOR VG1000 (ND15..32)
ELECTRIC ACTUATOR FOR VG1000 (ND40..50)
PROPORTIONAL ACTUATOR, 24VCA
OUTDOOR TEMPERATURE SENSOR,
DUCT TEMPERATURE SENSOR, 0 TO 40◦C
DUCT TEMPERATURE SENSOR, 0 TO 40◦C
ROOM TEMPERATURE SENSOR
DUCT HUMIDITY % SENSOR
CHARGES FOR 2ND YEAR
SERVICE CHARGES
Quarterly Routines on each ATU, Fan coil unit, Air filtration unit & Ventilation fan
DX Controller
(a). Check Supply voltage and fuse (b). Check Analog input & Output signals (c). Check Communication I/O Module (d). Connect the unit to computer and check through online all input & output of controller. Check I/O Module communication with DX Controller. If there is any error in DX controller then upload the programme and check the same
Proportional Actuator 24 VCA
(a). Check 24 AC Voltage at actuator terminal (b). Fuse check (c). Check actuator function with respect to temp requirement (d). Check feedback at module
Multifunctional Actuator, 24 VCA for Flanged valve
(a). Check 24 AC Voltage at actuator terminal (b). Fuse check (c). Check actuator function with respected input (d). Check feedback at module
Outdoor Temperature Sensor
(a). Check temperature sensor feedback to module (b). Fuse check (c). Check voltage at temp sensor terminal (d). Check current mA (e). Check sensor feedback to controller
Duct Temperature sensor
(a). Check temperature sensor feedback to module (b). Fuse check (c). Check voltage at temp sensor terminal (d). Check current mA (e). Check sensor feedback to controller
Antifreeze Sensor
(a). Disconnect the power supply from terminal box (b). Remove sensor from housing and check for electrical failure using tool kit (c). Repair / replace sensor if required
Relay
(a). Check relay for its functioning (b). Remove and replace the item with a new spare part (c). Open the main switch board front door
Contactor
(a). Check for any loose connection and spark (b). Health checks up of contactor coil (c). Check for any mechanical damage (d). Resistance check of contactors using millimeter
Thermal Protection
(a). Check for any loose connection and spark (b). Health checks up of Thermal Protection (c). Check for any mechanical damage (d). check functioning of Thermal Protection
Automatic Switch
(a). Check for any loose connection (b). Check input of auto switch from its source (c). Check functioning/operation of auto switch
Transformer
(a). Check input voltage to transformer (b). Check for overheating (c). Check output voltage
Dust Filter
(a). Withdraw filters from their seat through guide (b). Clean by compressed air (c). reassemble the filters
Damper (Motorised)
(a). Check electrical supply across damper terminals (b). Check and operate damper (c). Check dampers blade
Fan/Blower
(a). Check belt tension and replace if defective
Half yearly Routines on each ATU, Fan coil unit, Air filtration unit & Ventilation fan
Dust Filter
(a). Withdraw filters from their seat through guide (b). Clean by compressed air (c). reassemble the filters
Damper (Motorised)
(a). Check electrical supply across damper motor terminals (b). Damper functionality Checks (c). Clean damper blade (d). Check Motor damper coil healthiness
Fan System
(a). Check belt tension and replace if defective (b). Check airflow of fan (c). Replace belt if found damage
NBC Inlet Valve
(a). Check functional operation of valve (b). Check Hydraulic oil feed to the system (c). Check associated hydraulic accessories and solenoid valve (d). Check signal from hydraulic panel to valve
NBC Outlet Valve
(a). Check functional operation of valve (b). Check Hydraulic oil feed to the system (c). Check associated hydraulic accessories and solenoid valve (d). Check signal from hydraulic panel to valve
DX Controller
(a). Check Supply voltage and fuse (b). Check all Analog input & Output signals (c). Check Communication between I/O Module and DX Controller (d). Online health checks of DX controller and communication with I/O Module. Fixing of error if found
Proportional Actuator 24 VCA
(a). Check Voltage at actuator terminal (b). Fuse check (c). Check actuator function with respect to temp requirement (d). Check feedback at module
Multifunctional Actuator, 24 VCA for Flanged valve
(a). Check Voltage at actuator terminal (b). Fuse check and replace if required (c). Check actuator function with respected input/feed (d). Check feedback at module
Outdoor Temperature Sensor
(a). Check temperature sensor feedback to module (b). Fuse check (c). Check voltage at temp sensor terminal (d). Check current mA (e). Check temp sensor feedback to controller
Duct Temperature sensor
(a). Check temperature sensor feedback to module (b). Fuse check (c). Check voltage at temp sensor terminal (d). Check sensor current (e). Check temp sensor feedback to controller
Antifreeze Sensor
(a). Disconnect the power supply from terminal box (b). Remove sensor from housing and check for electrical failure using tool kit (c). Repair / replace sensor if required
Hydraulic panel of NBC System
(a). Check hydraulic oil. Replace if required (b). Check solenoid valve operation (c). Check I/O to and from panel (d). Check Hydraulic fittings
ECR panel Board
(a). Check panel board component condition (b). Loop mtesting (c). Online programme check up (d). Cleaning of duct by compressed air
Thermal Protection
(a). Check for any loose connection and spark (b). Health checks up of Thermal Protection (c). Check for any mechanical damage
Automatic Switch
(a). Check for any loose connection (b). Check input of auto switch from its source (c). Check functioning/operation of auto switch
Contactor
(a). Check for any loose connection and spark (b). Health checks up of contactor coil (c). Check for any mechanical damage (d). Resistance check of contactors using millimeter
Relay
(a). Check relay for its functioning (b). Remove and replace the item with a new spare part (c). Open the main switch board front door
Fan Motor
(a). Check for abnormal noise (b). Check all thermal connections (c).Check motor coil thrmister value (to be above 100 ohms) (d). Check Motor bearings with SPM Meter, to be in green zone. Replace if defective. (e). Check motor winding resistance and phase to phase (to be more than 2 Ohm) (f). Check motor starting and running current with load (g). Check motor running current with no load
Transformer
(a). Check input/Output voltage of transformer (b). Check for overheating (c). Health checks of coil (d). Fuse health checks and Cleaning of ducts by compressed air and tools
Yearly Routines on each ATU, Fan coil unit, Air filtration unit & Ventilation fan
DX Controller
(a). Check Supply voltage and fuse (b). Check all Analog input & Output signals (c). Check Communication between I/O Module and DX Controller (d)4. Online health checks of DX controller and communication with I/O Module. Fixing of error if found
Proportional Actuator 24 VCA
(a). Check Voltage at actuator terminal (b). Fuse check (c). Check actuator function with respect to temp requirement (d). Check feedback at module
Multifunctional Actuator, 24 VCA for Flanged valve
(a). Check Voltage at actuator terminal (b). Fuse check and replace if required (c). Check actuator function with respected input/feed (d). Check actuator feedback at module
Outdoor Temperature Sensor
(a). Check temperature sensor feedback to module (b). Fuse check (c). Check voltage at temp sensor terminal (d). Check sensor current (e). Check temp sensor feedback to controller
Duct Temperature sensor
(a). Check temperature sensor feedback to module (b). Fuse check (c). Check voltage at temp sensor terminal (d). Check sensor current (e). Check temp sensor feedback to controller
Antifreeze Sensor
(a). Disconnect the power supply from terminal box (b). Remove sensor from housing and check for electrical failure using tool kit (c). Repair / replace sensor if required
Relay
(a). Disconnect the power supply from terminal box (b). Remove sensor from housing and check for electrical failure using tool kit (c). Repair / replace sensor if required
Contactor
(a). Check for any loose connection and spark (b). Health checks up of contactor coil (c). Check for any mechanical damage (d). Resistance check of contactors using millimeter
Thermal Protection
(a). Check for any loose connection and spark (b). Health checks up of Thermal Protection (c). Check for any mechanical damage
Automatic Switch
(a). Check for any loose connection (b). Check input of auto switch from its source (c). Check functioning/operation of auto switch
Transformer
(a). Check input/Output voltage of transformer (b). Check for overheating (c). Health checks of coil (d). Fuse health checks
Dust Filter
(a). Withdraw filters from their seat through guide (b). Clean by compressed air, replace if defective (c). reassemble the filters
Damper (Motorised)
(a). Check electrical supply across damper motor terminals (b). Damper functionality Checks (c). Clean damper blade (d). Check Motor damper coil healthiness
NBC Inlet Valve
(a). Check functional operation of valve (b). Check Hydraulic oil feed to the system (c). Check associated hydraulic accessories and solenoid valve (d). Check signal from hydraulic panel to valve
NBC Outlet Valve
(a). Check functional operation of valve (b). Check Hydraulic oil feed to the system (c). Check associated hydraulic accessories and solenoid valve (d). Check signal from hydraulic panel to valve
NBC Filter
(a). Check air flow in NBC mode to monitor filter condition (b). Replace if desired flow not achieved . (c). For replacing filter follow safety instructions. (d). Cleaning of ducts by compressed air and some special tools
Hydraulic panel of NBC System
(a). Check hydraulic oil. Replace if required (b). Check solenoid valve operation (c). Check I/O to and from panel (d). Check Hydraulic fittings
ECR panel Board
(a). Check panel board component condition (b). Loop testing (c). Online programme check up (d). Check functional operation of ECR panel (e). Check all system status on monitor panel
Fan Motor
(a). Check for abnormal noise (b). Check all thermal connections (c). Check motor coil thermistor value (to be above 100 ohms) (d). Check Motor bearings with SPM Meter, to be in green zone. Replace if defective. (e). Check motor winding resistance and phase to phase (to be more than 2 Ohm) (f). Check motor starting and running current with load (g). Check motor running current with no load
Fan System
(a). Check belt tension and replace if defective (b). Check airflow of fan (c). Replace belt if found damage.
HVAC System check
(a). Check and monitor all compartment temp (b). Check airflow of all respective compartments (c). Check water flow of ATU & FCU (d). Check complete system functional checks
SPARE CHARGES
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
BELTS
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
FILTER
MOTOR BEARING
MOTOR BEARING
MOTOR BEARING
MOTOR BEARING
MOTOR BEARING
BEARING
MOTOR BEARING
MOTOR BEARING
MOTOR BEARING
MOTOR BEARING
MOTOR BEARING
FAN BEARING
FAN BEARING
FAN BEARING
FAN BEARING
FAN BEARING
FAN BEARING
FUSE 10.3x38 1A GG
FUSE 10.3x38 2A GG
CERAMIC FUSE 4A GT 5x20 UL
FUSE 10.3x38 1A GG, UE, UR & FOR TRANSFORMER A ON UA
FUSE 10x38 2A AM 690 V
FUSE 10x38 4A AM 690 V
FUSE 10x38 6A AM 690 V
FUSE 10x38 10A AM 690 V
FUSE 10x38 16A AM 690 V
FUSE 10x38 20A AM 690 V
FUSE 14x51 25A AM 690 V
FUSE 14x38 32A AM 690 V
FUSE 22x58 40A AM 690 V
FUSE 22x58 63A AM 690 V
3PH 14x51 FUSE HOLDER, 690V R.I.NA.
3PH 22x58 FUSE HOLDER, 690V R.I.NA.
3PH 10x38 FUSE HOLDER, 500V R.I.NA.
DAMPER THERMOELECTRICAL FUSE
THERMOELECTRICAL FUSE 72◦C
THERMOELECTRICAL FUSE 95◦C
THERMOELECTRICAL FUSE 72◦C EEXED SCHICSHEK FIRE SAFE
DAMPER MECHANICAL FUSE
MECHANICAL FUSE 47◦C F47
ANTIFREEZE THERMOSTAT
ANTIFREEZE SENSOR
FILL SOLENOID VALVE KIT
FILL SOLENOID VALVE KIT
A9-30-10 230V 50/60HZ CONTACTOR
A12-30-10 230V 50/60HZ CONTACTOR
A16-30-10 230V 50/60HZ CONTACTOR
A26-30-10 230V 50/60HZ CONTACTOR
A30-30-10 230V 50/60HZ CONTACTOR
A40-30-10 230V 50/60HZ CONTACTOR
CA5-10 AUX CONTACT 1NO
CA5-10 AUX CONTACT 1NC
TA 25DU THERMAL PROTECTION 0, 25÷0,4
TA 25DU THERMAL PROTECTION 0, 63÷2
TA 25DU THERMAL PROTECTION , 1÷1,4
TA 25DU THERMAL PROTECTION 0, 1,3÷1,8
TA 25DU THERMAL PROTECTION 0, 1,7÷2,4
TA 25DU THERMAL PROTECTION 0, 2,2÷3,1
TA 25DU THERMAL PROTECTION 0, 3,5÷5
TA 25DU THERMAL PROTECTION 0, 4,5÷6,5
TA 25DU THERMAL PROTECTION 0,7,5-11A
TA 25DU THERMAL PROTECTION 0,10-14A
TA 25DU THERMAL PROTECTION 0, 13-19A
TA 25DU THERMAL PROTECTION 0, 18÷25
TA 25DU THERMAL PROTECTION 0,24-32A
TA 25DU THERMAL PROTECTION 0,29-42A
4 POINTS MINI-RELAY 24VAC
4 POINTS MINI-RELAY 220VAC
1SFA 616400R1001 RED LIGHT
1SFA 616400R1002 GREEN LIGHT
S202M D 3A AUTOM SWITCH 10KA
S202M C 2A AUTOM SWITCH 10KA
S202M C 4A AUTOM SWITCH 10KA
S202M C 6A AUTOM SWITCH 10KA
S202M D 6A AUTOM SWITCH 10KA
1SFA 616400R1003 YELLOW LIGHT
1SFA 616400R1005 WHITE LIGHT
MULTILED BA9S DC 8 CH24V RED
MULTILED BA9S DC 8 CH24V GREEN
MULTILED BA9S DC 8 CH24V YELLOW
MULTILED BA9S DC 8 CH24V WHITE
N/O CONTACT
N/C CONTACT
COMMUNICATION MODULE
EXPANSION MODULE (8 BO)
EXPANSION MODULE (8 BI)
ELECTRIC ACTUATOR FOR VG1000 (ND15..32)
ELECTRIC ACTUATOR FOR VG1000 (ND40..50)
PROPORTIONAL ACTUATOR, 24VCA
OUTDOOR TEMPERATURE SENSOR,
DUCT TEMPERATURE SENSOR, 0 TO 40◦C
DUCT TEMPERATURE SENSOR, 0 TO 40◦C
ROOM TEMPERATURE SENSOR
DUCT HUMIDITY % SENSOR
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .