Supply, Installation, Testing & Commissioning (S.I.T.C.) of 7Mtr Hot Dip galvanised Octagonal Streetlight Poles with LED Luminaries Outdoor Streetlight fitting, control panel and allied accessories (Considering 25 Mtr. Distance between two poles ) incl. 5 Years Free comprehensive Guarantee period with 5 Years Free Operation & Maintenance for GIDC Chhapara Estate,District-Rajkot
314263
E -TENDER NOTICE NO: 05 of 2026-27
Open
Electrical Works
Rajkot
15 documents required · 14 mandatory · 1 optional
₹4,248
EXECUTIVE ENGINEER “GIDC" Rajkot
₹1.3 L
15 Jun 2026
15 Jun 2026
15 Jun 2026
6 Jul 2026
15 Jun 2026
NAME OF WORK: : Supply, Installation, Testing & Commissioning (S.I.T.C.) of 7Mtr Hot Dip galvanised
Octagonal Streetlight Poles with LED Luminaries Outdoor Streetlight fitting, control panel
and allied accessories (Considering 25 Mtr. Distance between two poles ) incl. 5 Years Free
comprehensive Guarantee period with 5 Years Free Operation & Maintenance for GIDC
Chhapara Estate,District-Rajkot
Schedule showing (approximately) the materials to be supplied from the GIDC store for work contracted to be
executed and the rates at which they are to be charged for:
Particulars Rate at which the material will be charged to the Place of Delivery.
Nil Nil Nil Nil Nil
Signature of Bidder EXECUTIVE ENGINEER (M&E)
Supply, Installation, Testing & Commissioning (S.I.T.C.) of 7Mtr Hot Dip galvanised Octagonal
Streetlight Poles with LED Luminaries Outdoor Streetlight fitting, control panel and allied
accessories (Considering 25 Mtr. Distance between two poles ) incl. 5 Years Free comprehensive
Guarantee period with 5 Years Free Operation & Maintenance for GIDC Chhapara
Estate,District-Rajkot
Executive Engineer (M&E),GIDC, Rajkot
DESCRIPTION OF ITEM RATE/
Sr. No. QTY. UNIT AMOUNT
PART - A - (Material incl.5 Years Free comprehensive Guarantee period)
1.0 237.00 Supplying and erecting approved make Ea 11411.99
Octagonal pole made from HR sheet steel. The
pole should be made as per IS. and shall be
coated with hot dip galvanizing of minimum
avg. coating thickness of 85 micron as per IS
2629/2633/4759, suitable suspend local wind
speed with integral Junction box consist of
terminal plate of min 12mm Hylam sheet,
standard profile 35mmX7.5mm Din-Rail for
MCB Mounting, stud type terminal and
arrangement for cable termination to be erected
on suitable foundation as per detils given by
manufacturer considering site requirment..(E)
Mtr. Long 70 mm Top X 135 mm bottom dia,
mm thickness with 225mmX225mmX16mm
base plate, 4-M20 Bolts and 600mm long J-Bolt
EN 8 grade HDG foundation bolts along with
template for the above poles with "GIDC" Logo
on Name Plate. Approx Pole weight
kg.(Make- As per Approved Vendor List as
below.).Note :- J-type EN 8 grade HDG
Foundation Bolt should be manufactured by
manufacturer of the poles (to be supplied)
2.0 237.00 Providing and laying controlled cement concrete Job 3544.36
M.200 / 1:1.5:3 and curing complete excluding
the cost of formwork and reinforcement for
reinforced concrete work in (A) Foundations,
footings, Base of columns and Mass concrete
with 20 to 25 mm stone metal duly plastered
with necessary curing for pole muffing by
Excavating hard Murrum or Metal road by
chiselling for preparing pit for poles or earth
plates or for laying pipes & clearing the site by
removing debris & making site good, Providing
and laying cement concrete M10/1:3:6 (1-
Signature of Bidder EXECUTIVE ENGINEER (M&E)
Cement : 3- coarse sand : 6- hand broken stone
aggregates 40 mmnominal size) and curing
complete excluding cost of formwork in (A)
Foundation and Plinth for Foundation PCC
Work of 100 mm thickness.Providing formwork
of ordinary timber planking so as to give a rough
finish including centering shuttering strutting
and propping etc. Height of propping and
centering below supporting floor to ceiling not
exceeding 4 M. and removal of the same for in
situ reinforced concrete and plain concrete work
in. (A) Foundations Footings Bases of Columns
etc. and Mass concrete. (Extra for Providing
formwork with sheathing steel sheets so as to
give a fair finish in (A) Foundations, Footings,
Bases of Columns etc. and Mass
concrete).Providng TMT bar FE
reinforcement for RCC work including
bending,binding and placing in position
complete upto floor two level. Finishing wall
with weather proof exterior emulsion paint on
wall surface (tWo coats) to give an required
shape even shade after thoroughly brushing the
surface to remove all dirt, and remains of loose
powedered materials etc. complete.- For 7 mtr
Pole Foundation sized :- 500 x 500 x 1550 mm
or as per OEM foundation drawing- (1 No. Per
St. Lght Pole).
3.0 1896.00 Providing & Fixing of Solderless Crimping Type Ea 15.15
Aluminium Lugs (4 Nos. per termination)
conforming to IS suitable for 1 x 4.0 Core x
16/25 Sq. MM PVC Insulated Aluminium
Armoured cable evenly crimped with high
pressure tool & connected to switchgear
terminals with brass/cadmium plated nut bolts in
an approved manner. - (4 Nos. Termination Per
St. Light Pole)
4.0 474.00 Providing & erecting 240 V MCB Single pole Ea 270.68
switch for lighting Load (B Curve) having
KA breaking capacity & confirms to IS :
8828/1996 in existing box having following
capacity.(A) 0.5 to 2 Amp. Cat.III - (2 No. Per
St. Lght Pole for 1No.- Phase & 1No. - Neutral)
(Make- As per Approved Vendor List as below.)
5.0 237.00 Providing and erecting Funnel Pipe type earthing Job 602.57
having 150 cms.long and 2.5 cms. dia.
galvanised iron pipe with coupling and buch
buried in specially prepared earth pit complete
with necessary 8 SWG earth wire and required
size HOT deep Galvanised iron strip for earthing
of Street light pole using proper clamp with
using salt and charcoal / coke as required for
pipe type earthing. (1 Job Per St. Light Pole)
(Make- As per Approved Vendor List as below.)
Signature of Bidder EXECUTIVE ENGINEER (M&E)
6.0 237.00 Providing & erecting Decorative Sword Type Ea 1897.77
Street Light pole Bracket comprising main B
Class MS pipe of 4.2 cms/require outside dia.
and shall be coated with hot dip galvanizing as
per IS 2629/2633/4759 complete with suitable B
Class MS sleeve tubing of approx. 45 cms length
and suitable for 76.5 mm /80 mm/ require size of
pole top having sufficient fastners for fixing the
brackets and having suitable rise as per site
condition and having spread of 1.5.mtr. length
with 110 deg.with vertical plane & suitable
welded stays, reducer and with check nuts
complete painted with one coat of Red oxide /
PU base primer and two coats of Aluminium /
PU paint suitable for side entry fitting brackets,
as per site condition and as per drawing /
directed by Engineer Incharge. with following
nos of arms. (A) Single Arm Bracket 1.5Mtr. –
Decorative Sword Type (1 No. Per St. Light
As per drawing attached (Make- same as per
pole make mentioned in Approved Vendor
List as below.)
7.0 237.00 Supplying and erecting 90 Watt LED street light Ea 6178.17
fittings with High power White LEDs wattage of
3 Watt and above assembled on single MCPCB
with Fixed Programmable microprocessor based
Dimmable Driver, efficiency more than
lm/w and corrosion free High pressure die cast
aluminum housing with smooth finish powder
coated and heat sink extruded aluminium with
diffuser and Polycarbonate optics/ lenses with
company mark/name engraved or embossed
to 300 V,Power Factor more than 0.95, THD <
10 %, CCT 4000 K to 5700K,Uniformity ratio
>0.45, Luminaire efficiency> 150 lumens/watt .
LED driver efficiency > 85 %.CREE / OSRAM /
PHILIPS Lumileds / NICHIA / SEOUL/
LG/BridgeLux (U.S.A.) make LED used for
luminaire. ( Fittings required LM-79 & LM-80
certificates)-(A) Street Light (IP-66), Surge
Protection -4KV and 10 KV non integral, Light
must have 440VAC line supply protection. It
should withstand 48 hours for 440VAC line
supply.(Cat-III) The fitting should be suitable for
side entry having suitable socket bore for
clamping complete erected having IP-66
Protection Class.(1 No. St. Light Fitting per Arm
x 1 Single Arm = 1 No. LED Fitting). (Make- As
per Approved Vendor List as below.)
8.0 2133.00 Supplying and erecting Flexible FR PVC Mtr 46.46
insulated multi strand multi core 1.1 kV grade
Signature of Bidder EXECUTIVE ENGINEER (M&E)
ISI Marked Copper wires of 1.5 Sq. MM.,3 core
round PVC sheathed in exising pipe/ in street
light pole erected with green colour for earth
continuity. - (11 / 9 Mtr. per St. Light Fitting x
No. St. Light Fitting =9/ 7 Mtr Pole.) (Make- As
per Approved Vendor List as below.)
9.1 8295.00 Providing & erecting of 1 x 4.0 Core x 10 Sq. Mtr 140.39
MM, XLPE (IS: 7098 (i) - 88), ISI Mark,
Armoured cable, Multistranded Aluminium
Conductor suitable for 1.1 kV grade to be laid on
wall with necessary clamps or to be laid 90 Cms
underground in existing cable trench/ pipe at
road crossing or on floor and making the ground
as per original. - For Streetlight between two
poles & Service Connections.(Considering
Mtr. Distance between two poles and extra cable
for loop = 35 Mtr.) (Make- As per Approved
Vendor List as below.)
9.2 60.00 Providing & erecting of 1 x 4.0 Core x 16 Sq. Mtr 153.52
MM, XLPE (IS: 7098 (i) - 88), ISI Mark,
Armoured cable, Multistranded Aluminium
Conductor suitable for 1.1 kV grade to be laid on
wall with necessary clamps or to be laid 90 Cms
underground in existing cable trench/ pipe at
road crossing or on floor and making the ground
as per original. - For Streetlight between two
poles & Service Connections.(Considering
Mtr. Distance between two poles and extra cable
for loop = 35 Mtr.)
(Make- As per Approved Vendor List as below.)
10.1 7110.00 Providing & laying of approved make 50 MM Mtr 62.62
outer dia Doubled Walled Corrugated Pipes
(DWC) of polyethylene (conforming to IS
- II) with necessary connecting accessories like
coupler, Tee, L - Bow, etc. of same material at
required depth (90 cms) for laying of cable
below ground/ road surface for enclosing cable
and back filling the same to make ground as per
original & as per instruction of Engineer
Incharge - for Streelight Cable of 1 x 4 core x
Sq. MM. (30 Mtr Per Between two Pole)
10.2 709.00 Providing & laying of approved make 90 MM Mtr 95.95
outer dia Doubled Walled Corrugated Pipes
(DWC) of polyethylene (conforming to IS
- II) with necessary connecting accessories like
coupler, Tee, L - Bow, etc. of same material at
required depth (90 cms) including excavation for
laying of cable below ground/ road surface for
enclosing cable and back filling the same to
make ground as per original & as per instruction
of Engineer Incharge - for Streelight Cable of
x 4 core x 16 Sq. MM and Service cable of 1 x
core x 16 Sq. MM.
(Make- As per Approved Vendor List as below.)
Signature of Bidder EXECUTIVE ENGINEER (M&E)
11.1 4.00 Smart 4G Timer, Supply of IoT based 4G Smart Ea 100427.33
Streetlight Control & Monitoring System having
a Smart Panel comprising of 3 Phase IoT
Streetlight Smart 4G Timer with 16x2 LCD to
display RSSI, relay status, RTC time &
diagnostics., Controller works on 3-phase & also
on any available 1-Phase., Controller with 8-
hour battery backup during external power
failure. External power failure alert immediately
to cloud., 110-630 V AC @ 50-60 Hz – 3 phase
operating range., Standby power consumption
<3W., Smart 4G Timer with RS232 port for
DLMS Energy meter., Smart 4G Timer must be
compatible with any make / brand of DLMS
(RS232) Energy Meter., DI: 4 Nos. (3 Contactor
/ Latch detection, 1 for Door Sensor.)., DO:
Relays for Independent control each phase (R,
Y, B) with 1 extra spare relay., Smart 4G Timer
with dual SIM functionality for connectivity
backup., 4G M2M SIM 3-Year communication
included., Local configuration via WiFi / BLE
for maintenance or during force majeure., GPS
chip inbuilt of Smart 4G Timer for auto location
tracking & astronomic schedule location.,
programmable schedules., Astronomic
scheduling with monthly offsets., Smart 4G
Timer has inbuilt timer stores schedules locally
& also stores schedule execution logs locally,
syncs to cloud whenever connected to cloud.,
Auto-scheduler overrides manual operations.,
Monitoring & alerts for MCB trips., Over/under
voltage, current, overload, power factor & short
circuit protections with alerts via Dashboard,
App, SMS, WhatsApp & Email., Contactor /
Latch chattering protection & alerts., Smart 4G
Timer with neutral failure protection and alert.,
Bulit-in Watchdog for anti-jamming., Smart 4G
Timer must send Regular "heartbeat" on
software for CCMS status., Accelerometer for
tamper & panel movement detection & alerts.,
Smart 4G Timer must be tested from an NABL
Lab for Surge Test @ 6 KV (IEC 61000-4-5),
ESD Test @ 4 KV (IEC 61000-4-2), EFT @
KV (IEC 61000-4-4), Conducted Emission @
150 KHz-30 MHz (CISPR11), Damp Heat Test
(40 Deg C @ 95% RH) 2 cycles of 12+12 hours
(IS: 9000 (Part 5/Sec.2):1981 latest) with all test
passing criteria as “Temporary degradation or
loss of function or performance which is self-
recoverable”., FOTA functionality required for
upgrades., Smart 4G Timer sends & stores
online/offline data of controller & load for lamp
burn hours analysis., It stores & syncs
connectivity logs for configuration of network
connections & analytics., PANEL &
SWITCHGEAR, The panel includes a Class
DLMS energy meter NABL approved with 1-2
Signature of Bidder EXECUTIVE ENGINEER (M&E)
months of stored data of daily, hourly, monthly,
load survey, instantaneous, events, tamper data
& with power events stored in meter memory for
audit purpose., Must monitor V, I, KWH, KVA,
PF, KVAH, etc., Panel made with 2 mm CRCA
sheet with ground mountable stand complete
with gland plate, waterproof glands, earthing
bolt., IP55, weatherproof panel with RAL7035
powder-coated., Smart 4G Timer must be fitted
on removable terminal sockets for easy
maintenance., Switchgear includes 3 Nos. 3 pole
Contactor / Latch having minimum 50 A Load
carrying capacity per phase, all other switchgear
& wires: 40 A load carrying capacity., 1 Nos. 4P
MCB 10 kA for Incomer & 6 Nos. 1P MCBs
kA for Outgoing., Phase-Wise Bypass MCBs
required., 4P RCCB 100 mA., door sensor. Also,
provide lock & key facility., Panel mount
outdoor antenna for GSM, GPS., Canopy design
for draining down water., CCMS SMART
SOFTWARE, OAuth 2.0 APIs for sending data
to Government clouds/software, etc., CCMS
Web dashboard with secure password & OTP
login., Hosted on trusted cloud, data security,
antivirus & attack protection., HTTPS.,
AES256-bit encryption., Vulnerability
Assessment and Penetration Testing (VAPT)
certificate for CCMS Software., Streetlight
management software for load status, live
analytics & reports., Energy meter data tables
(kW, kWh, PF, I, V, etc.) available., Utility
monthly bill reconciliation & Class 1 accuracy
reports for billing, energy monitoring & auditing
for streetlight load., Fault detection., Light fault
99% analysis on dashboard using energy
monitoring., WhatsApp integration., Hierarchy-
wise reporting & alerts., GIS mapping of live
connected streetlight control panels, poles &
streetlights., MQTT protocol., Smartphone app
with local configuration & navigation.,
Monitoring & reporting of lighting parameters.,
Facility for media attachments for site
photos/videos/work permits/checklists, etc. per
Feeder Panel for remote verification., Asset
management module for streetlight infrastructure
data., Complaint/service task management with
history & escalation must be available., Android
& iOS App for dashboard analytics, graphs,
energy data, alerts., 5 Years CCMS Web
Software & Cloud Server Hosting subscription
included., Customizable, user-friendly
(Make- As per Approved Vendor List as below.)
Signature of Bidder EXECUTIVE ENGINEER (M&E)
11.2 4.00 "Supplying & erecting in earthpit of minimum Ea 8636.51
bore dia. 150mm size approved make Earthing
Electrode consisting Pipe-in-Pipe Technology as
per IS 3043-1987 made of corrosion free hot
dipped G.I.Pipes having Outer pipe dia of
mm having 80-200 Micron galvanising, Inner
pipe dia of 25 mm having 200-250 Micron
galvanising, connection terminal dia of 12 mm
with constant ohmic value surrounded by highly
conductive compound with high charge
dissipation suitable for following type of
applications with chamber and heavy duty
cover.(approved make OEM has to submit test
certificate including value of earth resistane of
installation.) & having back filling compound of
(B) Inner Chemical (CCM Compound) -
Resistivity :- 0.2 Ohm/meter testing as per IEC
62561-2017 , Voltage Drop :- < 1 volt at no load
& dry form , Sulpher content :- <2% .(C) Back
filling copound :- Earthing compound should be
capable to retain moisture for log time.
Necessary test report must be submitted.(C) For
Electrical Installation covering Transformer
Neutrals, Lightning arrester Earthing, A.C.Plant
& Sensitive Computer System (like
Automation, SCADA) i.e. independent Earthing
located in other than normal soil i.e. Soft Rock,
Marshy Soil etc..-Length of Pipe : 3 Mtrs. -Back
filling Compound :2 nos Bags of 25 Kg.- (1 Job
per Distribution Box)" (Make- As per Approved
Vendor List as below.)
12.0 241.00 Painting the number and words for inventory No. 22.22
Identification on erected fittings / equipment’s or
Such accessories as may required with good
quality of enameled paint as directed by engineer
in charge (i) up to 20 characters, up to 50 mm
height. (As Instructed by engineer in charge.)
13.0 709.00 Drilling the road without breaking the road Mtr 616.10
surface (Asphalt) for laying of cable for feeding
power supply by making up to 150mm dia.size
of holes at both ends complete. (As Instructed by
engineer in charge.)
14.0 7110.00 Making trench in hard murrum/ tar road of Mtr 357.54
suitable width of 90 cms or required depth for
laying any size of cable or locating the fault all
over the run and back filling the same and
making the surface as normal ground.(B) If
additional machinery like hammer driller or JCB
use [Add] (As Instructed by engineer in charge.)
Part - A- Total
Signature of Bidder EXECUTIVE ENGINEER (M&E)
PART - B - ( Power Supply Connection Charges, Operation & Maintenance Charges of Complete Street
Light System for 5 Years)
15.0 4.00 Annual Maintenance charge: Agency has to Per 106287.69
carry out Maintenance of the streetlight network Year
after 1st year of completion of the project which
is included in Defect Liability Period,in such a
way that through all year,streetlight network will
run with 100% efficiency. Agency has to carry
out Manintenanc with Manpower, Material
,Tools & Tackles . No extra payment will be
provided to agency. (As Instructed by engineer
16.0 5.00 Annual Operation charge: Agency has to carry Per 401655.36
out Operation of the streetlight network after Year
completion of the project which is included in in
such a way that through all year, streetlight
network will run with 95% efficiency. Agency
has to carry out operation with Manpower,
Material ,Tools & Tackles . No extra payment
will be provided to agency (Unskilled Labour
No. & Skilled Labour 1 No.). (As Instructed by
engineer in charge.)
17.0 4.00 Service Connection Charges includes Charges Job 23178.79
for obtaining N.O.C from Electrical Inspector /
Statutory authority for Power / Ele. Installation
on behalf of client and shall be paid on
submission of orignial receipt to Client.Charges
shall include preparing required attasted
documents & drawing for obtaining NOC on
behalf of client.-10 KW , 3-Phase
Part - B- Total
Part - A- + Part - B - Total Rs.:
Note:- The quoted price shall include all taxes (excluding GST), duties, levies, overheads, insurance,
transportation, freight, construction cess etc. whatsoever is applicable and the price shall remain firm till the
completion of the project in all respect.
I / we am/are hereby agree to carry out the above work at _____________ % (in figures) above / below
____________________ percent (in words)below/above the estimated rates mentioned above (should be written in
figures and words). Amount of my / our tender works out as under:
*Estimated amount put *Estimated amount
to tender put to tender
Deduct__% below Rs.______________ Add___ % above Rs.______________
Signature of Bidder EXECUTIVE ENGINEER (M&E)
In words In words
I /We hereby declare that I /We have visited the site and fully requisite myself / ourselves with the local situation
regarding materials labour and other factors pertaining to work before submitting tender.
I /we hereby declare that / We have carefully studied the conditions of contracts detailed technical specification
and other tender documents of this work and agree to execute the same accordingly.
(1) The materials/sample for work should be got approved from the Competent Authority / Executive Engineer (M&E)
In charge of the work.
(2) The materials and work shall have to be used and carried out as specified in technical note.
(3) All works shall be carried out as per Public Works Department hand book & Other Specification of the Division Or
as directed by Engineer in- Charge/ Executive Engineer (M&E), GIDC, Rajkot.
(4) Rate are Inclusive of 1% Labour cess in Tender amount so 1% of total amount of bill will be deducted from the bill.
(4) Rate are Inclusive of 1% Labour cess in Tender amount so 1% of total amount of bill will be deducted from the bill.
Signature of Bidder EXECUTIVE ENGINEER (M&E)
SCHEDULE OF QUANTITIES
These preambles apply to all the sections of Schedule of quantities and tendered rates shall take into account all these
provisions in other parts of the tendered documents.
1. The quantities in this schedule are provisional. The contractor will be paid for the actual quantity of work executed
at site at the rates quoted in his tender. The Corporation reserves the right to increase or decrease any of the
quantities or to omit any item of work totally and any claim by the contractor in these accounts will not be
2. All the items of work given in this schedule of quantities shall be executed strictly in accordance with the Indian
Electricity Act, the Indian Electricity Rules & Regulations, Requirements of the Electric Supply Authority, National
Electrical Code (NEC) or NFPA 70, is a regionally adoptable standard for the safe installation of electrical wiring
and equipment in the United States. It is part of the National Fire Code series published by the National Fire
Protection Association (NFPA), National Building Code read in connection with the relevant drawings,
specifications and appropriate Indian Standards
3. All measurements shall be taken in accordance with the Indian Standard Electrical installation in Factory method of
measurement of IS 5908/1970 unless otherwise specified.
4. The contractor shall visit the site and shall satisfy himself as to conditions under which the work is to be performed.
No extra claim consequence of ignorance or on grounds of insufficient description will be allowed at a later date.
5. No alteration, whatsoever, is to be made to the text of quantities of this schedule of quantities unless alteration is
authorized in writing by the Corporation. Any such alteration, notes or additions shall unless authorized in writing
be disregarded when tender documents are considered.
6. In the event of error occurring to the amount column of the schedule, as a result of wrong extension unit rate and
quantity, the unit rate quoted by the Tenderer shall be regarded as firm and the extension shall be amended on the
basis of the rates.
7. All error in totaling in the amount column and in carrying forward totals shall be corrected.
8. All error in description or in quantity or omission of items from the contract schedule shall not vitiate this variation
required by the Corporation.
9. Wherever there are similar items appeared in the schedule of quantities under different headings, then the lowest
rate will be considered.
Signature of Bidder EXECUTIVE ENGINEER (M&E)
LIST OF APPROVED VENDOR OF ITEMS / EQUIPMENTS FOR STREETLIGHT
SR. LIST OF ITEMS APPROVED MAKES
1 HOT-DIP GALVANIZED BAJAJ/TRANSRAIL/VALMONT/RR ISPAT/UTKARSH or Eq.
OCTAGONAL POLE Incl. J-TYPE
BOLT and TEMPLET.
2 DECORATIVE STREET BAJAJ/TRANSRAIL/VALMONT/RR ISPAT/UTKARSH or Eq
LIGHT BRACKET (SWORD TYPE) (As per Drawing attached Separately )
3 LED OUTDOOR STREET LIGHT BAJAJ/PHILLIPS/SCHREDER/LIGMAN/WIPRO/ CROMPTON/
/ INDOOR LIGHT /HAVELLS or Eq
4 FR PVC INSULATED WIRE FINOLEX/TORRENT/POLYCAB/RAVIN(PRIMECAB)/KEI/RR
5 XLPE ARMOURED CABLE FINOLEX/TORRENT/POLYCAB/RAVIN(PRIMECAB)/KEI/RR
6 LUG DOWELL's/ISMILE/3D/JAINSON or Eq
7 GLAND COMET/HMI/SIEMENSE or Eq
8 MCCB/MCB/ELCB/MCCB/ ABB/L&T/SIMENSE/HAVELLS/LEGRAND/SCHNEIDER/HAGER
CONTACTOR or Eq
9 DIGITAL TIME SWITCH & /ABB/L&T/SIMENSE/HAVELLS/LEGRAND/SCHNEIDER/HAGER
CONTACTOR or Eq
10 DOUBLE WALL CORRUGATED DURALINE / JAIN Irrigation/GEMINI/VARAHI/REX or Eq
(DWC) POLYTHINE PIPE
11 CCMS PANEL MOTWANE/KAKATIYA ENERGY SOLUTION/MEMIGHTY/
PYROTECH or Eq.
12 EARTHING RAPID/ASHLOK/OBO/INDELEC/SULAH SAFE SOLTION or Eq
13 LED INDICATION LAMP SIEMENS /SCHNEIDER /L&T /BINAY /ABB /MG /KAPPA
/TECHNIC /GE /VAISHNO
Note :- For percentage/unit rate works, makes other than above which are approved time to time by R&B/
GWSSB/CPWD department and mentioned prevailing (Current) Govt. SOR can be considered /used with prior
approval of the competent authority / E.E (M&E) GIDC, Rajkot
Signature of Bidder EXECUTIVE ENGINEER (M&E)
(Bidder must read carefully and Submit the detail as Required by Annexure – E.)
Particulars and Details to be submitted by the bidder:
In order to properly assess and due diligence on submissions, the Proponent should provide following information on
the quality and photometric of proposed luminaries.
LUMINAIRE SELECTION CRITERIA
DESIGN PARAMETERS: -
It is defined as Performance Parameters and Fixed parameters as below: -
PERFORMANCE PARAMETERS: -
All the luminaries shall be finalised based on the performance requirement as below: -
Type of existing luminaire Rated Wattage of Rated Input Power of
existing luminaire LED luminaire (max.)
Sr. Parameter Data/ Details of For luminaire
No. 90 W 90 W (Offer by
1 Mounting Height (Vertical Distance 7.2 m (Approx.)
of luminaires from the floor level)
2 Width of the road Upto 24 mtr (ROW)
Upto 7 mtr (Carpet)
3 Average spacing 25 m (As per site
4 Measured Average Illumination 20 lx or more
Level(Based on the maintenance (As per site
factor of 0.90)
5 Tilt Angle (wrt to road surface) 0° to 15°
Signature of Bidder EXECUTIVE ENGINEER (M&E)
6 Min. Uniformity Ratio (Emin/ Eavg)
7 Min Transverse Uniformity Ratio
8 Correlated Colour Temperature 3000°Kto 4500°K
9 Colour Rendering Index (min.) >
10 Illumination Regulation <5% (wrt Ta & Line
Note: - Above performance parameter and fixed parameters (1, 3 and 4) shall be proved during on site testing.
Illumination Level:
The detailed calculation with uniform distribution including the lux distribution curve/ graph/spatial
distribution shall be submitted in support of the dimensions selected and variation thereof. The luminaire shall
be so designed that the illumination level shall be evenly distributed and shall be free from glare.
Signature of Bidder EXECUTIVE ENGINEER (M&E)
LED FIXTURES TECHNICAL PARTICULARS:-
The LED Street Light system will have to meet the following Specifications:
Sr No. Description GIDC Requirement Bidder's Specification
1 LED Fixture Make BAJAJ/PHILLIPS/SCH
(Mentioned Only One
2 LED Fixture Model No. Bidder has to specify as
per Technical design
Avg. 20 lx or more
(As per DiLuX/ Software
Lux Level Calculation
Mentioned Only One
3 90W with Fixed
Wattage of Fixtures and Programmable
Driver microprocessor based
Dimmable Driver
4 Stated Lumens output of For 90 W >=
5 LED Rated Operating Bidder has to specify
6 No(s) of LEDs (Chips) to be Bidder has to specify
Used in Luminaire
7 Luminaire manufacturer Bidder has to specify
8 Rated Input of LED Streetlight Bidder has to specify
9 Initial lumen output (Rated) Bidder has to specify
10 LED Luminaire's IS For 90 W
Registration Number &
11 BIS Certification (must 90W –
required otherwise
Signature of Bidder EXECUTIVE ENGINEER (M&E)
fitting shell not be Must be Valid Bureau of
accepted.) Indian Standard (BIS)
Certification of LED
luminaires respective
Model No / family of
LED luminaire models.
(In event of expiry of BIS
of the same model No,
Renewal license
application of same
Model to will be
presented along with
technical document
12 LED with Fixed For 90 W
(BIS approval is must
microprocessor based
along with R-number
Dimmable Driver’s make,
allotted by BIS.)
model no. and IS
Registration Number (R-
Number) (Separate
Registration Number (R-
Number) must required
otherwise fitting shell
not be accepted.)
13 Lumen output (as per LM79 Bidder has to specify
report, mentioning current
14 Lumen Depriciation (L70 Bidder has to specify
mentioning temperature in
Deg C and current mA)
15 Lighting Distribution Type Cut Off/ Semi Cut Off
type as per IESNA
Type II/ III Lighting
16 Maintenance Factor
17 Correlated colour >4000K ± 300K (Warm
temperature (CCT) White)
18 Protection Class IP 66 , Class 1 as per IEC
Signature of Bidder EXECUTIVE ENGINEER (M&E)
19 Impact Resistance of IK
complete luminaire
20 Avg. Ambient Temperature 35 deg C
21 Avg. Power Factor >
22 Material of Construction: - Bidder has to specify
23 Housing Construction The body shall be
robust, corrosion
resistant superior in
finish & without any
cracks or through holes,
made in a single piece
by high pressure die cast
ADC 12 aluminium alloy.
The luminaries shall be
monolithic construction
totally enclosed dust
tight & water proof. The
luminaries shall be class
I luminary. Degree of
protection shall be IP66
as defined in Appendix A
of IS10322 (Part-I
1982)with latest
24 Heat Sink/Dissipation Integrated with in
luminaire & The
luminaries shall be
adequate to permit
sufficient heat
dissipation through the
body itself, so as to
prevent abnormal
temperature rise inside
consequential damage
Signature of Bidder EXECUTIVE ENGINEER (M&E)
to cover & gasket
materials ,LEDs, lenses
& Electronic Driver.
25 Covers Toughened glass/IP
Lenses. It shall not get
discoloured shall not
suffer degradation due
to heat and ageing. The
cover shall preferably be
secured with suitable
metallic or stainless
steel hinges or with
metallic stainless steel
hinges at one end on
the footpath side and
with toggle at the other
end. The toggle shall
catch the glass cover
firmly and shall not get
released due to shock,
vibrations and breeze.
UV stabilized glass cover
shall not get cracked
due to frequent opening
and closing of hinges
and toggle. When the
luminaries is closed,
should conform with IP-
Note : Driver box
should have separate
dedicated cover to
ensure IP protection of
the LED side in case of
repair/maintenance.
26 Gasket A extruded silicon loop
gasket shall be provided
in the lantern body to
ensure a weather proof
seal between the UV
glass cover and the
metal housing to
exclude the entry of
dust, water, insects, etc.
When the luminaries is
Signature of Bidder EXECUTIVE ENGINEER (M&E)
closed, should conform
with IP 66 Class. Felt
gasket will not be
27 Application Outdoor use
28 System Efficacy - Lm/W at ≥150
25 deg C Amb. Temp.
(supported by LM79 Test
report from government
approved third party lab)
29 Guarantee/ Warranty Five (05) Years Free on-
site replacement
Guarantee/ Warranty
on the SITC of LEDs,
Fixture & Driver which
covering material
fixture, finish and
30 Protection Over Heat, Over Load,
Short Circuit, HV Surge -
4 KV (Inbuilt within
Driver) , external 10kv
30.1 Short Circuit protection Recovers automatically
after fault condition is
30.2 Over Voltage protection Should be able to
withstand 440V for
minimum 4 hours.
30.3 High – Low voltage cut off In side Luminary or a
device to be installed on
the pole in an IP
protected box sustaining
270V for Higher side
cutoff & 140 V on lower
side cut off- Beyond&
below it Shut down &
restore normal working
condition when voltage
Earthing Driver Unit shall have
provision for proper
Signature of Bidder EXECUTIVE ENGINEER (M&E)
31 Certification LM 79, LM 80, RoHS,
32 Marking Company LOGO
Engraving/ Embossing
on Body, GIDC – Estate
(Stickering not allowed)
33 Electrical Connector LED Wire with Flexible
3core 1.5 Sq MM FRLS
copper cable of Min.
meter long should be
34 Usage Hours Dusk to Down. (range
hours to 12.75 hours/
35 Beam angle 135 deg / 80 Deg
Horizontal Spread
Vertical Spread 80 Deg.
36 LED High Power White LED
of 3 Watt and above.
LED should be photo
biological complied
Bidder has to specify
36.1 Name of LED chip CREE / OSRAM / PHILIPS
manufacturer Lumileds / NICHIA /
SEOUL/LG Bridge Lux
(Mentioned Only One
36.2 LED chip model name and Bidder has to specify
36.3 LM 80 report from the LED Bidder has to specify
chip manufacturer on the
lumen depreciation
Signature of Bidder EXECUTIVE ENGINEER (M&E)
characteristics of the
specific LED chip employed
in the proposed luminaire
36.4 LED junction temp. in deg C >80
36.5 Rated Life of LED Chip at L70 > 50,000 Hrs (with Min.
(LM 70) 70 % Lumen
Maintenance @ Ta =
deg C ambient temp)
36.6 P/N junction temperature <100 Degrees C at
Junction point and <60
36.7 Lens Material Polycarbonate
36.8 Electrical connector(s) Bidder has to specify
36.9 Optical System The optical system will
consists of individual
Penut/PC/PMMA lenses
on high power LEDs
designed & tested to
achieve typical street
lighting distribution
from the LED lantern.
This is to ensure
maximum utilisation of
light flux on the
carriageway and
minimum glare on the
footpath side of the
lantern and also in the
direction of vehicular
36.10 Rated Supply Voltage (AC, 230/ 240 V
36.11 Optical Efficiency > 88%
36.12 Working Humidity 10% - 90 % RH
36.13 Working Temp in deg C 00 to 50 deg C
36.14 Input Voltage Range ( Vac) 90 to 300 V AC with
Auto resetting Safety
Signature of Bidder EXECUTIVE ENGINEER (M&E)
36.15 Input Frequency 50 Hz +/- 3% Hz
36.16 CRI (Color Rendering Index) >
36.17 Lumen Maintenance Factor 70% upto
Burning Hrs. Life Span
36.18 Uniformity Ratio >
36.19 Audible Noise Shall have Class-A sound
rating with audible noise
in power supply
36.20 Dimensions Bidder has to specify
36.21 Weight Bidder has to specify
37 LED Driver Type and Constant Current
Drivers should be
(Fixed Programmable constant current drivers
microprocessor based with separate
Dimmable Driver) compartment, also
driver compartment
should be IP66. Driver
should have cut off
protection above 300V
AC and should work
automatically at
nominal voltage. Driver
should also have Double
phase protection, no
load, open circuit and
short circuit protection.
SELV (Safety extra low
voltage) complied driver
with more than 65V DC
output. LED drivers
appropriately sealed/
potted. Driver Should
Certified. Necessary
certification submitted
along with data sheet.
37.2 Name of the manufacture Bidder has to specify
Signature of Bidder EXECUTIVE ENGINEER (M&E)
(Mentioned Only One
37.3 Model Name and Number Bidder has to specify
Bidder has to specify
37.5 Driver Efficiency > 90%
LED Driver’s rated life Bidder has to specify
(hours) {min. 50,000 (Expected lifetime of the
Operating hours) LED driver used in the
proposed luminaire)
37.7 Additional MOV protection Must be provided,
for protection of LED voltage rating of 270±
37.8 Protection of MOV must phase-neutral, neutral-
cover earth & phase-earth
37.9 LED driver Cut off Bidder has to specify
Voltage/optional
arrangement (if provided)
37.10 Estimated cost of driver Bidder has to specify
replacement by your
company, including
component and installation
37.11 Control Gear Integral Design (Tested
& Certified for
Performance & Safety
Government approved
37.12 Total Harmonic Distortion < 10 %
37.13 Total Harmonic Distortion < 10 %
37.14 IEC/BIS Compliance Confirming to IEC-
Signature of Bidder EXECUTIVE ENGINEER (M&E)
2,CISPR-15 or BIS
38 Certification Electrical safety
certification such as ISI
39 Test Reports:- The tenderer shall
submit the test reports
from Government
accredited test
laboratory of offered
luminaires confirming to
all type test as per IS
10322 (Part5 Sec 3)/ IS
essentially LM79(For
luminaire efficiency &
performance) and LM80
(For LED Source life
manufacturer) test
Engineering Society of
North America(IESNA)
along with the offer. IP
66 Report for luminary
and driver (for
protection from dust
and water), Type test
report of 10KV surge
test (For SPD as per IES
61000-4-5, IK08 report
for luminary along with
Manufacture’s should
have Valid ISO-9001-
2008, ISO 14000 and
ISO 45001 or equivalent
certificate for the
Bidder for In-House
Design, Development,
Testing, Manufacturing,
Marketing and Lighting
Signature of Bidder EXECUTIVE ENGINEER (M&E)
LM79 report along
with IES file of the
luminary must be from
NABL, ERDA, CPRI,
Note: - Above performance parameter and fixed parameters (1, 3 and 4) shall be proved during on site testing.
Illumination Level:
The detailed calculation with uniform distribution including the lux distribution curve/ graph/spatial distribution shall be
submitted in support of the dimensions selected and variation thereof. The luminaire shall be so designed that the
illumination level shall be evenly distributed and shall be free from glare.
Design for the GIDC – Estate Road
Sr.No GIDC- Estate specification requirement Bidder confirmation
LED Source (Input Average Illum. LED Source Average Illum. Level
Power) Including Level reqd. on (Input Power) reqd. on road
driver power in Watts road carriageway Including driver carriageway with LED
with LED power in Watts luminaire (Lux)
luminaire (Lux)
1 90 W 20 or More __ __
SIGNATURE AND THE SEAL OF MANUFACTURER SIGNATURE AND THE SEAL OF BIDDER
Signature of Bidder EXECUTIVE ENGINEER (M&E)
TESTING AND DOCUMANTATION
Performance Methods of Required Documentation Bidder to Confirm
Characteristic Measurement
Integral LED Lamp IESNA LM-79- Laboratory test results must be
Efficacy: Light 2008 ANSI C82.2- produced using the specific modules/
Output Input Power 2002 arrays and power supply combination
that will be used in production.
Power Factor ANSI C82.77- 2002 Laboratory test results must be
produced using the specific modules/
arrays and power supply combination
that will be used in production
Lumen Maintenance IESNA LM-80- LED manufacturer test results for
(L70) for LEDs 2008 Minimum 6000 hour lumen
maintenance data for the LED
packages/arrays/modules used in the
integral LED lamp.Lumen
maintenance data must meet at least
the following conditions: - Collected
at LED case or solder point
temperature (Ts) equal to or greater
than the verified TMP temperature of
the integral LED lamp; and-
Measured at a forward drive current
equal to or greater than the drive
current applied to the LEDs in the
integral LED lamp.
Colour Rendering ANSI C78.377- Laboratory test results must be
Index 2008 IESNA LM- produced using the specific modules/
79- 2008 CIE 13.3- arrays and power supply combination
1995 IESNA LM- that will be used in production
Chromaticity & ANSI C78.377- Laboratory test results must be
Correlated Colour 2008 IESNA LM- produced using the specific modules/
Temperature 79- 2008 CIE 15 : arrays and power supply combination
2004 that will be used in production
Signature of Bidder EXECUTIVE ENGINEER (M&E)
Colour Spatial IESNA LM-79- Self Certification
Uniformity and 2008 CIE 15 :
Colour Maintenance IESNA LM-58
Audible Noise Class-A sound Self Certification
rating: Power supply
not to exceed 24 dB
Integral LED lamp Provide copy of the actual three-year
Warranty manufacturer warranty included in
Safety of LED BIS Certificate LED manufacturer test results of the
Lamps safety test report with a general
coverage statement.
Test certificates ERTL / The bidder shall furnish test
CPRI/MNRE certificates certifying performance of
/ERDA/ NABL the integral luminaries’ for the tests
Accredited mentioned as below: a) Insulation
Laboratory resistance test b) HV test c) Over
Voltage Protection test d) Surge
Protection test e) Reverse polarity
test f) Temperature rise test g) Fire
Retardant test h) Photometric tests i)
IP class test j) Power Consumption
Driver Performance Testing
Safety of drives BIS Certificate Valid Driver BIS Certificate should
Surge test IEC 61000-4-5/BIS Laboratory test results must be
produced using the specific modules/
arrays and power supply combination
that will be used in production
SPD Test IEC 61000-4-5/BIS Laboratory test results must be
produced using the specific modules/
arrays and power supply combination
that will be used in production
SIGNATURE AND THE SEAL OF MANUFACTURER SIGNATURE AND THE SEAL OF BIDDER
Signature of Bidder EXECUTIVE ENGINEER (M&E)
Document Need to Submitted with Technical – Bid.
Sr. Description Remarks Mode of Submission
1 LM 80 Report of LED : ___ Attested hard Copy **
Chip(s) to be used
2 LM 79 report of LED : ___ -as above-
Luminaire(s) to be
3 Impact resistance (IK) : ___ -as above-
test report(s) for all
LED luminaires to be
4 LED driver test report : ___ -as above-
including efficiency
5 LED Driver approval : Documentary evidences are -as above-
certificate issued by must.
BIS with R-Number
6 LED Luminaire : Documentary evidences are -as above-
approval certificate must.
7 IES file(s) : The bidder must submit ies file Must be provided for all
generated from LM 79 from UL luminaires within 30 days
or NABL approved laboratory from the date of work order
All bidders must note specifically & submit their offer accordingly: -
All certificates/ documents/ submission(s) should be sealed and signed by relevant authority/ authorized
person/ authorized signatory only.
Bidder must check all certificate(s)/ document(s) to be furnished as mention in tender. If it is found (during
any stage) that any content of any certificate/ document is being modified in comparison with the original
then it will be considered as fraudulent practice and the bidder who has submit the offer/ tender will be held
responsible for such practice(s).
Further, various certificate(s) / document(s), which are issued by the other authority / agency / organization
/ govt. body shall be verified with the original certificate(s) / document(s) issued to the bidder, if required.
Moreover, in case it is found that the content of document(s) / certificate(s) is / are modified then action(s)
including debarring the bidder for min. 2 years for participation in any of GIDC's tender/ work and/or other
action(s) as deemed fit as decided by the competent authority shall be taken.
Signature of Bidder EXECUTIVE ENGINEER (M&E)
If, it is found that, OEM has provided wrong / false / manipulated information / data to the bidder then, all
the lighting products of concerned OEM will be banned for min. 2 years or other action(s) as deemed fit as
decided by the competent authority shall be taken.
All tests defined as “Acceptance Tests” other than IES LM 79 and IES LM 80, are allowed to be carried out
at Manufacturer’s works. LM 79 must be prepared by NABL approved laboratory only. LM 80 report is
prepared by LED Chip Manufacturer.
SIGNATURE AND THE SEAL OF MANUFACTURER SIGNATURE AND THE SEAL OF BIDDER
Signature of Bidder EXECUTIVE ENGINEER (M&E)
E-Tender (Online) Invitation Notice No: 08/2023-24/Sr No.5
Contractor’s/ Bidder’s Undertaking/ Certificate
NAME OF WORK: Supply, Installation, Testing & Commissioning (S.I.T.C.) of 7Mtr Hot Dip galvanised Octagonal
Streetlight Poles with LED Luminaries Outdoor Streetlight fitting, control panel and allied
accessories (Considering 25 Mtr. Distance between two poles ) incl. 5 Years Free comprehensive
Guarantee period with 5 Years Free Operation & Maintenance for GIDC Chaapra Estate,District-
I/we hereby declare that I/We have persuaded in detail and examined closely the specifications/ general terms &
conditions/ special terms & conditions/ important instructions/notes described in the tender documents. I/We
hereby agree to be bound by and comply with all such specifications/terms, conditions etc.
I/We also certify that I/We have visited the sites and inspected the locations of the proposed work and have
collected all information including any minor modification work(s) required at sites before quoting my/our
I/We also confirm that my/our offer is strictly in line with the tender specifications, stipulations, terms and
conditions etc. and understand that in the event of any deviations, technical or commercial, my/our price bid
will not be opened.
I/We also confirm that power consumption along with the required parameters will be proven during site
testing. I/ We also confirm that our offer will not be considered in case not opted for site testing of the sample
I/We have understand the tender specifications/ terms/ conditions/ all content of tender and particularly intent
behind the content and bind my/ ourselves for same.
If any items/ conditions/ specifications/ scope of work is mentioned differently at more than one place(s) by
chance, most appropriate decided by the department will apply & binding to the tenderer.
SIGNATURE AND THE SEAL OF TENDERER:
Signature of Bidder EXECUTIVE ENGINEER (M&E)
B1 Agreement Form and prevailing circulars
Signature of Bidder EXECUTIVE ENGINEER (M&E)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
0_DTP of SITC_Str Lt__Front Page Done.pdf
1_Technical BID cum PQ_Chhapara_STREET LIGHT WORK-06102026 Done.pdf
2_DTP_Chhapara_STREET LIGHT WORK.pdf
3_PRICE BID _Sch A_Sch_B Annexure- E_05122023 Chhapara.pdf
4.1 B-1 Agreement part 1.pdf
4.2 B-1 Agreement part 2.pdf
4.3 B-1 Agreement part 3.pdf
5.1_General Specification of Electrical Wiring in Govt Building.pdf
5.2_ Performance and Operation and maintanance bond.pdf
5.3_FOR ELECTRICAL MATERIAL.pdf
6.1_Contractor Registration Paripatra.pdf
6.2Clause in Tender for Registration of Labour - 09.03.2022.pdf
7.1_Foundation Drawing.pdf
7.2_Typical Drawing_Decorative Sword type Fitting-converted.pdf
7.3_Earthing Drawing.pdf
Download all tender documents and submit your bid