Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.8 LAccepted-AOC RAJKOT ROAD AIR FORCE STATION HALWARA 141106 PUNJAB | HALWARA | LUDHIANA | PUNJAB | 141106 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹34.2 L+₹25,550 (0.75%)Rejected-Finance MANDIR ROAD NEW ABADI AKALGARH AIR FORCE STATION HALWARA TEH RAIKOT DISTT LUDHIANA PB 141106 | LUDHIANA | LUDHIANA | PUNJAB | 141106 | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹39.0 L+₹5.0 L (14.7%)Rejected-Finance | L3 | Rejected-Finance Other than lowest |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
14 Dec 2023, 6:00 pmClosed
GE (AF) Halwara
GE (AF) Halwara
REPAIR MAINT OF WATER SUPPLY DISTRIBUTION PIPE LINE RISING MAIN CONTROL VALVE CLEANING OF O/H TANKS AND OTHER MISC WORKS OF WATER SUPPLY IN DOMESTIC AREA AT AF STATION HALWARA
2023_MES_628269_1
GE/HAL-50/2023-24
Open Tender
Civil Works
Item Rate
365 days
GE (AF) Halwara
MES ENLISTED CONTRACTORS CLASS D AND CATEGORY a(ii)
9 documents required · 9 mandatory
₹500
Yes
GE (AF) Halwara
₹80,000
Yes
8 Jan 2024
14 Nov 2023
16 Dec 2023
14 Nov 2023
14 Dec 2023
29 Nov 2023
Amount
Excavation in trenches not exc 1.5m wide and not exc 1.5M depth for laying of GI/CI/DI pipe lines etc getting out including forming bottom surface to required level and gradient in soft / loose soil complete all as specified and directed.
Returning and filling in excavated soil including spreading leveling, watering, well ramming in layers not exc 25 Cm thick complete all as specified and directed.
Removing of excavated materials not exceeding 50 Mtrs and depositing where directed at a level not exceeding 1.5 Mtrs above the starting point complete all as specified and directed..
Complete, arrangement , transporting, accessories for carrying out of Chemical Analysis test including Bacteriological Examination of drinking water. The Sample of drinking water for testing shall be taken from follwing locations for further submission to the Lab and submit the test report to Engineer-in-charge on quarterly basis. The cost of sampling, transportation and testing charges shall be born by the contractor. (a) Pump House No 1. (b) Pump House No 2 (c) Pump House No 7 (d) Pump House No 8 (e) Pump House No 9 (f) Pump House No 11 (g) Pump House No. 13 (h) Pump House No 12 (MAP Qtrs) Address of reputed laboratories are given below :- (i)The Shriram Institute for Industrial reasearch 19, University road Delhi-7. (ii) Dr Ghuman and Gupta Geotech Consultents Sec 17 A , Chandigarh or F-81 Phase vii , Industrial Focal point Mohali (Punjab). (iii) Water Testing Reasearch Laboratory Hisar Haryana. (iv) AFMC- PUNE (Deptt of PSM,Post Graduate Wing). (v) Delhi Test House A- 62/3 G.T Road Karnal road Azadpur Delhi-33. (vi) Alfa Test House
Taking out/burning out of leakage and damaged lead joints in the existing CI mains including removing the old lead carefully with out damaging the pipe complete for 80 mm bore of pipes complete all as specified and directed. Note :- Excavation and earth work will be measured and paid separately if repairs required to be carried out for joints only without taking out pipe)
All as per Srl item No. 5.00 above but 100 mm bore.
All as per Srl item No. 5.00 above but 150 mm bore.
All as per Srl item No. 5.00 above but 200 mm bore.
M&L for run lead joint including jointing materials such as spun yarn etc complete for the 80 mm bore CI pipe complete all as specified and directed.
All as per Srl item No. 9.00 above but 100 mm bore.
All as per Srl item No. 9.00 above but 150 mm bore.
All as per Srl item No. 9.00 above but 200 mm bore.
M&L for repair to rubber gasket joint for 80mm bore CI pipe including jointing materials complete all as specified and directed. Note :- Excavation and earth work will be measured and paid separately if repair carried out for joint only).
All as per Srl item No. 13.00 above but 100 mm bore.
All as per Srl item No. 13.00 above but 150 mm bore.
All as per Srl item No. 13.00 above but 200 mm bore.
Repairs to 80mm bore sluice valves such as replacement of unserviceable/warnout gland on stuffing box, rubber gasket of suitable size, filling or grinding to gate, replacement of worn out check nut, cleaning inside gate valve properly and remove scaling and other waste materials, replacement of worn out nut/bolts with washers, including testing of leakage and operation complete all as specified and directed.
All as per Srl item No. 17.00 above but 100 mm bore.
All as per Srl item No. 17.00 above but 150 mm bore.
All as per Srl item No. 17.00 above but 200 mm bore.
All as per Srl item No. 17.00 above but 300 mm bore.
Disconnecting and removing the unserviceable/wornout spindle from the sluice valve 80 mm dia after opening the nut and bolts and replace the same with new brass spindle of same size , length and turns including necessary fixing arrangements,testing and commissioning complete all as specified and directed.
All as per Sl item No 22.00 above but 100mm dia
All as per Sl item No 22 above but 150mm dia
All as per Sl item No. 22.00 above but 200 mm dia.
All as per Sl item No 22 above but 300mm dia
S&F Cast iron sluice valve 80mm dia bore both end flanged with brass spindle and cast iron handle wheel,heavy duty , class PN-1.0 ISI marked and fixing with existing pipe line including jointing material nuts,bolts,washers gasket as in replacement complete all as specified and directed.
All as per Srl item No. 27.00 above but 100mm bore.
All as per Srl item No. 27.00 above but 150mm bore.
All as per Srl item No. 27.00 above but 200mm bore.
Taking out existing CI pipe 80mm bore (including all fittings) with spigot and socket ends and lead joints / flange joint including burning out joints and removing lead from the ground cleaning the pipes free from sedimentation/scaling etc for reusing the serviceable pipes complete all as specified and directed. Note :- Excavation and earth work will be measured and paid separately.
All as per Srl item No. 31.00 above but 100 mm bore.
All as per Srl item No. 31.00 above but 150 mm bore.
Laying only cast iron pipes 80mm dia (Serviceable pipes obtained from dismantling shall be reused in the work) complete all as specified and directed.. Note : Joints and jointing material shall be measured seperately.
All as per Srl item No. 34.00 above but 100 mm dia.
All as per Srl item No. 34.00 above but 150 mm dia.
M&L for supply and laying CI pipe of 80mm bore with spiogt and socket ends centrifugally cast class LA suitable for lead joints laid in trenches including necessary cut to length to match the existing fitting/pipes complete all as specified and as directed.
All as per Srl item No. 37.00 above but 100 mm bore.
All as per Srl item No. 37.00 above but 150 mm bore.
Cutting the CI pipe 80mm dia and reducing the required length in positioning for insertion of new CI specials such as Tees/Reducers/Tail pieces/collers/sluice valve/Air release valve etc complete all as specified and directed.
All as per Srl item No. 40.00 above but 100 mm bore.
All as per Srl item No. 40.00 above but 150 mm bore.
M&L for CI/GI specials such as bends, tees, collars tail pieces flanges, etc complete suitable for CI/GI mains upto 200 mm sizes complete all as specified and directed
M&L for Cast iron double flanged non slam round type non return valve 80mm bore with by pass arrangements ISI marked heavy duty confirming to IS-5312 Part I / 84 of pressure rating PN 1.0 as in replacement complete all as specified and directed.
All as per Srl item No. 44.00 above but 100 mm dia bore
All as per Srl item No. 44.00 above but 150mm dia bore
All as per Srl item No. 44.00 above but 200mm dia bore
S&F cast Iron flanged type foot valve 80 mm bore with drilled flanged end all as per IS : 4038 with Cast Iron Strainer, nuts, bolts, washers etc as in replacement complete all as specified and directed.
S&F cast Iron flanged type foot valve 100 mm bore with drilled flanged end all as per IS : 4038 with Cast Iron Strainer nuts, bolts, washers etc as in replacement complete all as specified and directed
M&L for cast iron detachable joint suitable for 80mm dia bore pipes of CI/GI/PVC Pipe including nuts,bolts and rubber ring etc conforming to IS : 8794 (CL-15) all as specified and directed
All as per Srl item No. 50.00 above but 100 mm bore.
All as per Srl item No. 50.00 above but 150 mm bore.
All as per Srl item No. 50.00 above but 200 mm bore.
Taking up or down steel water GI tubing 15mm dia bore and connections including clearing the pipes free from scaling for reusing the same complete all as specified and directed.
All as per Srl item No. 54.00 above but 20 mm bore.
All as per Srl item No. 54.00 above but 25 mm bore.
All as per Srl item No. 54.00 above but 50mm bore.
All as per Srl item No. 54.00 above but 80 mm bore.
All as per Srl item No. 54.00 above but 100 mm bore.
Laying only steel water tubing GI medium grade 15mm bore with all new fittings such as bend, elbow, socket, nipple, tapers, reducers, unions etc as required, laid in trenches or fixed to wall etc complete all as specified and directed. Note :- Serviceable pipes obtained from dismantling shall be re-used in the work. Excavation and earth work will be measured and paid separately.
All as per Srl item No. 60.00 above but 20mm bore.
All as per Srl item No. 60.00 above but 25mm bore.
All as per Srl item No. 60.00 above but 50mm bore.
All as per Srl item No. 60.00 above but 80 mm bore.
All as per Srl item No. 60.00 above but 100 mm bore.
M&L for supply and laying 15mm bore galvanised steel water tubing, medium grade with necesary fittings/fixtures laid in trenches or fixed to walls/ceilings complete all as specified and directed. (Excavation and earth work will be measured and paid separately).
All as per Srl item No. 66.00 above but 20mm bore.
All as per Srl item No. 66.00 above but 25mm bore.
All as per Srl item No. 66.00 above but 50mm bore.
All as per Srl item No. 66.00 above but 80mm bore.
All as per Srl item No. 66.00 above but 100 mm bore.
Taking up or down 150mm dia existing centrifugally cast (spun) ductile iron pressure pipes for water with socket and spigot ends suitable for rubber gasket pushon joining complete all as specified and directed.
All as per Sl item No 72 above but 100mm dia
Supply and laying 150mm dia centrifugally cast (spun) ductile iron pressure pipes for water with socket and spitot ends suitable for rubber gasket pushon joining confirming to IS 8329:2000 having inside cement mortar lining and outside zine coating with finishing layer of blue epoxy in standard length, classification K-9 in standard length of 5.50/6.0 mtrs including push on joints with cement mortar lining complete all as specified and directed.
All as per Srl item No. 74.00 above but laying only complete all as specified and directed. Note : Serviceable pipes obtained from Sl item No 72 above shall be reused in the work.
Supply and laying 100mm dia centrifugally cast (spun) ductile iron pressure pipes for water with socket and spitot ends suitable for rubber gasket pushon joining confirming to IS 8329:2000 having inside cement mortar lining and outside zine coating with finishing layer of blue epoxy in standard length, classification K-9 in standard length of 5.50/6.0 mtrs including push on joints with cement mortar lining complete all as specified and directed.
All as per Srl item No. 76.00 above but laying only complete all as specified and directed.. Note : Serviceable pipes obtained from Sl item No 73 above shall be reused in the work.
S&F in repairs 15mm dia bore Gun metal gate valve with iron wheel head screwed both ends for iron pipes and fixed complete all as specified and directed.
All as per Srl item No. 78.00 above but 20mm bore.
All as per Srl item No. 78.00 above but 25mm bore.
All as per Srl item No. 78.00 above but 40mm bore.
All as per Srl item No. 78.00 above but 50mm bore.
S&F in repairs 15 mm bore Stop valve, cast copper alloy,screwed down high pressure with crutch or butterfly handle screwed both ends complete suitable for the of pipe complete all as specified and directed.
All as per Srl item No. 83.00 above but 20 mm bore of pipe
All as per Srl item No. 83.00 above but 25 mm bore of pipe
Dismantling the water mains from the delivery lines, lifting/taking up GI/UPVC Column pipes, pumping sets including submersible cable after disconnecting pumping sets of capacity 20 HP to 50 HP from cable, repairs to the defective submersible cable and jointing of submersible cable by using water proofing jointing kit, transporting the pumpset to civil workshop and back to site after repairs, replacement of defective column pipes, and including Lowering of submersible pump Sets, submersible cable, column pipes, reonnecting main delivery mains as existing and testing for satisfactory running and continuous flow of water etc complete all as specified and directed at bore wells at various location in domestic area. Note :- Repair to Motor & Pumping sets shall be measured and paid seperately. Column pipes as required for replacement shall be measured under relevant item of schedule.
Dismantaling the submersible pumpset of capacity 20 HP to 50 HP for servicing/repairs, replacement of defective parts, reassembling the motor properly and testing for satisfactory running, working with continuous flow of water etc including replacement of unserviceable suitable MS stud with nuts complete all as specified and directed. Note : Spare parts will be measured and paid under relevant item of schedule
Rewinding the motor of capacity upto 25 HP using required SWG of PVC insulated copper wire, making winding leak proof with superior quality insulating materials, properly jointing terminals with submersible cable, etc complete all as specified and directed.
Rewinding the motor of capacity 30 HP using required SWG of PVC insulated copper wire, making winding leak proof with superior quality insulating materials, properly jointing terminals with submersible cable, etc complete all as specified and directed.
Rewinding the motor of capacity 35 HP using required SWG of PVC insulated copper wire, making winding leak proof with superior quality insulating materials, properly jointing terminals with submersible cable complete all as specified and directed.
Rewinding the motor of capacity 50 HP using required SWG of PVC insulated copper wire, making winding leak proof with superior quality insulating materials, properly jointing terminals with submersible cable, etc complete all as specified and directed.
Part of Submersible pumpset of capacity 20 HP to 50 HP complete all as specified and directed :- Supply only Gun metal impeller
Supply only CI stage bowl
Supply only Brass neck ring
Supply only Thrust pad
Supply only Distance sleeve
Supply only Motor bush
Supply only Sealing kit
Supply only Thrust plate
Supply only Pump coupling stainless steel with key
Supply only Sand guard
Supply only Stud & Nut
M&L for dismantling the water mains from the delivery lines, lifting/taking up GI/UPVC Column pipes, pumping sets including submersible cable after disconnecting pumping sets 0.5 to 5 HP from cable, repairs to the defective submersible cable and jointing of submersible cable by using water proofing jointing kit, transporting the pumpset to civil workshop and back to site after repairs, replacement of defective column pipes, and including Lowering of submersible pump Sets, submersible cable, column pipes, reonnecting main delivery mains as existing and testing for satisfactory running and continuous flow of water etc complete all as directed by Engineer in charge at bore wells at various locations under GE(AF) Halwara Note: Repair to Motor & Pumping sets shall be measured and paid seperately. Column pipes required for replacement shall be measured under relevant item of schedule
Dismantaling the submersible pumpset of capacity 0.5 HP to 5.00 HP for servicing/repairs, replacement of defective parts, reassembling the motor properly and testing for satisfactory running, working with continuous flow of water etc including replacement of unserviceable suitable MS stud with nuts complete all as specified and directed. Note : Spare parts will be measured and paid under relevant item of schedule
Rewinding the submersible motor of capacity 0.5 to 5.00 HP motor using required SWG of PVC insulated copper wire, making winding leak proof with superior quality insulating materials, properly jointing terminals with submersible cable, etc complete all as directed by Engineer-in-charge.
Part of Submersible pumpset of capacity 0.5 HP to 5.00 HP complete all as specified and directed. Supply only Gun metal impeller
Supply only Stainless steel shaft
Supply only Thrust pad
Supply only Distance sleeve
Supply only Motor bush
Supply only Pump coupling stainless steel with key
MS column pipe medium grade of size 100mm dia 10' long flanged both ends and slot made for submersible cable as in replacement complete all as specified and directed.
All as per Sl item No 112 above but 125mm bore pipe
Opening and disconnecting centrifugal pump from electric motor 12.5 HP capacity, including shifting, transportation, overhauling shaft metering, welding , brazing and grinding the shaft and replacing of worn out parts and re-assembling and connecting it to the electric motor complete all as specified and directed. Note : (i) The unit rate shall include for minor spares such as bolts, nuts washers, oil seal, gasket, greasing etc as required. (ii) Major spares as required shall be measured and paid for separately.
All as per Srl item No. 114.00 above but 5 to 7.5 HP
All as per Srl item No. 114.00 above but 0.5 to 3.00 HP including booster motor
Rewinding of electric motor of capacity upto 5 HP for centrifugal non clog pumping set with supper enameled copper winding wire of existing gauge, size and weight with insulating material complete all as specified and directed.
All as per item No 117.00 above but upto 7.5 HP
All as per item No 117.00 above but upto 12.5 HP Note for Sl item No 88 to 91, 105, 117 to 119 :- Motor of any site undergone repair/rewinding will be liable for repair again free of cost in case of same fault occuring during the engagement of contract. Repair/rewinding of the motor will be measured only once for a particular site/motor. The downtime at site/time required for repair of motor if is more than 24 hrs, the contractor will be liable to provide & install a standby motor at site during the downtime with no extra cost to the department failing to this the contractor will be liable to penalty of Rs 500/- every hour post 24 hrs repair timeline.
S&F coupling with rubber bush and coupling nuts & bolts for 12.5 HP non clog pumping set complete
Parts of electric motor 12.5 HP complete all as specified and directed. Supply only Impeller GM
Supply only Gland box
Supply only Ball bearing for 12.5 HP non clog pumping set
Supply only Ball bearing of electric motor upto 7.5 HP
Supply only Gun metal bushes of pump upto 7.5HP
Supply only MS coupling of pump upto 7.5 HP
Supply only Ball bearing of electric motor upto 5 HP
Supply only Gun metal bushes of pump upto 5 HP capacity
Supply only Rubber coupling of pump upto 5 HP
S&F Butterfly valve of size 300 mm dia as in replacement.
S&F Butterfly valve of size 150 mm dia as in replacement.
S&F Butterfly valve of size 100 mm dia as in replacement.
S&F Butterfly valve of size 80 mm dia as in replacement.
S&F in replacement single phase Preventor, Model VSP- D2-L&T/Telemechanic
S&F shunt capacitor suitable for motor upto 50 HP capacity
Hand Wheel for Actuator suitable for 200mm/150mm/100mm/ 80mm dia Butterfly Valve as in replacement.
S&F Fully automatic star delta starter of range 17-24 relay rating, 3 phase, 415 volt, in sheet metal enclosure with surge protection device, single phase preventor 50 Hz, complete suitable for 20 to 50 HP capacity submersible pump set including dismantling, disconnecting as in replacement complete all as specified and directed.
S&F Fully automatic Auto start Direct on Line starter in SS (stainless Steel) enclosure with surge protection device, single phase preventor, 230-400 V Coil Overload relay range 3.8/6.0 A Back up Fuse (A)20 Suitable for Submersible motor capacity upto 3.00 HP as in replacement complete all specified.
S&F in replacement fully automatic Auto start Direct on Line starter in SS (stainless Steel) enclosure with surge protection device, single phase preventor 230-400 V Coil Overload relay range 6.0/9.3/3.8 A Back up Fuse (A)25 suitable for Submersible motor capacity 5/3.7 HP/KW complete all as specified and directed.
Fully automatic Auto start Direct on Line starter in SS (stainless Steel) enclosure with surge protection device, single phase preventor, 8.9-13.5 A with 230-400 V Coil Overload relay suitable for CF Pump upto 10.00 HP as in replacement complete all as specified and directed.
Fully automatic Auto start Direct on Line starter in SS (stainless Steel) enclosure with surge protection device, single phase preventor, 6.00-9.3 A with 230-400 V Coil Overload relay suitable for CF Pump upto 20.00 HP as in replacement complete all as specified and directed.
S&F in replacement single phase 1.5 HP relay 8.9-13.5 contactor rating 16 Amp SPS with 2P contactyor+overload relay (Ammeter+voltmeter) with 160-220V AC coil complete all as specified and directed.
Supply only 2.5 sqmm single core cable life line plus S3 yellow HRFR PVC flexible cable complete all as specified and directed.
S&F isolator single pole 32 Amp as in replacement complete all as specified and directed.
S&F MCB SPN 6 to 40 Amp, 415V including all terminals fittings as in replacement complete all as specified and directed.
S&F in replacement, single core PVC insulated unsheathed stranded copper FT conductor of size 6 sqmm 1100 volt grade confirming to IS 694-1990 complete all as specified and directed.
All as per item No 146.00 above but 10Sqmm.
All as per item No 146.00 above but 16Sqmm.
S&F First Aid chart with clear glass cover & wooden frame of size as directed by Engr-in-Charge as in replacement complete all as specified and directed.
All as per Sl item No 149 above but shock treatement chart.
Supply Only First Aid Kit box No-08 (Size : 360 mm x 150 mm x 80 mm) containing following items :- (a) Dettols bottle100 ml 02 bottles (b)Antiseptic Ointment 100 mg © Crocin tabletes 01 strips ( containings 10 Tablets each). (d) Hydrogen peroxide 50 ml 01 bottle (e) Cotten small rolls 2 Nos (f) Cotten strip small roll 04 Nos (g)Moove tube 01 Nos (h) Betadine Tube 100 mg
Supply only orthotodoline solution for chlorine test in 500 ML bottle complete all as specified and directed.
Supply only Chlorine gas test kit up to 2 PPM. Make : Pearl Filter/RMCO complete all as specified and directed.
S&F in replacement Submersible Cable 2.5Sq mm flat Three Core PVC Insulated & PVC Sheathed copper conductor 1100 Volts for Submersible Pump Moter complete all as specified and directed.
All as per item No 154 here-in-before for but 4Sq mm.
All as per item No 154 here-in-before for but 6Sq mm.
All as per item No 154 here-in-before for but 10Sq mm.
All as per item No 154 here-in-before for but 16Sq mm.
All as per item No 154 here-in-before for but 25Sq mm.
M&L for cleaning the OH RCC tank 100000 gallons capacity at staging height exceeding 15 metre and not exceeding 21.5 meter staging at Pump House No-01 located in Domestic area removing the mud, silt, sand, foreign particles, sludge etc from inside the tank, washing the walls, floor and roof from inside the tank including all pipes and applying disinfecting chemical (Chlorine) including closing of opening at pressure release/air passage using galvanised mild steel wire cloth 0.63mm nominal dia of wire and average width of apeture 1.40mm and fixed with tinned tacks or galvanised wire staples (Total quantity of wire cloth not exceeding 15.00 Sqm in each job), applying one coat of synthetic enamel paint to rising main pipes/ delivery pipes/wash out pipes/over flow CI/GI pipes line 80mm to 150mm dia existing at site, grills. staircase steel surfaces, railing after preparation of surfaces and two coat of Apex painting on external plastered surfaces of columns, beams, landings, stairs, chajjas/projections etc and overhead tank dome (Top & bottom) as per existing colour including writing the date of cleaning with white paint over black colour base using synthetic enamel paint complete all as specified and directed. Note : (i) The quoted rates are deemed to be inclusive for shuttering/scafolding & supports required upto 21.5mtr height of OH tank. (ii) The Colour & Make of synthetic enamel paint and Apex paint shall be approved by GE before procurement. (iii) The contractor will submit the accidental insurance of the workers from Insurance Company before engaging them on work and submit the same to the Engr-in-Charge for record. (iv) The contractor is responsible for providing the safety tools/proper scafolding to the workers and rates are deemed to be included for the same. (v) The contractor is responsbile to provide any compensation/accidental expenditure to the workers during mishappening if any. (vi) The Govt will not pay any compensation/accidental expenditure to the workers.
All as per item No 160 above but 50000 Gallons at 60 ft staging at pump house -8 near Officer Gate.
All as per item No 160 above but 50000 Gallons at 60 ft staging at OP area NCEs Qtr New Pump House No 13.
All as per item No 160 above but 75000 Gallons at 60 ft staging at pump house -7 Officers Enclave.
All as per item No 160 above but 50000 Gallons at 60 ft staging at pump house -9 Rattowal Complex.
All as per item No 160 above but 75000 Gallons at 60 ft staging at pump house -11 Near MES MT.
All as per item No 160 above but 100000 Gallons capacity of semi under ground sump staging at KK Ground Pump House No-12
All as per item No 160 above but 100000 Gallons capacity of semi under ground staging at RP Area
All as per item No 160 above but 11000 Gallons capacity mounted on multi storey buildings at MAP Accn
Supply and fix in replacement calcium based chlorination dosing pump and agitator system installed at water supply installations at different location in Domestic area including testing complete all as specified and directed by Eng in Charge.
Supply only Calcium Hypo hypochlorite (65% to 70% chlorine content in granular and tablet form) in 45 Kg packing as approved by GE complete all as specified and directed.
M&L for disconneting three phase power supply from LT panel and taking out submersible pump motor set of capacity 20 to 50 HP along with column pipe and submersible cable including provision of developing of bore well for cleaning of water with the help of air compressor machine of rating pressure capacity upto 250 PSI/550 cfm till the borewell found sand free and clear water is obtained from the bore well and all the blockage removed from the stainer pipes including opening the bore well upto depth 400 feet and reassembling all the column pipe and pump with motor duly fixed with submersible cable, joints and replacement of all defective nuts, bolts, washers, gasket packing etc and lowering the electrical connections complete all as specified and directed.
S&F in replacement Ammeter 25 A for three phase submersible pump starter complete all as specified and directed.
S&F in replacement Ammeter 50 A for three phase submersible pump starter complete all as specified and directed.
S&F in replacement volt meter 0-500 volts for three phase submersible pump starter complete all as specified and directed.
S&F in replacement volt meter 0-300 volts for three phase submersible pump starter complete all as specified and directed.
Supply and fix in replacement of battery 150 AH complete all as specified and directed.
S&F in replacement MCCB 4 Pole 100A breaking capacity ICU at 415 (50KA) complete all as specified and directed.
S&F in replacement MCCB 4 Pole 250A breaking capacity ICU at 415 (50KA) complete all as specified and directed.
S&F in replacement MCCB 4 Pole 200A breaking capacity ICU at 415 (50KA) complete all as specified and directed.
S&F in replacement MCCB 4 Pole 160A breaking capacity ICU at 415 (36KA) complete all as specified and directed.
S&F in replacement MCCB 3 Pole 100A breaking capacity ICU at 415 (36KA) complete all as specified and directed.
S&F in replacement MCCB 3 Pole 63A breaking capacity ICU at 415 (36KA) complete all as specified and directed.
S&F in replacement off load change over switch AC-21 200 Amp side handle in sheet encloser, 415 V AC, 50 Hz complete all as specified and directed.
S&F in replacement off load change over switch 100A AC-23 side handle in sheet encloser, 415 V AC, 50 Hz complete all as specified and directed.
S&F in replacement off load change over switch AC-21 400 Amp side handle in sheet encloser, 415 V AC, 50 Hz complete all as specified and directed.
S&F in replacement power contactor 3 pole AC control AC-3 rating 32 Amps (20 HP/15KW) 415 volts including Aux contact 1 No + NC with colil voltage 380/415 volts complete all as specified and directed.
S&F in replacement power contactor 3 pole AC control AC-3 rating 40 Amps (20 HP/15KW) 415 volts including Aux contact 1 No + NC with colil voltage 380/415 volts complete all as specified and directed.
S&F in replacement power contactor 3 pole AC control AC-3 rating 63 Amps (50 HP) 415 volts including Aux contact 1 No + NC with colil voltage 380/415 volts complete all as specified and directed.
S&F in replacement Electronic timer for three phase submersible pump starter complete all as specified and directed.
S&F in replacement PVC (Heavy duty) electric cable with copper conductor 1100 volts cross section 6 Sqmm 3 core complete all as specified and directed.
M&L for boring under road/path/hardstanding to pass the pipe lines upto 150mm dia bore with mechanical arrangements complete all as specified and directed.
Cleanning of UG static water tank of approximate capacity up to 20000 gallons in domestic area after dewatering the tank using diesel engine pump sets and cleaning with a steel wire brush, removing mud, sludge, foreign articles, ulgac etc and sand upto bottom level and washing with bleaching powder solution and applying one coat of white wash inside tank including writing date of cleaning with white colour over black colour base of snythetic enamel paint complete all as specified and directed. Note : Sludge/waste material shall be thrown away from SWT premises as directed by Engr-in-Charge.
S&F copper thimbles of size 6 to 25 sqmm conductor as in replacement complete all as specified and directed
S&F aluminium thimbles of size 6 to 50 sqmm conductor as in replacement complete all as specified and directed
S&F in replacement 15mm dia bore high density polethylene pipes (HDPE) of pressure rating 6 kgf/sqcm laid in trenches/ borewell complete all as specified and directed
All as per Sl item No 195 above but 20mm dia bore
All as per Sl item No 195 above but 25mm dia bore
M&L for preparation of old painted steel surfaces of any description over 10cm width and girth and applying one coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
S&F distribution chart / electronic board for water/electrical distribution network to the writing letter locations etc in replacement complete all as specified and directed
S&F pressure gaugeof capacity 0-200 Psi/0-14 Kg/Sqcm including connected accessories for installation of the same for pump at pump houses / tubewell in replacement complete all as specified and directed by Engineer in charge. The rate of all connected items shall be deemed to be included in the quoted rates.
M&L for writing letter for figures over RCC OH tank /sign board surface or iron surface or any other loc near pump house (block, roman, or italic n.exc 90cm height) complete all as specified and directed by Engineer-in-Charge.
Supply, fabricate and fixing in replacement mild steel work conforming to Fe-290, E-165 as in framed grills, gratings, framed guard bars, ladder, framework of volve pit cover, water tanks etc or similar work as ordered and febricated from MS rolled section of any size and shape as complete all as specified and directed by Engineer-in-charge. Note: MS sheet where required shall be measured and paid seperately)
S&F mild steel plate / sheet plain or chequered 3.00mm thick cut to piece as required and fixed to MS frame work be means of electric arc / gas welding complete all as specified and directed by Engineer-in-charge
M&L for masonary valve pit of size 1.2mx1.2mx1.1m (internal size) using 100mm thick PCC 1:4:8 type D2 using 40mm graded stone aggregate for foundation, 230mm thick brick wall with sub class `B’ bricks built in CM 1:6, 40mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate for coping, 15mm rendering in CM (1:4) on internal surfaces, 15mm thick rendering in CM 1:6 on external surfaces including provision of MS sheet cover 2mm thick fixed to MS angle frame made of 50x50x6mm thick and applying 2 coats of synthetic enamel paint over one coat of red oxide primer to steel surfaces and making locking arrangements including dismantling old unserviceable valve pit with necessary excavation and earth work in any type of soil complete, all as specified and directed.
All as per item No 204 but size 0.9mx0.9mx.86 m.
Supply, installation, testing and commissioning in replacement LT panel, indoor cubical type whether and vermin proof totally enclosed made out of 3.00 mm thick CRCA sheet machine preesed of suitable size, suitable to operate on 3 phase 4 wire system, 415 volts, 50 Hz with front and rear openable with locking arrangement incl shutters for mounting switchgear etc, bottom gland plate with sufficient numbers of circular cable entry holes, prewired complete duly powder coated with 7 tank process mounted on agle iron stand made out of angle size 50 x 50 x 6 mm grouted in PCC (1:3:6) 450mm above ground level, 400 mm below ground level comprising with following complete all as specified :- (a) Bus bar strip, four pole and capacity 250 Amps copper strip size be based on 1.5 Amps per sqmm, coloured with plastic coated insulated and sleaves in four colours (Red, Yellow, blue and black) fixed on porcelain insulators with necessary nuts and bolts and washers etc. (b) Indicator with LED lamps for RYB, 3 phase with MCBs set of three-01 Set INCOMING (a) MCCB 125 Amp, 415 V, 25 KA, 4 pole with microprocessor release - 02 Nos (b) Panel meter of size 96 x 96 mm with LCD display, accuracy class 1.0, having parameters voltage, current, frequency, power factor, power & energy with RS 485 including suitable CT complete all as specified, duly prewired with suitable size of copper insulated FRLS wire with universal code including suitable CTs complete all as specified and directed. OUTGOING (a) MCCB 100 Amp, 415 V, 25 KA, 4 pole with adjustable thermal magnetic release-02 Nos (b) Onload changeover switch 100 A, 4P 415 V open execution type -01 . (c) MCB SPN 32 Amp, 240 V, 10 KA, 02 Nos. (d) MPCB 63 A -01. (e) SP preventor- 01. (f) Automatic Star delta starter three phase 36-120A-01 Nos.
M&L for earthing in replacement for LT Panel / Feeder Pillars with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of the earth plate at a depth not less than 1.5 metre below ground level earth plate surrounded by 15cm thick and packed with layer of charcoal dust and common salt earth lead GI strip 32mm x 6mm by means of bolts, nuts, check nuts and washers of galvanised iron and thimbles and other end connecions to main switch board and protected by galvanised iron light grade 50mm dia pipe, 20mm dia pipe for water with funnel, wire mesh, PCC chamber in cement concrete (1:3:6) using 20mm graded stone aggregate and 50mm thick RCC cover (1:2:4) type B-1 using 20mm graded stone aggregate and 8mm dia TMT bar @ 10cm c/c both way including MS frame using MS angle of size 45mmx4mmx5mm complete all as specified and shown in electrical plate No-5 in MES Schedule (Part-I). Notes - (i) Outer edge of earth pit will be 1.5 metre away from the outer edge of PCC chamber. (ii) GI wire upto DBs earth connection is included in this item. (iii) Water pipe shall be provided in slantling position.(Earth wire and protection pipe upto 7.50m length is included in the unit rate)
Supply & fixing in replacement LED aviation obstruction light fitting 302 LED IP 55 with all accessories,including giving power supply/connection to the light using 3 multi core copper wire of length as required,brackets for fixing arrengement etc. on over head tank complete all as specified & directed . Make : Bajaj/Havells/crompton. Note :- Payment of this item will only be made post successful testing of the obstruction light by Engr-in-charge. Rate of all will be deemed to be included in quoted rate.
Supply , fixing, testing and commssioning electonic water level indicator device sensor system with LED , 10 level showing water level in cm/mtr (before overflow) as per predetermined limits and power failure as in replacement complete with all accessories complete all as specified & directed.
S&F in replacement aluminium strip of size 25mm x 3 mm with new saddle and fixing screw for roof conductor/down conductor above ground.
S&F in replacement test point terminal block made of gun metal or phosphorus size 75mm x 75mm x25mm duly drilled and screwed including provision of nuts, bolts etc complete.
S&F in replacement air termination rod single pointed aluminium of dia 12mm and 300 mm long.
M&L for energy saving & environmental friendly long life versatile pressure die-cast aluminium housing luminaire with heat resistant glass and suitable optics for uniform distribution of light 60 watt LED for building security lights with high efficiency electronic driver BIS approved, having IP-65/66 protection, surge protection min 2 KV power factor more than 0.9 complete operative on AC supply 140 volts to 270 volts pre-wired and product should be made in India only including GI pipe medium grade 40mm dia 1.2 mtr long bend to shape as required and fixing with two nos MS clamp of size 40x6mm for fixing of street light fitting as in replacement complete all as specified and directed. Note : (i) Contractor shall be provided 2 years written manufacture's guarntee for the LED fixture complete including driver from the certified date of completion. (ii) Contractor shall be prodce LM-79 & LM-80 report of NABL accredited laboratory from manufacturer's.
Kular and Company
CHOUDHARY ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .