Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹98.1 L
Closing Date
20 Dec 2021, 2:00 pmClosed
XEN JPDCL ED RAJOURI
OFFICE OF XEN, JPDCL ED RAJOURI
SUPPLY, INSTALLATION, TESTING AND COMMISSIONING FOR CREATION OF 16x25 KVA S/STN and 4x63 kVA S/STN ALONG WITH HT/LT NETWORK UNDER TSP FOR BLOCK KOTRANKA BUDHAL ON TURNKEY BASIS.
2021_PDD_150295_1
EDR/65 of 2021-22
Open Tender
Electrical Works
Turn-key
60 days
RAJOURI
Please refer Tender documents.
4 documents required · 4 mandatory
₹2,000
XEN, JPDCL ED RAJOURI
Exempted
5 Apr 2022
27 Nov 2021
22 Dec 2021
27 Nov 2021
20 Dec 2021
29 Nov 2021
27 Nov 2021 - 4 Dec 2021
Amount
HT Line (Note: 1. Key Material ie Poles and ACSR Conductor is to be inspected before Delievery at Factory level 2. Scrap Material must be returned to Divisional Store, ED Rajouri. 3. All Material must be as per IS/REC Standard. Hence Price quoted must be must be absolute in all respect and no extra charges will be paid. For detailed specifications please refer attached SBD which forms a part of the tender)
Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and erection of 8 Mtr. Long ST Poles (410, SP-15) with pit excavation. (As per recommended IS/REC Standard)
Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site, Laying, stringing and binding of conductor including joints with PG clamps of required size 30 mm2 ACSR ( Weasel) (As per recommended IS/REC Standard)
Supplying and erection of GI Channel cross-arm (75x40x6mm) with GI Angle Braces, GI Pole Top Bracket (50x50x6 mm) including GI back clamps of 50X8 mm for fixing Cross arm and pole top bracket without making holes in the ST pole as per REC standard. NOTE: Please refer Pole drawings for details (As per recommended IS/REC Standard)
Supplying and fixing of 11 kV Pin Insulators (polymer) with Pins ( 5 KN) (As per recommended IS/REC Standard)
Supplying and fixing of 11 kV Disc Insulators (polymer) Complete with fittings (45KN) depending upon conductor size. (As per recommended IS/REC Standard)
Supply and erection Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete for 11 KV Tension points. (As per recommended IS/REC Standard)
Supplying and fixing of Galvanized Nuts and Bolts of sizes.
16 x 25 kVA and 4 x 63 kVA Sub Stations (Note: 1. Key Material ie Poles and ACSR Conductor is to be inspected before Delievery at Factory level 2. Scrap Material must be returned to Divisional Store, ED Rajouri. 3. All Material must be as per IS/REC Standard. Hence Price quoted must be must be absolute in all respect and no extra charges will be paid. For detailed specifications please refer attached SBD which forms a part of the tender)
Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and installation of 25 kVA, 11/0.433 kV Distribution Transformer, Energy Efficiency Level-II, Aluminium Wound, oil filled, with LT cable termination box with detachable Aluminium Gland Plate.(As per recommended IS/REC Standard)
Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and installation of 63 kVA, 11/0.433 kV Distribution Transformer, Energy Efficiency Level-II, Aluminium Wound, oil filled, with LT cable termination box with detachable Aluminium Gland Plate.(As per recommended IS/REC Standard)
Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and erection of 8 Mtr. Long ST Poles (410 SP-15) with pit excavation (As per recommended IS/REC Standard)
Supply and installation of Gapless Surge Arrestor,9 kV,10 kA, LA with (polymer) housing, Station Type (As per recommended IS/REC Standard)
Supply and installation of 11 kV Horn, Gap Fuse Set, 3-phase, 200A (As per recommended IS/REC Standard)
Supply and installation of 11 kV, G.O AB Switch Vertical Type , 3-phase, 200A (As per recommended IS/REC Standard)
Supplying and erection of GI channel/angle cross arms including fixing GI channels ( 100x50x6mm) / (75x40x6 mm) / angles(50x50x6 mm) with 50X8 mm GI back clamps/braces without drilling/punching holes in the poles. (As per recommended IS/REC Standard)
Supply and erection Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete for 11 KV Tension points. (As per recommended IS/REC Standard)
Supply and fixing of Un Armoured Single Core XPLE, FRLS Cable with Thimbles (120 mm2) (As per recommended IS/REC Standard)
Supplying and fixing of 11 kV Pin Insulators (polymer) with Pins ( 5 KN) (As per recommended IS/REC Standard)
Supply and installation of 11 kV Disc Insulators (polymer) Complete with fitting( 45 KN) (As per recommended IS/REC Standard)
Supplying and fixing of Galvanized Nuts and Bolts of sizes.
Excavation of 3 Nos Earthing Pits of dia = 600 mm and depth= 3000 mm as per REC specified spacing(Delta Configuration) Supplying and fixing of 3 No. sub station Earthing by GI Pipe 40 mm or GI Rod 20mm, 2.5 mtr long through GI Strip of size 50X6 mm for neutral earthing and GI Stip of size 25X3 mm for connection with transformer body , Pole , LA and GO handle, through GI Nuts, Bolts and Clamps, refilled with earth enhancement materials and earthing chamber made of brick masonary with RCC Slab Cover. (Note: For Neutal and LA earth pipe shall be kept separate) (As per recommended IS 1239 IS 2629/85/REC Standard)
LT Line (Note: 1. Key Material ie Poles and ACSR Conductor is to be inspected before Delievery at Factory level 2. Scrap Material must be returned to Divisional Store, ED Rajouri. 3. All Material must be as per IS/REC Standard. Hence Price quoted must be must be absolute in all respect and no extra charges will be paid. For detailed specifications please refer attached SBD which forms a part of the tender)
Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site and erection of 8 Mtr. Long ST Poles (410, SP-15) with pit excavation. (As per recommended IS/REC Standard)
Supply, Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site, Laying, stringing and binding of conductor including joints with PG clamps of required size 20 mm2 ACSR (Sq) (As per recommended IS/REC Standard)
Supply and fixing of GI Mukky clamps (50x8) along with LT Polymer Shackle insulators (16 kN) and GI back clamps (50x8) to be fixed without drilling/punching of poles on ST poles. (As per recommended IS/REC Standard)
Supply and erection Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete for 11 KV Tension points. (As per recommended IS/REC Standard)
Supplying and fixing of Galvanized Nuts and Bolts of sizes.
Gee Sab Electricals
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .