Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.6 LAccepted-AOC | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹13.9 L+₹2.3 L (19.7%)Rejected-Finance | L2 | Rejected-Finance highest bidder | |
| 3 | L3₹14.2 L+₹2.6 L (22.4%)Rejected-Finance BBMB SUNDERNAGAR HIMACHAL PRADESH | SHIMLA | HIMACHAL PRADESH | 172101 | L3 | Rejected-Finance highest bidder | |
| 4 | L4₹14.4 L+₹2.8 L (24.3%)Rejected-Finance | L4 | Rejected-Finance highest bidder | |
| 5 | L5₹14.5 L+₹2.9 L (25.0%)Rejected-Finance | L5 | Rejected-Finance highest bidder |
Tender Value
₹17.2 L
EMD Value
₹34,380
Closing Date
31 Aug 2020, 11:00 amClosed
Executive Engineer
Jal Shakti Division Jawali
1. PLWSS to PC habitation to village HarsarHawalChakban in Tehsil Jawali District Kangra sub head L J and testing of GI pipe rising main and Prov and installation of submersible pumping machinery with allied accessories
2020_HPIPH_39738_1
EE/JSV/DIV/JWL-2020/3471-3520 dt.10.08.2020
Open Tender
Civil Works - Water Works
Item Rate
90 days
Harsar
Please refer Tender documents.
8 documents required · 8 mandatory
₹400
Yes
EE Jawali
₹34,380
Yes
18 Nov 2020
12 Aug 2020
31 Aug 2020
12 Aug 2020
31 Aug 2020
12 Aug 2020
Amount
Sub-Head:- Laying, jointing & testing of Rising Main Excavation in foundation and trenches ( For pipes and pits ) up to all depths in all classification of earth work such as pick work ,jumper work ,saturated soil including bailing or pumping out water ,blasting soft/hard rock or chiseling soft/hard rock where blasting is prohibited in all lifts including trimming & dressing of sides, leveling of beds to correct grade i/c shoring /strutting ,planking ,timbering & dewatering wherever required ,stacking the usable & unusable material /soil separately & after laying ,jointing & testing of pipes ,returning the useable soil in trenches in 15 cm ,layers including consolidating of such deposited layer by ramming & watering & then deposing of all surplus excavated soil / unusable material as directed with in all leads and lifts including restoration of unmetalled surfaces to its original condition and including cost of diversion for traffic , night signals ,fixing caution boards ,crossing over trenches for access to houses ,fencing etc. including jungle clearing, uprooting of rank, vegetation, grass bursh wood, trees and sapling of all girth/ depth complete in all respects with in all lead and lifts as per direction & satisfaction of Engineer - in - charge.
Laying, jointing & testing in trenches to be levelled to grades, BIS marked GI pipes conforming to BIS:1239 ( latest with up to date amendments ) of 150 mm dia ( Medium class ) duly flanged after every 5th pipe with intermediate butt welded joints including the cost of flanges, bends of required degree, tee/ short pieces made from parent tubes of different degrees cutting , welding & jointing with flanges conforming to table as specified below of BIS:6392 ( latest with up date ammendments ) two layers on both faces welded as per BIS:816 ( latest with up date ammendments ) with electrodes conforming to BIS 814 (latest with up date ammendments ) & provided with nuts & bolts BIS 1369 (latest with up date ammendments) of required sizes, 4.80 mm thick ( Champion make ) compressed asbestos fiber gasket or synthetic rubber gaskets conforming to BIS 2712 (latest with up date ammendments ) & approved specification as per site conditions including flushing, cleaning and hydraulic testing complete to respect with in all leads and lifts as per the direction and satisfaction of the Engineer-in-charge.
T/Well to collection tank ( T/Well Badela)
GI pipe 65 mm (M .C.) Table - 5
T/Well Harsar to Collection Tank
GI pipe 50 mm (M .C.) Table - 5
T/Well Hawal to Collection Tank
GI pipe 50 mm (M .C.) Table - 5
Collection Tank to U/G Storage Tank
GI pipe 80 mm (M .C.) Table - 5
Providing and fixing C.S NRV 80 mm dia PN1.0 Kg/cm2 Bir make including M.S. flange of table 17 Having weight 21.30 kg welded of M.S. flanges in two layer on both face & i/c carriage complete to respect with in all leads and lifts as per the direction and satisfaction of the Engineer-in-charge.
Sub-Head:- Supply & errection of Pumping Machinery along with allied accessories. For T/Well Badehla
Supply of submersible pumping set of KSB/ Kirloskar/Crompton / Johnston / BS/ SU approved makes by IPH Department confirming to BIS - 8034 -1979 (latest) suitable for clear water fitted with bronze impellers or suitable alloys directly coupled to squirrell cage electric induction motor of same make as that of pump confirming to IS: 9238-1979 latest with up to date amendments ) and totally water proof for submersible duty.,isolated from the pump by intermediate casing with double mechanical seal in oil chamber grease packed lubricated bearing & provided with stainless steel thurst bearing plate to with stand non vertical loads with minimum wear & tear. It should also be fitted with device to a take up expansion of water with heating of motor including water level guard errection clamps, cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-
Location of site :- The site is located at a distance of 7 Kms from Jawali Railway station to site of work.
The Altitude of place in which the motor is intended to work :- Altitude of phase is 500 mtr. Above mean sea level.
Type of current :- A.C. Three phase supply with frequency of 50 cycles per second.
Rated Voltage :- 415 (+/-) 10% Treated.
Charactrstics of water : - (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= _______ (f) Total Solids ____ Mg/Litre (h) Other ______
Depth of well assembly 148.00 mtr.
L.W.L. in Tube-well 9.14 mtr
Centerline level of pump 78.00 mtr
Suction Head ________
Discharge level of highest point 434.50 mtr
No. of pump required 2 Nos
Discharge required from each Pump 2.09 LPS
Maximum draw down 65.00 mtr.
Total head in mtr 98.01 mtr.
Length of R/Main 900.00 mtr.
Dia of R/Main 65 mm dia G.I. Pipe Medium class
No of working hours P/day 8.00 Hours
Limits of pump operction ( - ) 15 % ( + ) 10 % of total head
H.P. Motor /drive unit: - BHP with following margins/multipying factor at duty point whichevear is higher (a) Up to 2 HP = 1.5 (d) 10 to 20 HP = 1.2 (b) 2 to 5 HP = 1.4 (e) 20 to 100 HP = 1.15 (c) 5 to 10 HP = 1.3 (f) Above 100 HP = 1.10
Test Run 20 hours Continueously for 7 days
Providing & fixing Cast Iron double flanged sulice valve of Kirloskar / Kilburn /IVC/ Fouress / Gled / BHEL/ Leader make of size 65 mm dia suitable as per offered pump and class PN- 1.0 having one size higher to delivery size of pump and capable of with standing nominal seat pressure of 10.20 kg/Cm2. (as per IS -780-1984) 65 mm dia.
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement suitable size higher to delivery size of pump( Size 65 mm & class PN-1.0 ) and shall be suitable for with standing nominal seat pressure of 10.20 Kg /Cm^2 ) ( sa per IS - 5312-1984 65 mm dia.
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement and size equal to dia of R/Main that is 65 mm dia and class -PN-1.0 ) and shall be suitable for with standing nominal seat pressure of 10.00 Kg /Cm^2 ) conforming to IS :5312-1984
Providing and laying of suitable size copper PVC insulated armoured power 3.5 core cable .confirming to BIS 1554 (Part-I) 1988 of latest with up to date amendements of siemen / Gloster /ICC finollex make from meter of HPSEB-to-MCB / & from OCB to Busbar switch and starter (one cable carrying all three phases ) including all other electrical equipment /accessories such as thimbles ,flexible pipe solder ,nuts and bolts ,cable glands etc. laid in pipes of trenches under floor . The type size and make will be subject to approval of HPSEB autherities . In case of non -acceptance by HPSEB autherities it shall have to be replaced by the tenderer free of coat. a ) Supply side of size 2.50 mm Sqm
Providing and laying of PVC jointless flat water proof cable as per BIS,694-1990 (latest with up to date amendements ) suitable for the pump sets offered from OCB to motor , Motor to starter including all other electric equipment such as thimbles ,flexible pipe , solder , nut & bolt ,cable , glands etc . laid in pipes or trenches under floor . The type & make will be subject to approval of HPSEB authorities . In case of non acceptance by HPSEB authorities it shall have to be replaced by the tender free of cost. a ) Motor side of size 2.50 mm²
Providing and laying of double loop earthing with copper plate 600x600 x3mm thick electrode complete with material such as charcoal ,common salt ,G.I. pipe ,thimbles ,nuts and bolts .digging of pits ,G.I. wiring & 25x5 mm thick copper sterips of required capacity conforming to BIS 3043-1987 latest with up to date amendements for above motors and other electrical equipment.
Supply of standard make circular dial pressure gauge of suitbale rangs of Feibeg / Bourden / Precision make with all accessories such as stop cock copper tubing etc. Conforming to BIS: 3624-1987 latest with up to date ammendements.
Laying of column assembly of 50 mm dia G.I pipe confirming to BIS: 1239 considering site requirement duly flanged at every 3 metre length with flanges conforming to BIS - 6392-1971/ BIS 1239 ( Table -5 ) including tapers , flanges , rubber , gasket 3mm thick as per BIS -2712-1978 , nuts & boult as per 1364-1983 & specials up to collection tank as per direction of Engineer in Charge as per layout approved by Engineer -in-charge .The pipe shall be capable of with standing 1.5 times the total pressure indicated in item No. 1 (xii ) NOTE :- Actual laying to be done as per final drawings to be approved by the Enginbeer-in- charge.
Erection of all equipment from Sr. No. 1 to 6 includeing cost of tees, bends , tapers and any other fitting required as per site conditions and as per direction of Engineer- in - charge.
Sub-Head:- Supply & errection of Pumping Machinery along with allied accessories. For T/Well Hawal
Supply of submersible pumping set of KSB/ Kirloskar/Crompton / Johnston / BS/ SU confirming to BIS - 8034 -1979 (latest) suitable for clear water fitted with bronze impellers or suitable alloys directly coupled to squirrell cage electric induction motor of same make as that of pump confirming to IS: 9238-1979 latest with up to date amendments ) and totally water proof for submersible duty.,isolated from the pump by intermediate casing with double mechanical seal in oil chamber grease packed lubricated bearing & provided with stainless steel thurst bearing plate to with stand non vertical loads with minimum wear & tear. It should also be fitted with device to a take up expansion of water with heating of motor including water level guard errection clamps, cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-
Location of site :- The site is located at a distance of 9 Kms from Jawali Railway station to site of work.
The Altitude of place in which the motor is intended to work :- Altitude of phase is 500 mtr. Above mean sea level.
Type of current :- A.C. Three phase supply with frequency of 50 cycles per second.
Rated Voltage :- 415 (+/-) 10% Treated.
Charactrstics of water : - (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= _______ (f) Total Solids ____ Mg/Litre (h) Other ______
Depth of well assembly 198.50 mtr.
L.W.L. in Tube-well 3.05 mtr
Centerline level of pump 82.27 mtr
Suction Head ________
Discharge level of highest point 434.50 mtr
No. of pump required 2 Nos
Discharge required from each Pump 1.08 LPS
Maximum draw down 76.22 mtr.
Total head in mtr 92.67 mtr.
Length of R/Main 20.00 mtr.
Dia of R/Main 50 mm dia G.I. Pipe Medium class
No of working hours P/day 8.00 Hours
Limits of pump operction ( - ) 15 % ( + ) 10 % of total head
H.P. Motor /drive unit: - BHP with following margins/multipying factor at duty point whichevear is higher (a) Up to 2 HP = 1.5 (d) 10 to 20 HP = 1.2 (b) 2 to 5 HP = 1.4 (e) 20 to 100 HP = 1.15 (c) 5 to 10 HP = 1.3 (f) Above 100 HP = 1.10
Test Run 20 hours Continueously for 7 days
Providing & fixing Cast Iron double flanged sulice valve of Kirloskar / Kilburn /IVC/ Fouress / Gled / BHEL/ Leader make of size 50 mm dia suitable as per offered pump and class PN- 1.0 having one size higher to delivery size of pump and capable of with standing nominal seat pressure of 10.20 kg/Cm2. (as per IS -780-1984)
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement suitable size higher to delivery size of pump( Size 50 mm & class PN-1.0 ) and shall be suitable for with standing nominal seat pressure of 10.20 Kg /Cm^2 ) ( sa per IS - 5312-1984
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement and size equal to dia of R/Main that is 50 mm dia and class -PN-1.0 ) and shall be suitable for with standing nominal seat pressure of 10.00 Kg /Cm^2 ) conforming to IS :5312-1984
Providing and laying of suitable size copper PVC insulated armoured power 3.5 core cable .confirming to BIS 1554 (Part-I) 1988 of latest with up to date amendements of siemen / Gloster /ICC finollex make from meter of HPSEB-to-MCB / & from OCB to Busbar switch and starter (one cable carrying all three phases ) including all other electrical equipment /accessories such as thimbles ,flexible pipe solder ,nuts and bolts ,cable glands etc. laid in pipes of trenches under floor . The type size and make will be subject to approval of HPSEB autherities . In case of non -acceptance by HPSEB autherities it shall have to be replaced by the tenderer free of coat. a ) Supply side of size 2.50 mm Sqm
Providing and laying of PVC jointless flat water proof cable as per BIS,694-1990 (latest with up to date amendements ) suitable for the pump sets offered from OCB to motor , Motor to starter including all other electric equipment such as thimbles ,flexible pipe , solder , nut & bolt ,cable , glands etc . laid in pipes or trenches under floor . The type & make will be subject to approval of HPSEB authorities . In case of non acceptance by HPSEB authorities it shall have to be replaced by the tender free of cost. a ) Motor side of size 2.50 mm²
Providing and laying of double loop earthing with copper plate 600x600 x3mm thick electrode complete with material such as charcoal ,common salt ,G.I. pipe ,thimbles ,nuts and bolts .digging of pits ,G.I. wiring & 25x5 mm thick copper sterips of required capacity conforming to BIS 3043-1987 latest with up to date amendements for above motors and other electrical equipment.
Supply & Errection of floor / wall mounted power factor shunt capacitor conforming to BIS : 2834-1986 latest with upto date amendements L & T / BHEL/ GEC/ Machneil /Mager / Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of required KVAR according to HP of motor offered including cable siemens/Gloste/ICC make form busbar chamber to capacitor and also including L&T/LK/Kilburn make ICTP Switches conforming to BIS-4064-1978 or latest with HRC fuses. ( Range to be specified by the tenderers )
Supply of standard make circular dial pressure gauge of suitbale rangs of Feibeg / Bourden / Precision make with all accessories such as stop cock copper tubing etc. Conforming to BIS: 3624-1987 latest with up to date ammendements.
Laying of column assembly of 50 mm dia G.I pipe confirming to BIS: 1239 considering site requirement duly flanged at every 3 metre length with flanges conforming to BIS - 6392-1971/ BIS 1239 ( Table -5 ) including tapers , flanges , rubber , gasket 3mm thick as per BIS -2712-1978 , nuts & boult as per 1364-1983 & specials up to collection tank as per direction of Engineer in Charge as per layout approved by Engineer -in-charge .The pipe shall be capable of with standing 1.5 times the total pressure indicated in item No. 1 (xii ) NOTE :- Actual laying to be done as per final drawings to be approved by the Enginbeer-in- charge.
Erection of all equipment from Sr. No. 1 to 6 includeing cost of tees, bends , tapers and any other fitting required as per site conditions and as per direction of Engineer- in - charge.
Sub-Head:- Supply & errection of Pumping Machinery along with allied accessories. For T/Well Harsar Supply of submersible pumping set of KSB/ Kirloskar/Crompton / Johnston / BS/ SU approved makes by IPH Department confirming to BIS - 8034 -1979 (latest) suitable for clear water fitted with bronze impellers or suitable alloys directly coupled to squirrell cage electric induction motor of same make as that of pump confirming to IS: 9238-1979 latest with up to date amendments ) and totally water proof for submersible duty.,isolated from the pump by intermediate casing with double mechanical seal in oil chamber grease packed lubricated bearing & provided with stainless steel thurst bearing plate to with stand non vertical loads with minimum wear & tear. It should also be fitted with device to a take up expansion of water with heating of motor including water level guard errection clamps, cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-
Location of site :- The site is located at a distance of 9 Kms from Jawali Railway station to site of work.
The Altitude of place in which the motor is intended to work :- Altitude of phase is 500 mtr. Above mean sea level.
Type of current :- A.C. Three phase supply with frequency of 50 cycles per second.
Rated Voltage :- 415 (+/-) 10% Treated.
Charactrstics of water : - (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= _______ (f) Total Solids ____ Mg/Litre (h) Other ______
Depth of well assembly 130.50 mtr.
L.W.L. in Tube-well 10.00 mtr
Centerline level of pump 65 mtr
Suction Head ________
Discharge level of highest point 434.50 mtr
No. of pump required 2 Nos
Discharge required from each Pump 1.35 LPS
Maximum draw down 52.00 mtr.
Total head in mtr 99.56 mtr.
Length of R/Main 1200.00 mtr.
Dia of R/Main 50 mm dia G.I. Pipe Medium class
No of working hours P/day 8.00 Hours
Limits of pump operction ( - ) 25 % ( + ) 10 % of total head
H.P. Motor /drive unit: - BHP with following margins/multipying factor at duty point whichevear is higher (a) Up to 2 HP = 1.5 (d) 10 to 20 HP = 1.2 (b) 2 to 5 HP = 1.4 (e) 20 to 100 HP = 1.15 (c) 5 to 10 HP = 1.3 (f) Above 100 HP = 1.10
Test Run 20 hours Continueously for 7 days
Providing & fixing Cast Iron double flanged sulice valve of Kirloskar / Kilburn /IVC/ Fouress / Gled / BHEL/ Leader make of size 65 mm dia suitable as per offered pump and class PN- 1.0 having one size higher to delivery size of pump and capable of with standing nominal seat pressure of 10.20 kg/Cm2. (as per IS -780-1984)
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement suitable size higher to delivery size of pump( Size 65 mm & class PN-1.0 ) and shall be suitable for with standing nominal seat pressure of 10.20 Kg /Cm^2 ) ( sa per IS - 5312-1984
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement and size equal to dia of R/Main that is 50 mm dia and class -PN-1.0 ) and shall be suitable for with standing nominal seat pressure of 10.00 Kg /Cm^2 ) conforming to IS :5312-1984
Providing and laying of suitable size copper PVC insulated armoured power 3.5 core cable .confirming to BIS 1554 (Part-I) 1988 of latest with up to date amendements of siemen / Gloster /ICC finollex make from meter of HPSEB-to-MCB / & from OCB to Busbar switch and starter (one cable carrying all three phases ) including all other electrical equipment /accessories such as thimbles ,flexible pipe solder ,nuts and bolts ,cable glands etc. laid in pipes of trenches under floor . The type size and make will be subject to approval of HPSEB autherities . In case of non -acceptance by HPSEB autherities it shall have to be replaced by the tenderer free of coat. a ) Supply side of size 2.50 mm Sqm
Providing and laying of PVC jointless flat water proof cable as per BIS,694-1990 (latest with up to date amendements ) suitable for the pump sets offered from OCB to motor , Motor to starter including all other electric equipment such as thimbles ,flexible pipe , solder , nut & bolt ,cable , glands etc . laid in pipes or trenches under floor . The type & make will be subject to approval of HPSEB authorities . In case of non acceptance by HPSEB authorities it shall have to be replaced by the tender free of cost. a ) Motor side of size 2.50 mm²
Providing and laying of double loop earthing with copper plate 600x600 x3mm thick electrode complete with material such as charcoal ,common salt ,G.I. pipe ,thimbles ,nuts and bolts .digging of pits ,G.I. wiring & 25x5 mm thick copper sterips of required capacity conforming to BIS 3043-1987 latest with up to date amendements for above motors and other electrical equipment.
Supply of standard make circular dial pressure gauge of suitbale rangs of Feibeg / Bourden / Precision make with all accessories such as stop cock copper tubing etc. Conforming to BIS: 3624-1987 latest with up to date ammendements.
Laying of column assembly of 50 mm dia G.I pipe confirming to BIS: 1239 considering site requirement duly flanged at every 3 metre length with flanges conforming to BIS - 6392-1971/ BIS 1239 ( Table -5 ) including tapers , flanges , rubber , gasket 3mm thick as per BIS -2712-1978 , nuts & boult as per 1364-1983 & specials up to collection tank as per direction of Engineer in Charge as per layout approved by Engineer -in-charge .The pipe shall be capable of with standing 1.5 times the total pressure indicated in item No. 1 (xii ) NOTE :- Actual laying to be done as per final drawings to be approved by the Enginbeer-in- charge.
Erection of all equipment from Sr. No. 1 to 6 includeing cost of tees, bends , tapers and any other fitting required as per site conditions and as per direction of Engineer- in - charge.
Sub-Head:- Supply & errection of Pumping Machinery along with allied accessories. For Collection Tank to U/G Storage Tank
Supply & Errection of horizontal spindle, horizontal/ radial split casing and suction (backpull out arrangement ) single/ Double/ multi stage Centrifugal Pumps or combination of pumps in series / Parallel of KSB/ Kirloskar/ Mathar & Platt / Jyoti/ BE/ Beaconwire make conforming to BIS :1520-1980 (latest with upto date amendments) read with BIS :9137-1978 (latest edition) suitable for lifting clear water of under mentioned characteristics wih impellers of bronze/suitable alloy, priming funnels, casing ring & shaft sleeves of bronze /suitable alloy, shaft of suitable steel grade with cast iron casing coupled directly through a flexible coupling on a common C.I. / Cast steel base plate (base plate to be form the principle manufacturer of pumping set) to slippering /squired cage screen protected drip proof electric induction motor of KSB/ Kirlokar /Cropton /Sieman & Jyoti/ BE/ Beaconweir/ BHEL/ GEC/ ABB Conforming to BIS 325-1978 read with BIS: 900-1968 ( latest with upto date amendments ) It should include the cost of bearings . Nuts & bolts , painting etc. and shall be suitable for operation as per data given below.
Location of site :- The site is located at a distance of 15 Kms from Nurpur Railway station to site of work.
The Altitude of place in which the motor is intended to work :- Altitude of phase is 500 mtr. Above mean sea level.
Type of current :- A.C. Three phase supply with frequency of 50 cycles per second.
Rated Voltage :- 415 (+/-) 10% Treated.
Charactrstics of water : - (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= _______ (f) Total Solids ____ Mg/Litre (h) Other ______
Depth of well assembly 0.00 mtr.
L.W.L. in C/Tank 432.60 mtr
Centerline level of pump 432.60 mtr
Suction Head 3.00 mtr.
Discharge level of highest point 530.00 mtr
No. of pump required 2 Nos
Discharge required from each Pump 4.52 LPS
Static Head 97.40 mtr.
Total head in mtr 133.21 mtr.
Length of R/Main 1520.00 mtr.
Dia of R/Main 80 mm dia G.I. Pipe
No of working hours P/day 8.00 Hours
Limits of pump operction ( - ) 25 % ( + ) 10 % of total head
H.P. Motor /drive unit: - BHP with following margins/multipying factor at duty point whichevear is higher (a) Up to 2 HP = 1.5 (d) 10 to 20 HP = 1.2 (b) 2 to 5 HP = 1.4 (e) 20 to 100 HP = 1.15 (c) 5 to 10 HP = 1.3 (f) Above 100 HP = 1.10
Test Run 8 hours Continueously for 7 days
Providing & fixing Cast Iron double flanged sulice valve of Kirloskar / Kilburn /IVC/ Fouress / Gled / BHEL/ Leader make of size suitable as per offered pump and class PN- 1.6 having one size higher to delivery size of pump and capable of with standing nominal seat pressure of 21.00 kg/Cm2. (as per IS -780-1984) To be specified by the Tenderer.
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement suitable size higher to delivery size of pump( Size __ & class PN-1.6 ) and shall be suitable for with standing nominal seat pressure of 21.00 Kg /Cm^2 ) ( sa per IS - 5312-1984 To be specified by the Tenderer.
Providing & fixing of Cast Iron double flanged swing check type Reflex valve of Kirloskar / Kildurn / IVC / Fouress / Gled / BHEL/ Leader/ Kartar make having by pass arrangement and size equal to dia of R/Main that is 80 mm dia and class -PN-1.6 ) and shall be suitable for with standing nominal seat pressure of 21.00 Kg /Cm^2 ) conforming to IS :5312-1984 To be specified by the Tenderer. 80 mm dia.
Providing and laying of suitable size copper PVC insulated armoured power 3.5 core cable .confirming to BIS 1554 (Part-I) 1988 of latest with up to date amendements of siemen / Gloster /ICC finollex make from meter of HPSEB-to-MCB / & from OCB to Busbar switch and starter (one cable carrying all three phases ) including all other electrical equipment /accessories such as thimbles ,flexible pipe solder ,nuts and bolts ,cable glands etc. laid in pipes of trenches under floor . The type size and make will be subject to approval of HPSEB autherities . In case of non -acceptance by HPSEB autherities it shall have to be replaced by the tenderer free of coat. a ) Supply side of size 4 mm Sqm
Providing and laying of PVC jointless flat water proof cable as per BIS,694-1990 (latest with up to date amendements ) suitable for the pump sets offered from OCB to motor , Motor to starter including all other electric equipment such as thimbles ,flexible pipe , solder , nut & bolt ,cable , glands etc . laid in pipes or trenches under floor . The type & make will be subject to approval of HPSEB authorities . In case of non acceptance by HPSEB authorities it shall have to be replaced by the tender free of cost. a ) Motor side of size 2.5 mm²
Providing and laying of double loop earthing with copper plate 600x600 x3mm thick electrode complete with material such as charcoal ,common salt ,G.I. pipe ,thimbles ,nuts and bolts .digging of pits ,G.I. wiring & 25x5 mm thick copper sterips of required capacity conforming to BIS 3043-1987 latest with up to date amendements for above motors and other electrical equipment.
Supply of standard make circular dial pressure gauge of suitbale rangs of Feibeg / Bourden / Precision make with all accessories such as stop cock copper tubing etc. Conforming to BIS: 3624-1987 latest with up to date ammendements.
Laying of column assembly of 65 mm dia G.I pipe confirming to BIS: 1239 considering site requirement duly flanged at every 3 metre length with flanges conforming to BIS - 6392-1971/ BIS 1239 ( Table -5 ) including tapers , flanges , rubber , gasket 3mm thick as per BIS -2712-1978 , nuts & boult as per 1364-1983 & specials up to collection tank as per direction of Engineer in Charge as per layout approved by Engineer -in-charge .The pipe shall be capable of with standing 1.5 times the total pressure indicated in item No. 1 (xii ) ( The size of pipe shall be suppling by the tenderer ) NOTE :- Actual laying to be done as per final drawings to be approved by the Enginbeer-in- charge.
Erection of all equipment from Sr. No. 1 to 8 includeing cost of tees, bends , tapers and any other fitting required as per site conditions and as per direction of Engineer- in - charge.
sadeep kumar
SHIV KUMAR
Sarabjit Singh Katoch
TARSEM SINGH
SG Engineers and Consultants
M/S Sharma Enterpirses
dinesh kumar lath
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .