| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹57.5 LAccepted-AOC 7A BENTINCK STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | L1 | Accepted-AOC Accepted | |
| 2 | L2₹58.5 L+₹1.0 L (1.74%)Rejected-AOC 14 BEPIN BEHARI GANGUALY STREET KOLKATA 700 012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | L2 | Rejected-AOC Rejected | |
| 3 | L3₹62.6 L+₹5.1 L (8.88%)Rejected-Finance | L3 | Rejected-Finance Quoted Higher Amount | |
| 4 | L4₹64.7 L+₹7.2 L (12.5%)Rejected-Finance GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | L4 | Rejected-Finance Quoted Highest Amount |
Tender Value
Refer Docs
EMD Value
₹1.4 L
Closing Date
14 Mar 2022, 2:00 pmClosed
The Superintending Engineer, KHEC, PWD
KIT Annex Building, 5th FLOOR, KOLKATA 700073
Construction of Administrative cum Academic Building for West Bengal University of Health Science at Salt Lake Electrical Works, SITC of Fire Detection system
2022_WBPWD_365199_1
WBPWD/SEKHEC/NK/NIQ04 /2021-2022
Open Tender
ELECTRICAL WORKS ORG
Item Rate
120 days
West Bengal University of Health Science SaltLake
Please refer Tender documents.
4 documents required · 4 mandatory
₹1.4 L
The Superintending Engineer, KHEC, PWD
13 Jun 2022
10 Feb 2022
16 Mar 2022
11 Feb 2022
14 Mar 2022
18 Feb 2022
16 Feb 2022
Amount
SITC of Microprocessor based Intelligent, addressable,expandable and fully networkable fire alarm control panel ( VDS / UL / FM / ULC approved )having requisite numers of loop suitable to cater for all the detectors and devices along with 20 % spare capacity with each loop loading not exceeding 80 % of the full capacity of dectecrectors an devices taken together complying to IS 2189:2008 or its latest amendmnts, and with the requisite number of character alpha numeric lieuid crystal display . The panel shall be soft addressable type.The panel shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended IS / NBC.
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system and BMS( RS 485 ). The panel should have modbus output & ready to communicate with remote computer. The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supply, Installation,Testing & Commisioning of Analog Addressable Intelligent multisensor detector ( VDS / UL / FM / ULC approved ) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended IS / NBC ) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supplying, installation, testing and commissioning of Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / UL / FM / ULC approved ) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL / FM / ULC approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL / FM / ULC approved) approved. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supply, Installation, Testing & Commissioning of Addressable transponder/ Monitor Modules ( VDS / UL / FM / ULC approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supply, Installation, Testing & Commissioning of Addressable Relay Modules (VDS / UL & FM approved) for switching / integration of Lift / AHU etc complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supply, Installation, Testing & Commissioning of Power supply 230 V AC to 24V DC with all other accessories. (Make: Reputed)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab ) with 20 mm NB PVC rigid conduit pipe(Make: Precision /AKG/ATUL /VIP/ Universal /BEC/Polycab) on the surface of the wall.
TERMS & CONDITIONS
a.The Fire Alarm system shall comply with latest requirements of -- 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm Code 5. local Statutory Regulations 6. Manufacturer Recommendation.
b. TESTS:1.The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.
c. Auto CAD Drawing of whole FDA system & submission of 5 set hard copy of drawing and soft copy (in Auto-CAD format) is to be submitted.
d. The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
e. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
f. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
NOTE : 1. The Fire Alarm system shall comply with latest requirements of -- 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm Code 5. local Statutory Regulations 6. Manufacturer Recommendation.
TESTS: 1.The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system under active monitoring of OEM. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done. Before taking up the work necessary building drawing/ floor plan with layout should be prepared and to be approved from the fire safety Cell of PWD according to the prevailing fire safety policy. After commissioning, necessary testing to be done in presence of fire safety cell.
The Agency must procure the materials from the Manufacturer/OEM or from their authorized sales channel so that the standard warranty/supprot of the Manufacturer/OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer/OEM or from their authorized sales channel and standard warranty/support should be sent from the e-mail of the Manufacturer/OEM/authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
Defect Liability period 1 (One) Year
(Rates should be Quoted inclusive of all taxes & duities and L.W.C. @ 1% as applicable)
ASSOCIATED ELECTRICAL CONST CO. 1963 PVT.LTD
MAM ENTERPRISE
GLYPTIC
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .