Electrical General work in Connection with "AMRIT BHARAT STATION SCHEME: - Provision of New Station Building at Jalpaiguri Railway Station."
30_2026
30_2026
Open
6 Months
Jalpaiguri, West Bengal
₹0
₹2.5 L
13 Jun 2026
13 Jun 2026
22 Jun 2026
Provision of New Station Building at Jalpaiguri Railway Station."
Item- 1 Please see item breakup for details.
S No. Item Description of Item Unit Qty Rate Amount
1 1 Supply, wiring, testing & commissioning of FL Numbers 445.00 184.00 81880.00
point/ Lamp point/Fan point (loop wiring) with
angular/ batten holder by FR PVC insulated and
unsheathed single core, 1.5 sq mm
multistranded copper cable to be drawn through
rigid PVC conduit pipe not less than 20 mm dia
medium gauge including bends, joints etc. from
main line under PP shed and 1 sq mm single
core FR PVC insulated and unsheathed copper
wire for earth continuity without controlling
switch under PP shed/FOB as per instruction of
Engineer incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
2 2 Supply, fixing, connection, testing & Numbers 445.00 4503.00 2003835.00
commissioning of Surface/Suspended mounted
LED Trunking Batten 40 watt, extruded
aluminum housing provided for efficient heat
dissipation with polycarbonate diffuser & Built-In
electronic driver. IP 54, CRI 80, THD(%) 10, CCT.
6500 K Power Factor 0.95, Operating
temperature: -10 C to +50 C, Operating voltage
range: 165 V - 270 V, Average life 50000 hours,
LED lumen efficacy 145 lm/W with a viewing
angle of 120, Powered by built-in electronic
driver (SMPS based constant current supply)
with Output Open/Short-circuit, Thermal fold
back, 440V 8 Hrs protection, Surge protection 4
KV & others safety test as per IS:15885 Part
2/Sec 13. Havells Model No.
ACETRUNKINGADVS40WLED865PSYMBOPCWHT.
3 3 Supply, wiring, testing & commissioning of Numbers 340.00 797.00 270980.00
concealed point wiring by FR PVC insulated and
unsheathed 1.5 sq mm, single core multi strand
copper wire with earth continuity wire by PVC
insulated and unsheathed 1 sq mm , single core
multi strand copper wire concealed on wall
through PVC rigid conduit pipe of dia not less
than 20 mm dia heavy duty including all types
of joints and bends as required, complete with 6
amps flush type controlling modular switch to
be mounted on modular GI inner plate and
modular mounting frame of suitable module as
per requirement complete to be concealed in
wall as per instruction of Engineer Incharge at
site. Existing wall should be cut and re-mended
to original finish by contractor's own material.
(a) FL Point/LED Tube Point/LED Recess Light
Point/Wall Bracket Fan Point/LED Mirror Light
Point/LED Decorative Wall Light Point with
5 5 (c) Fan point with c/rose and 5 step fan Numbers 60.00 1450.00 87000.00
7 7 (e) Plug point 6 amps on board complete Numbers 20.00 361.00 7220.00
8 8 Supply, wiring, testing & commissioning of Numbers 60.00 737.00 44220.00
c o n c e a l e d plug point on separate board
complete with 2 x 6 Amp modular socket and
6/10 amps modular switch to be mounted on
modular GI inner plate 6M and 6M modular
mounting frame with GI box to be concealed in
wall as per instruction of Engineer Incharge at
site. Existing wall should be cut and re-mended
to original finish by contractor's own material.
9 9 Supply, wiring, testing & commissioning of Numbers 60.00 855.00 51300.00
concealed 6/16 amps power plug point on
separate board complete with modular 16 amps
switch (with indicator) and 6/16 amps 3 pin
combined shuttered socket to be mounted on
modular GI inner plate 4M or suitable size with
modular mounting frame to be concealed in wall
as per instruction of Engineer Incharge at Site.
10 10 Supply, wiring, testing & commissioning of Numbers 15.00 1598.00 23970.00
concealed computer point on separate board
complete with 4 nos. 6 amps modular switch
and 4 nos. 6 amps 5 pin shuttered modular
socket to be mounted on modular GI inner plate
12M and 12M modular mounting
frame/combined plate to be concealed in wall as
per instruction of Engineer Incharge at Site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
11 11 Supply, fixing, connection & testing of 40 Watt Numbers 168.00 1890.00 317520.00
LED Tubelight, Surface/ Pendent mounting LED
Battens in Extruded aluminium housing as per
instruction of Engineer Incharge at Site.
12 12 Supply, installation, testing & commissioning of Numbers 100.00 2303.00 230300.00
Surface/Recessed LED luminaire with slim line
CRCA sheet metal body, square type, (System
wattage-18 Watt, Nominal system efficacy 120
lm/watt) suitable for 600 x 600 mm modular
ceiling as per instruction of Engineer incharge
13 13 Supply and testing of wall mounted bracket fan Numbers 20.00 1998.00 39960.00
400 mm sweep complete with all accessories to
be fixed on wall by suitable fixing arrangement
including connection by 2 core, 1.5 sqmm PVC
insulated and FR PVC Round Sheathed, Copper
Conductor (flexible) industrial cable as per
instruction of Engineer Incharge at Site.
14 14 Supply, fixing, connection, testing & Numbers 12.00 1336.00 16032.00
commissioning of surface mounting sleek LED
mirror light 5 W or 7 W, IP 20, 1 ft version
powder coated CRCA housing, high output
diffuser including suitable fixing arrangement on
surface as per instruction of Engineer incharge
15 15 Supply and fixing of Wall mount Decorative light Numbers 40.00 2439.00 97560.00
fitting with 1 x 7 Watt LED lamp, E27 (Jaguar
JNL-CHR-WLSL55004E27 or similar), Heritage
type as per instruction of Engineer Incharge at
16 16 Supply, fixing & testing and commissioning of Numbers 10.00 670.00 6700.00
LED 12 W B22 CDL INVERTER BULB V2 as per
instruction of Engineer Incharge at Site.
17 17 Fixing, testing & commissioning of ceiling fan Numbers 60.00 46.00 2760.00
with supply & fixing of MS clamp with hook, nut,
bolt, washer etc. as per instruction of Engineer
incharge at site. (Fan will be supplied by
18 18 Supply, installation, testing & commissioning of Numbers 10.00 2824.00 28240.00
300 mm sweep (metallic) heavy duty exhaust
fan, 1400 RPM complete with fixing on wall by
suitable size bolts & nuts grouted on wall as per
instruction of Engineer incharge at site.
19 19 Supply, installation, testing & commissioning of Numbers 10.00 1292.00 12920.00
250 mm Sweep (PVC/Plastic Body) Exhaust Fan
complete with suitable size, bolts & nuts
grouted on wall as per instruction of Engineer
Incharge at Site.
20 20 Supply, wiring & testing of main wire by 2.5 sq Metre 6000.00 75.00 450000.00
mm, Single Core FR-LSH PVC Insulated Industrial
Grade Copper Conductor (Unsheathed) Flexible
Cables, 1100 Volts and earth continuity wire by
1.0 sq mm FR-LSH PVC Insulated Industrial
Grade Copper Conductor Conforming to IS: 694
concealed in wall through PVC rigid conduit pipe
not less than 20 mm dia as per instruction of
Engineer incharge at site.
21 21 Supply, wiring & testing of main wire by 4 sq Metre 6000.00 87.00 522000.00
mm, Single Core FR-LSH PVC Insulated Industrial
Grade Copper Conductor (Unsheathed) Flexible
Cables, 1100 Volts and earth continuity wire by
1.0 sq mm FR-LSH PVC Insulated Industrial
Grade Copper Conductor Conforming to IS: 694
concealed in wall through PVC rigid conduit pipe
not less than 20 mm dia as per instruction of
Engineer incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
22 22 Supply, wiring & testing of main wire by 6 sq Metre 4000.00 100.00 400000.00
mm, Single Core FR-LSH PVC Insulated Industrial
Grade Copper Conductor (Unsheathed) Flexible
Cables, 1100 Volts and earth continuity wire by
1.0 sq mm FR-LSH PVC Insulated Industrial
Grade Copper Conductor Conforming to IS: 694
through PVC rigid conduit pipe/polythene pipe
not less than 20 mm dia as per instruction of
Engineer incharge at site.
23 23 Supply, installation, testing & commissioning of Numbers 15.00 4200.00 63000.00
ILLUMINA PENDANT 1LS E27 MATT GLD Ceiling
Light with an elegant oval-shaped fixture with a
matte gold finish designed to illuminate from it's
center perfectly pairing with Dazzle Shine lamp
as per instruction of Engineer Incharge at Site.
24 24 Supply, fixing & testing of hanging type Mini Numbers 2.00 23882.00 47764.00
Chandelier, Colour-Gold with 5 watt LED Lamp
as per instruction of Engineer Incharge at Site.
25 25 Supply, installation, testing & commissioning of Numbers 30.00 16193.00 485790.00
LED Luminaire Flood Light, Flame Proof 250
watts complete with pressure die cast
aluminium housing, IP 66, Luminous efficacy
120 lm/watt with heat sink feature, surge
protection etc including wire connection as per
instruction of Engineer incharge at site.
26 26 Supply, installation, testing & commissioning of Numbers 26.00 1193.00 31018.00
modular power unit complete with 32 Amp mini
MCB DP "C" series 3kA , 25 amps starter, 25
Amp Socket and 25 Amp plug to be mounted on
6 module GI box, 6 module combined plate
concealed on wall and wiring by 6 sq mm, Single
Core FR-LSH PVC Insulated Industrial Grade
Copper Conductor (Unsheathed) Flexible Cables,
1100 Volts with earth coninuity wire by 1 sq mm
copper cable Conforming to IS: 694 to be drawn
through Rigid PVC conduit pipe not less than 20
mm dia as per instruction of Engineer incharge
at site. (For AC & Geyser)
27 27 Supply, installation, testing & commissioning of Numbers 20.00 54091.00 1081820.00
Inverter Split Air Conditioners 1.5 Ton, (BEE star
rating-5 star, Coil material-Copper, Echo-friendly
refrigerant, Nominal cooling capacity in Ton /
(kcal/hr)-1.5 Ton / 4500 kcal/hr) with all
accessories as per OEM suitable for operation
on 230V AC ,single phase, 50 Hz as per
instruction of Engineer incharge at site. Re-
mending work should be done after installation
of RAC. (with 1 pair outdoor wall stand)
(Industrial AC/Heavyduty AC)
28 28 Supply, installation, testing & commissioning of Numbers 6.00 11309.00 67854.00
Stationary storage type electric water heater
(Geyser), Digital display, Type:-Vertical,
Capacity (Ltrs):25, Power input: 2000 watt,
Class:-I, Star Rating: 5 Star suitable for
operation on 230 Volts, single phase AC, 50 Hz.
Storage electric water heater shall be complete
in all respect with fittings as per general
technical requirements and as per instruction of
Engineer incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
29 29 "Supply, installation, testing & commissioning of Numbers 4.00 100011.00 400044.00
Aquaguard Institutional Water cooler-cum-
Purifier with Storage Capacity 120 Ltrs. & Option
for Cold & Normal Purified Water. a) Approx.
Dimensions : 750 mm (W) x 570 mm (D) x 1350
mm (H) b) Power rating : 850 ± 10% watt c)
Water flow capacity : 80 LPH d)Operating power
supply : 170-260 VAC, 1 ph e)No. of stages for
filter-cum-purifier : 3 nos. f) Storage capacity :
120 Ltr g) Nos. of Faucets : 03 nos. h) Body
material: Front SS 304 and the rest in Pre-
coated steel i) Refrigerant used: Freon 22 or
30 30 Supply,installation, testing & commissioning of Numbers 10.00 3490.00 34900.00
insect killer of dimension (L - 26 inch X W - 4.5
inch x H - 11 inch) having coverage area 550 ft
with 02 nos tube of power consumption 60 watt
as per instruction of Engineer incharge at site. It
should be fixed with necessary clamping.
31 31 Supply, installation, testing & commissioning of Numbers 10.00 59202.00 592020.00
Pure Sine Wave 2400 VA Inverter with
Integrated 2560 WH LiFePO4 Lithium-Ion
Battery as per instruction of Engineer Incharge
32 32 Supply, installation, testing & commissioning of Set 2.00 229608.00 459216.00
Power One' make 3 KVA true online UPS system,
1 Phase input & 1 Phase output with Exide /
Amara Raja make SMF batteries of 12V, 150 AH
x 8 Nos. (Total: 14400 VAH) to provide 4-6 Hrs.
backup along with suitable Battery Rack &
battery interlink as per instruction of Engineer
Incharge at Site.
33 33 Supply, installation, commissioning & testing of Square 180.00 1772.00 318960.00
LED indication station name board (Length of Foot
board will be as per proportion of letter so that
all the 4 side of the board will have extra space)
with channel letters with 3.75 ft. in lenght with
suitable widen and 4 mm projection size which
inside ACP board (Brand- ALUDECOR, category-
AL 33 series exterior & thikness-3 mm) with
acrylic face on front and having Sumsung 5630
LED's (Shape- Lens type, operating voltage- 12
V DC, carring current-80 mA, power Dissipation-
0.96 watt, working hours-50000, case material-
ABS ,protection-IP68) inside for illumination
letters in English, Hindi, Bengali or regional
language complete with all materials including
provision of erection structure made of MS
angle/channel/flat duly painted with aluminium
paint over a coat of red oxide primer with CC
foundation (1:3:6) of cement, sand and stone
chips as required at site and as per instruction
of Egnineer incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
34 34 Design, manufacture, display of wall /hanging / Square 120.00 2868.00 344160.00
floor mounting type LED illuminated sign / Foot
direction boards in half elliptical shape. The
display sheet shall be of unbreakable 040
translucent polycarbonate sheet of 2 mm
thickness. The text / graphics matter visibility
shall not be less than 160 deg. The approved
colour text and graphics shall be printed / router
cut on monomeric calendered vinyl of 70 mm
thickness and shall be firmly pasted on display
sheets. The mounting arrangement shall be
hanging, wall mounting, ceiling mounting, pole
mounting or floor mounting and as per site
requirement. The signage shall have the integral
mounting arrangements with sturdy structural
frame and ACP cladding on the back side of the
signage to avoid rusting and entry of dust. The
LED board shall have uniform illumination with
4-8 W / sq. ft and with brightness more than
ambient light. Suitable size end cap of 1.5 mm
thick SS 304 should be provided. (Signage
Board should as per Railway Board Letter No.
35 35 Erection and installation of wall / hanging / floor Square 120.00 287.00 34440.00
mounting type LED illuminated sign / direction Foot
boards in half elliptical shape. The display sheet
shall be of unbreakable 040 translucent
polycarbonate sheet of 2 mm thickness. The
text/graphics matter visibility shall not be less
than 160 deg. The approved colour text and
graphics shall be printed / router cut on
monomeric calendered vinyl of 70 mm thickness
and shall be firmly pasted on display sheets.
The mounting arrangement shall be hanging,
wall mounting, ceiling mounting, pole mounting
or floor mounting and as per site requirement.
The signage shall have the integral mounting
arrangements with sturdy structural frame and
ACP cladding on the back side of the signage to
avoid rusting and entry of dust. The LED board
shall have uniform illumination with 4-8 W / sq.
ft and with brightness more than ambient light.
Suitable size end cap of 1.5 mm thick SS 304
should be provided. (Signage Board should as
per Railway Board Letter No. 2023/SD-
36 36 Supply, installation, testing & commissioning of Numbers 6.00 13091.00 78546.00
swaged type GI tubular pole 9 mt long conforms
to IS - 2713/1980 with following technical
specification and complete with base plate and
cap: - a) Length of section : - Bottom - 5 mt,
Middle - 2 mt, Top - 2 mt b) Outside diameter
and thickness of section : - Bottom - 114.3 x
4.50 mm, Middle - 88.9 x 4.05 mm , Top - 76.1 x
37 37 Supply & testing of GI octagonal pole 6 mt long Numbers 30.00 14193.00 425790.00
with foundation bolt, loop box of bakelite sheet
with one 6A SP MCB and 16 sq mm stud type
connector etc. The octagonal pole shall be hot
dip galvanized in single dip. Technical
specification of pole as following:- Height - 6 mt
Top dia (A/F) - 70 mm Bottom dia (A/F) - 130
mm Sheet thickness - 3 mm Base plate (L x B x
T) - (200 x 200 x 12) mm Foundation Bolt size
(no.x dia) - 4 x 20 dia mm Pitch Circle Dia (PCD)
- 200 mm Bolt length - 600 mm Projected Bolt
Length - 100 mm .
38 38 Supply & fixing of 1 mtr GI Single arm bracket Numbers 30.00 1615.00 48450.00
(header) and holder with Nut & bolt as per
instruction of Engineer incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
39 39 Erection of Rail/Tubular/Octagonal pole to 1/5 th Numbers 36.00 1712.00 61632.00
of its height with CC foundation from base block
(30 cm x 30 cm x 15 cm) including digging &
refilling of earth to a height of 30 cm above
ground level as per drawing
no.CEE/OH@47'40@FGA) in ratio 1:3:6 by
cement sand & Chips 19 mm & down including
excavation of earth.
40 40 Supply, installation, testing & commissioning of Numbers 30.00 14159.00 424770.00
150 Watt LED Street Light made up of pressure
die cast aluminium housing with high efficiency
LEDs as lighting source and lens embedded PC
cover having TOP Opening seperate driver
compartment with IP66 protection and impact
resistance of IK08. as per instruction of Engineer
incharge at site.
41 41 Supply, installation, testing & commissioning of Metre 100.00 1561.00 156100.00
Hot Dipped Galvanized Wire Mesh Cable Tray of
size (Depth- 54 x Width- 150) mm, made of
carbon steel (ASTM A510, Grade-1008 specified)
finished by electrozinc plating (ASTM B 633
specified) alongwith all accessories like suitable
type of splices, locking tab, divider coupler,
preclick, SWK, clamp, Tee, bend, bracket, nut,
bolts etc. Trays should comply standard EN ISO
1461: atleast 550 h of SST. Assemblies with
specific fire resistant properties must have an
E30-E90 certificate. Rod-dia must be from 3.9
mm to 5.9 mm or higher and as per site site
requirement and as per instruction of engineer
incharge at site.
42 42 Supply, installing, testing & commissioning of Numbers 1.00 404250.00 404250.00
High Volume Low Speed (HVLS) FAN, 3 Phase,
1.2 KW, 20 ft. Diameter, 6 (Six) Blade with
Control Panel and all acessories as per
Instruction of Engineer Incharge at Site.
43 43 Supply & execution of transformer bed by CC cum 24.00 4433.00 106392.00
foundation (1:3:6) of size (3.0 m x 2.0 m x 2.0
m) including plastering by morter ratio (1:4)
including digging of soil/surface as per
instruction of Engineer incharge at site. (For
installation of transformer)
44 44 Supply, erection, testing & commissioning of 11 Set 4.00 5174.00 20696.00
kV lightning arrestor polymer type with all
accessories. Lighting arrestor must conform to
IEC-60099-4 IS: 3070 (Part-III) (3 no in a set) as
per instruction of Engineer incharge at site.
45 45 Supply, erection, testing & commissioning of 11 Numbers 4.00 11314.00 45256.00
kV, 200 amps, 3 Pole vertical type Gang
Operated Air Break switch TILTING type
complete with square shaft, operating pipe,
handle, guide clamp etc ( 3 no in a set) as per
instruction of Engineer incharge at site.
46 46 Horizontal machine boring of 300 mm dia hole Metre 100.00 2538.00 253800.00
across track/Road/High drain etc. at a depth of
1.0 mtr below of ground level with suitable
boring instruments & neessary arrangement
and as per technical procedure.
47 47 Supply, laying, commissioning & testing of CI Metre 120.00 877.00 105240.00
Pipe 100 mm dia Class LA type (IS 1536-2001)
to be laid partly along the pole and partly
through ground under railway track/road in
cable trench for protection of cable with suitable
fixing arrangement by MS clamp,
nut,bolt,washer etc.as per instruction of
Engineer incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
48 48 Supply, laying, commissioning & testing of HDPE Metre 500.00 383.00 191500.00
pipe 110 mm dia PN-6 grade conforming IS
4984/1995 or latest to to be laid partly along the
p o l e with suitable fixing arrangement by MS
clamp made of MS flat of size 50x6 mm and
suitable size nut, bolt, washer as per instruction
of Engineer incharge at site.
49 49 Supply, laying, commissioning & testing of HDPE Metre 500.00 70.00 35000.00
pipe 50 mm dia, PN-6 grade to be laid partly
along the p o l e / w a l l with suitable fixing
arrangement by MS clamp made of MS flat of
size 50x6 mm and suitable size nut, bolt,
washer etc as per instruction of Engineer
Incharge at site.
50 50 Supply, fixing, testing & commissioning of IP Numbers 2.00 10035.00 20070.00
66/67 thermoplastic cable junction box / loop
box of size (300 x 450 x 170) mm with
knockouts & 04 nos terminals as per instruction
of Engineer Incharge at Site.
51 51 Supply, fixing, testing & commissioning of IP Numbers 16.00 5291.00 84656.00
66/67 thermoplastic cable junction box / loop
box of size (210 x 310 x 116) mm with
knockouts & 04 nos terminals as per instruction
of Engineer incharge at site.
52 52 Supply & Erection of earth by 50 mm dia 3 Mtrs. Numbers 20.00 4349.00 86980.00
long (3.6 mm thickness) GI pipe, 32x6 mm GI
strip- 5 Mtrs, GI nuts, bolts including masonry
materials for earthing pit, salt, charcoal,
soldered end terminal etc. and construction of
earth pit covered with RCC cover slab12.7 mm
thickness and watering pipe as per Drg. No.-
PCEE/ELG/DRG/2024/1 Date:- 30.09.2024 and as
per instruction of Engineer Incharge at site.
53 53 (a) Supply, installation, testing & commissioning Set 8.00 12330.00 98640.00
of 4 way VTPN MCCB DB (MCCB+12 modules)
with IP 43 grade protection, metal door with
wire sets, busbar, earth bar, blanking plates,
cable ties etc with supply and fixing of following
MCCB/MCB as per instruction of Engineer
incharge at site.
Conforms to IS/IEC 60898 - 1:2002
56 56 (a) Supply, installation, testing & commissioning Set 8.00 2005.00 16040.00
of 12 way SPN Distribution Board, Flush/Surface
mounting, IP 43 grade protection with copper
bus bar, fully shrouded neutral bar, earth bar,
cable ties, metal double door as per IS 8623 - III
with supply and fixing of following RCBO/MCB's
as per instruction of Engineer Incharge at Site.
Conforms to IS/IEC 60898 - 1:2002
Conforms to IS/IEC 60898 - 1:2002
KATIHAR DIVISION-ELECTRICAL/N F RLY
59 59 (a) Supply, fabrication, erection, testing, Set 1.00 32916.00 32916.00
commissioning & painting of floor mounted
powder coated cubicle panel board (Modular
look) of suitable size (neither big nor small) ),
outdoor type with double door made of suitable
size MS/GI angle 50 x 50 x 6 mm, MS/GI flat 50 x
6 mm, 14 SWG MS sheet/Powder coated CRCA
sheet with provision of weather proof,rust
proof,dust proof,water proof having internal
rubber gasket with supply and fixing of following
ACB/MCCB/Bus bar/Meter etc. (Connections to
be made by copper strips, glands should be
provided at cable entry and exit, components
should be compartmentalized, Each
compartment will be provided with the door and
pad locking arrangement. The compartment
illumination lamp with door operated switch
shall be provided for each compartment. Panel
board drawing approval must be obtained with
clear indication of make of items of
electrolytic grade copper consisting of 4 bars ( 3
Ph and Neutral ) ( Bus bar should have
insulation cover)
64 64 (f) Digital voltmeter (0-500) amps and Digital Set 1.00 5581.00 5581.00
ammeter (0-500) amps with s/switch and CTs
66 66 (h) Supply, installation and testing of Astro Set 1.00 9777.00 9777.00
(Analog) time switch with 3 pole 63 amp
contractor and suitable thermoplastic box and
fitted on mounting plate/DIN rail.
67 67 Supply, laying & testing of 3 core, 2.5 sq mm Metre 500.00 147.00 73500.00
PVC insulated and FR PVC Round Sheathed,
Copper Conductor (flexible) industrial cable,
1100 Volt, conforming to IS 694 as per
instruction of Engineer Incharge at Site.
68 68 Supply, drawing, commissioning & testing of 3 Metre 500.00 179.00 89500.00
core, 4 sq mm PVC insulated and FR PVC Round
Sheathed, Copper Conductor (flexible) industrial
cable, 1100 Volts, conforming to IS: 694 as per
instruction of Engineer incharge at site.
insulated and FR PVC Round Sheathed, Copper
Conductor (flexible) industrial cable, 1100 Volt,
conforming to IS 694 as per instruction of
Engineer Incharge at Site.
70 70 Laying, commissioning & testing of HT/LT Metre 3500.00 55.00 192500.00
XLPE/PVC cable of different sizes partly along
the pole and partly through ground in cable
trench by excavation of ground below 1.5 mt
from ground level with suitable fixing
arrangement by MS clamp of size 50x6 mm and
suitable size nut, bolt. Loading, Unloading &
Carrying of cable to actual work site by
contractor's own arrangement. (Aluminium
Crimping Socket should be provided for each
Cable Termination). (Cable will be supplied by
KATIHAR DIVISION-ELECTRICAL/N F RLY
71 71 Excavation of cable trench (0.3 x 1.5) mtr below Metre 1530.00 148.00 226440.00
ground level for laying of cable & refilling the
soil after digging the earth as per instruction of
Engineer incharge at site. Cable should be laid
on bedding of height 75 mm sand at the bottom
of trench, and covering it with additional sand of
height 75 mm and thereafter protecing it by
mean of bricks before refilling the soil as per IS
72 72 Supply, erection, testing & commissioning of HT Set 7.00 23700.00 165900.00
11 kV (E) cable termination Kit out door, heat
shrinkable type for 3 core, 120-185 sq mm XLPE
insulated PVC armoured cable complete with
jointing materials as per instruction of Engineer
Incharge at Site.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
NITABSSNewStnBldgofJPGRlyStn..pdf Tender Paper
ATTACHMENT
GCC 2022 works with ACS
ATTACHMENT
NITABSSNewStnBldgofJPGRlyStn..pdf
ATTACHMENT
GCCApril-2022PDFwithallACS_compressed.pdf
ATTACHMENT
Download all tender documents and submit your bid