| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.7 LAccepted-AOC GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | L1 | Accepted-AOC Accepted. | |
| 2 | L2₹20.3 L+₹2.6 L (14.8%)Rejected-Finance 7A BENTINCK STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | L2 | Rejected-Finance Higher Bid Value. | |
| 3 | L3₹20.3 L+₹2.7 L (15.2%)Rejected-Finance 24A BARICKPARA ROAD FLAT NO 2A 2ND FLOOR KOLKATA 700034 | KOLKATA | WEST BENGAL | 700034 | L3 | Rejected-Finance Higher Bid Value. |
Tender Value
Refer Docs
EMD Value
₹55,771
Closing Date
25 Mar 2019, 3:00 pmClosed
Ex. Engineer,PWD, Jalpaiguri Electrical Division.
Office of the Executive Engineer, P.W.D., Jalpaiguri Electrical Division, Purta Bhawan, Hakim Parra, Jalpaiguri-735101.
Construction of Youth Hostel at Gazol Doba, Jalpaiguri - Installation of Fire Detection and Alarm System.
2019_WBPWD_217262_1
WBPWD/EE/JED/NIQ 33e/Q of 2018-19.
Open Tender
Miscellaneous Works
Item Wise
30 days
Youth Hostel at Gazol Doba
Please refer Tender documents.
2 documents required · 2 mandatory
₹55,771
Jalpaiguri.
10 Feb 2020
19 Feb 2019
27 Mar 2019
19 Feb 2019
25 Mar 2019
19 Feb 2019
21 Feb 2019
Amount
SITC of Main Fire Alarm Control Panel: Microprocessor based Intelligent Addressable 2 loop expandable upto 10 Loop Modular Type Fire Alarm Panel capacity loops 250 Detectors and Devices and having Hot redundant Microprocessor CPU, Power Supply, Loop Card with display of 5" Capacitive TFT Screen with Touch Sensitive Keyboard. Addressability of the Intelligent Panel shall be soft addressed so as to consume minimum time of addressing the system with Detectors and Devices . The Intelligent panel shall be able to give pin point location of all fire/fault conditions. All the multicriteria Detectors as applicable for various areas based on application and design considerations shall be fitted on Loop along with Loop powered Alarm Devices; MCPs and Input /output Modules . The panel shall have in built rectifier, Loop cards,provision for external, LCD unit to indicate Fire/Fault Signal with address. 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. (Approval standards:VDS, EN54; Approved Make: Esser by Honeywell / Securiton / Autronica by UTC/ Synteso by Siemens )
Supply, installation, testing & commissioning of EN Standard, VDS approved Addressable Dual Optical Smoke cum Heat type Multi-Sensor Detector with inbuilt / equal number of additional Isolator for each detector and integral LED status indicator with 360 degree viewing angle. Detector shall communicate for differentiated alarm activation and high tolerance to dust,dirt, temperature fluctuations and air currents. Detector should have unquie address for communication and assigned through panel with Mounting Base as required. (Approval standards:VDS, EN54; Approved Make: Esser by Honeywell / Securiton / Autronica by UTC/ Synteso by Siemens)
Supply, Installation, Testing & Commissioning of Response Indicator, with all other accessories. (Approved Make: Esser by Honeywell / Securiton / Autronica by UTC/ Synteso by Siemens)
Supply, installation, testing & commissioning of EN Standard, VDS approved Inteliigent addressable manual call point with inbuilt / equal number of additional Isolator for each manual call point suitable for flush or surface mounting, call point shall include test key feature without removing the glass. Approved Make: Esser by Honeywell / Securiton / Autronica by UTC/ Synteso by Siemens)
Supply, installation, testing & commissioning of EN Standard, VDS approved Inteliigent addressable loop powered sounder with base, inbuilt /equal number of additional Isolator for each sounder, able to provide an o/p of minimum 80dBA at 1m, for evacuation.. Approved Make: Esser by Honeywell / Securiton / Autronica by UTC/ Synteso by Siemens / Bosch)
Supply, installation, testing & commissioning of EN Standard, VDS approved Inteliigent addressable Control Module with inbuilt /equal number of additional Isolator for each providing automatic facility for On Off AHU/Lift etc. during Emergency. (Approval standards:VDS, EN54; Approved Make: Esser by Honeywell / Securiton / Autronica by UTC/ Synteso by Siemens)
Supply, Installation, Testing & Commissioning of 240 Watt Power Amplifier with 2 zone and gooseneck Microphone. (Make: Honeywell/ Bose/ Bosch/Ahuja)
Supply, Installation, Testing & Commissioning of 6 Watt Celling Mounted Speaker along with Necessary Accessories . (Make: Honeywell/ Bose/ Bosch/Ahuja)
Supply, installation, testing and commissioning of Fire graphics software for Centralize Control & Monitoring and Operation of Installed Fire Detection Devices. (Approved Make: Esser by Honeywell / Securiton / Autronica by UTC/ Siemens)
Supply, Installation, Testing & Commissioning of OEM requirment type Work Station for 24X7 Opearion along with Necessary Keyboard, Mouse & Licensed Software.
Supply & Laying of 2 Core 1 sq.mm FRLS copper Cable. (Make. Finolex / RR-Kable / MEM/Polycab)
Supply & Laying of 20 mm NB FR PVC rigid conduit pipe on the surface of the wall. (Make: Precisson Medium).
PERFECT IMAGE SOLUTIONS
Romeetech Engineering & Services
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .