Vadodara Division: Electrical works in connection with infrastructure facilities for maintenance of HHP electric locomotives, capacity augmentation from 200 locos to 250 locos and extension of existing three-phase electronics laboratory at Electric Loco Shed, Vadodara Yard.
BRC-EL-P-12-2476-2528-35-~WR
BRC-EL-P-12-2476-2528-35-
Open
Works - General
12 Months
Vadodara, Gujarat
₹0
₹4.4 L
27 Jul 2026
26 Jun 2026
13 Jul 2026
A- Electrical Works
Wiring of light/fan/exhaust fan point in concealed manner with modular accessories - The price shall cover for concealed wiring of light/fan/exhaust fan point with 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, 1 conforming to IS: 694/1990 with 1.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/Prestoplast/Gerard make. The accessories shall be of modular type of C&S/MK/North West/L&T/ Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make.
Providing plug point, 6 Amp in concealed manner on existing board with modular accessories - The price shall cover for providing plug point with modular type universal socket and switch, 6 Amp, 230 Volt, AC on existing board. The accessories shall be of modular type of C&S/MK/North West/L&T/Crabtree/ Siemens/Anchor/Legrand/ Havells/Luminous make.
Providing plug point, 6 Amp in concealed manner on separate board with modular accessories - The price shall cover for providing plug point board with modular type universal socket and switch, 6 Amp, 230 Volt, AC with modular accessories. The accessories shall be of modular type of 3 C&S/MK/ North West/L&T/Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make. The price shall also cover for concealed wiring of sub-main with 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.0 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/Prestoplast/Gerard make.
Providing power plug point, 16 Amp in concealed manner on separate board with modular accessories - The price shall cover for providing power plug point with modular type universal socket and switch, 16 Amp, 230 Volt, AC on separate board with modular accessories. The accessories shall 4 be of modular type of C&S/MK/North West/L&T/Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make. The price shall also cover for concealed wiring of plug point with 2.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/Prestoplast/Gerard make.
Providing board with two switches and two sockets, 6 Amp in concealed manner with modular accessories - The price shall cover for providing multi-plug point board (switch, 6 Amp - 2 Nos and universal socket, 6 Amp - 2 Nos) with modular type universal five-pin socket and switch, 6 5 Amp, 230 Volt, AC with modular accessories. The accessories shall be of modular type of C&S/MK/North West/L&T/ Crabtree/Siemens/Anchor/Legrand/ Havells/Luminous make. The price shall also cover for concealed wiring of board with 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.0 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/ Prestoplast/Gerard make.
Providing board with four switches and four sockets, 6 Amp in concealed manner with modular accessories - The price shall cover for providing multi-plug point board (switch, 6 Amp - 4 Nos and universal socket, 6 Amp - 4 Nos) with modular type universal five-pin socket and switch, 6 6 Amp, 230 Volt, AC with modular accessories. The accessories shall be of modular type of C&S/MK/North West/L&T/ Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make. The price shall also cover for concealed wiring of board with 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.0 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/ Prestoplast/Gerard make.
Providing board with two switches and two sockets, 16 Amp in concealed manner with modular accessories - The price shall cover for providing multi-plug point board (switch, 16 Amp - 2 Nos and universal socket, 16 Amp - 2 Nos) with modular type universal five-pin socket and switch, 6 7 Amp, 230 Volt, AC with modular accessories. The accessories shall be of modular type of C&S/MK/North West/L&T/ Crabtree/Siemens/Anchor/Legrand/ Havells/Luminous make. The price shall also cover for concealed wiring of board with 2.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.0 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/ Prestoplast/Gerard make.
Concealed wiring of sub-main with 2.5 sq. mm copper wire, single-core in PVC conduit - The price shall cover for concealed wiring of sub 8 main with two-wire single core 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in concealed manner as per site requirement in PVC conduit.
Concealed wiring of sub-main with 4.0 sq. mm copper wire, single-core in PVC conduit - The price shall cover for concealed wiring of sub 9 main with two-wire single core 4.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in concealed manner as per site requirement in PVC conduit.
Wiring of light/fan/exhaust fan point in PVC casing-capping/conduit - The price shall cover for wiring of light/fan/exhaust fan point with 1.5 sq. mm, multi-stranded, PVC insulated, unsheathed FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to relevant and latest IS and 1.0 sq. mm, single-core, multi-stranded, PVC insulated, unsheathed FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to relevant and latest IS in medium grade PVC casing-capping double lock type, ISI marked of make Modi/Precision/Gerard/Prestoplast or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions with surface mounted molded polypropylene switch board with modular cover plate of suitable size including switches/angular holders/ceiling rose. Space shall be kept on board to accommodate modular electronic fan regulator. Molded polypropylene switch board shall be as per IS: 14772. The accessories shall be of modular type of C&S/MK/ North West/L&T/Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make.
Providing board with two switches and two sockets, 6 Amp - The price shall cover for wiring of multi-plug point (switch, 6 Amp - 2 Nos and socket, 6 Amp - 2 Nos) on separate surface mounted polypropylene switch board with modular cover plate of suitable module with 2.5 sq. mm PVC 11 insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire in medium grade PVC casing capping, double lock type, ISI marked of Modi/Precision/Gerard/Prestoplast make or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions at an approximate distance up to 3.0 meter or as per site requirement. PVC box shall be as per IS: 14772.
Providing board with four switches and four sockets, 6 Amp - The price shall cover for wiring of multi-plug point (switch, 6 Amp - 4 Nos and socket, 6 Amp - 4 Nos) on separate surface mounted polypropylene switch board with modular cover plate of suitable module with 2.5 sq. mm PVC 12 insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire in medium grade PVC casing capping, double lock type, ISI marked of Modi/Precision/Gerard/Prestoplast make or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions at an approximate distance up to 3.0 meter or as per site requirement. PVC box shall be as per IS: 14772.
Providing plug point, 15/16 Amp on separate board - The price shall cover for providing modular power plug point with flush type universal 5 pin socket and switch 15/16 Amp, 230 Volt AC, 50 Hz on separate surface mounted molded polypropylene switch board with modular cover plate of 13 suitable module with 2.5 sq. mm multi-stranded, PVC insulated, unsheathed FRLS copper conductor and 1.5 sq. mm multi-stranded, PVC insulated, unsheathed FRLS copper conductor in green colour as earthing wire of 1100 Volt grade, ISI marked, conforming to relevant and latest IS in medium grade PVC casing capping double lock type, ISI marked, make Modi/Precision/Gerard/Prestoplast or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/ Modi/Gerard as per site conditions at an approximate distance up to 3.0 meter or as per site requirement. Molded polypropylene switch board shall be as per IS: 14772.
Wiring of sub-main with copper wire, single-core 2.5 sq. mm in PVC casing-capping/ conduit - The price shall cover for wiring of two wire 14 sub-main with 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with one wire of 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in medium grade PVC casing capping of not less than 25 mm size, double lock type, ISI marked of make Prestoplast/Precision/Modi/Gerard or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions.
Wiring of sub-main with copper wire, single-core, 2.5 sq. mm in existing PVC casing-capping - The price shall cover for wiring of two wire 15 sub-main with 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with one wire of 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in existing PVC casing-capping or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions.
Wiring of sub-main with copper wire, single-core 4.0 sq. mm in PVC casing-capping/ conduit - The price shall cover for wiring of two wire 16 sub-main with 4.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with one wire of 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in medium grade PVC casing capping of not less than 25 mm size, double lock type, ISI marked of make Prestoplast/Precision/Modi/Gerard or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions.
Wiring of sub-main with copper wire, single-core, 4.0 sq. mm in existing PVC casing-capping - The price shall cover for wiring of two wire 17 sub-main with 4.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with one wire of 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in existing PVC casing-capping or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions.
Providing sub-main board with MCB DP 16/20 Amp and Kit-Kat fuse, 16 Amp - The price shall cover for supply, fixing, testing and 18 commissioning of sub-main board with one no MCB DP, 16 Amp, 10 KA breaking capacity, 'C' curve of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make in sheet steel enclosure of same make as MCB with one no of flush type Kit-Kat fuse, 16 Amp for incoming supply and two Nos of flush type Kit-Kat fuse, 10 Amp for outgoing supply on sun mica top T.W. board of size 250 x 200 x 50 mm with hinged door.
Tapping of light/fan point with 1.5 sq. mm copper wire with connector from existing catenary/PVC trunking - The price shall cover for 19 tapping of light/fan point with heavy duty connector with two wires of 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 1.0 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in green colour as earthing wire in PVC flexible pipe from existing catenary/PVC trunking.
Wiring of sub-main with copper wire, single-core, 4.0 sq. mm - 4 Nos and 2.5 sq. mm - 1 No in PVC conduit/casing-capping with junction box - The price shall cover for wiring of four wire sub-main with 4.0 sq mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 20 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 2.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in green colour as earthing wire in medium grade PVC casing capping of not less than 25 mm size, double lock type, ISI marked of make Prestoplast/Precision/Modi/Gerard or in medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard with heavy duty PVC junction box as per site conditions.
Wiring of sub-main with copper wire, single-core, 6.0 sq. mm - 4 Nos and 2.5 sq. mm - 2 Nos in PVC conduit/casing-capping with junction box - The price shall cover for wiring of four wire sub-main with 6.0 sq mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 21 Volt grade, ISI marked, conforming to IS: 694/1990 and two wires of 2.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in green colour as earthing wire in medium grade PVC casing capping of not less than 25 mm size, double lock type, ISI marked of make Prestoplast/Precision/Modi/Gerard or in medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard with heavy duty PVC junction box as per site conditions.
Providing junction box, three-phase, four-wire - The price shall cover for supply and fixing of three-phase, four-wire, IP:65 rated PVC junction box made from fire-retardant and self-extinguishing ABS or polycarbonate thermoplastic. The PVC junction box shall be DIN rail mounted and suitable for termination of 6 sq mm to 10 sq mm cable terminals. The current capacity of terminals shall be 10 Amp.
Providing electronic fan regulator, modular type - The price shall cover for supply, fixing, testing and commissioning of hum-free modular 23 type electronic fan regulator suitable for 80/100-Watt ceiling fan of step type with 'OFF' position, surface/flush type on existing board and its connection from existing supply. Miniature switch type regulators shall not be accepted. The regulator shall be of Anchor-Roma/Cona/ Leader/Crabtree/Legrand/C&S/HPL/Indo Asian/Havells/Standard/Bentec/Elleys/Precision make.
Supply, fixing, testing and commissioning of BLDC ceiling fan, decorative type with three blades, 1400 mm sweep - The price shall cover for supply of Brushless DC ceiling fan of 1400 mm sweep confirming to IS: 374 (2019) latest complete with top and bottom canopies, 300/600/900 mm down rod, shackles, nuts, bolts, clamps and all other accessories as per site requirement. The fan shall be supplied with remote control unit and shall be ISI marked and of reputed make of ATOMBERG/HAVELLS/ ORIENT/CROMPTON/USHA or any other make approved by Sr. DEE (Power) Vadodara confirming 24 to the IS mentioned above. The price shall also cover for fixing, testing and commissioning of ceiling fan on existing hook and its connection by FRPVC insulated, flexible copper cord, 1100 Volt grade, 24/0.20 mm from existing ceiling rose with earth connection. A suitable suspension clamp made from G.I. flat of 40 x 6 mm with MS 'S' shaped hook of diameter not less than 10 mm shall be provided as per site requirement if fan hook is not available and this is included in the scope of work. The colour of the BLDC fan shall be in sync with the room ambience and shall be got approved from site engineer before supply.
Fixing, testing and commissioning of ceiling fan - The price shall cover for fixing, testing and commissioning of ceiling fan on existing hook 25 and its connection by FRPVC insulated, flexible copper cord, 1100Volt grade, 24/0.20mm from existing ceiling rose with earth connection. A suitable suspension clamp made from G.I. flat of 40 x 6 mm with MS 'S' shaped hook of diameter not less than 10 mm shall be provided as per site requirement if fan hook is not available and is included in the scope of work. The ceiling fans shall be supplied by railways at site in-charge's office/store.
Providing down rod of 3.0 feet length complete with all accessories like nut-bolts, rubber reels, cotter pin, shackles etc - The price shall cover for supply and fixing of M.S. down rod for ceiling fan of 3.0 feet length, 12.0 mm diameter, 2.0 mm thick, powder coated with matching colour of ceiling fan, complete with suspension assembly, rubber reels, shackles, galvanized nuts and bolt, washers, split pins, insulator and slot at bottom.
Providing Exhaust fan 300 mm sweep/heavy duty with louver/bird guard - The price shall cover for supply of heavy duty, industrial Exhaust 27 Fan of metal body, 300 mm sweep with bird guard operating on 230 Volt, 50 Hz AC supply complete with all accessories of make Crompton Greaves/GEC/ Almonard/Usha/Bajaj. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade.
Providing Exhaust Fan, 380/400 mm sweep, industrial, heavy duty with louver/bird guard - The price shall cover for supply of heavy duty, 28 industrial Exhaust Fan of metal body, 380/400 mm sweep with bird guard operating on 230 Volt, 50 Hz AC supply complete with all accessories of make Crompton Greaves/GEC/Almonard/Usha/Bajaj. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade.
Providing BLDC Exhaust fan, 200 mm sweep - The price shall cover for supply of energy efficient, BLDC Exhaust Fan of ABS plastic body, 29 200 mm sweep with automatic flaps to keep bugs out, operating on 230 Volt (Voltage range - 140 to 285 Volt), 50 Hz AC supply, Power Consumption - 16 Watt with all accessories of Atomberg/Havells/Crompton Greaves/GEC/Almonard/Usha/Bajaj make. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade.
Providing BLDC Exhaust fan, 250 mm sweep - The price shall cover for supply of energy efficient, BLDC Exhaust Fan of ABS plastic body, 30 250 mm sweep with automatic flaps to keep bugs out, operating on 230 Volt (Voltage range - 140 to 285 Volt), 50 Hz AC supply, Power Consumption - 16 Watt with all accessories of Atomberg/Havells/Crompton Greaves/GEC/Almonard/Usha/Bajaj make. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade.
Providing decorative wall bracket fan, 400 mm sweep - The price shall cover for supply of decorative wall mounted bracket fan, 400 mm 31 sweep, operating on 230 Volt, 50 Hz AC supply, oscillating type, 90° swing with three-speed regulator, three aerodynamically balanced blades made of aluminium and base made of MS pipe/plate. The decorative wall bracket shall be of Crompton Greaves/Usha/Orient/Bajaj/ GEC/Almonard make. The price shall also cover for fixing, testing and commissioning of bracket fan on wall by suitable size of MS clamps and its connection from existing socket/supply point as per site requirement. The wall bracket fan shall be got approved from site engineer before supply.
Supply of pedestal fan, 400 mm sweep - The price shall cover for supply of pedestal fan, 400 mm sweep, operating on 230 Volt, 50 Hz AC 32 supply, 90° horizontal oscillation, neck tilting mechanism, three-speed regulator, three aerodynamically balanced blades and copper winding. The fan shall have high air delivery of 85 cum/min and speed of 1350 RPM. The pedestal fan shall be of Crompton Greaves/Usha/ Orient/Bajaj/GEC/Almonard make.
Supply of energy efficient, BLDC pedestal fan, 400 mm sweep - The price shall cover for supply of energy efficient, five-star rated, 33 Brushless DC pedestal fan of 400 mm sweep with all other accessories. The power consumption shall be 28 Watt at a speed of 1350 RPM and air delivery of 65 cum per minute. The pedestal fan supplied be with remote control unit and shall be of reputed make of ATOMBERG/HAVELLS/ORIENT/CROMPTON/USHA or any other make approved by Sr. DEE (Power) Vadodara.
Supply of industrial, heavy-duty, pedestal fan, 600 mm sweep - The price shall cover for supply of industrial, heavy duty pedestal fan, 600 34 mm sweep, operating on 230 Volt, 50 Hz AC supply, 90° horizontal oscillation, neck tilting mechanism, three-speed regulator, three aerodynamically balanced blades made of aluminium alloy. The pedestal fan shall be copper wound. The power consumption shall be 180 Watt (approximately) at speed of 1400 RPM. The pedestal fan shall be of ALMONARD/USHA/GEC/ Crompton Greaves make and shall be got approved by site engineer before supply.
Providing Air circulator fan, 750 mm sweep, heavy-duty, industrial type complete with all accessories - The price shall cover for supply of heavy duty, wall mounted, Air Circulator fan, 750 mm sweep (approximately) having aluminium alloy one piece blade, double ball bearing, 90° oscillation, 35 sturdy, closed mesh guard, single phase motor, to work on 230 Volt, 50 Hz single phase AC supply. The air circulator fan shall be of ALMONARD/USHA/GEC/Crompton Greaves make and shall be got approved by site engineer before supply. The Air Circulator fan shall be provided with three core FRPVC copper flexible cord 48/0.20 mm size of suitable length. The Air Circulator shall be fitted on the structure/wall/pillar by providing M.S. clamp of 50 x 5 mm made from M. S. flat duly painted with two coats of anti-corrosive red oxide and two coats of silver enamel paint by providing proper rake bolts. The circulator shall be connected with existing supply point as per site conditions.
Supply, fixing, testing and commissioning of MCB and starter with three-pin plug point for Air Conditioner unit - The price shall cover for supply, fixing, testing and commissioning of power unit for Air Conditioner in enclosure with MCB DP 20/25 Amp, 3 KA breaking capacity, DOL starter of 36 16 to 25 Amp capacity suitable for 1.5/2.0 TR A.C. unit, one No 16/20/25 Amp socket and three-pin plug top, 16/25 Amp of ANCHOR-ROMA/CRABTREE/ NORTH-WEST make with 4.0 sq. mm single core multi-stranded, PVC insulated, unsheathed FRLS copper conductor and 2.5 sq. mm single core multi- stranded, PVC insulated, unsheathed FRLS copper conductor in green colour as earthing wire of 1100 Volt grade, ISI marked, conforming to relevant and latest IS in medium grade PVC casing-capping, double lock type, ISI marked of Modi/Precision/Gerard/Prestoplast make at an approximate distance up to 3 meter or as per site requirement. The colour of enclosure should be in sync with the decor of the room and as decided by site engineer.
Supply of material, laying, testing and commissioning of four-core, multi-stranded, flexible copper cable, 2.5 sq. mm from indoor unit to outdoor unit of Split Air Conditioner - The price shall cover for supply, fixing, testing and commissioning of PVC insulated, multi-stranded, four-core, 37 copper conductor cable, 2.5 sq. mm, 1100 Volt grade, ISI marked, conforming to IS: 694 or latest. The cable shall be of Johnson/Neocab/Nicco/Finolex/R.R. Kabel/Asian/Ecotek/L&T/Havells/Polycab/Avocab/APAR make. The cable shall be connected from the indoor and outdoor units of split A.C. along with 8 SWG earth wire in PVC sleeve of good quality for earthing the equipment from existing nearby earth point/electrode. The copper wire and earth wire shall be laid in PVC conduit of suitable size and properly fixed.
Supply of material and fixing of copper piping for suction and discharge lines of Air Conditioner unit - The price shall cover for supply, fixing, testing and commissioning of refrigerant copper piping suitable for R-22, R-134 A, R-407 refrigerant and conforming to IS: 10773/2006 (latest) from 38 indoor unit to outdoor unit. The copper piping shall be insulated with polyurethane foam tubing duly covered with weather protection. The copper refrigerant pipe shall be suitable for bearing 350 PSI pressure and the thickness should be 19 SWG and diameter should be suitable for handling of refrigerant for capacity 3.5 TR of refrigerant quantity without creating any extra pressure due to quantity of refrigerant and as per manufacturer's recommendations. The exposed copper piping shall be suitably concealed as per site requirement.
Supply of material and providing rigid PVC drain piping - The price shall cover for supply and fixing of rigid uPVC pipe medium grade of required diameter from indoor unit to main drain hole for draining of condensed water from cooling coil (Indoor unit) to main drain discharge point.
Supply and fixing of MS stand for outdoor unit of Split Air Conditioner - The price shall cover for supply, fixing and commissioning of MS 40 angle frame/stand made from MS angle for outdoor unit of split AC. The stand shall be of universal design suitable for mounting of outdoor units of capacity 1.0 TR to 2.0 TR Split Air Conditioners. The stand shall be made with thick CRC Steel with additional hemming bend for added strength. The thick steel shall be finished with weather proof, seven tank powder coating of shade as advised by site engineer. The stand shall be tested for 160 kg load. The stand shall be fixed at site with anchor bolts. Necessary civil works involved are included in the scope of work.
Installation, testing and commissioning of Split Air Conditioner - The price shall cover for installation, fixing, testing and commissioning of the split AC as per the site-engineer's instructions/ requirements with all associated wiring, copper piping, existing drain piping, existing MS outdoor stand. This shall also cover for making a hole of suitable diameter in the existing brick masonry/RCC wall for laying of cables, pipes etc. from indoor to outdoor unit in a neat and aesthetic manner. The hole shall be sealed with plaster of Paris to prevent entry of insects, rain water, lizards etc. Manufacturer's recommendations/ instructions shall be strictly followed. Split AC shall be supplied by railways from the site engineer's office/ stores.
Providing three-core flexible copper wire, 24/0.2 mm conforming to IS: 694, 1100 Volt grade for connection to LED fittings - The price shall 42 cover for supply and connection of three-core, flexible copper wire of size 24/0.20 mm, ISI marked, PVC insulated, conforming to IS: 694, 1100 Volt grade from the existing overhead line/catenary/junction box to LED street light fitting as per site conditions. The connection cord shall be protected by suitable size of heavy duty flexible PVC conduit.
Supply and laying of flexible copper cable, single-core 1.5 sq mm - The price shall cover for supply and laying of XLPE sheathed and 43 insulated, LTUG cable, single-core, 1.5 sq. mm, stranded Copper conductor, 1100 Volt grade conforming to IS: 7098 Part I (latest), ISI marked of Johnson/Neocab/ Nicco/Finolex/R R Kabel/Asian/Ecotek/L&T/Havells/Polycab/Avocab/APAR make. A copy of test certificate shall be submitted along with the cable.
Supply and laying of flexible copper cable, single-core 2.5 sq mm - The price shall cover for supply and laying of XLPE sheathed and 44 insulated, LTUG cable, single-core, 2.5 sq. mm, stranded Copper conductor, 1100 Volt grade conforming to IS: 7098 Part I (latest), ISI marked of Johnson/Neocab/ Nicco/Finolex/R R Kabel/Asian/Ecotek/L&T/Havells/Polycab/Avocab/APAR make. A copy of test certificate shall be submitted along with the cable.
Supply and laying of flexible copper cable, single-core 4.0 sq mm - The price shall cover for supply and laying of XLPE sheathed and 45 insulated, LTUG cable, single-core, 4.0 sq. mm, stranded Copper conductor, 1100 Volt grade conforming to IS: 7098 Part I (latest), ISI marked of Johnson/Neocab/ Nicco/Finolex/R R Kabel/Asian/Ecotek/L&T/Havells/Polycab/Avocab/APAR make. A copy of test certificate shall be submitted along with the cable.
Supply and laying of flexible copper cable, three-core 1.5 sq mm - The price shall cover for supply and laying of XLPE sheathed and 46 insulated, LTUG cable, three-core, 1.5 sq. mm, stranded Copper conductor, 1100 Volt grade conforming to IS: 7098 Part I (latest), ISI marked of Johnson/Neocab/ Nicco/Finolex/R R Kabel/Asian/Ecotek/L&T/Havells/Polycab/Avocab/APAR make. A copy of test certificate shall be submitted along with the cable.
Supply and laying of flexible copper cable, three-core 2.5 sq mm - The price shall cover for supply and laying of XLPE sheathed and 47 insulated, LTUG cable, three-core, 2.5 sq. mm, stranded Copper conductor, 1100 Volt grade conforming to IS: 7098 Part I (latest), ISI marked of Johnson/Neocab/ Nicco/Finolex/R R Kabel/Asian/Ecotek/L&T/Havells/Polycab/Avocab/APAR make. A copy of test certificate shall be submitted along with the cable.
Supply and laying of flexible copper cable, four-core 6.0 sq mm - The price shall cover for supply and laying of XLPE sheathed and 48 insulated, LTUG cable, four-core, 6.0 sq. mm, stranded Copper conductor, 1100 Volt grade conforming to IS: 7098 Part I (latest), ISI marked of Johnson/Neocab/Nicco/ Finolex/R R Kabel/Asian/Ecotek/L&T/Havells/Polycab/Avocab/APAR make. A copy of test certificate shall be submitted along with the cable.
Providing digital timer - The price shall cover for supply, installation, testing and commissioning of digital time switch for daily/weekly/pulse 49 switching operating on 110/240 Volt, 50 Hz AC supply. The time switch shall 25 ON/OFF programs with LED indication of status, simple reset and manual override, keypad locking arrangement with six years of battery reserve life. The digital time switch shall be of "CRONO" of L&T make or similar of Siemens/Minilec/GELCO/Selec/Protek-G/ABB/Schneider/Legrand make.
Supply, installation, testing and commissioning of control panel suitable for 5.0/7.5 HP pump with automation, suitable capacity of capacitor and energy meter - The price shall cover for supply, fixing, testing and commissioning of pump motor control panel for 5.0/7.5 HP pump as per the details given in Annexure-XXI of tender document.
Providing power plug and socket, single-phase, 16 to 32 Amp with MCB DP, 16 to 32 Amp in SS enclosure - The price shall cover for supply of single-phase power plug and socket as per below mentioned specifications - (i) Single phase, 230 Volt power plug and three-pin socket, 16 to 32 Amp of BCH make, Cat. No. MPSEU202 or similar model of L&T/SIEMENS/HPL with MCB DP, 20 Amp -- 1No (ii) MCB DP, 10 KA breaking capacity, 16/32 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/ Schneider/Havells make --- 1 No (iii) Outdoor type enclosure fabricated from 18 SWG CRCA sheet steel, 51 powder coated with grey enamel, wall/pillar mounted, dust and vermin proof, water resistant confirming to relevant IS. The enclosure shall fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system. (iv) The enclosure shall be internally wired by suitable size FRPVC insulated, single core flexible copper multi-stranded wires with crimped copper lugs. The price shall also cover for fixing testing and commissioning of the enclosure securely on cover shed pillars/rails/wall with necessary M.S. clamps, nuts, bolts etc. The SS enclosure shall be provided with two nos of earthing terminals on each side and riveted metallic caution board in three languages. The drawing, design of plug socket, switchgears with make and model shall be got approved from site- engineer before fabrication and supply.
Providing power plug and socket, three-phase, 63 Amp with MCB TPN, 63 Amp and single-phase, 20 Amp with MCB DP, 16 to 32 Amp in SS enclosure - The price shall cover for supply of three-phase power plug and socket as per below mentioned specifications - (i) Three-phase, 415 Volt power plug and five-pin socket, 63 Amp of BCH make, Cat. No. DS6A7A1 or similar model of L&T/SIEMENS/HPL --- 1 No (ii) Single phase, 230 Volt power plug and three-pin socket, 20 Amp of BCH make, Cat. No. MPSEU202 or similar model of L&T/SIEMENS/HPL --- 1No (iii) MCB TPN, 10 KA breaking capacity, 63 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/ Schneider/Havells make --- 1 No (iv) MCB DP, 10 KA breaking capacity, 20 Amp of 52 ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/ Schneider/Havells make --- 1 No (v) Outdoor type enclosure fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, wall/pillar mounted, dust and vermin proof, water resistant confirming to relevant IS. The enclosure shall fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system. (vi) The enclosure shall be internally wired by suitable size FRPVC insulated, single core flexible copper multi-stranded wires with crimped copper lugs. The price shall also cover for fixing testing and commissioning of the enclosure securely on cover shed pillars/rails/wall with necessary M.S. clamps, nuts, bolts etc. The SS enclosure shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes. The drawing, design of plug socket, switchgears with make and model shall be got approved from site-engineer before fabrication and supply.
Providing Distribution Board with incomer MCB DP, 16/32 Amp - 1 No, RCBO, two-pole, 25 Amp - 1 No and outgoing MCB DP, 6/10/16 Amp - 4 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The 53 DB shall be equipped with incomer MCB DP, 16/32 Amp - 1 No, RCBO, two-pole, 30 mA sensitivity, 25 Amp - 1 No and outgoing MCB DP, 6/10/16 Amp - 4 Nos. The MCBs/RCBOs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi- stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes. The Distribution Board shall be suitable for surface/recessed installation as per site requirement.
Providing Distribution Board, double-door, with incomer MCB TPN, 63 Amp - 1 No and outgoing MCB TPN, 32 Amp - 3 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The Distribution Board 54 shall be suitable for surface/concealed mounting. The Distribution Board shall be equipped with incomer MCB TPN, 63 Amp - 1 No and outgoing MCB TPN, 32 Amp - 3 Nos. The MCBs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes. The Distribution Board shall be suitable for surface/recessed installation as per site requirement.
Providing lighting control board with incomer MCB TPN, 32 Amp - 1 No and outgoing MCB DP, 16 to 32 Amp - 4 Nos with time switch, 16 Amp - 3 Nos and single phase contactor, 32 Amp - 3 Nos - The price shall cover for supply, fixing, testing and commissioning of lighting control board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA 55 breaking capacity. The board shall be equipped with incomer MCB TPN, 32 Amp - 1 No, outgoing MCB DP, 16/25/32 Amp - 4 Nos, Time switch, 16 Amp - 3 Nos and Single phase contactor of 32 Amp rating - 3 Nos. The MCBs shall be of ABB/L&T/HPL/GE/MDS/ Siemens/BCH/C&S/Schneider/CGL/Havells make, the contactor shall be of L&T/BCH/C&S/CGL/Schneider/ Siemens make and Digital Time Switch "CRONO" of L&T make or similar of Siemens/Minilec make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes.
Providing Distribution Board double-door with incomer MCB DP, 16/32 Amp - 1 No, RCBO, two-pole, 32 Amp - 1 No and outgoing MCB SP, 6/10/16 Amp - 6 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The Distribution Board shall be suitable for surface/concealed mounting. The Distribution Board shall be equipped with incomer MCB DP, 16/32 Amp - 1 No, RCBO, two-pole, 30 mA sensitivity, 32 Amp - 1 No and outgoing MCB SP, 6/10/16 Amp - 6 Nos. The MCBs/RCBOs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes. The Distribution Board shall be suitable for surface/recessed installation as per site requirement.
Providing Distribution Board, double-door with incomer MCB, TPN, 63 Amp - 1 No and outgoing MCB DP, 32 Amp - 3 Nos and MCB SP, 16/20 Amp - 6 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking 57 capacity. The Distribution Board shall be suitable for surface/concealed mounting. The Distribution Board shall be equipped with incomer MCB TPN, 63 Amp - 1 No and outgoing MCB DP, 32 Amp - 3 Nos and MCB SP, 16/20 - 6 Nos. The MCBs shall be of ABB/L&T/ HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes. The Distribution Board shall be suitable for surface/recessed installation as per site requirement.
Providing Distribution Board, double-door, with incomer MCB, TPN, 32 Amp - 1 No, RCBO, TPN, 32 Amp - 1 No and outgoing MCB DP, 16/20/32 Amp - 6 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA 58 breaking capacity. The Distribution Board shall be suitable for surface/concealed mounting. The Distribution Board shall be equipped with incomer MCB TPN, 32 Amp - 1 No, RCBO, TPN, 30 mA sensitivity, 32 Amp - 1 No and outgoing MCB DP, 16/20/32 Amp - 6 Nos. The MCBs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes. The Distribution Board shall be suitable for surface/recessed installation as per site requirement.
Providing Distribution Board, double-door, with incomer MCB TPN, 32 Amp - 1 No, RCBO, TPN, 32 Amp - 1 No and outgoing MCB DP, 16/32 Amp - 8 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking 59 capacity. The Distribution Board shall be suitable for surface/concealed mounting. The Distribution Board shall be equipped with incomer MCB TPN, 32 Amp - 1 No, RCBO, TPN, 30 mA sensitivity, 32 Amp - 1 No and outgoing MCB DP, 16/32 Amp - 8 Nos. The MCBs/ RCBOs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes. The Distribution Board shall be suitable for surface/recessed installation as per site requirement.
Providing Distribution Board, double-door, with incomer MCB, TPN, 63 Amp - 1 No and outgoing MCB TPN, 32 Amp - 2 Nos and MCB DP, 16/20/32 Amp - 4 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA 60 breaking capacity. The DB shall be equipped with incomer MCB TPN 63 Amp - 1 No and outgoing MCB TPN, 32 Amp - 2 Nos and MCB DP, 16/20/32 Amp - 4 Nos. The MCBs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes. The Distribution Board shall be suitable for surface/recessed installation as per site requirement.
Providing Distribution Board with incomer MCB TPN, 63 Amp - 1 No and outgoing MCB TPN, 32 Amp - 6 Nos, MCB DP, 16/25 Amp - 6 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The DB 61 shall be equipped with incomer MCB TPN 63 Amp - 1 No and outgoing MCB TPN, 32 Amp - 6 Nos and MCB DP, 16/25 Amp - 6 Nos. The MCBs shall be of ABB/L&T/HPL/GE/ MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes. The Distribution Board shall be suitable for surface/recessed installation as per site requirement.
Supply, installation, testing and commissioning of MCCB, four-pole, 100 Amp in outdoor type MS enclosure - The price shall cover for supply, fixing, testing and commissioning of MCCB, four-pole, 100 Amp, with thermal-magnetic release range 80 - 100 Amp, Ics = 100% Icu having 35 KA 62 breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/Schneider/Havells make. The MCCB shall be supplied with spreader terminals and rotary handle in sheet steel modular enclosure or pre-fabricated double-door enclosure of same make as the MCCB as far as possible. The enclosure should be suitable for outdoor installation conforming to IP: 65 protection. The SS enclosure shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes.
Providing Distribution Board, double-door, with incomer MCB, TPN, 63 Amp - 1 No and outgoing MCB TPN, 32 Amp - 4 Nos and MCB DP, 16 to 32 Amp - 8 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated 63 from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The DB shall be equipped with incomer MCB TPN 63 Amp - 1 No and outgoing MCB TPN, 32 Amp - 4 Nos and MCB DP, 16 to 32 Amp - 8 Nos. The MCBs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals
Providing Distribution Board, double door with incomer MCB TPN, 63 Amp - 1 No and outgoing MCB TPN, 32 Amp - 4 Nos and RCBO, two- pole, 25 Amp - 4 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking 64 capacity. The DB shall be equipped with incomer MCB TPN 63 Amp - 1 No and outgoing MCB TPN, 32 Amp - 4 Nos and RCBO, two-pole, 30 mA sensitivity, 25 Amp - 4 Nos. The MCBs/RCBOs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes.
Supply, installation, testing and commissioning of MCCB, four-pole, 125 Amp in outdoor type MS enclosure - The price shall cover for supply, fixing, testing and commissioning of MCCB, four-pole, 125 Amp, with thermal-magnetic release range 100 - 125 Amp, Ics = 100% Icu having 35 KA 65 breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/CGL/Schneider/Havells make. The MCCB shall be supplied with spreader terminals and rotary handle in sheet steel modular enclosure or pre-fabricated double-door enclosure of same make as the MCCB as far as possible. The enclosure should be suitable for outdoor installation conforming to IP: 65 protection. The SS enclosure shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes.
Providing on load change over switch, four-pole, 200 Amp in sheet steel enclosure - The price shall cover for supply, fixing, testing and commissioning of on load changeover switch, four-pole, 415 Volt, AC 23A duty, 200 Amp capacity in sheet steel enclosure conforming to IS/IEC 60947-3. 66 The enclosure version should not require separate cable gland box and shall be suitable for vertical as well as horizontal mounting and equipped with flip- able handle. The changeover switch should have staggered terminals to make cable termination easy and should have door interlock and padlock facility. Terminal shrouds, source separator and phase barriers shall be included in the changeover switch. The changeover switch shall be of ABB/L&T/GE/MDS/Siemens/BCH/C&S/HPL/Havells/Schneider make. The SS enclosure shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes.
Providing on load change over switch, four-pole, 400 Amp in sheet steel enclosure - The price shall cover for supply, fixing, testing and commissioning of on load changeover switch, four-pole, 415 Volt, AC 23A duty, 400 Amp capacity in sheet steel enclosure conforming to IS/IEC 60947-3. The enclosure version should not require separate cable gland box and shall be suitable for vertical as well as horizontal mounting and equipped with flip- able handle. The changeover switch should have staggered terminals to make cable termination easy and should have door interlock and padlock facility. Terminal shrouds, source separator and phase barriers shall be included in the changeover switch. The changeover switch shall be of ABB/L&T/GE/MDS/Siemens/BCH/C&S/HPL/Havells/Schneider make. The SS enclosure shall be provided with two nos of earthing terminals on each side, riveted metallic caution board in three languages and cable glands of required sizes.
Providing Distribution Board, double-door, wall/floor mounted with incomer MCCB, four-pole, 63 Amp - 1 No and outgoing MCB TPN, 32 Amp - 2 Nos, MCB DP, 16/32 Amp - 8 Nos with Time Switch, 16 Amp - 2 Nos and Single-Phase Contactor, 16 Amp - 2 Nos - The price shall cover for fabrication, supply, fixing, testing and commissioning of pre-fabricated Distribution Board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, outdoor type confirming to relevant IS and complete with MCCBs and MCBs. The Distribution Board shall be suitable for surface/concealed mounting. The board shall be fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/ accessories - (a) Incomer - MCCB, four-pole, 63 Amp, with thermal-magnetic release range 50 - 63 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary handle. The MCCB shall be of 68 ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/ CGL/Havells make --- 1 No (b) Outgoing - MCB TPN, 10 KA breaking capacity, 32 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ Schneider/CGL/Havells make ---- 2 Nos MCB DP, 10 KA breaking capacity, 16/32 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ Schneider/CGL/Havells make ---- 8 Nos (c) Time switch, 16 Amp and Single phase contactor of rating 32 Amp. The contactor shall be of L&T/ BCH/C&S/CGL/Schneider/Siemens make and the Digital Time Switch "CRONO" of L&T make or similar of Siemens/Minilec make --- 2 sets (d) Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set (e) Multi LED type indication lamp for three-phases (Red, Yellow and Blue) of L&T/Schneider/Siemens/ C&S/ABB/BCH make with protection fuses --- 1 Set (f) Cable glands of required sizes --- LOT (g) Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom. (h) Metallic Caution Board in three languages riveted to the panel board --- 2 Nos
Providing Distribution Board, double-door, wall/floor mounted with incomer MCCB, four-pole, 100 Amp - 1 No and outgoing MCCB, four-pole, 63 Amp - 3 Nos - The price shall cover for fabrication, supply, fixing, testing and commissioning of pre-fabricated Distribution Board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, outdoor type confirming to relevant IS and complete with MCCBs and MCBs. The Distribution Board shall be suitable for surface/concealed mounting. The board shall be fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/ accessories - (a) Incomer - MCCB, four-pole, 100 Amp, with thermal-magnetic release range 80 - 100 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary 69 handle. The MCCB shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ Schneider/CGL/Havells make --- 1 No (b) Outgoing - MCCB, four-pole, 63 Amp, with thermal-magnetic release range 50 - 63 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary handle. The MCCB shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/ CGL/Havells make --- 3 Nos (c) Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set (d) Multi LED type indication lamp for three-phases (Red, Yellow and Blue) of L&T/Schneider/Siemens/ C&S/ABB/BCH make with protection fuses --- 1 Set (e) Cable glands of required sizes --- LOT (f) Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom. (g) Metallic Caution Board in three languages riveted to the panel board --- 2 Nos
Supply, installation, testing and commissioning of MCCB, four-pole, 250 Amp with bus-bar arrangement in outdoor type MS enclosure - The price shall cover for supply, fixing, testing and commissioning of bus-bar panel of 250 Amp capacity fabricated from 16 SWG MS sheet, standard angles, channels etc. as required in design. The bus-bar panel shall be rectangular cubicle type, dust and vermin proof suitable for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulation and having cross sectional area current density of 1.6 Amp/sq. mm. Knock out/gland plates as applicable shall be provided. Gland plates of suitable size shall be designed for terminating cables in a straight and easy manner. All power connections from the bus bar shall be made in such a manner that there is a clear metal to metal clearance available at the tapping as per relevant standard/code. Both spring washers and flat washers shall be used with stud/nuts to ensure proper contact pressure. The bus-bar panel shall have metal 70 locks and operated by a common key. All covers and doors to be provided with neoprene gasket and hinges. The sheet steel enclosure/angle/channel used in the fabrication of panel shall be provided with double coating of red oxide and final coating of Siemens grey powder coating. The bus-bar panel shall be supplied complete with C-channel base of 75 mm, louver on sides, four lifting hooks and feeder name plates completely wired and ready for commissioning. The panel shall be suitable for wall/floor mounting. Two nos of caution boards in Hindi, Gujarati and English of metallic type shall be riveted on the panel. Minimum two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom. Multi LED type indication lamp confirming to relevant IS having colour code Red, Yellow and Blue with control fuses on each incoming and outgoing feeder shall be provided. The bus-bar panel shall comprise of the following switch gears - (a)MCCB, four-pole, 250 Amp, with thermal-magnetic release range 200 - 250 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection of ABB/L&T/HPL/GE/MDS/Siemens/BCH/ C&S/CGL/Schneider make. The MCCB shall be supplied with spreader terminals and rotary handle ---- 1 Nos
Providing Distribution Board, double-door, wall mounted with incomer MCCB, four-pole, 160 Amp - 1 No and outgoing MCB TPN, 63 Amp - 12 Nos - The price shall cover for fabrication, supply, fixing, testing and commissioning of pre-fabricated Distribution Board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, outdoor type confirming to relevant IS and complete with MCCBs and MCBs. The Distribution Board shall be suitable for surface/concealed mounting. The Distribution Board shall be suitable for vertical installation as per site conditions. The board shall be fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/accessories - (a)Incomer - MCCB, four-pole, 160 Amp, with thermal-magnetic release range 120 - 160 Amp, Ics = 71 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary handle. The MCCB shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ Schneider/CGL/Havells make --- 1 No (b)Outgoing - MCB TPN, 10 KA breaking capacity, 63 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ Schneider/CGL/Havells make ---- 12 Nos (c)Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set (d)Multi LED type indication lamp for three-phases (Red, Yellow and Blue) of L&T/Schneider/Siemens/ C&S/ABB/BCH make with protection fuses --- 1 Set (e)Cable glands of required sizes --- LOT (f)Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom. (g)Metallic Caution Board in three languages riveted to the panel board --- 2 Nos
Providing Distribution Board, outdoor type, double-door, floor mounted with incomer MCCB, four-pole, 200 Amp - 1 No and outgoing MCCB, four-pole, 100 Amp - 2 Nos, MCCB, four-pole, 63 Amp - 4 Nos, MCB TPN, 32 Amp - 4 Nos and MCB DP, 16/32 Amp - 4 Nos with multifunctional energy 72 meter, indication lamp and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switch gears with make and model of the LT panel shall be submitted by the contractor in three copies and got approved from site engineer before fabrication. The LT panel shall be indoor/outdoor, rectangular cubicle type, dust and vermin proof suitable for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document.
Providing Distribution Board, outdoor type, double-door, floor mounted with incomer MCCB, four-pole, 250 Amp - 1 No and outgoing MCCB, four-pole, 125 Amp - 2 Nos, MCCB, four-pole, 63 Amp - 6 Nos and MCB DP, 16/32 Amp - 4 Nos with multifunctional energy meter, indication lamp and all 73 accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switch gears with make and model of the LT panel shall be submitted by the contractor in three copies and got approved from site engineer before fabrication. The LT panel shall be indoor/outdoor, rectangular cubicle type, dust and vermin proof suitable for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document.
Providing Distribution Board, outdoor type, double-door, floor mounted with incomer MCCB, four-pole, 250 Amp - 1 No and outgoing MCCB, four-pole, 125 Amp - 2 Nos, MCCB, four-pole, 100 Amp - 2 Nos, MCCB, four-pole, 63 Amp - 2 Nos and MCCB, four-pole, 32 Amp - 2 Nos with multifunctional 74 energy meter, indication lamp and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switch gears with make and model of the LT panel shall be submitted by the contractor in three copies and got approved from site engineer before fabrication. The LT panel shall be indoor/outdoor, rectangular cubicle type, dust and vermin proof suitable for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document.
Providing Distribution Board, outdoor type, double-door, floor mounted with incomer MCCB, four-pole, 125 Amp - 2 Nos and outgoing 75 MCCB, four-pole, 63 Amp - 6 Nos and MCCB four-pole, 32 Amp - 6 Nos with multifunctional energy meter, indication lamp and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switch gears with make and model of the LT panel shall be submitted by the contractor in three copies and got approved from site engineer before fabrication. The LT panel shall be indoor/outdoor, rectangular cubicle type, dust and vermin proof suitable for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document.
Providing Distribution Panel with incomer MCCB, four-pole, 250 Amp - 1 No and outgoing MCCB, four-pole, 125 Amp - 3 Nos, MCCB, four- pole, 63 Amp - 4 Nos and MCCB, four-pole, 32 Amp - 4 Nos with multifunction energy meter, indication lamp etc. - The price shall cover for design, supply, 76 installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switch gears with make and model of the LT panel shall be submitted by the contractor in three copies and got approved from site engineer before fabrication. The LT panel shall be indoor/outdoor, rectangular cubicle type, dust and vermin proof suitable for three-phase, four- wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document.
Supply, installation, testing and commissioning of 200 KVAR Automatic Power Factor Correction panel - Supply, installation, testing and commissioning of 200 KVAR Automatic Power Factor Correction capacitor panel - The price shall cover for supply, fixing, testing and commissioning of Intelligent Automatic Power Factor Correction (APFC) capacitor panel suitable for 433 Volt AC, 50 Hz, three-phase, four-wire system, floor mounted with 77 base channel made up of 16 SWG CRCA sheets steel, all bolted construction with PU gasket suitable for indoor installation, dust and vermin proof with detachable cable gland plates at the bottom for cable entry, totally compartmentalized with separate compartments for capacitors, with seven-tank process of surface treatment and powder coating with Siemens grey shade and 3.0 mm mounting plate with IP:55 degree of protection incorporating, with auto and manual switching option for individual capacitors. Scope of work includes design, manufacturing, supply, installation, testing and commissioning of APFC Panel of 200 kVAR capacity in seven-step, 40 stages as per the specifications given in Annexure-XXI of tender document.
Item No. 78 - Providing L.T. Distribution Panel, outdoor type, double-door, floor mounted with incomer MCCB, four-pole, 400 Amp - 2 Nos and outgoing MCCB, four-pole, 200 Amp - 2 Nos, MCCB, four-pole, 100 Amp - 3 Nos, MCCB, four-pole, 63 Amp - 4 Nos and MCB TPN, 25/32 Amp - 6 Nos 78 with multifunctional energy meter, indication lamp and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switch gears with make and model of the LT panel shall be submitted by the contractor in three copies and got approved from site engineer before fabrication. The LT panel shall be indoor/outdoor, rectangular cubicle type, dust and vermin proof suitable for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed specifications are given in Annexure-XXI of tender document.
Supply of H.T. hand gloves - The price shall cover for supply of Dielectric latex (rubber) hand gloves suitable for 11 KV system and tested on 33,000 Volt potential as per IS: 4770 (1991). The hand gloves shall protect against electrical risks from 500 to 36,000 Volt. Make - NATIONAL/RAYCHEM/ ANCHOR/CRYSTAL/KMC.
Supply of fire bucket set complete with stand and 6 Nos buckets - The price shall cover for supply set of 6 Nos fire buckets of 80 approximately 10 liters capacity, P.O. Red painted, filled with river sand and mounted on M.S. stand outside sub-station. M.S. stand shall be fabricated from M.S. Channel ('I' Section) of suitable size with M.S. Rod and locking arrangement (one no. pad lock not less than 70 mm) etc. M.S. stand shall be grouted by providing PCC foundation.
Supply of rubber mat of size 2.0 x 1.0 meter and 2.5 mm thick - The price shall cover for supply of rubber matting of size 2.0 x 1.0 meter and 25/30 mm thick Made of Dielectric "Elastomer" rubber and Synthetic Polymer as per IS: 15652-2006 (latest) in HT/LT panel room for electrical insulation above the ground. The rubber mat shall be got approved by site engineer before supply.
Supply and providing 6 kg DCP (CO2 Cartridge type) Fire Extinguisher - The price shall cover for supply and erection of dry chemical powder type fire extinguisher of 6.0 kg capacity duly filled and ready for use. The fire extinguisher shall be got approved by Site-Engineer before supply. It should be provided on wall with suitable clamp. Location shall be advised by Site-Engineer.
Supply, fixing, testing and commissioning of indoor type, heat shrinkable, cable end termination kit for three-core, 11 KV, 185 sq mm, XLPE H.T. cable - The price shall cover for supply, jointing, testing and commissioning of 11 KV indoor type heat shrinkable cable end box for 11 KV, three- 83 core, 185 sq. mm XLPE cable of make DENSON/M-SEAL/CCI/RAYCHEM/SUPERSEAL. The individual cores of the cables shall be properly identified to avoid cross connections of the core while connecting them to the corresponding phases. The contractor shall engage skilled cable jointer for making the end termination and it should be provided only in presence of Railways' representative after taking proper shut down. Proper size of cable gland and lugs shall be provided for termination of cable. The cable shall be tested with a 5.0 KV Megger before and after preparation of joint and the values to be recorded jointly.
Supply, fixing, testing and commissioning of outdoor type, heat shrinkable, cable end termination kit for three-core, 11 KV, 185 sq mm, XLPE H.T. cable - The price shall cover for supply, jointing, testing and commissioning of 11 KV outdoor type heat shrinkable cable end box for 11 KV, 84 three-core, 185 sq. mm XLPE cable of make DENSON/M-SEAL/CCI/RAYCHEM/SUPERSEAL. The individual cores of the cables shall be properly identified to avoid cross connections of the core while connecting them to the corresponding phases. The contractor shall engage skilled cable jointer for making the end termination and it should be provided only in presence of Railways' representative after taking proper shut down. Proper size of cable gland and lugs shall be provided for termination of cable. The cable shall be tested with a 5.0 KV Megger before and after preparation of joint and the values to be recorded jointly.
Supply, fixing, testing and commissioning of straight through cable jointing kit suitable for four-core L.T. Cables of sizes 10 sq. mm to 70 sq. mm - The price shall cover for supply, jointing, testing and commissioning of 1.1 KV outdoor/indoor type heat shrinkable straight through cable jointing 85 kit for 1100 Volt, four-core, XLPE LT cables of sizes from 10 sq mm to 70 sq mm cable of make DENSON/M-SEAL /CCI/RAYCHEM/SUPERSEAL. The individual cores of the cables shall be properly identified to avoid cross connections of the core while connecting them to the corresponding phases. The contractor shall engage skilled cable jointer for making the straight joint and it should be provided only in presence of Railways' representative after taking proper shut down. The cable shall be tested with a 500 Volt megger before and after preparation of joint and the values to be recorded jointly.
Supply, fixing, testing and commissioning of straight through cable jointing kit suitable for four-core L.T. Cables of sizes 95 sq. mm to 300 sq. mm - The price shall cover for supply, jointing, testing and commissioning of 1.1 KV outdoor/indoor type heat shrinkable straight through cable jointing 86 kit for 1100 Volt, four-core, XLPE LT cables of sizes from 95 sq mm to 300 sq mm cable of make DENSON/M-SEAL /CCI/RAYCHEM/SUPERSEAL. The individual cores of the cables shall be properly identified to avoid cross connections of the core while connecting them to the corresponding phases. The contractor shall engage skilled cable jointer for making the straight joint and it should be provided only in presence of Railways' representative after taking proper shut down. The cable shall be tested with a 500 Volt megger before and after preparation of joint and the values to be recorded jointly.
Supply, erection, testing and commissioning of 11 KV Gang Operated Switch with Drop Out fuses and lighting arrester including hardware and operating rod - This price shall cover for supply, fixing, testing and commissioning of 11 KV Air Break Switch of 300 Amp capacity along with drop out fuses of 25 Amp capacity and Lightening Arrestors of 9 KV and all accessories for outdoor installation for use on transformers. The A.B. Switches shall be complete with all components necessary for its effective and trouble-free operation along with associated equipment etc and shall be suitable for satisfactory continuous operations under tropical conditions. The A.B. Switches shall have triple pole construction and shall be suitable for vertical mounting. The A.B. Switch shall have two 11 KV Polymeric Insulator having 320 CD mounted on 75 x 40 mm M.S. Channel per phase. The channel support shall be mounted on a steel frame made of two channel supports. The switch shall be manually operated with a locking type arrangement through a 25 mm Hollow Square coupling rod of 2 meter length and G.I. Pipe of 30 mm diameter and 6 meter length with operating handle. The 11 KV Polymeric Insulators to be used in manufacturing of A.B. Switches should confirm to IEC: 61109 with latest amendment. Male and female contacts shall be prepared from hard drawn copper strip as per IS 1897/1983 (with latest amendment if any). Further the contact should be silver plated with thickness of coating not less than 2.5 Micron. The arcing horn shall be made of galvanized rod of 10 mm diameter and shall have spring assisted operation. The speed of breaking of load current shall be independent of the speed of operation. The male and female contacts from electrolytic copper will have to be mounted on the Gunmetal base. The arcing horn should be provided on the G.M. base and they should be made in such a way that they make contact before the male-female contact make the contact and should part only after the male and female contact have completely separated while switching off operation. The spacing between the phases shall be adjustable between 600 mm to 700 mm for 11 KV switch. Total length of square coupling rod shall be 2000 mm for 11 KV class minimum. The Hollow square rod for coupling the three phases should be made from square G.I. Pipe having outside dimensions 25 x 25 mm and 3 mm thick duly hot dip galvanized as per IS: 2633/1986. Vertical operating rods shall comprise of 30 mm diameter GI Pipe of medium class as per IS 1161/1979. Length of the operating pipe shall be of 6000 mm. Suitable arrangement should be provided to lock the operating handle in 'ON' and 'OFF' position. The Switch shall be provided with palm type terminal connector made of Aluminum Alloy material with bimetallic Plate suitable for Rabbit conductor and also of the same size of the contacts on which they are fixed. The Polymeric insulators shall be mounted on a tilting base, which shall be made of cast metal with smooth surface. The supplier has to make suitable arrangement for fixing the hollow square rod and connector of vertical rod for smooth and trouble-free operation. The scope of work also covers supply of insulated HT operating rod made of fiber body and telescopic type of length 15 feet for replacement of dropout fuses along with each set. The entire assembly (11 KV Gang Operated Switch with Drop Out fuses and lighting arrester including hardware and operating rod) shall be mounted on rail pole of approximately 7.5 meter height. Detailed specifications are given in Annexure-XXI of tender document.
Providing M.S. chequered plate, 5.0 mm thick for covering of cable trench - The price shall cover for supply and fixing of M.S. chequered 88 plate of 5.0 mm thickness conforming to IS: 2062. The M.S. chequered plate shall have raised, patterned surface (checkered/treaded) for enhanced grip and safety. Angle stiffeners shall be provided at the bottom of the plate for structural integrity. The M.S. chequered plate shall be finished with hot dip galvanization for durability. The M.S. chequered plate shall be laid over cable trenches on suitable supports. Collapsible handles shall be provided for lifting of the plates for maintenance purposes.
Digging of cable trench 450/600 mm wide and 900 mm deep in all types of soil including hard, rocky etc - The price shall cover for digging of 450/600 mm wide and 900 mm deep trench in all types of soil including soft, rocky as per cable route plan and filling back the trench after laying of cables. This also includes clearing of roots of trees and bushes and other temporary obstructions on the selected route.
Digging of cable trench 100 mm wide and 200 mm deep in concrete/tar road/platform and refilling to its original position after laying of 90 cable in 50 mm diameter HDPE pipe - The price shall cover for digging of cable trench of size 100 x 200 mm deep in concrete/tar road/platform surface and its refilling/plastering after laying of cable in 50 mm diameter HDPE pipe of Tijaria/Himalyan/Koncept/Poddar /Unique/Dutron/Reliance/Baba/Shivam make in existing trench. Supply and laying of HDPE pipe, 50 mm diameter is included in the scope of work.
Digging of cable trench 200 mm wide and 200 mm deep in concrete/tar road/platform and refilling to its original position after laying of 91 cable in 110 mm diameter HDPE pipe - The price shall cover for digging of cable trench of size 200 x 200 mm deep in concrete/tar road/platform surface and its refilling/plastering after laying of cable in 110 mm diameter HDPE pipe of Tijaria/Himalyan/Koncept/ Poddar/Unique/Dutron/Reliance/Baba/Shivam make in existing trench. Supply and laying of HDPE pipe, 110 mm diameter is included in the scope of work.
Supply and laying of RCC half round pipe, 150 mm diameter - The price shall cover for supply of half round RCC pipes of 150 mm inner 92 diameter and 1.0 meter in length as per given description. The internal surface shall have a smooth finish without any bulge or projections to avoid damage to the cable. Detailed specifications are given in Annexure-XXI of tender document. The price shall also cover for laying of half round RCC pipes above the cables for mechanical protection on laid cables in the existing trench. After laying of RCC half round pipe, the trench shall be filled up with soil available thereby.
Supply and laying of DWC pipe, 63 mm diameter - The price shall cover for supply of Double Wall Corrugated (DWC) HDPE pipe of 63 mm diameter. DWC HDPE pipe shall have corrugation on outer wall but inner wall shall be plain conforming to IS: 14930 Part I and II amended from time to time. The pipes shall be "ISI" marked. Accessories like HDPE snap fit coupler with neoprene 'O' ring shall be part of supply to make the joints water/damp 93 proof. The strength and stiffness class of the pipe shall be SN4 and SN8 respectively. The price shall also cover for laying the DWC pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water.
Supply and laying of DWC pipe, 120 mm diameter - The price shall cover for supply of Double Wall Corrugated (DWC) HDPE pipe of 120 mm diameter. DWC HDPE pipe shall have corrugation on outer wall but inner wall shall be plain conforming to IS: 14930 Part I and II amended from time to time. The pipes shall be "ISI" marked. Accessories like HDPE snap fit coupler with neoprene 'O' ring shall be part of supply to make the joints 94 water/damp proof. The strength and stiffness class of the pipe shall be SN4 and SN8 respectively. The price shall also cover for laying the DWC pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water.
Providing uPVC pipe, 20 mm diameter - The price shall cover for supply of uPVC pipe of 20 mm nominal bore diameter and working pressure of 14 kg/sq. cm along with coupling, elbow, tee etc for protection of cable. The upright cable shall be encased in uPVC pipes for mechanical 95 protection. The pipe shall be clamped with flat MS clamp at each location on upright cable length. uPVC Pipe shall be as per ASTM-D:1785, Sch-80 of PARIXIT/SWASTIK/ASHIRWAD/ASTRAL/DOLPHIN/POLYTECH/FALCON/DUKE make. The price shall also cover for laying the uPVC pipes in ground/road and under the track by digging open trench method. Each length of the pipes shall be joined together using proper size of uPVC coupler and properly aligned in a straight line, keeping an inclination to facilitate the draining of water.
Providing uPVC pipe, 50 mm diameter - The price shall cover for supply of uPVC pipe of 50 mm nominal bore diameter and working pressure of 14 kg/sq. cm along with coupling, elbow, tee etc for protection of cable. The upright cable shall be encased in uPVC pipes for mechanical 96 protection. The pipe shall be clamped with flat MS clamp at each location on upright cable length. uPVC Pipe shall be as per ASTM-D:1785, Sch-80 of PARIXIT/SWASTIK/ASHIRWAD/ASTRAL/DOLPHIN/POLYTECH/FALCON/DUKE make. The price shall also cover for laying the uPVC pipes in ground/road and under the track by digging open trench method. Each length of the pipes shall be joined together using proper size of uPVC coupler and properly aligned in a straight line, keeping an inclination to facilitate the draining of water.
Supply and laying of HDPE pipe, 110 mm diameter by pushing method under track/road - The price shall cover for supply of HDPE (High Density Polyethylene) pipe of 110 mm nominal diameter as per IS 4984-1995 of make Tijaria/Himalyan/Koncept/Poddar/Unique with accessories required 97 for laying such as coupler, bend etc. as per description given in Annexure-XXI of tender document. The price shall also cover for laying the HDPE pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water.
Providing PVC maxi trunking of size 50 x 50 mm - The price shall cover for supply, fixing, testing and commissioning of ISI marked PVC 98 Maxi Trunking of size 50 x 50 mm with all accessories of make Precision/Gerard/Modi/Prestoplast. The PVC Maxi trunking shall be fixed at site by fabricated clamp of 18 SWG GI sheet at a distance not more than 1.5 meters by machine screw/GI nut bolts, washers etc. The existing power cables shall be laid in the PVC Maxi trunking properly dressed and secured by means of suitable clamps/fasteners etc.
Providing PVC maxi trunking of size 100 x 50 mm - The price shall cover for supply, fixing, testing and commissioning of ISI marked PVC 99 Maxi Trunking of size 100 x 50 mm with all accessories of make Precision/Gerard/Modi/Prestoplast. The PVC Maxi trunking shall be fixed at site by fabricated clamp of 18 SWG GI sheet at a distance not more than 1.5 meters by machine screw/GI nut bolts, washers etc. The existing power cables shall be laid in the PVC Maxi trunking properly dressed and secured by means of suitable clamps/fasteners etc.
Supply and erection of G.I. perforated cable tray of size 150 mm x 100 mm x 100 mm on MS frame with cover - The price shall cover for fabrication, supply and fixing of M.S. perforated cable tray, hot dip galvanized as per latest ISS/BSS of size 150 x 100 x 100 mm and 2.0 mm approximate 100 thickness with appropriate cover of thickness 1.6 mm. The cable tray shall be fixed horizontally or vertically at site and the existing LT cables shall be laid/shifted in the cable tray by disconnecting from the panel/switch end and reconnecting as per site requirement duly tied with suitable clamps with GI nuts, bolts and washers in a safe and secure manner. The fixing clamps shall be fabricated from 50 x 50 x 6 mm MS angle or 50 x 6 mm MS flat duly painted and fixed at approximate distance of 1.5 to 2.0 meter apart with 2" long dowel/fisher rack bolts. The tray shall be fabricated in lengths of 2.0 m and couplers shall be provided at joints. The cable tray cover shall be fixed with GI screws.
Supply and erection of G.I. perforated cable tray of size 200 mm x 100 mm x 100 mm on MS frame with cover - The price shall cover for fabrication, supply and fixing of M.S. perforated cable tray, hot dip galvanized as per latest ISS/BSS of size 200 x 100 x 100 mm and 2.0 mm approximate 101 thickness with appropriate cover of thickness 1.6 mm. The cable tray shall be fixed horizontally or vertically at site and the existing LT cables shall be laid/shifted in the cable tray by disconnecting from the panel/switch end and reconnecting as per site requirement duly tied with suitable clamps with GI nuts, bolts and washers in a safe and secure manner. The fixing clamps shall be fabricated from 50 x 50 x 6 mm MS angle or 50 x 6 mm MS flat duly painted and fixed at approximate distance of 1.5 to 2.0 meter apart with 2" long dowel/fisher rack bolts. The tray shall be fabricated in lengths of 2.0 m and couplers shall be provided at joints. The cable tray cover shall be fixed with GI screws.
Laying of cable in trench - The price shall cover for laying, testing and commissioning of LTUG armoured cable in existing trench/pipe and 102 its connection at both ends. The cable shall be tested with 500 Volt Megger earth tester before laying it in the trench. The cable cores shall be tested for continuity, absence of cross phasing, Insulation Resistance between conductors to earth/armour and between conductors. The results should be recorded in presence of railways' representative. A composite cable layout plan on ferro-print or computerized print duly laminated in A-4 size should be submitted by the contractor to this office as well as site in-charge after laying of cable. Cables shall be supplied by railways at site engineer's stores.
Laying of cable on wall/cover shed/existing tray with MS clamp - The price shall cover for laying, testing and commissioning of LTUG 103 armoured cable on wall/cover shed/in existing tray and its connection at both ends. The cable shall be tested with 500 Volt Megger before laying it in the tray. The cable cores shall be tested for continuity, absence of cross phasing, Insulation Resistance between conductors to earth/armour and between conductors. The results should be recorded in presence of railways' representative. A composite cable layout plan on ferro-print or computerized print duly laminated in A-4 size should be submitted by the contractor to site engineer and Divisional Office after laying of cable.
Supply, fixing, testing and commissioning of 5.0-meter height G.I. Street Light octagonal pole, single arm complete with all accessories and foundation - The price shall cover for supply, erection and commissioning of 5.0-meter height single arm, G.I. Street light octagonal pole as per the specifications given in Annexure-XXI of tender document.
Supply, fixing, testing and commissioning of 5.0-meter height G.I. Street Light octagonal pole, double arm complete with all accessories and foundation - The price shall cover for supply, erection and commissioning of 5.0-meter height double arm, G.I. Street light octagonal pole as per the specifications given in Annexure-XXI of tender document.
Providing decorative pole 3.0/3.5 meter height for facade lighting complete with foundation etc - The price shall cover for supply of Mild Steel Decorative Pole of 3.0/3.5 meter length with cast aluminium mounting ring at top. The pole shall be conical in design with a round cross-section. The diameter shall be approximately 70 mm at bottom and 50 mm at top. The thickness of pole shall be 1.5 mm. The pole shall be supplied with a mounting base (suitable for grouting) of thickness 6.0 mm and 130 mm diameter. The mounting base shall be provided with four nos of mounting holes. Holes of suitable diameter with rubber grommet for cable entry shall be provided at top and bottom of the pole. The price shall also cover for erection of the pole, 106 including digging of pole pit of suitable depth and casting of foundation with cement, sand and metal in the ratio of 1:3:6. The foundation shall be of 250 mm diameter of suitable depth and 300 mm height above ground level. The pole foundation top surface above ground level shall have a smooth finish and straight alignment. All items such as cement, sand, metal, foundation bolts, nuts etc. required for execution of this item shall be arranged by the contractor. The price shall also cover for supply, fixing, testing and commissioning of pole mounted junction of SMC model No. GSJB-3020 of SINTEX or similar make for terminating the incoming and outgoing cables and connecting wire of street lights. Junction box shall be complete with suitable connectors and fuse unit for streetlight. Complete unit shall be mounted on the pole by means of suitable hardware, terminal strips, cable glands, clamps etc. After erection of the pole in truly vertical position, it shall be painted with two coats of red oxide paint and one coat of enamel paint as per the colour decided by Railways. Enamel paint shall be of make Asian/Nerolac/ Berger. The coping/foundation above the ground level shall be white washed.
Design, supply, erection, testing and commissioning of 20.0 meter High Mast complete with all accessories including LED flood light 107 luminaries, 200 Watt - The price shall cover for design, supply, erection, testing and commissioning of 20-meter-high mast suitable for installation 10/12 Nos LED flood light luminaries of 200 Watt complete with lantern carriage ring, mounting brackets, foundation bolts, templates, winch wire ropes, power tools, etc. including connection required for fixing of the above fixture on the high mast. Detailed technical specifications are given in Annexure-XXI of tender document.
Erection and commissioning of high mast with all required tools and tackles - The price shall cover for erection and commissioning of high mast with all required tools and tackles. The tenderer must see the site closely before quoting the rates with regard to the nature of soil, average depth of de-composed garbage and debris at mast locations and other site conditions before working out the type foundation and specifications for the proposed 108 high mast of Tender schedule. The tenderer shall be responsible for the design of the foundation and safe erection and installation of the high mast in mechanically and structurally safe working condition for the design life of the mast. The load bearing capacity of the soil of site should be taken in to account to decide the type of foundation and its specifications, as recommended by the manufacturer. The holding down bolts shall be as per the size and quantity as per OEM's design of high tensile strength (TOR steel, 410 Mpa Y.S.) and shall be supplied complete with anchor plate of required thickness for casting into the foundation. The precision made steel template with tube holes should be provided to ensure correct verticality and horizontally of bolt alignment. Two earth terminals shall be provided for each mast and shall be connected to earth.
- Supply, erection, testing and commissioning of foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template - The price shall cover for supply, erection, testing and commissioning of foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template as per the detail given in Annexure-XXI of tender document or as per OEM's design.
Construction of high mast foundation - The price shall cover for providing extra M20/1:2:4 RCC foundation block of suitable dimensions for 110 the high masts considering the safe soil bearing capacity at site as 10 Ton/sq. meter at 2 meter depth with all materials and labour. The foundation should be as per designed approved by the manufacturer of the high mast. The foundation should be capable of holding load of said high mast along with acting wind pressure and other stresses.
Dismantling and removal of existing Flood Light Mast from the existing site - The price shall cover for dismantling of existing, redundant flood light masts in a safe and secure manner. In case of flood light masts installed in the proximity of main line or running lines, the contractor shall be responsible for framing the schedule of work involved for safe and secure removal of flood light masts with the site engineer and put up for approval of Sr. DEE (Power) Vadodara. Power block shall be granted and work shall be completed within the block timings. All tools, tackles, manpower etc required for the work shall be arranged by the contractor well in advance. The scope of the work shall consist of dismantling existing flood light masts along with DP lattice structure with platform on the top and cat ladder along with light fittings and its switch gear etc. The complete flood light towers to be 111 dismantled and stacked properly. The work also involves breaking the CC/RCC foundation of the FL masts above the ground level. The work shall be carried out during day time. The Contractor shall be responsible for making good at his cost to the satisfaction of Railway any loss or any damage to buildings, structures, equipment, installations, properties etc belonging to Railway or being executed or procured or being procured by Railway or of other agencies within the premises of Railway if such losses or damages is due to fault and/or negligence or willful acts, omission, and/or any other reason whatsoever of the Contractor or his employees/agents/representatives etc. The price shall also cover for transportation of the dismantled FL Masts from site to PRTN Stores Depot. The FL masts shall be cut into pieces and laden in vehicle of suitable carrying capacity and transported to PRTN Stores Depot in the presence of railway's representative. The released material shall be shifted to PRTN Stores Depot on the designated date and time as decided by railway authorities.
Supply, fixing, testing and commissioning of step-down transformer, 3.0 KVA, three-phase, 415/110 Volt AC complete with connection - The price shall cover for supply, erection, testing and commissioning of 5.0 KVA, 440/100-120 Volt, 50 Hz step-down transformer housed in MS box. The 112 step-down transformer shall be suitable for outdoor installation and weather proof design. The transformer should be copper wound with tapping for 110 to 120 Volt on low voltage side. Each tapping shall be provided with MCB TPN, 63 Amp on incoming side and three Nos of MCB DP, 40 Amp on outgoing side. Suitable size of MS angle frame shall be provided for erection of the step-down transformer. The step-down transformer shall be of TRIO or any other make approved by Railway.
Fabrication, supply and fixing of outdoor type M.S. box of size 250 mm x 150 mm x 100 mm fabricated from M.S. sheet of 16 SWG thickness with standard angles, channels etc. suitable for housing LED fitting, 12 Watt - The price shall cover for fabrication, supply and fixing of M.S. Box of size 250 mm x 150 mm x 100 mm fabricated from M.S. Sheet of 16 SWG thickness for housing of LED fitting. The box shall be suitable for outdoor application with standard angles, channels etc. The front of the box shall be covered with SS 202 wire mesh grill. The M.S. box should have hinged opening for access to LED fitting. The complete box should be painted with two coats of red oxide paint and finished with one coat of Siemens grey paint.
Supply of M.S. "I" beam of size 150 x 75 mm - The price shall cover for supply of M.S. "I" beam of size 150 x 75 mm confirming to IS-808, type - MB 150, 4.54 kg/feet in 2.0 meter length. The material is to be supplied at site of work.
Providing PVC insulated and sheathed, single core, multi-stranded, Aluminium conductor cable, 10.0 sq. mm - The price shall cover for 115 supply of single core, PVC insulated and sheathed, stranded, Aluminium conductor of 10 sq. mm cross sectional area conforming to IS 1554 - Part-1. The cable shall be flame retardant, should not support combustion and shall be self-extinguishing and shall be of Johnson/Neo-cab/Nicco/Finolex/R.R. Kabel/Asian/Ecotek/L&T/Havells/Polycab/Avocab make. The price shall also cover for laying of the cable for earth continuity from different points as advised by site engineer.
Providing G.I. Earth Wire, 8 SWG in PVC sleeve along with cable - The price shall cover for supply and laying of soft G.I. wire of 8 SWG covered with black coloured PVC sleeve of superior quality and laid along with PVC LTUG cable properly fixed and connecting earthing terminals of each panel.
Providing GI earthing strip, 25 x 4 mm with PVC sleeve - The price shall cover for supply and laying of G.I. earthing strip of 25 x 4 mm size covered with black coloured PVC sleeve of superior quality from earth pit to control/distribution panel board. The earthing strip when laid on wall shall be fixed by means of suitable size of GI clamps and screws.
The price shall cover for providing maintenance free earthing as per the following specifications - 1. High tensile-low carbon steel rod having diameter not less than 17 mm complying with requirements of BS 4360 Grade 43A or EN10025:2-004 S275JR, molecularly bonded by 99.99% pure high conductivity copper on outer surface with copper coating thickness of 250 micron or more, Length 3000 mm (minimum). Certificates from NABL approved labs shall be submitted with test results. 2. Copper earth bus-bar of size 250 mm x 50 mm x 6 mm having electrical conductivity of 101% IACS, minimum 99.9% copper content shall be exothermically welded to rod with 4 holes of 12 mm diameter (two on each side) for connecting earthing conductor. 3. Earth Enhancement compound should have characteristics as mentioned in the RDSO specifications. It should have low resistivity preferably below 0.2 Ohm-meter, supplied in sealed bags (minimum 75 kg per pit for 5' x 5' x 10' size pit and minimum 50 kg per pit for 300 mm bore type pit. The bags shall be marked with manufacturer's name or trade name, quality, Batch No. and date of manufacture. Certificates from NABL approved labs shall be submitted with test results, for at least following parameters - i) Composition of Earth Enhancement compound ii) Resistivity - < 2 Ohm-meter iii) pH value - > 7 but < 9 iv) Moisture retaining capacity - > 10% at 105 degrees Celsius v) Water solubility - < 5% 4. Backfill material - Good quality soil or 118 excavated soil free from sand, gravel and stones shall be used for backfilling. 5. Earth pit of size 5 feet x 5 feet x 10 feet or min 300 mm bore up to 10 feet using earth auger shall be made. 6. Inspection chamber - A concrete box of 300 x 300 x 300 mm (inside dimensions) and 50 mm thickness of wall, with smooth cement plaster finish shall be provided on the top of the pit. A concrete lid, painted black, approximately 50 mm thick with pulling hooks shall be provided to cover the earth pit. PVC sleeve shall be provided in concrete wall to take out earthing connections. 7. On backside of the cover, date of the testing and average resistance value shall be written with yellow paint on black background. 8. Instead of copper bus-bar and strips mentioned in the drawing, a GI main bus-bar of minimum size 300 mm x 75 mm x 8 mm to be installed on nearby wall etc. It shall be connected to earthing with two GI strips of 50 mm x 6 mm size each, up to a distance of 10 meters from earth bus-bar (minimum 3 meters x 2 Nos GI strips to be supplied). 9. Earthing shall generally be carried out in accordance with the requirement of I.E. Rules, 1956, as amended from time to time and shall confirm to IS: 3043 of 1987 with latest amendment. 10. The earth value shall be measured and recorded at the site by painting on earth pit or nearest wall along with date of testing. It shall be less than 2 Ohms and neutral to earth voltage shall be less than 3 Volt. 11. Earthing performance after a year of installation shall be jointly checked and measured. It should be less than 2 Ohm. 12. General arrangement of the earth system shall be as per the drawing given in Annexure-XXI of tender document.
Providing copper plate earthing - The price shall cover for providing Copper plate earthing made from Copper plate of 600 mm x 600 mm x 3.15 mm thick (approximately) buried at not less than 2.5 m deep in soil along with charcoal and salt layer alternately. The earth connection should be 119 made with PVC insulated stranded copper conductor of 16 mm2 from earth electrode to earthing bus bar/apparatus. The earth pit shall be 4 m away from the other earth pits and at least 30 m away from the earth pit of Lightning Arrestor. The potential difference between earth and neutral of filtered/stabilized source should be less than 2 Volt. The earthing installation should be provided with RCC circular box with cover and G.I. "J" bolts. The earthing should be carried out as per IS 3043/1987 or latest and relevant I.E. regulations. The contractor shall maintain the earth resistance below 0.5 and joint testing report along with railways' representative shall be submitted to the site-in-charge.
Providing LED based name board in English, Hindi and Guajarati languages with controlling board, time switch and contactor - The price shall cover for design, fabrication, supply, installation, testing and commissioning of LED Name Boards in English, Hindi and Gujarati languages as per following description - The letters for the Name Board in English, Hindi and Gujarati languages shall be designed in separate boards at suitable locations with superior quality of acrylic sheet of Mitshubishi/Astari or equivalent make of minimum 2.0 mm thickness in red colour. The embossed height of the letter should be minimum 50 mm. The height of the letters should be 450 mm and the width shall be proportionate to the height. All the letters shall be fixed on white-coloured ACP sheet of minimum 3.0 mm thickness and the entire sheet shall be supported on a suitable size of MS angle/Square Pipe 120 frame from the back side to withstand wind pressure as advised by the site in-charge. The letters shall be illuminated from inside by providing Super Flux LED of low heat with extra bright light. The LED modules shall be made air tight, water proof and shock proof. One module of three LEDs shall be taken for every 9 square inch space approximately. The power LEDs shall be duly fixed in cups by silica gel or fusing gum. The LEDS shall be of Cree/Nichia/Osram/Phillips/Lumiled/Avago/ Lednium/ADS/Seoul make. The LEDs are to be glued with the base of the acrylic letters along with appropriate wiring. The wiring shall be done carefully to avoid fusing. The LED modules shall be electrically connected with proper polarity. The SMPS, Drivers and Controllers for the LED module of suitable capacity and quantity shall be suitably selected and provided in weather proof, insect free box with proper ventilation. The input voltage to the drivers should be 230 Volt AC and the output voltage shall be 12/24 Volt DC. The SMPS are installed to regulate the voltage and wattage in the whole circuit which is to be precisely regulated. This shall be designed as per the site requirement. The acrylic sheet, LED modules, SMPS power supply, ACP sheet etc shall be got approved from site in-charge before fabrication.
Supply, installation, testing and commissioning of Solar Street Light unit complete with 30 Watt LED fixture, panel, battery and pole of 6.0 121 meter height including foundation and complete with all accessories - The price shall cover for supply, installation, testing and commissioning of Solar Street Light unit complete with 30 Watt LED fixture, panel, battery and pole of 6.0 meter height including foundation and complete with all accessories as per the detailed specification given in Annexure-XXI of tender document. Above/
B- LED Fittings
Providing four-feet long, 18/20 Watt LED fitting complete with all accessories and LED tube - The price shall cover for supply of 1 x 18/20 Watt LED batten fitting. The fixture shall be of CRCA channel finished with white polyester powder coating with high UV and corrosion resistance. The fixture shall be equipped with end caps, push fit type lamp holders and mains connector to directly fix 4 feet long LED tube. The LED lamp shall be of 1 18/20 Watt. The fitting shall conform to Western Railways' specification no. WR/CCG/Specification/P/001 (Rev. 01) - 2018. The tube shall be of polycarbonate material. The entire fixture shall be of reputed quality and make. The price shall also cover for fixing testing and commissioning of the complete fitting at site by means of bracket made from GI flat of 25 x 3 mm with nuts, bolts and washers or on heavy duty, ISI marked PVC square box as per site requirement. Connection shall be given by means of 24/0.2 mm three-core flexible copper wire through connector and heavy duty flexible PVC conduit. Removal of existing fittings along with brackets and handing over the same to the site in-charge is included in the scope of work.
Supply and fixing of 15/18 Watt LED down lighter - The price shall cover for supply, fixing, testing and commissioning of 15/18 Watt LED luminary operating on 230 Volt, 50 Hz AC supply. The fitting shall conform to Western Railways' specification no. WR/CCG/Specification/P/001 (Rev. 01) - 2018 and shall be of reputed quality and make. The fitting shall be of pressure die cast aluminum suitable for surface/recessed mounting with high 2 efficiency Polycarbonate diffuser. Luminous flux - 2000 lumen, rated luminous efficacy - 110 lumen/Watt, CCT - 6500 deg K, Colour rendering index (CRI) - 80, SDCM - < 5, iTHD - < 10%, Power Factor - 0.95, Median useful life L70B50 @ Ta - 45° C 50,000 burning hours, surge protection level - 2.5 kV with aluminum die cast housing. The fitting shall be fixed at site by means of suitable size of GI Clamps/PVC block as decided by site engineer. The connection shall be given by means of 24/0.2 mm three-core flexible copper wire through proper connector. The fitting arrangement shall be as per the aesthetics of the room. Removal of existing fittings and handing over the same to the site engineer at his store is included in the scope of work.
Providing LED panel light, 20-22 Watt with battery backup - The price shall cover for supply, fixing, testing and commissioning of LED panel 3 light, 2 feet x 2 feet, 20/22 Watt, suitable for surface/recessed mounting. CCT- 6500 deg K, Lumen output - 2000 to 2200 Lumen, Cool Day Light. The fitting shall have in-built battery of 3.9 Volt - 6 AH capacity. The fitting shall have zero-flickering light with 2 hours of battery back-up in emergency situations. The fitting shall be of reputed make and shall be got approved by site engineer before supply and commissioning.
Supply, fixing, testing and commissioning of LED Bulkhead fitting, 20 Watt for operation on 110 Volt, AC supply - The price shall cover for supply of 20 Watt, LED bulk head fitting, IP: 65 protection, operating on 110 Volt AC supply complete with LED tubes. Technical specification of the bulk head fitting are as given in Annexure-XXI of tender document.
Providing LED module 2 feet x 2 feet, 38 Watt ±3 Watt suitable for recessed/surface mounting complete with all accessories - The price shall cover for supply, fixing, testing and commissioning of eco-friendly, maintenance free and energy efficient LED module, 2 feet x 2 feet of 36/38 Watt ±3 Watt made from CRCA housing with high efficiency diffuser for full glow and constant current electronic driver suitable for 220 - 240 Volt, 50 Hz AC 5 supply. The fitting shall conform to Western Railways' specification no. WR/CCG/Specification/P/001 (Rev. 01) - 2018 and shall be of reputed quality and make. The fitting shall be suitable for recessed/surface mounting arrangement. The fitting shall be fixed at site by means of suitable size of GI Clamps/PVC block as decided by site engineer. The connection shall be given by means of 24/0.2 mm three-core flexible copper wire through proper connector. The fitting arrangement shall be as per the aesthetics of the room. Removal of existing fittings and handing over the same to the site engineer at his store is included in the scope of work.
Providing LED Street light luminary, 45 Watt ±10% complete with all accessories - The price shall cover for supply of 45 Watt (±10%) LED Street Light fitting made from pressure die-cast LM6/ADC12/LM24 housing with optimal heat sink for better thermal dissipation and toughened glass or UV stabilized polycarbonate cover with high transmission index for superior light output. The fitting shall be as per Western Railways' specification no. WR/CCG/Specification/P/001 (Rev-01)-2018 and shall be of reputed quality and make. The fitting shall be designed for IP: 65 class protection for 6 pole/bracket mounting. The fitting shall be provided with special moisture proof vent. The fitting shall be of reputed quality and make. The price shall also cover for fixing, testing and commissioning of the above street light fitting on pole/truss/roof/wall by fabrication and supply of 'B' class G.I. pipe of required length, diameter and shape and fixed with M.S. clamps made from M.S. flat of 40 x 5 mm size duly painted with nut, bolts and washers of 12 mm diameter. The connection shall be carried out through ISI marked, PVC insulated, flexible three-core copper wire of size 24/0.20 mm from the existing overhead line/catenary/junction box as per site conditions. The connection cord shall be protected by suitable size of heavy duty flexible PVC conduit. Removal of existing fittings along with pipe and clamps and handing over the same to the site in-charge is included in the scope of work.
Providing LED batten fitting, 2 x 18/20 Watt, IP: 65 rated complete with four-feet LED tubes - The price shall cover for supply of 36/38 Watt LED weather proof fitting with IP: 65 protection. The fitting shall conform to Western Railways' specification no. WR/CCG/ Specification/P/001 (Rev. 01) - 7 2018 and shall be of reputed quality and make. The housing and cover of the fitting shall be made from virgin polycarbonate. The price shall also cover for fixing testing and commissioning of the complete fitting at site by means of bracket made from GI flat of 25 x 3 mm with nuts, bolts and washers or on heavy duty, ISI marked PVC square box as per site requirement. The connection to the fitting shall be carried out through three-core, 1.0 sq. mm, FRLS PVC insulated, ISI marked, flexible copper wire through connector and heavy-duty flexible PVC conduit as per site conditions. Removal of existing fittings, if any, along with brackets and handing over the same to the site in-charge is included in the scope of work.
Supply, fixing, testing and commissioning of LED high/mid bay luminary, 50/60 Watt - The price shall cover for supply of energy efficient LED high/mid bay luminary 50/60 Watt capacity having pressure die cast aluminium housing, toughened front glass cover, fitted with secondary optics, heat sink and integrated electronic driver for long life with IP 65 protection class for provision on high masts. The fitting shall operate on 240 Volt, 50 Hz 8 AC supply and shall be as per Western Railways' specification no. WR/CCG/Specification /P/001 (Rev-01)-2018. The price shall also cover for fixing, testing and commissioning of the above high/mid bay luminary on pole/truss/roof/wall/high mast by fabrication and supply of 'B' class G.I. pipe of required length, diameter and shape and fixed with M.S. clamps made from M.S. flat of 40 x 5 mm size duly painted with nut, bolts and washers of 12 mm diameter. The connection shall be carried out through ISI marked, PVC insulated, flexible three-core copper wire of size 24/0.20 mm from the existing overhead line/catenary/junction box as per site conditions. The connection cord shall be protected by suitable size of heavy duty flexible PVC conduit. Removal of existing fittings along with pipe and clamps and handing over the same to the site in-charge is included in the scope of work.
Supply, fixing, testing and commissioning of LED high/mid bay luminary, 100 Watt - The price shall cover for supply of energy efficient LED high/mid bay luminary 100 Watt capacity having pressure die cast aluminium housing, toughened front glass cover, fitted with secondary optics, heat sink and integrated electronic driver for long life with IP 65 protection class for provision on high masts. The fitting shall operate on 240 Volt, 50 Hz AC supply 9 and shall be as per Western Railways' specification no. WR/CCG/Specification /P/001 (Rev-01)-2018. The price shall also cover for fixing, testing and commissioning of the above high/mid bay luminary on pole/truss/roof/wall/high mast by fabrication and supply of 'B' class G.I. pipe of required length, diameter and shape and fixed with M.S. clamps made from M.S. flat of 40 x 5 mm size duly painted with nut, bolts and washers of 12 mm diameter. The connection shall be carried out through ISI marked, PVC insulated, flexible three-core copper wire of size 24/0.20 mm from the existing overhead line/catenary/junction box as per site conditions. The connection cord shall be protected by suitable size of heavy duty flexible PVC conduit. Removal of existing fittings along with pipe and clamps and handing over the same to the site in-charge is included in the scope of work.
Supply, installation, testing and commissioning of Extruded Aluminium Linear LED luminary, IP 54/65 - The price shall cover for supply, installation, testing and commissioning of Extruded Aluminum Linear LED luminary, IP 54/65 as per site condition (in case of indoor installation the fitting shall be IP 54 and in case of outdoor installation the fitting shall be IP 65) to be decided by railways. Depth of the luminaire (without driver) should not be 10 greater than 35 mm. The housing shall be constructed of extruded aluminum. System lumen output of 4000 lumens @ 6500 deg K, CCT and CRI - >80. The luminary shall be supplied with LED Driver with operating voltage 140 to 270 Volt AC, iTHD - <10%, P.F. - >0.95 and inbuilt 4 KV protection inside the driver. The luminary should conform to Western Railways' Specification No. WR/CCG/Specification/P/001 (Rev. 01) - 2018 and shall be of reputed quality and make. The fitting shall be fixed at site by means of suitable size of GI Clamps/PVC block as decided by site engineer. The connection shall be given by means of 24/0.2 mm three-core flexible copper wire through proper connector as per site requirement. The fitting arrangement shall be as per the aesthetics of the room. Removal of existing fittings and handing over the same to the site engineer at his store is included in the scope of work.
Supply, fixing, testing and commissioning of LED high/mid bay luminary, 150 Watt - The price shall cover for supply of energy efficient LED high/mid bay luminary 150 Watt capacity having pressure die cast aluminium housing, toughened front glass cover, fitted with secondary optics, heat sink and integrated electronic driver for long life with IP 65 protection class for provision on high masts. The fitting shall operate on 240 Volt, 50 Hz AC supply 11 and shall be as per Western Railways' specification no. WR/CCG/Specification /P/001 (Rev-01)-2018. The price shall also cover for fixing, testing and commissioning of the above high/mid bay luminary on pole/truss/roof/wall/high mast by fabrication and supply of 'B' class G.I. pipe of required length, diameter and shape and fixed with M.S. clamps made from M.S. flat of 40 x 5 mm size duly painted with nut, bolts and washers of 12 mm diameter. The connection shall be carried out through ISI marked, PVC insulated, flexible three-core copper wire of size 24/0.20 mm from the existing overhead line/catenary/junction box as per site conditions. The connection cord shall be protected by suitable size of heavy duty flexible PVC conduit. Removal of existing fittings along with pipe and clamps and handing over the same to the site in-charge is included in the scope of work.
Supply, fixing, testing and commissioning of LED Flood Light luminary, 200 Watt - The price shall cover for supply of energy efficient LED flood light luminary, 200 Watt capacity having pressure die cast aluminium housing, toughened front glass cover, fitted with secondary optics, heat sink and integrated electronic driver for long life with IP 65 protection class for provision on high masts. The fitting shall operate on 240 Volt, 50 Hz AC supply 12 and shall be as per Western Railways' specification no. WR/CCG/Specification /P/001 (Rev-01)-2018. The price shall also cover for fixing, testing and commissioning of the above flood light luminary on high mast by suitable and secure fixing arrangement. The connection shall be carried out through ISI marked, PVC insulated, flexible three-core copper wire of size 24/0.20 mm from the existing junction box. The connection cord shall be protected by suitable size of heavy duty flexible PVC conduit. Removal of existing fittings and handing over the same to the site in-charge is included in the scope of work.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .