Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.1 LAdmitted-Finance G 58 KIRAN GARDEN UTTAM NAGAR NEW DELHI 110059 | NEW DELHI | WEST DELHI | DELHI | 110059 | ₹15.1 L | L1 | Admitted-Finance |
| 2 | L2₹18.2 LAdmitted-Finance GF AKRITI TOWER 19 B VIDHAN SABHA MARG LUCKNOW PIN 226001 | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226001 | ₹18.2 L | L2 | Admitted-Finance |
| 3 | L3₹20.9 LAdmitted-Finance 1170 BENGALI MOHALLA NEAR PRABHAKAR HOSPITAL AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | ₹20.9 L | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Sumit Enterprises L1 | Prime Technology L2 | The Rahul Vig L3 |
|---|---|---|---|---|---|---|
| 1.00 | M&L for preventive maintenance of fire alarm system complete conventional / Addressable type at technical area AFS Ambala having smoke, heat, multi detector, beam detector, Addressable module, manual call point, addressable electronic sounder cum strobe, short circuit isolator, electronic siren, PA system complete with quarterly checkup of entire system and unlimited breakdown calls complete all as specified & directed.
Note :-
(i) The entire fire alarm system shall be tested by representative of Accepting Officer after completion of repair as per relevant IS in the presence of the user GE and Engr-in-Charge. Contractor shall request for testing through GE.
(ii) The spare parts required to be replaced will be measured and paid seperately.
(iii) The programming of panel, if required, is deemed to be included in quoted rate.
(iv) The unserviceability noticed of fire alarm system shall be attended with in 72 hours ( after reported by JE / Engineeer in charge) failing which a sum of Rs 1000/- per day shall be recovered from the contractor.
(v) The preventive maintenance of fire alarm system under this contract shall be done through rep of OEM only.
(vi) The contractor shall carry out routine checking of the complete fire alarm system and rectify the minor/major defect noticed during checking immediately. Cleaning of Panel & detector once in a quarter for smooth functioning and making the maintenance register for above maintenance and one separate register to be maintained by the contractor. The register will be signed by Engr-in-Charge /JE (E/M) and user rep after rectifying the defect.
(vii) Contractor shall rectify the defect between 0700 Hrs to 1500 Hrs.
(viii) The payment shall be made after succeesuful completion of the quarter and one complete site will be measured as one unit. No seperate payment shall be paid for complaints / site visit any number of time throughout the quarter. | 48 | Each Job | 4,200 ₹2.0 L | 11,000 ₹5.3 L | 14,375 ₹6.9 L |
| 2.00 | Supply, installation, testing & commisioning in replacement of intelligent addressable microprocessor based panel 1 loop addressable microprocessor based with each loop capable of handling 60 Detectors and 60 devices upto 120 devices with suitable battery back up upto 72 hours, 32 bit dual core microprocessor touch LCD display to indicate power, alarm silence, trouble system, trouble disable, test supervision, delay audio alarm with push button for acknowledgement test, reset complete with power supply of 24 volt DC of suitable AH and 230 volt complete all as specified & directed .
Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley
Note : The panel shall be CE certified and ERTL approved. | 2 | Each | 26,000 ₹52,000 | 33,750 ₹67,500 | 65,998.5 ₹1.3 L |
| 3.00 | Supply, installation, testing & commisioning in replacement of intelligent addressable microprocessor based panel 2 loop addressable microprocessor based with each loop capable of handling 125 Detectors and 125 devices upto 250 devices with suitable battery back up upto 72 hours, 80 bit dual core microprocessor touch LCD display to indicate power, alarm silence, trouble system, trouble disable, test supervision, delay audio alarm with push button for acknowledgement test, reset complete with power supply of 24 volt DC of suitable AH and 230 volt complete all as specified & directed .
Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley
Note : The panel shall be CE certified and ERTL approved. | 2 | Each | 34,000 ₹68,000 | 66,000 ₹1.3 L | 95,787.5 ₹1.9 L |
| 4.00 | Supply, installation, testing & commisioning in replacement of intelligent addressable multisensor type (combination of Heat & Smoke) detectors with base. The detectors shall sense real fire/smoke and generate alarm if any fire/smoke occurred in the building . The detectors shall have two built-in LEDs for 360 degree viewing complete all as specified & directed .
Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley | 210 | Each | 1,695 ₹3.6 L | 2,075 ₹4.4 L | 1,543 ₹3.2 L |
| 5.00 | Supply, installation, testing & commisioning in replacement of loop driven addressable sounders with strobe in built. The addressable soundres with strobe shall form part of loop devices such that, no additional seprate wiring is required. The sounders shall have audible range of 93 DB when heared at distance of 1.00 mtr. The sounders shall be suitable for wall/ ceiling mounting and shall operate on +24 volts DC complete all as specified & directed .
Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley | 8 | Each | 1,900 ₹15,200 | 2,550 ₹20,400 | 4,000 ₹32,000 |
| 6.00 | Supply, installation, testing & commissioning in replacement of addressable manual pull station. The addressable manual call point (MCP) shall be housed in metallic box.The address module shall be in-built and shall form part of loop module . The MCP shall be red colour with red LED for display of fire complete all as specified & directed .
Note: Break Glass type MCP with chain and hammer is not acceptable
Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley | 5 | Each | 1,900 ₹9,500 | 1,100 ₹5,500 | 3,000 ₹15,000 |
| 7.00 | Supply, installation, testing & commissioning in replacement of Detectors complying with and type certified to EN- 45 intelligent addressable Ultra violet /infra red flame detector with IP-66 enclosure suitable for ceiling or wall mounting complete all as specified & directed .
Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley | 4 | Each | 51,000 ₹2.0 L | 45,500 ₹1.8 L | 50,000 ₹2 L |
| 8.00 | Supply, installation, testing & commisioning in replacement of response indicator assembly mounted on wall/partition in dust tited enclosure with indication dual lamp LED compatibility with all detector for multisensor type heat and smoke detectors complete all as specified & directed.
Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley | 9 | Each | 50 ₹450 | 100 ₹900 | 150 ₹1,350 |
| 9.00 | M&L in replacement wiring for connecting fire detectors and fire Alarm panels with PVC insulated, sheathed, armoured (as per IS:7098-Part-l) 2 x 1.5 Sqmm multistrand 1100 volt FRLS copper conductor cable and core sheath shall be FRLS and insulated with HFC sheathing. The HFC cable shall be of red in colour and marking of every 1.00 mtr in the cable complete all as specified & directed . | 850 | RM | 180 ₹1.5 L | 120 ₹1.0 L | 125 ₹1.1 L |
| 10.00 | Supply, Installation, Testing & commissioning in replacement of electrically operated siren, single phase continuous operation for at least 50 minutes with sound level 65 decibal to 120 decibal measured at 1.5 mtr with sound output variation +/-5 decibal, 500 mtr range complete all as specified & directed. | 5 | Each | 3,800 ₹19,000 | 4,850 ₹24,250 | 7,500 ₹37,500 |
Updated dates
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
8 Apr 2026, 6:00 pmClosed
CWE (AF) Ambala
HQ CWE (AF) Ambala Cantt-133001
CWE/AF AMB/AMB-48/2025-26 REPAIR MAINT AND REPLACEMENT OF FIRE ALARM DETECTION SYSTEM IN OTM ACCN OF DOMESTIC AREA AND TECH AREA AT AF STN AMBALA UNDER GE AF AMBALA
2026_MES_755650_1
CWE/AF AMB/AMB-48/2025-26
Open Tender
Civil Works
365 days
Ambala
For MES enlisted contractor Class E Category c vi and for un-enlisted contractor
refer NIT
8 documents required · 8 mandatory
₹500
GE (AF) Ambala
₹50,000
Yes
22 Apr 2026
9 Mar 2026
10 Apr 2026
9 Mar 2026
8 Apr 2026
24 Mar 2026
9 Mar 2026 - 20 Mar 2026
Supply, installation, testing & commisioning in replacement of intelligent addressable microprocessor based panel 1 loop addressable microprocessor based with each loop capable of handling 60 Detectors and 60 devices upto 120 devices with suitable battery back up upto 72 hours, 32 bit dual core microprocessor touch LCD display to indicate power, alarm silence, trouble system, trouble disable, test supervision, delay audio alarm with push button for acknowledgement test, reset complete with power supply of 24 volt DC of suitable AH and 230 volt complete all as specified & directed . Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley Note : The panel shall be CE certified and ERTL approved.
Supply, installation, testing & commisioning in replacement of intelligent addressable microprocessor based panel 2 loop addressable microprocessor based with each loop capable of handling 125 Detectors and 125 devices upto 250 devices with suitable battery back up upto 72 hours, 80 bit dual core microprocessor touch LCD display to indicate power, alarm silence, trouble system, trouble disable, test supervision, delay audio alarm with push button for acknowledgement test, reset complete with power supply of 24 volt DC of suitable AH and 230 volt complete all as specified & directed . Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley Note : The panel shall be CE certified and ERTL approved.
Supply, installation, testing & commisioning in replacement of intelligent addressable multisensor type (combination of Heat & Smoke) detectors with base. The detectors shall sense real fire/smoke and generate alarm if any fire/smoke occurred in the building . The detectors shall have two built-in LEDs for 360 degree viewing complete all as specified & directed . Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley
Supply, installation, testing & commisioning in replacement of loop driven addressable sounders with strobe in built. The addressable soundres with strobe shall form part of loop devices such that, no additional seprate wiring is required. The sounders shall have audible range of 93 DB when heared at distance of 1.00 mtr. The sounders shall be suitable for wall/ ceiling mounting and shall operate on +24 volts DC complete all as specified & directed . Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley
Supply, installation, testing & commissioning in replacement of addressable manual pull station. The addressable manual call point (MCP) shall be housed in metallic box.The address module shall be in-built and shall form part of loop module . The MCP shall be red colour with red LED for display of fire complete all as specified & directed . Note: Break Glass type MCP with chain and hammer is not acceptable Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley
Supply, installation, testing & commissioning in replacement of Detectors complying with and type certified to EN- 45 intelligent addressable Ultra violet /infra red flame detector with IP-66 enclosure suitable for ceiling or wall mounting complete all as specified & directed . Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley
Supply, installation, testing & commisioning in replacement of response indicator assembly mounted on wall/partition in dust tited enclosure with indication dual lamp LED compatibility with all detector for multisensor type heat and smoke detectors complete all as specified & directed. Make: EST / Honeywell / Siemens / Notifire / Ravel / Agni protection / Morley
M&L in replacement wiring for connecting fire detectors and fire Alarm panels with PVC insulated, sheathed, armoured (as per IS:7098-Part-l) 2 x 1.5 Sqmm multistrand 1100 volt FRLS copper conductor cable and core sheath shall be FRLS and insulated with HFC sheathing. The HFC cable shall be of red in colour and marking of every 1.00 mtr in the cable complete all as specified & directed .
Supply, Installation, Testing & commissioning in replacement of electrically operated siren, single phase continuous operation for at least 50 minutes with sound level 65 decibal to 120 decibal measured at 1.5 mtr with sound output variation +/-5 decibal, 500 mtr range complete all as specified & directed.
S&F in replacement Digital display of Fire alarm addresable Panel complete all as specified & directed .
S&F in replacement Power supply/SMPS 24 volt, including transformer for digital panel complete all as specified & directed . Make: Siemens, model No.FP2011U1 or equivalent in Bosch or Agni protection
S&F in replacement Batteries 7 AH 12 Volt, complete all as specified & directed .
M&L for Comprehensive maintenance of electrically operated passenger lift of capacity 8 passengers of Make - KONE inside Technical Area (G+4) by OEM or Agency authorised by OEM for a period of Twelve Months from the date of handing over of site. The scope of CMC is excluding Refinishing repair or replacement of following components :- (a) Elevator car enclosure (b) Elevator car and landing door panels/ gates (c) Alarm bell/ buzzer (d) Incoming electrical wiring up to main switches in the m/c room. (e) Main switches in the m/c room (f) LCDs (g) Decorative items including mirror and hand rail. Notes: (i) The CMC will be covering the entire lift i.e Limit swiches, door/lift Sensors, Elevator switch panel, Electric control panel, drives, pully, rope, gear system including accessories and oil etc. (ii) All parts and components fitted by KONE will be original genuine parts or components. If original parts or components are not available the parts or components fiitted will be of equal quality and functionality as per OEM recommendation in writing. (iii) Monthly serviceability report will be submitted to Engineer-in-Charge after due inspection of OEM. (iv) Reported serviceability will be attended by contractor through authorised Engineer of OEM within 48 hours. A penalty of Rs.1000/- per Day will be levied after 48 hours of reporting of Fault. (v) Payment shall be done only after successful comprehensive maint & visit of OEM in every month. For Credit Schedule, refer tender documents. The amount of credit schedule shall be deducted from total quoted amount of BOQ to arrive contract sum.
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.25 MB
BOQ_846395.xls
BOQ • 1.48 MB
Tender48.pdf
Tender Documents • 0.77 MB
Download all tender documents and submit your bid