Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹5.2 LAccepted-AOC COMET ELECTRICAL ENGINEERING CO KOTTAKKAL MALAPPURAM | 1 | Accepted-AOC AEE/LSGD-DIV/MPM/085/20-21 | |
| 2 | 2₹5.3 L+₹8,921 (1.73%)Rejected-Finance | 2 | Rejected-Finance L2 |
Tender Value
₹6.0 L
EMD Value
₹15,000
Closing Date
14 May 2020, 6:55 pmClosed
Executive Engineer
OFFICE OF THE EXECUTIVE ENGINEERLSGD DIVISION, MALAPPURAM DISTRICT PANCHAYATH CIVIL STATION (PO), MALAPPURAM -676505
Malappuram DP Annual Plan (2020-21), Project No. 715/21, Electrification of Elad Lift Irrigation Project - Elamkulam
2020_LSGD_355097_1
DB4/TN/05/20-21
Open Tender
Electrical Works
Item Rate
120 days
Malappuram
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,344
Yes
online
₹15,000
Yes
26 Jul 2020
6 May 2020
19 May 2020
6 May 2020
14 May 2020
6 May 2020
Amount
Charges for removing the mud, sand and other particles deposited due to the natural calamity (flood) from motors, pump, starter ,motor basement etc using suitable tools and water
Charges for disconnecting the electric supply of motor pump set, starters and dismantling the motor pump set, starters from foundations and panel board etc with out any further damages or losses using suitable tools etc and servicing l reconnecting, the same and making good working condition etc as required.
Charges for 60 HP motor leading to nearest road side, loading into the vehicle and convey to the workshop including leading, loading and unloading. at work shop, separating the motor, in to stator & rotor,reassembling and convey to pump house and refitting , test run and making good working condion etc as required.
Charges fo Checking the dismantled 60 HP motor stator and rotor andcleaning the the stator andCharges for rotor thoroughly using fresh water removing the sand and mud particles from core, coil etc and removing the water and moisture content using and heating the same for 6 days to get required IR value.cleaning the windings, cleaning with petrol, attending minor repairs, retaping the coils if necessary, varnishing the coils with best quality insulation varnish, cleaning and greasing the bearings with Lithium base grease, heating and baking the windings, reassembling scraping cleaning and pasinting etc as required
Dismantling the 60 HP oil immersed motor starter, drain out existing transformer oil, cleaning the contacts, attending minor repairs, and refilling the required quantity of best quality transformer oil and replacing the 600v, 50Hz no volt coil and reassembling the same including giving connection, test running etc as required
Charges for suction pipe removing mud and pther particles and resetting etc as required
Dismantling the existing delivery pipe supply anf fitting valves, NRV etc for operting two pumps alternatly after cutting and welding etc using required matierilas and fittings and making good working condion and test run etc as required
Charges for disconnecting the electric supply, dismantling the Incomer, Bus bar, outgoing swtches meters etc from the existing main panel board cleaning thoroughly, heating to get the required IR value,scraping,cleaning and painting the whole board with two coats of sinthetic enamel paint over a coat of red oxide primer and refitting the dismantled switches and accessories in position including checking and taping the wires, checking and tightening all connections etc and giving connection
Supply and renewal of Carbon brushes for 60-75 HP motor in place of damaged one
Supply and renewal of Roller bearing for pump side in place of damaged one
Supply and renewal of Ball bearing for pump side in place of damaged one
Supply and renewal of Gland packing for pump set in place of damaged one
Supply and renewal of Gasket set for pump set in place of damaged one
Supply installation testing and commissioning of Kirloskar 10HP Three Phase 1450RPM, 50*50 size Vacuum Pump with 10C4 Coupled Motor, DV-50 suitable for 60 HP motor pump set and test run etc as reuired
Supply and wiring with PVC insulated stranded single core copper conductor cables for interconnecting the control devices/ equipments including the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. 1.5Sqmm single run
Supply and wiring with PVC insulated stranded single core copper conductor cables for interconnecting the control devices/ equipments including the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. 4.00Sqmm single run
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc. Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
Supply and providing heavy duty 'A' section neoprene gasket in the panel board U' section rubber beeding suitable for 1.60/ 2.00 mm sheet
Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
Supply and providing copper earth bus in the panel board
Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required. 250A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required. 200A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with icroprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 3 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
MCCB Accessories Supply and fixing one number under voltage release for all voltage range up to 630A MCCB.
MCCB Accessories Supply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 315-630 A
MCCB Accessories Supply and fixing one number earth fault Relay up to 250A to 400A with CBCT.
supply and fixing Red, Green, blue, Yellow, Orange colours LED indicator, AC/DC, as required
400/5 A, 5 VA, accuracy class 1, Tape wound Metering CT
Supply and fixing Digital Multifunction meter to read: V, A, F, PF-3 phase accuracy class 1 LED
0 - 600 V analogue type AC volt meter with 90° deflection scale, accuracy class 1 & of size 72 x 72 mm
CT operated, analogue type AC ammeter with 90° deflection scale, suitable dial, accuracy class 1 & of size 72 x 72 mm
Supply and fixing Danger notice board of size, 125 x 75 mm
S & F Motor starters of the following ratings Fully automatic star delta starter for 15HP motor
Supply andproviding of 150 mm NRV in with new one
Supply and jointing of 150mm Full way valve in existing delivery pipe as required
Supply and providing single phase ntor and giving connection etc as required.
Supply and fixing 32mm dia G.I. pipe or nearest size (medium class) with fittings as required
Supply, threading laying and jointing of 100mm dia B class GI pipe with all required accessories as required and giving connections to both ends at pump elivery/suction side
Supply, threading laying and jointing of 150mm dia B class GI pipe with all required accessories as required and giving connections to both ends at pump delivery/suction side
Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the onduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare opper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories). Single Control light point with 6A, plate ceiling rose - Short point
Supply and fixing cast aluminium stove enameled bulk head fitting with deep drawn anodised aluminium body, epoxy powder coated, heat resistant prismatic glass cover with 9W LED bulb to wall / ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and making good the surface as required.
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required 4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
Supplying and fixing 40 amps to 63 amps rating 240/415 volts, "C" curve Triple pole., miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 16 sq mm with factory made clamp
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 70 sq mm
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 95 sq mm
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 3.5 core 35 sq mm with factory made clamp
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 16 sq. mm (28mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm)
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required 2.00 mm copper conductor ( 14 SWG)
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required 3.15 mm copper conductor ( 10 SWG)
Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required. 2.00 mm (14 SWG)
Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required. 3.15 mm (10 SWG)
Supply and providing 25x6mm brass nut and bolt etc. as required.
Supply and providing 12x3mm brass nut and bolt etc. as required.
P. R. RIJESH
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_499450.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .