Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
Tender Value
₹15.1 L
EMD Value
₹30,129
Closing Date
1 Oct 2022, 6:00 pmClosed
EE(E), BSNL, ED-2 ,Ernakulam
EE(E), BSNL, ED-2 ,Ernakulam
Repairs, service to the existing fire hydrant wet riser system and renovation of automatic fire detection and alarm system in Administrative building Thrissur for obtaining final fire NOC
2022_BSNL_129773_1
08/NIT/BSNL/Ed-2/2022-23
Open Tender
Electrical Works
Item Rate
90 days
BSNL, Sanchar Bhavan
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹30,129
Yes
29 Dec 2022
22 Sept 2022
3 Oct 2022
22 Sept 2022
1 Oct 2022
22 Sept 2022
22 Sept 2022 - 1 Oct 2022
Amount
Servicing of 48 HP (37.25 KW) Water pump (model of DSM 100/36) driven by 72 BHP capacity Diesel Engine i/c Servicing and Replacing of lub oil for 72 HP Engine for the standby pump set i/c replacing lub oil filters and diesel filters, cleaning of air filter etc i/c applying lubrication, changing the gland packing of pump to arrest the leakages if any, cleaning, checking and making to running condition etc as required. (The Engine oil shall be as per the recomendation of Engine OEM)
Servicing of 65 HP (49.07 KW) water pump (model of DSM 100/36) with 45KW Electric motor , including checking working of motor and pump, rectifying minor complaints, changing the gland packing to arrest the leakage if any and applying lubrication including cleaning etc as required.(Re-winding of motor is not in included)
Servicing of 12.5 HP centrifugal pump with 9.3 KW Electric motor, including checking working of motor and pump, rectifying minor complaints, arresting water leakage through seals, changing the gland packing to arrest the leakage if any and applying lubrication including cleaning etc as required.(Re-winding of motor is not included)
Servicing of Electrical control panel of wet riser system , i/c checking & tightening of all connections , setting and testing the automatic system, identifying of faulty components if any , i/c Rectifying the fault in the auto operation of the pumps i/c replacing the minor faulty accessories, i/c cleaning and painting the accessible area of the control panel with enamel paint after removing rust, testing etc as reqd
Servicing, cleaning, arresting leakage by replacing packings and applying lubrication of all the internal and external hydrant valves, , single and double hydrant valves, 2 Nos Siamese Fire brigade inlet, its couplings, Pressure switches sluice valves, Hose real, Shutoff nozzle, Air release valve etc as required ( excluding gate valves & non return valves )
Servicing and cleaning the diesel tank , fuel line , valves etc connected to the existing Diesel Engine as required
Servicing and cleaning the priming tank ,water line , valves etc as required
Painting the 72 BHP diesel engine with 48 HP water pump, 45 KW electrical motor with 65 HP water pump, 9.3 KW electrical motor with 12.5 HP jockey water pump with suitable color enamel paint, i/c complete cleaning, removing rust etc as required
Painting of the entire hydrant piping ( accessible area ) of the wet riser system including internal hose cabinets with 2 coat for external systems and one coat for internal with postal red colour enamel paint after removing rust , complete cleaning etc as required.
Servicing of existing 2 nos of 200 mm dia Gate valves in existing fire hydrant line i/c removing the damaged gland packing/ washers , providing new packings refixing testing etc as required.
Servicing of existing 1no 100 mm dia Gate valves in existing fire hydrant line i/c removing the damaged gland packing/ washers , providing new packings refixing testing etc as required.
Supply and fixing following items in the Electrical control panel
Contactor MNX 40
Star Delta Timer
Supplying and fixing of the following valves & gauges as per specifications of following types (ISI marked)
20 mm GI Pipe
Pressure switch
Pressure gauge
20 mm connection hose
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :
(a) 100mm dia
(b) 150mm dia
S/F 100 MM dia cast iron foot valve in the existing suction line of jokey pump after dismantling and removing the damaged one as required.
S/F 200 MM dia cast iron foot valve in the existing suction line of Diesel engine pump/ main electric motor pump after dismantling and removing the damaged one as required.
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
(a) 150 mm dia
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :
Stainless Steel (Grade 304)
Supplying & fixing 63 mm dia SS short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :
Stainless Steel (Grade 304)
Supplying and fixing hose cabinet for accommodating two number 15metre hose made out of 1.6mm M.S. sheet as per specifications for
External hydrant
Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required ( to be provided in existing 80mm dia c class GI pipe )
Single headed Stainless steel
Supplying and laying C class GI pipes with all accessories ( i/c fittings like bends, 'T' sections , elbows, gaskets etc ) including cutting, welding, laying, conducting pressure testing, but excluding valves, gauges in under ground , including excavating the soil and cement concrete pavements/ cement concret floor i/c cutting the cement concrete flooring, i/c laying the new pipe cutting, welding, jointing to existing vertical wet riser i/c applying 2 coats of primer, applying anticorosive warpping coating/ asphalt tape on the GI pipe including making good the damages in concrete floor, as per specifications as reqd.
150mm dia
Supplying and laying C class GI pipes with all accessories ( i/c fittings like bends, 'T' sections , elbows, gaskets etc ) including cutting, welding, laying, conducting pressure testing, but excluding valves, gauges on above ground on wall / floor / free standing with suitable brackets/ in existing trench with suitable platform or providing suitable concrete pedastals from ground pedastals and fixing the pipe with suitable iron strip, clamps, brackets etc from existing fire pump room to building end , i/c cutting, welding, applying 2 coats of primer, applying one coat of postal red enamel paint, and fixing the pipe with suitable iron strip, clamps, brackets etc as reqd.
150mm dia
80mm dia
Making sutable opening of approximate 150mm dia in the existing over head tank by core cutting for connecting the existing fire hydrant line to the over head tank i/c removing the debris from the tank etc as reqd.
Supplying and installing lead acid automotive battery of the following capacity suitable for Gen set applications with initial charging , transportation, loading and unloading, giving terminal connections i/c supply of battery leads, testing ,commissioning etc complete as required. Note : (The battery shall be supplied in buy back scheme)
12V,150 AH (Model : Exide Express/ SFS)
Supply installation testing and commissioning of Signage system in the existing G+5 floor Admn Building with following arrangements i/c providing wiring , connections testing etc as reqd.
LED Signage “Fire Duct / FIRE” with battery back up
Signage board “Fire Exit”
Signage board “No Smoking”
Floor identification signage
Supplying Installation , testing & commissioning of Intelligent analog addressable photothermal detector complete with mounting base complete as required ( Item Model to be compatable with Notifier panel )
Supplying Installation , testing & commissioning of Intelligent analog addressable thermal detector with rate of rise cum fixed temperature thermister completee with base as required ( Item Model to be compatable with Notifier panel )
Supplying Installation , testing & commissioning of addressable manual call point complete as required ( Make:to be compatable with the existing Notifier panel)
Supplying , Installation, testing & commissioning of addressable horn cum strobe complete as required .( Item Model to be compatable with Notifier panel )
S/L of 2 x 1.5 sq mm fire alarm armoured cable, 600/ 1000 v rated with anealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required
Supplying, installation, testing and commissioning of fault isolator complete with base as required.
Two loop panel
Supply, Installation of 3X3 metal box for Fire modules
Servicing of existing addressable type AFD repeater panels in G+5 floors ( make : Notifier ) i/c reprogramming if reqd testing commissionng etc as reqd.
Servicing of existing addressable type multidensor/ smoke detector i/c cleaning , servicing testing commissionng etc as reqd. ( Make: Notifier )
Servicing of existing addressable type MCP i/c cleaning , servicing testing commissionng etc as reqd. ( Item Model to be compatable with Notifier panel )
Supply and fixing of following type Fire extinguishers i/c handling, fixing testing etc as reqd.
CO 2 type 4.5 Kg
Powder type ABC 2 Kg
Servicing/ Refilling of following type Fire extinguishers i/c handling, pdg To and fro transportation ,testing , refixing etc as reqd.
CO 2 type 4.5 Kg
Powder type BC 4.5 Kg
ABC 2.0 Kg
AB type 9 Litre
Preparing necessary Drawing, documentation and conducting inspection from both local fire station and divisional office and to getting final NOC from Fire and rescue department i/c remitting necessary fees etc as reqd..(Note :statutary fee paid by the agency will be reimbursed on production of original receipt from the department ) including the fire drill and operational demo to the occupants of the building
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .