Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.9 CrAccepted-AOC | ₹13.9 Cr Quoted ₹15.1 Cr | L1 | Accepted-AOC Agreement executed |
Tender Value
₹13.1 Cr
EMD Value
₹5 L
Closing Date
2 Nov 2023, 4:00 pmClosed
Superintending Engineer
Superintending Engineer KWA PH Circle Muvattupuzha
JJM CWSS TO IDUKKI KANJIKKUZHY VAZHATHOPE MARIYAPURAM KAMAKSHI VATHIKUDY AND VANNAPPURAM SUPPLY AND ERECTION OF FLOATING PUMP AND RAW WATER PUMPING MAIN PACKAGE I
2023_KWA_614266_1
Re-206/2023-24/SE/PHC/MVPA
Open Tender
Civil Works - Water Works
365 days
PH Circle Muvattupuzha
As per NIT
12 documents required · 12 mandatory
₹16,540
₹5 L
PH Circle Muvattupuzha
26 Feb 2024
19 Oct 2023
3 Nov 2023
19 Oct 2023
2 Nov 2023
19 Oct 2023
21 Oct 2023
Amount
floating Pantoon with submerged type pumpset and allied accessories
OD74402/2022-2023:Design, manufacture, inspection, transportation, supply, installation, testing and commissioning of centrifugal pump set with a variable frequency drive starter as per specification for a duty of 186 LPS at a total head of 65 mtrs at 1000 RPM, suitable for operation on 415V +/- 6%, AC, 3 phase supply 50HZ +/- 5% with suitable mounting frame and power cable of appropriate size.
OD25920/2023-2024:Supply of Submersible EPR Cable copper flexible round Power & control cable (1R X 3Cx35 mm2 + 3Cx25&3 Run 20 Cx1 sqmm)
OD74404/2022-2023: Design, manufacture, transportation to site, erection and testing of one no pontoon made of MS cubes/ HDPE heavy duty pipes both sides closed, SS framework, plat form, hoisting posts, cross beam, pulley block, pump set holding frame, Screen facility to prevent foreign materials from infiltrating the pump suction bell, fixing bolts, MS pipe powder coated hand rails etc.
OD74405/2022-2023:Design, Supply and Erection of suitable metallic walkway (floating type) for carrying the delivery pipelines (3.5 mtr wide)
OD74406/2022-2023:Design, Supply and erection of SS Flexible Hose Pipe (delivery pipe from platoon to shore) of required diameter suitable for withstanding 15 kg/cm2 of maximum pressure during pumping with suitable 12mm thick M.S flanges for jointing each other - minimum 3 mts long
OD74407/2022-2023:Suitable Gasket ,Bolt & Nut for flexible joint
OD75357/2022-2023:In situ fabrication of M.S. pipes of size 300mm (I.D.) using 10mm thick M.S. plate including cost and conveyance charges of M.S. plate, all fabrication charges, charges of painting the steel work with two or more coat deluxe multi surface paint to give an even shade over an under-coat of primer etc., complete.
OD75362/2022-2023:Fabricating M.S. flanges of diameter 300mm using 12mm thick M.S. plate including cost and conveyance charges of M.S. plate, all fabrication charges, charges of painting the steel work with two or more coat deluxe multi surface paint to give an even shade over an under-coat of primer etc., complete: For pipes fabricated with 10mm thick M.S. plates.
OD75366/2022-2023:Cutting, Grinding & welding 300mm (I.D.) M.S. pipes for making bends and other specials by gas cutting including cost of gas, all labour and hire charges of tools etc., complete: For pipes fabricated with 10mm thick M.S. plates.
100.37.14.1:In situ fabrication of M.S. pipes of size 600mm (I.D.) using 8mm thick M.S. plate including cost and conveyance charges of M.S. plate, all fabrication charges, charges of painting the steel work with two or more coat deluxe multi surface paint to give an even shade over an under-coat of primer etc., complete.
OD250732/2022-2023:In site fabrication of 600mm dia MS manifold of 4m length with 2nos of 400mm dia inlet and 1 no of 600mm outlet branches including all cost of conveyance, material and labour charges.
OD250740/2022-2023:In site fabrication of 500mm dia MS manifold of 4m length with 2nos of 300mm dia inlet and 1 no of 400mm outlet branches including all cost of conveyance, material and labour charges.
OD250803/2022-2023:In site fabrication of 500mm dia MS manifold of 4m length with 3nos of 300mm dia inlet and 4 no of 400mm outlet branches including all cost of conveyance, material and labour charges.
OD75378/2022-2023:Supply, fixing and commissioning of SITC 80 mm dia., PN-2.0, Flanged End High Performance Tamper Proof Kinetic Air Valve with Automatic Air Release Valve with Isolating PN 2.0 Sluice Valve, for water combination type (non-tampering type) having double ball, double orifice with stainless steel ball, tamper proof air vents rolling seal mechanism for air release and anti-vacuum application designed for 15 kg/cm2 working pressure and tested for 15 kg/cm2 pressure, having flat faced flanges and drilled to IS : 1538 / Part-IV /VI.
OD75385/2022-2023:Supply, fixing and commissioning of 0-25 kg / cm2 - 150 mm dia, Glycerin Filled Type Pressure Gauge with siphon & cock as per IS specifications with SS ball valve, SS hex nipple, with required accessories, erection hardware, necessary mounting supports, etc. complete and as per the direction of engineer in charge (on each Pump delivery pipe & on header pipeline)
OD74412/2022-2023:Supply Fabricated MS Specials of (i) D/F Enlarger (ii) 90 Deg. D/F Bend (iii) D/F Distance Piece for DPCV & BFV (iv) Double flanged M.S.Pipes piece for Air Valves (v) 90 Deg. Bend ,(vi) Blind Flange/ Blank plate (vii) Std. Drilled Flange for pumpset delivery (viii) Std. Drilled Flange for Header line including bolts, nuts, washers, rubber packing etc, suitable for above pumpsets and common header. Dimensions and Drilling of flanges should be as per IS;1538/1976. Flange faces should be machined and holes should be drilled on drilling machine. M.S pipe should be conforming to IS-3589/ 2001 / suitable / latest with epoxy painted of following sizes
OD75388/2022-2023:Supply and Installation of control cable from butterfly valve actuator to the starter and operating module including one module with necessary NC/NO contacts, contactor, timers and indication lamps with on and off push button stations and off mode lockable system.
OD75390/2022-2023:SITC of all weather juntion boxes with aluminium bus insulated bushings, connection on the pontoon and shore near the pumping header
OD75401/2022-2023:Supply of necessary marine rope, steel ropes, concrete blocks for using as counter weight etc. as required for stabilising the pontoons and walk way & Supply and Erection of electrically operated winches to anchor the floating system with supplied steel/ marine rope and electrical control system
OD76447/2022-2023:Supply, fixing and commissioning of 300 mm diameter sizes PN-2.0 (Suitable), Double Flanged Dual Plate Check Valve (DPCV) confirming to API - 594 having body, door, cover in graded Cast Steel ASTM A216 Grade WCB, Metal Seat, Hing/ stop pin, Spring - S.S. AISI 410, Resilient seal - Nitride. Valve seat tested to 15 kg/cm2 and body to 24 kg/cm2. Flanges machined faced and drilled to IS : 1538 / 1976 Part-IV/VI.
OD76449/2022-2023:Supply, fixing and commissioning of 600 mm dia, PN-2.0 (Suitable), Double Flanged Motor operated Butterfly valve generally confirming to IS :13905 having body, disc, in graded cast iron to IS:210, FG : 260, shaft, thrust pad of stainless steel AISI 410, body seat ring, internal hardware of SS AISI 304. Valve seat tested to 15 kg/ cm2 and body to 24 kg / cm2 flanges machined faced and drilled to IS : 1538 / 1976 Part-IV/VI.
OD75372/2022-2023:Supply, fixing and commissioning of 600 mm diameter sizes PN-2.0 (Suitable), Double Flanged Dual Plate Check Valve (DPCV) confirming to API - 594 having body, door, cover in graded Cast Steel ASTM A216 Grade WCB, Metal Seat, Hing/ stop pin, Spring - S.S. AISI 410, Resilient seal - Nitride. Valve seat tested to 15 kg/cm2 and body to 24 kg/cm2. Flanges machined faced and drilled to IS : 1538 / 1976 Part-IV/VI.
OD75373/2022-2023:Supply, fixing and commissioning of 400 mm dia, PN-2.0 (Suitable), Double Flanged Motor operated Butterfly valve generally confirming to IS :13905 having body, disc, in graded cast iron to IS:210, FG : 260, shaft, thrust pad of stainless steel AISI 410, body seat ring, internal hardware of SS AISI 304. Valve seat tested to 15 kg/ cm2 and body to 24 kg / cm2 flanges machined faced and drilled to IS : 1538 / 1976 Part-IV/VI.
100.98.487:Supply of CI Double Flanged Sluice Valve Conforming to IS 14846 - 2000, Sluice Valve with Hand Wheel PN 1.6, Size 300mm.
OD250801/2022-2023:Supply and Laying HDPE pipes (IS : 4984) on on the newly placed floating system including conveying within initial lead and aligning the pipes, electro-fusion welding using automatic or semi-automatic electrofusion machines, testing the pipeline thus fabricated to suit the hydraulic working pressure and after testing, aligning the pipeline - including all labour charge, cost of pipe and hire for appliances etc., complete : 315mm Nominal Outside Diameter Pipes.
Transformer, DP Structure & Yard
OD78149/2023-2024:Supply, installation, testing and commissioning of one number 630 kVA, DYn11, 3Ph, 50Hz, 11/0.433 kV, ONAN cooled, copper wound outdoor distribution transformer with tappings from +5% to -10% in steps of 2.5% with OFTC. The HT side & LT side shall have cable end box for XLPE cable. The transformer shall have suitable enclosure for The HT side & LT side. The transformer shall be complete with all standard accessories and fittings & conform to IS:2026. The rate shall be inclusive of all materials, lead, lift, first fill of oil, necessary civil works for mounting to the existing transformer foundation complete as per single line schematic diagram & particular specifications.
OD78170/2023-2024:Supply & Providing 5P10 Protection Class, 150/5A, 15VA Neutral CT in a suitable enclosure including giving connections to Transformer Neutral etc. complete
OD78171/2023-2024:Supply & erection of Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with : Cement mortar 1:6 (1 cement : 6 coarse sand).
OD78172/2023-2024:Supplying and filling the substation yard with 40mm size blue jelly of 150mm thick including cost and conveyance of all materials, labour charges etc complete
OD78173/2023-2024:Providing, fabricating and fixing 2m high chainlink fencing over 4mm thick barbed wire with a framework of 50x50x6mm MS angle between vertical posts of ISMC 75 at 2400mm interval, Earthing as per KSEI/KSEB standards shall be done around the periphery of the fencing. The MS framework for chainlink fencing shall be Hot Dip Galvanised. The rate shall be inclusive of all materials, labour, lead, lift etc including escalation works and fabrication and assembly works including all nuts, bolts and other miscallaneous items etc complete as per drawing and as directed by the Engineer in Charge.
OD78174/2023-2024:Supply & Providing 3 phase, 4wire, HT CT/PT operated, bi-directional with accuracy class 0.2S for both Active and Reactive energy, -/5A, HT static tri vector meter with TOD register, DLMS compliant & AMR compatible with optical port and RS232 port having ISI Marking, suitable for measurement of active kWh, reactive energy kVARh and apparent energy kVAh and kVA MD, kW MD at nominal frequency in the range of 47.5 Hz to 52.5 Hz in balanced as well as unbalanced load conditions in the existing outdoor Meter cubicle including testing & commissioning etc. complete.
OD78175/2023-2024:Construction of 11kV DP STRUCTURE - Erection of RCC/ PCC pole of following length in brick ballast and ramming the foundation, finishing with 150 mm thick cement concrete (1:3:6) layer on top with including excavation and refilling etc. as required. - Supplying and erection - (1) a set of cross bracing framework for 11 kV overhead line double pole structure having four members fabricated out of 50 mm X 50 mm X 6 mm angle iron to form a rectangle of minimum size 1400 mm width X 2500 mm height, complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts and nuts etc. (as per drawing) and painting with primer and finish paint as required. - (2) Erection of double pole 3 wire cross arm for 11kV/22kV/33 kV overhead lines as required. - (3) 11 kV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required. - (4) three-piece nonlinear resistor type lightning arrestor suitable for 3 wire, 11 kV overhead lines with rated voltage 9 kV (rms) with a nominal discharge current rating of 5 kA and complete with galvanized clamping arrangement, G.I. bolts, nuts, washers etc. as required. etc complete as per the direction of the department officer in charge.
MV panel boards, Distribution Box, Cables and accessories
OD78771/2023-2024:Supply, fabrication, erection, testing and commissioning of cubicle type fully compartmentalised, dust tight, vermin proof, water proof 1000A LT- Main MV Panel falling to IP54 category fabricated out of 16 SWG CRCA Sheet Steel painted as per standards with Alumimium Busbars of suitable size, earth bus of adequate capacity, double earth connection to all switches, internal rigid connection etc. including suitable chambers, front open, top cable entry with water proof shrouding, free standing panel consisting of the following as per standards ( All switches shall confirm to conforming to IEC 60947-2 standards). (1) Incomer - 1000A FP Microprocessor based MCCB (50kA) with overcurrent and Earthfault release - 1 Nos., Restricted Earth Fault Relay - 1 Set, 1000A TPN best conductivity Aluminium busbar with SMC supports, heat shrinkable sleeves etc. as per ISS - 1set, RYB indicators ( LED Pilot type ) with 2A Control MCB and toggle switches - 4 Set, Multifunction Digital Panel meter to read V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh Class 1.0 - 1 Set, 1000/5A CL 1.0, 15VA Metering CTs - 1 Set - (2) Outgoings - 400A 36kA FP MP MCCB - 3 Nos with suitable mechanical interlocking with each other so as to operate 2 Nos at a time, 250A 36kA FP MP MCCB-2nos, 160A 36kA FP MP MCCB - 2 Nos, 10A TP D curve MCB (10kA) - 1 Nos. (3) Surge Protection - Pluggable type surge arrester with potential free contact, thermal disconnector & provision for inbuilt common remote indication for defective arresters to connect between Line and Neutral and one number Spark Gap type arrester to connect between Neutral and Earth of following ratings including base element & pluggable arresters. Nominal voltage 230V, 50Hz, Nominal Discharge current 30 kA (8/20 sec) for Line to Neutral & 50 kA (8/20 sec) for Neutral to Earth, Maximum Discharge Current Imax 50 kA (8/20 sec) -1Set - (3) Supports - The panel shall be supported to ground using framework fabricated out of MS Flats / Angles etc. painted with two coats of Zinc Chromate primer and two coats of enamel paint. The framework shall be firmly supported to ground using suitable cement concrete plinth., The Panel Board shall be provided with 25 x 3mm copper earth bus for the full length. Painting letters / identifications for the incoming and outgoing switches, cable, fuse sizes, etc., in white enamel paint. The board shall be fabricated in such a way that future extenstion be possible.
OD78775/2023-2024:Supplying and making Outdoor cable end jointing with heat shrinkable jointing kit, including lugs and other jointing materials, for following sizes, XLPE aluminium conductor cable of 11 KV grade as required. - HT Cable Termination - 3C x 300 Sqmm
OD78776/2023-2024:Supplying and making Outdoor cable end jointing with heat shrinkable jointing kit, including lugs and other jointing materials, for following sizes, XLPE aluminium conductor cable of 11 KV grade as required. - HT Cable Termination - 3C x 150 Sqmm
OD78777/2023-2024:Supply & laying 11KV stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3 kA for 1 sec.), cores laid up, inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable of the following sizes in the existing cable trench conforming to IS: 7098 part II 1985 with latest amendments. (1) 3C x 150 Sqm
OD78778/2023-2024:Supply & laying 11KV stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3 kA for 1 sec.), cores laid up, inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable of the following sizes in the existing cable trench conforming to IS: 7098 part II 1985 with latest amendments. (1) 3C x 300 Sqmm
OD78779/2023-2024:Supply and providing the following MCCB/ RCCB / MCB / MCB Isolators/COS etc. to the existing DBs / MCS / Junction Boxes etc. including giving proper termination using suitable Bananna copper lugs, sleeves, insulation etc. complete. (1) 63A, 100mA 3Ph RCCB - 1no, (2) 63A, 4P MCB Isolator - 1no, (3) 6A to 32A , 10kA SP MCB - 36nos
OD78780/2023-2024:Supply, installation, testing & commissioning of best quality sheet steel, phosphatised and painted, dust and vermin proof enclosure (IP43) Vertical TPN Double door DB including copper bus bar, neutral link, earth bus and DIN rail suitable for fixing RCCB + Isolator (8 module )as incommer and SP/TP MCB as outgoings etc. on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing, dressing the DB including termination etc. as required. ( Including closing vaccant slots using Dummy ) - 12 way distribution board
OD78781/2023-2024:Supply, fabrication, erection, testing and commissioning of cubicle type fully compartmentalised, dust tight, vermin proof, water proof 200A MV Panel falling to IP54 category fabricated out of 16 SWG CRCA Sheet Steel painted as per standards with Alumimium Busbars of suitable size, earth bus of adequate capacity, double earth connection to all switches, internal rigid connection etc. including suitable chambers, front open, top cable entry with water proof shrouding, free standing panel consisting of the following as per standards ( All switches shall confirm to conforming to IEC 60947-2 standards). (1) Incoming - 200A TPN best conductivity Aluminium busbar with SMC supports, heat shrinkable sleeves etc. as per ISS - 1set, Multifunction Digital Panel meter to read V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh Class 1.0 - 1 Set, RYB indicators ( LED Pilot type ) with 2A Control MCB and toggle switches - 1 Set, 100/5A CL 1.0, 15VA Metering CTs - 1 Set - (2) Outgoings - 200A 36kA FP MP MCCB - 2 Nos, 160A 36kA FP MP MCCB - 3 Nos, 10A TP D curve MCB (10kA) - 1 Nos. - (3) Supports - The panel shall be supported to ground using framework fabricated out of MS Flats / Angles etc. painted with two coats of Zinc Chromate primer and two coats of enamel paint. The framework shall be firmly supported to ground using suitable cement concrete plinth., The Panel Board shall be provided with 25 x 3mm copper earth bus for the full length. Painting letters / identifications for the incoming and outgoing switches, cable, fuse sizes, etc., in white enamel paint. The board shall be fabricated in such a way that future extenstion be possible. (1) Incomer - 125A TPN MCB - 1 No., 125 A TPN best conductivity Aluminium busbar with SMC supports, heat shrinkable sleeves etc. as per ISS - 1set, Multifunction Digital Panel meter to read V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh Class 1.0 - 1 Set, RYB indicators ( LED Pilot type ) with 2A Control MCB and toggle switches- 1 Set, 160/5A 15VA CL 1.0 Metering CTs - 3 Sets, Microprocessor based intelligent, 8 step IPFC relay with PF display - 1 No. - (2) Out goings - 40A, 10kA C Curve TP MCB - 3 Nos, 20A, 10kA C Curve TP MCB - 2 Nos , 10A, 10kA C Curve TP MCB - 1 Nos, 6A, 10kA C Curve TP MCB - 3 Nos, Capacitor duty contactors working on 3 Phase 415V AC supply of the following ratings wired with Pilot LED indication for ON & OFF, Push Buttons for Manual ON & OFF operation using suitable NO / NC contacts for all the stages, 20 kVAr - 3 Nos, 10 kVAr- 2 Nos, 7.5 kVAr- 4 Nos, 480 V,50 Hz Double di-electric polypropylene ( MPP heavy duty ) Capacitors of the following ratings including fixed compensation for low load losses., 20 kVAr - 3 Nos, 10 kVAr - 2 Nos, 5 kVAr- 1 Nos, 2 kVAr - 2 Nos, 1 kVAr - 1 Nos - (3) Supports - The panel shall be supported to ground using framework fabricated out of MS Flats / Angles etc. painted with two coats of Zinc Chromate primer and two coats of enamel paint. The framework shall be firmly supported to ground using suitable cement concrete plinth., The Panel Board shall be provided with 25 x 3mm copper earth bus for the full length. Painting letters / identifications for the incoming and outgoing switches, cable, fuse sizes, etc., in white enamel paint.
OD78782/2023-2024:LT Cables - Supply & laying UG 2XFY,PVC insulated and PVC sheathed Copper conductor armoured Power / Control cable of 1.1 KV grade of the following sizes through trench/wall/ ceiling - 4C x 2.5 Sqmm
OD78783/2023-2024:LT Power Cables - Supply & laying UG A2XFY,PVC insulated and PVC sheathed Aluminium conductor armored power cable of 1.1 KV grade of following sizes through trench/wall/ ceiling. - 3C x 4 Sqmm
OD78784/2023-2024:LT Power Cables - Supply & laying UG A2XFY,PVC insulated and PVC sheathed Aluminium conductor armored power cable of 1.1 KV grade of following sizes through trench/wall/ ceiling. - 3C x 6 Sqmm
OD78785/2023-2024:LT Power Cables - Supply & laying UG A2XFY,PVC insulated and PVC sheathed Aluminium conductor armored power cable of 1.1 KV grade of following sizes through trench/wall/ ceiling. - 3C x 16 Sqmm
OD78786/2023-2024:LT Power Cables - Supply & laying UG A2XFY,PVC insulated and PVC sheathed Aluminium conductor armored power cable of 1.1 KV grade of following sizes through trench/wall/ ceiling. - 3C x 25 Sqmm
OD78787/2023-2024:LT Power Cables - Supply & laying UG A2XFY,PVC insulated and PVC sheathed Aluminium conductor armored power cable of 1.1 KV grade of following sizes through trench/wall/ ceiling. - 3C x 35 Sqmm
OD78788/2023-2024:LT Power Cables - Supply & laying UG A2XFY,PVC insulated and PVC sheathed Aluminium conductor armored power cable of 1.1 KV grade of following sizes through trench/wall/ ceiling. - 4C x 4 Sqmm
OD78789/2023-2024:LT Power Cables - Supply & laying UG A2XFY,PVC insulated and PVC sheathed Aluminium conductor armored power cable of 1.1 KV grade of following sizes through trench/wall/ ceiling. - 4C x 6 Sqmm
OD78790/2023-2024:LT Power Cables - Supply & laying UG A2XFY,PVC insulated and PVC sheathed Aluminium conductor armored power cable of 1.1 KV grade of following sizes through trench/wall/ ceiling. - 4C x 16 Sqmm
OD78791/2023-2024:LT Power Cables - Supply & laying UG A2XFY, PVC insulated, and PVC sheathed Aluminium conductor armored power cable of 1.1 KV grade of following sizes through trench/wall/ ceiling. - 3.5C x 35 Sqmm
OD78792/2023-2024:LT Power Cables - Supply & laying UG A2XFY,PVC insulated and PVC sheathed Aluminium conductor armored power cable of 1.1 KV grade of following sizes through trench/wall/ ceiling. - 3.5C x 400 Sqmm
OD78793/2023-2024:LT Power Cables - Supply & laying UG A2XFY,PVC insulated and PVC sheathed Aluminium conductor armored power cable of 1.1 KV grade of following sizes through trench/wall/ ceiling. - 3.5C x 185 Sqmm
OD78795/2023-2024:Supply route marker with 10cmx10cm GI plate 5mm thick with inscriptions there on bolted / welded to 35x35x6mm angle iron 60cm long and fixing the same in ground as required.
OD78796/2023-2024:Supply and erection of 6mm MS Chequered Plates for covering cable trench. ( Rate for 10 Sq.m)
OD78797/2023-2024:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. - Above 95 sq. mm and upto 185 sq. mm
OD78798/2023-2024:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. - Above 35 sq. mm and upto 95 sq. mm
OD78799/2023-2024:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. - Upto 35 sq. mm
OD78800/2023-2024:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. - Above 120 sq. mm and upto 400 sq. mm
OD78801/2023-2024:Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required - 600 mm width X 50 mm depth X 2 mm thickness
OD78802/2023-2024:Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required - 300 mm width X 50 mm depth X 1.6 mm thickness
OD78803/2023-2024:Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required - 150 mm width X 50 mm depth X 1.6 mm thickness
OD78804/2023-2024:Circuit Mains - Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. - 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
OD78805/2023-2024:Circuit Mains - Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. - 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
OD78806/2023-2024:Circuit Mains - Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. - 2 X 4 sq. mm + 1 X 4 sq. mm earth wire
OD78807/2023-2024:UG Cable Tamper Protection - Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required - 100mm
OD78808/2023-2024:UG Cable Tamper Protection - Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required - 80mm
OD78809/2023-2024:UG Cable Tamper Protection - Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required - 50mm
OD78810/2023-2024:PVC Conduits - Supply & providing Capping / Casing of good quality of the following sizes. - 25mm
OD78811/2023-2024:PVC Conduits - Supply & providing Capping / Casing of good quality of the following sizes. - 20mm
OD78812/2023-2024:PVC Conduits - Supply and providing the following size of ISI Marked rigid PVC conduits with specials confirming to IS 9537/1983 on surface / concealed position making good the damages made etc. complete. - 32mm dia 1.5mm thick
OD78813/2023-2024:PVC Conduits - Supply and providing the following size of ISI Marked rigid PVC conduits with specials confirming to IS 9537/1983 on surface / concealed position making good the damages made etc. complete. - 25mm dia 1.5mm thick
OD78814/2023-2024:PVC Conduits - Supply and providing the following size of ISI Marked rigid PVC conduits with specials confirming to IS 9537/1983 on surface / concealed position making good the damages made etc. complete. - 20mm dia 1.5mm thick
OD78815/2023-2024:Supply & drawing the following size of FR Multi-core PVC Insulated and PVC sheathed Copper conductor round flexible wire manufactured with bright annealed bare copper conductor as per IS 8130/1984 Insulated and sheathed with electrical grade PVC compound as per IS 5831/1984 generally conforming to IS 694/1990 for working voltage up to and including 1100 V through existing PVC conduit / casing capping wall. - 3C x 1.5 Sqmm
OD78816/2023-2024:Supply & drawing the following size of FR Multi-core PVC Insulated and PVC sheathed Copper conductor round flexible wire manufactured with bright annealed bare copper conductor as per IS 8130/1984 Insulated and sheathed with electrical grade PVC compound as per IS 5831/1984 generally conforming to IS 694/1990 for working voltage up to and including 1100 V through existing PVC conduit / casing capping wall. - 3C x 0.5 Sqmm
OD78817/2023-2024:Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE copperconductor cable of 1.1 KV grade as required. - 4C x 2.5 Sqmm
OD78818/2023-2024:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. - 3.5C x 185 Sqmm, 3.5C x 400 Sqmm, 3.5C x 35 Sqmm, 4C x 16 Sqmm, 4C x 6 Sqmm, 4C x 4 Sqmm, 3C x 35 Sqmm, 3C x 25 Sqmm, 3C x 16 Sqmm, 3C x 6 Sqmm and 3C x 4 Sqmm
Earthing and Accessories
OD78890/2023-2024:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required - 4.75 mm copper conductor (6 SWG)
OD78891/2023-2024:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required - 4.00 mm copper conductor ( 8 SWG)
OD78892/2023-2024:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required - 3.15 mm copper conductor ( 10 SWG)
OD78893/2023-2024:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required - 2.65 mm copper conductor (12 SWG)
OD78894/2023-2024:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run) 25 x 3 mm copper strip
OD78895/2023-2024:Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but with charcoal/ coke and salt ) as required.
OD78896/2023-2024:Earthing with 1200x1200x12.5 mm CI - Plate Earthing thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Substation Equipments
OD78882/2023-2024:Supply & providing Aluminium anodised Danger Notice Board of size 200 x 150 mm. with inscriptions ( both in English and Malayalam) and conventional Skull and Bone in Red colour at locations as directed by the Engineer in Charge
OD78883/2023-2024:Supply and providing Laminated Electrical Schematic diagram framed and placed in a conspicuous location for clear vision.
OD78884/2023-2024:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
OD78885/2023-2024:Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint 'FIRE' mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor stand including making good the damages, colour washing etc. as required.
OD78886/2023-2024:Supply and providing 5 Kg. Dry Chemical Powder type Fire Extinguisher with hose and clamps including fixing it to wall as required.
OD78887/2023-2024:Supply and providing 12 mm thick & 1 m wide electrical grade chequered type rubber mat to withstand 15 KV dielectric strength conforming to IS 5429/ 1969 in front of the HT Breaker Panel.
OD78888/2023-2024:Supply and providing 6 mm thick & 1 m wide electrical grade chequered type rubber mat to withstand 3.3 KV dielectric strength conforming to IS 5429/ 1969.
Supply and providing safety equipment/lights in floating pump house
OD83977/2022-2023:Supply, erection, testing and commissioning of street light facility with 70W LED bulb near the floating walk ways including the cost of iron poles and its installation in the ground etc complete
OD86559/2023-2024:Supply, Erection, Testing and Commissioning of flood light (150W LED) inside the floating platoon to see the components inside and light towards outside to see the water around the platoon clearly etc complete
OD86608/2023-2024:Supply of Life buoy ring preserver with a minimum holding capacity of 60kg etc complete
power factor improvement capacitors
OD84013/2022-2023:Supply,erection,testing and commissioning of 415V 60 KVAr power factor improvement capacitors suitable for each motor with suitable enclosure for indoor application and conforming to IE rules and provided with necessary cable and cable termination kits of good quality.
Final approval from KSEI
OD78904/2023-2024:Preparation and submission of latest scheme drawings, Voltage drop calculations, Earthing design & fault level calculations to the Electrical Inspectorate including all MV additions recently made and obtaining approval, arranging inspection for entire installation, obtaining sanction orders for the electrical installation, complete (Including all incidental and statutory expenses ).
Construction of Transformer control room
2.33.1:Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 30 cm girth up to and including 60 cm girth
2.33.2:Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 60 cm girth up to and including 120 cm girth
2.33.3:Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyond 120 cm girth up to and including 240 cm girth
2.6.1:Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil
2.8.1:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
7.1.1:Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) up to plinth level with:Cement mortar 1:6 (1 cement : 6 coarse sand)
4.1.2:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:1/2:3 (cement : 11/2 coarse sand : 3 graded stone aggregate 20 mm nominal size)
5.33.1:Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work upto plinth level
5.33.2:Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work above plinth level upto floor V level
5.9.1:Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
5.9.3:Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform
5.9.5:Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
5.9.6:Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts
5.22.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
50.6.1.2:Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement: 6 coarse sand) etc complete.
13.1.1:12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand)
13.43.1:Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer
13.60.1:Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work
10.6.1:Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters.80x1.25 mm M.S. laths with 1.25 mm thick top cover
50.9.1.1:Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately), using good quality Anjili wood /jack wood
50.9.5.1:Providing and fixing glazed shutters for doors, windows and clerestory windows using 4 mm thick float glass panes including ISI marked M.S pressed butt hinges bright finished of required size with necessary screws. Using Anjili wood/ jack wood 35 mm thick shutters.
50.9.4.1:Providing and fixing paneling or paneling and glazing in paneled or paneled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured) paneling for paneled or paneled and glazed shutters 25 mm to 40 mm thick using good quality Anjili/ Jack wood
13.48.2:Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Painting wood work with Deluxe Multi Surface Paint of required shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.75 ltr/10 sqm of approved brand and manufacture
13.48.3:Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture
11.39:Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS: 15622, of approved make in colours White, Ivory, Grey, fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 cement : 4 Coarse sand), including grouting the joints with white cement and matching pigments etc., complete.
11.36:Providing and fixing I st quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer -in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
13.71:Lettering with black Japan pint of approved brand and manufacture
10.25.2:Item Shifted to Sub head 14 as item 14.73 Item Shifted to head 14 as item 14.74 Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
OD74400/2022-2023:Supply , delivery and fixing of 3 T or suitable capacity Electrically and manually working on single girder with overhead travelling trolley and clear lift as per site conditions for lifting the chemicals, Chlorine, pumps etc.. and fitting as required, supplied with one set of crane slings with GI D shackle and clamps etc. complete as per the instruction of the Engineer in charge.<br>
17.3.1:Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :W.C. pan with ISI marked white solid plastic seat and lid
17.7.4:Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap
OD74401/2022-2023:Water supply and sanitary arrangments
Road Restoration Charge (Morth)
3.6:Excavation for roadwork in soil with hydraulic excavator of 0.9 cum bucket capacity including cutting and loading in tippers, trimming bottom and side slopes, in accordance with requirements of lines, grades and cross sections, and transporting to the embankment location within all lifts and lead upto 1000m
4.1.B.2:Construction of granular sub-base by providing graded material, spreading in uniform layers with a motor grader on a prepared surface, mixing by mix in-place method with rotavator at OMC, and compacting with a vibratory roller to achieve the desired density, complete as per clause 401. Grading-VI - For sub-base cum drainage layer - Mix in Place Method
4.12:Providing, laying, spreading and compacting graded stone aggregate to Wet Mix Macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver in sub- base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density.
5.1.a:Providing and applying primer coat with bitumen emulsion ( SS) on prepared surface of granular Base including clearing of road surface and spraying primer at the rate of 0.70 - 1.0 kg/sqm using mechanical means.
OD74415/2022-2023:Mix seal surfacing Providing,laying and rolling of close-graded premix surfacing material of 20mm thickness composed of 11.2mm to 0.9mm Type-A aggregate using penetration grade bitumen to required line,grade and level to serve as wearing course on previously prepared base,including mixing in a suitable plant,laying and rolling with a three wheel 8-10 KN static roller and finishing to required level and grades as per Technical specification cluse 509 of MORD(Usage of bitumen is 22.00Kg/(10m2)By Manual Means
Part VI-Operators Cabin near Floating Pumphouse
2.33.1:Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 30 cm girth up to and including 60 cm girth
2.33.2:Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 60 cm girth up to and including 120 cm girth
2.6.1:Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil
2.8.1:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
4.1.2:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:1/2:3 (cement : 11/2 coarse sand : 3 graded stone aggregate 20 mm nominal size)
5.33.1:Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work upto plinth level
5.33.2:Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work above plinth level upto floor V level
5.9.1:Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
5.9.5:Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
5.9.6:Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts
50.6.1.2:Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement: 6 coarse sand) etc complete.
5.22.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
13.1.1:12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand)
13.43.1:Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer
13.60.1:Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work
10.25.2:Item Shifted to Sub head 14 as item 14.73 Item Shifted to head 14 as item 14.74 Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
13.48.3:Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture
16.17.1:Fencing with R.C.C. post placed at required distance, embedded in cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and end post one side only, provided with horizontal lines and two diagonals of barbed wire weighing 9.38 kg per 100 metres (minimum), between the two posts fitted and fixed with G.I staples on wooden plugs or G.I binding wire tied to 6 mm bar nibs fixed while casting the post (cost of R.C.C. posts, struts, earth work and concrete to be paid for separately):- Payment to be made per metre cost of total length of barbed wire used .With G.I barbed wire
5.2.2:Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up tot floor five level excluding cost of centering, shuttering, finishing and reinforcement :1:1.5:3( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size)
5.22.1:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelMild steel and Medium Tensile steel bars
50.10.2:Steel work for purlin/single section with G I pipes including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete
12.1.1:Providing corrugate G.S. sheet roofing including vertical/ curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete ( up to any pitch in horizontal / vertical or curved surfaces), excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.1.00 mm thick with zinc coating not less than 275 gm/m2
700mm DI K9 pipe -from floating Pump house Control room to WTP
100.98.125:Supply of DI K9 Pipe Conforming to IS 8329/2000, 700mm Dia.
100.98.117:Supply of DI K9 Pipe Conforming to IS 8329/2000, 200mm Dia.
100.98.447:Supply of CI Air Valve, Conforming to IS 14848 - 2000, Double Orifice Type DS2, Size 200mm.
100.98.463:Supply of CI Double Flanged Sluice Valve Conforming to IS 14846 - 2000, Sluice Valve with Cap PN 1.6, Size 300mm.
100.98.450:Supply of CI Air Valve with Flanges, Conforming to IS 14845 - 2000, Kinetic Air Valve Type DS1, Size 80mm.
Working Charges-RWPM
100.1.1:Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20cm in depth, including consolidating each deposited layer by ramming, watering, etc., and disposing of surplus excavated soil as directed, within a lead of 50m, in all kinds of soil.
100.1.5:Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20cm in depth, including consolidating each deposited layer by ramming, watering, etc., and disposing of surplus excavated soil as directed, within a lead of 50 m, in Ordinary Rock.
100.1.13:Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20cm in depth, including consolidating each deposited layer by ramming, watering, etc., and disposing of surplus excavated soil as directed, within a lead of 50m, in Hard Rock where Blasting is Prohibited.
100.2.7:Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20cm in depth, including consolidating each deposited layer by ramming, watering, etc., and disposing of surplus excavated soil as directed, within a lead of 50m, in Medium Rock where Blasting is Prohibited.
100.59.1:Cutting the bituminous / concrete roads with cutting machine for a minimum depth of 200mm along the sides of proposed alignment of the pipe to be laid without causing any damage to other utilities, including the charges for hire and conveyance of tools and plant, cost of consumables and charges for lighting, watching, ribbon fencing, caution boards, traffic diversion, and as per the direction of departmental officers etc. complete, before carrying out the demolition of bituminous / concrete road by mechanical means and carrying out the excavation.
15.43.2:Dismantling manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer -in-Charge:Bituminous road
15.2.1:Demolishing cement concrete manually / by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in-Charge.Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix)
15.3:Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material with in 50 metres lead as per direction of Engineer -in-Charge.
100.8.1:Fencing one side of trenches, 1.50m height with two rows of 10cm plastic caution tape in vertical casuarina pole (girth 15cm to 24cm) fixed at 2m intervals.
100.14.11:Conveying and laying S&S Centrifugally Cast (Spun) / Ductile Iron Pipes conforming to IS: 8329 excluding cost of pipes and specials: 700mm diameter Ductile Iron Class K-9 Pipes.
OD113832/2023-2024:Dismantling existing 200mm DI pipes including taking out the pipes, manually / by mechanical means including stacking of pipes & lead at site within 50 metre lead as per direction of Engineer - in- Charge:Above 150 mm dia upto 300 mm dia
100.14.3:Conveying and laying S&S Centrifugally Cast (Spun) / Ductile Iron Pipes conforming to IS: 8329 excluding cost of pipes and specials: 200mm diameter Ductile Iron Class K-9 Pipes.
18.70.3:Providing push - on-joints to Centrifugally (Spun) Cast Iron Pipes or Ductile Iron Pipes including testing of joints and including the cost of rubber gasket:200 mm dia pipes
OD85917/2022-2023:Labour for cutting DI pipe with saw cutter 700 mm diameter DI pipe
100.35.11:Testing 700mm DI/CI pipeline with potable water to the required test pressure. 700 mm dia Observed Data derived from item no.1030 of PHED DATA
18.70.12:Providing push - on-joints to Centrifugally (Spun) Cast Iron Pipes or Ductile Iron Pipes including testing of joints and including the cost of rubber gasket:700 mm dia pipes
18.68.2:Providing and laying D.I specials of class K - 12 suitable for push - on jointing as per IS : 9523 :Above 600 mm dia
18.68.1:Providing and laying D.I specials of class K - 12 suitable for push - on jointing as per IS : 9523 :Upt 600 mm dia
100.37.15.1:In situ fabrication of M.S. pipes of size 700mm (I.D.) using 8mm thick M.S. plate including cost and conveyance charges of M.S. plate, all fabrication charges, charges of painting the steel work with two or more coat deluxe multi surface paint to give an even shade over an under-coat of primer etc., complete.
100.37.15.2:Fabricating M.S. flanges of diameter 700mm using 16mm thick M.S. plate including cost and conveyance charges of M.S. plate, all fabrication charges, charges of painting the steel work with two or more coat deluxe multi surface paint to give an even shade over an under-coat of primer etc., complete: For pipes fabricated with 8mm thick M.S. plates.
100.37.15.3:Cutting 700mm (I.D.) M.S. pipes for making bends and other specials by gas cutting including cost of gas, all labour and hire charges of tools etc., complete: For pipes fabricated with 8mm thick M.S. plates.
100.37.15.4:Welding 700mm (I.D.) M.S. pipes for making bends and other specials by gas/electric welding machine including cost of gas and welding rods, all labour and hire charges of tools etc., complete: For pipes fabricated with 8mm thick M.S. plates.
100.37.15.5:Grinding cut and weld edges of 700mm (I.D.) M.S. pipes during fabrication work including all labour and hire charges of tools etc., complete: For pipes fabricated with 8mm thick M.S. plates.
100.31.2.7:Conveying and fixing C.I. sluice valves (with cap) by providing bolts, nuts, rubber insertions etc., complete, but excluding the cost of the valve (tail pieces, if required, will be paid separately): 300mm diameter, Class II.
100.32.7:Conveying and fixing C. I. Double Acting Air Valve of approved quality with bolts, nuts, rubber insertions etc., complete, but excluding the cost of air valve (tail pieces, if required, will be paid separately): 200mm Double Acting Air Valve.
100.32.4:Conveying and fixing C. I. Double Acting Air Valve of approved quality with bolts, nuts, rubber insertions etc., complete, but excluding the cost of air valve (tail pieces, if required, will be paid separately): 80mm Double Acting Air Valve.
Construction of Valve chambers and Providing Anchor Block
2.6.1:Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil
4.1.3:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:2:4 (cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size)
5.1.2:Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level:1:1:5:3 (1 cement 1.5 coarse sand :3 graded stone aggregate 20 mm nominal size
5.22.4:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelHot rolled deformed bars
4.3.1:Centering and shuttering including strutting, propping etc. and removal of form work for:Foundations, footings, bases for columns
Bidder Name
MANOHARAN D
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid