Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹10.5 LAccepted-AOC MEDICAL COLLEGE KOTTAYAM PHASE I GENERAL ELECTRICAL WORK ADDITIONAL WORKS OF BASEMENT FLOOR KERALA KL | ₹10.5 L | 1 | Accepted-AOC admited |
| 2 | Not Admitted-Fee/PreQual/Technical/Finance ARACKAL H VARAPPETTY P O KOTHAMANGALAM 686691 | ERNAKULAM | KERALA | 686691 | - | - | Not Admitted-Fee/PreQual/Technical/Finance Others-Not Admited |
| 3 | Not Admitted-Fee/PreQual/Technical/Finance CHANGANACHERRY GENERAL ELECTRICAL WORK | ERNAKULAM | KERALA | 682001 | - | - | Not Admitted-Fee/PreQual/Technical/Finance Others-Not Admited |
| Sl No | Description | Qty | Unit | Mighty L1 |
|---|---|---|---|---|
| 1.00Maintenance | ||||
| 1.00 | OD459508/2024-2025:Supply installing testing and Commissioning of , IP 65 , Gate / Garden light of E 27 type power holder , product code GL110 , dimension 22.5x22x22 cm light fitting suitable for 9 W LED bulb , on existing concrete foundation with foundation bolts etc as required( Dewton or Equivalent make.) | 12 | each | 1,600 ₹19,200 Lowest |
| 1.00 | OD459507/2024-2025:Supply and fix E-22/E-27 Type 9W LED bulb 3000 K in Existing angle / straight brass lined skirt type, Bakelite batten holder etc. as required | 12 | each | 130 ₹1,560 Lowest |
| 1.00 | 90.15.4.3:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) | 19 | each | 6,800 ₹1,29,200 Lowest |
| 1.00 | 90.15.1.1:Supply installation testing and commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70mm top diameter. 130mm bottom diameter thickness 3mm base plate dimensions of 200x200x16mm suitable for windspeed as per IS 875 Part III fixed head frame including round arm luminary carriage suitable to install 4/6 nos luminaries in symmetrical arrangement including connector foundation bolt 4 nos existing RCC foundation and junction box etc, complete 8 Meters | 3 | each | 27,000 ₹81,000 Lowest |
| 1.00 | 90.15.3.1:Supply installation testing commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70mm top diameter, 130mm bottom diameter thickness 3mm base plate dimensions of 200x200x12mm suitable for wind speed as per IS 875 Part III single arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junctions box etc.complete 5 Meters | 15 | each | 18,400 ₹2,76,000 Lowest |
| 1.01 | 90.15.3.2:Supply installation testing commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70mm top diameter, 130mm bottom diameter thickness 3mm base plate dimensions of 200x200x12mm suitable for wind speed as per IS 875 Part III double arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junctions box etc.complete 5 Meters | 2 | each | 19,000 ₹38,000 Lowest |
| 1.01 | 90.15.4.8:Supply Conveyance, installation, testing and commissioning of 120W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) | 12 | each | 9,000 ₹1,08,000 Lowest |
| 1.01 | 90.3.18.3:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.40 mm dia with clamps made from 20 x 3 mm MS flat | 18 | metre | 60 ₹1,080 Lowest |
| 1.01 | 90.6.10.2:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required25 mm | 10 | metre | 60 ₹600 Lowest |
Tender Value
Refer Docs
EMD Value
₹31,004
Closing Date
19 Apr 2025, 5:00 pmClosed
SECRETARY
VENGOOR GRAMA PANCHAYAT
SO440/25-Kodampilly Tourism Project Destination Challange Electrification and Installation of Mini Mast Lights-General Electrical Work
2025_DP_759419_1
SC1-102/2025/440
Open Tender
Electrical Works
Item Rate
180 days
KOMBANAD
Please refer Tender documents.
6 documents required · 6 mandatory
₹2,760
₹31,004
13 Aug 2025
9 Apr 2025
21 Apr 2025
9 Apr 2025
19 Apr 2025
9 Apr 2025
Amount
Maintenance
OD459508/2024-2025:Supply installing testing and Commissioning of , IP 65 , Gate / Garden light of E 27 type power holder , product code GL110 , dimension 22.5x22x22 cm light fitting suitable for 9 W LED bulb , on existing concrete foundation with foundation bolts etc as required( Dewton or Equivalent make.)
OD459507/2024-2025:Supply and fix E-22/E-27 Type 9W LED bulb 3000 K in Existing angle / straight brass lined skirt type, Bakelite batten holder etc. as required
90.15.4.3:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.1.1:Supply installation testing and commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70mm top diameter. 130mm bottom diameter thickness 3mm base plate dimensions of 200x200x16mm suitable for windspeed as per IS 875 Part III fixed head frame including round arm luminary carriage suitable to install 4/6 nos luminaries in symmetrical arrangement including connector foundation bolt 4 nos existing RCC foundation and junction box etc, complete 8 Meters
90.15.3.1:Supply installation testing commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70mm top diameter, 130mm bottom diameter thickness 3mm base plate dimensions of 200x200x12mm suitable for wind speed as per IS 875 Part III single arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junctions box etc.complete 5 Meters
90.15.3.2:Supply installation testing commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70mm top diameter, 130mm bottom diameter thickness 3mm base plate dimensions of 200x200x12mm suitable for wind speed as per IS 875 Part III double arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junctions box etc.complete 5 Meters
90.15.4.8:Supply Conveyance, installation, testing and commissioning of 120W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.3.18.3:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.40 mm dia with clamps made from 20 x 3 mm MS flat
90.6.10.2:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required25 mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.30:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm
2.3.1:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator6 way, Double door
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm
90.6.5.12:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 2.50 sq mm
OD459503/2024-2025:Supply and fixing 25A AC1, MNX 9, 2 Pole power contactor (L&T) conforming to IS/IEC 60947-4-1 & IEC60947-4-1 in the existing enclosure and giving connection as required?
OD459500/2024-2025:Supply and fixing Time switch 240V AC DIN/BASE mounting(L&T J648B1-Analog version) in the existing enclosure and giving connection as required.
90.12.2.1:Supply and laying of one number additional PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground in the same trench in one tier horizontal formation including widening the trench by 20 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil)2 core 4 sq mm
90.12.2.2:Supply and laying of one number additional PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground in the same trench in one tier horizontal formation including widening the trench by 20 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil)2 core 6 sq mm
90.12.7.1:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 4 sq mm with factory made clamp
90.12.7.2:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 6 sq mm with factory made clamp
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
OD459502/2024-2025:Steel reinforcement for RCC Work including straightening, cutting, bending, placing in position and binding all complete.
OD459505/2024-2025:Supply and fixing 20mm corrugated flexible pvc conduit
2.10.2:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole and netural
OD459501/2024-2025:Supply and fixing Sintex junction box GSJB 1616 top hinged door of size 140x140x 100 with provision for fixing SP/DP MCB for terminating cable.
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class)
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.1:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD459506/2024-2025:12x3mm brass bolt with hexagonal/square head, nut and washer
OD459504/2024-2025:Supply and providing 25x3mm brass nut and bolt etc. as required.
Bidder Name
Mighty
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1234280.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].