Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.9 LAccepted-AOC BALTIKURI INDUSTRIAL ESTATE PLOT NO A 01 DASNAGAR HOWRAH 711113 | HOWRAH | HOWRAH | WEST BENGAL | 711113 | L1 | Accepted-AOC L1 | |
| 2 | L2₹5.7 L+₹74,398.51 (15.1%)Rejected-Finance | L2 | Rejected-Finance 567278.51 | |
| 3 | L3₹5.9 L+₹97,824 (19.8%)Rejected-Finance 10B DR LAHIT BANERJEE SARANI GROUND FLOOR KOLKATA 700 073 | KOLKATA | KOLKATA | WEST BENGAL | 700073 | L3 | Rejected-Finance 590704.00 | |
| 4 | L4₹7.1 L+₹2.1 L (43.2%)Rejected-Finance 86 TOLLYGUNGE CIRCULAR ROAD KOLKATA WEST BENGAL 700053 | KOLKATA | KOLKATA | WEST BENGAL | 700053 | L4 | Rejected-Finance 705651.00 |
Tender Value
Refer Docs
EMD Value
₹14,509
Closing Date
1 Dec 2020, 2:00 pmClosed
Executive Engineer PWD BDN ELEC DIVN
Room no 1081st fl purta bhawan salt lake kolkata
Supply and Installation of Cassette type Split Air conditioner and allied electrical work at work station SPO PBBSM in the 2nd floor Bikash Bhavan Salt Lake Kol 91
2020_WBPWD_305318_1
WBPWD/EE/BED/21/e-IT of 2020_21
Open Tender
ELECTRICAL WORKS M/R
Item Rate
14 days
PBBSM
Please refer Tender documents.
5 documents required · 5 mandatory
₹14,509
Yes
18 Jan 2021
13 Nov 2020
3 Dec 2020
25 Nov 2020
1 Dec 2020
25 Nov 2020
Amount
Supplying, Installation, Testing and Commissioning of Pakage Type, Inverter Air Conditioning System comprising of Cassette Indoor Unit with wireless Remote system, Power supply- 230V/50Hz/1ph, Cooling Capacity (Min ~ Max): 7.1 kw (min: 3.2 kw, max: 8.0 kw), ISEER Star Rating: 5 Star. The Indoor unit should be as below mentioned specification: Indoor unit type: Cassette, 4 way air distribution. Air flow rate : 812 cfm, Sound level : 37 dB(A) (max). and having features of individual air flow control and drain pump operation system. The Outdoor unit should be as below mentioned specification: Compressor type: Hermetically sealed swing type Refrigerent gas type: R-32, Certified operation range 21 ~ 48 ◦CDB (Make: Daikin /Hitachi / Voltas)
Supplying & Installation of interconnecting following size of refrigerant copper pipe work with fitting duly insulated with 13mm / 19mm thk. Class 'O' rated Nitrile rubber Insulation between each set of indoor & outdoor units. Outdoor pipe shall be covered with UV resistant Fiber Glass Cloth between each set of indoor & outdoor units. Make of Cu Pipe - Rajco / Maxflow / Mandev Make of Insulation - Supreme / Armaflex / K-flex / A-flex. (i) 9.53 mm dia with 13mm thick Nitrile Rubber
(ii) 12.7 mm dia with 13mm thick Nitrile Rubber
Supplying and fixing of rigid PVC pipe complete with fittings, supports as per specifications and duly insulated with 9 mm thick closed cell nitrile rubber insulation. (i) 32 mm
Providing and fixing control cum transmission wiring with 3 core x 4 Sq.mm copper cable through rigid PVC pipe. Make - Polycab / Havells / KEI.
Supply & fixing of pre-fabricated/ suitable iron structure platform suitable for cassette outdoor unit considering safety with heavy duty MS angle for as per site requirement for 05 nos cassette AC machines. (As per direction of EIC)
L.W.C. must be quoted manually @1% on the total quoted value else the total quoted rate shall be treated incl. LWC as per rule. N.B. Rate should be quoted inclusive of GST.
Auto-Tech Projects Pvt.Ltd.
CARRION AIR COOLING
Lyric International
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .