Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.7 LAccepted-AOC DOOR NO 68 2963 E3 MANDAKKARA ROAD AYYAPPANKAVU ERNAKULAM KERALA 682 018 | ERNAKULAM | ERNAKULAM | KERALA | 682018 | ₹6.7 L Quoted ₹6.8 L | L1 | Accepted-AOC AOC |
| 2 | L2₹7.5 L+₹73,350 (10.8%)Rejected-Finance 42 608A PULLOMPARAMBIL HOUSE MANDAKARA ROAD KOCHI 682 018 | ERNAKULAM | KERALA | 682018 | ₹7.5 L+₹73,350 (10.8%) | L2 | Rejected-Finance NOT BEING L1 |
Tender Value
₹9.5 L
EMD Value
₹19,000
Closing Date
24 Jun 2024, 6:00 pmClosed
AGE I R AND D KOCHI,
AGE I R AND D KOCHI, THRIKKAKARA,KAKKANAD, KOCHI 682021
REPAIR MAINTENANCE TO HT LT FEEDER PILLAR BOX, DISTRIBUTION PANEL BOARDS AND CONNECTED WORKS AT TECHNICAL AND RESIDENTIAL AREA AT NPOL KOCHI
2024_MES_655485_1
8285E8AGERDK
Open Tender
Civil Works
Item Rate
270 days
KAKKANAD
As per tender documents
6 documents required · 6 mandatory
₹500
Yes
AGE I R AND D KOCHI
₹19,000
Yes
25 Apr 2025
22 May 2024
26 Jun 2024
22 May 2024
24 Jun 2024
5 Jun 2024
Amount
Supply and fixing in replacement MCCB of following ratings in existing indoor/ Outdoor HT/LT panel board including connecting with proper size link set at incoming and outgoing cable connections and making necessary modification in existing panel as required complete all as specified and directed by engineer in charge . Note: cost include taking down the existing MCCB from panel board disconnecting incoming / outgoing cable and fix the new MCCB in position at panel board including necessary cable connections of any size/ rating complete all as specified and as directed.
MCCB 63 to 100 Amp 4 pole 16 KA; Make: Havells/Legrand/L& T
MCCB 125 Amp 4 pole 16 KA; Make:Havells/Legrand/L& T
MCCB 125 Amp 3 pole 16 KA; Make:Havells/Legrand/L& T
MCCB 200 Amp 4 pole 25 KA Make: Havells/Legrand/L& T
MCCB 200 Amp 3 pole 25 KA Make: Havells/Legrand/L& T
MCCB 250 Amp 4 pole 25 KA Make: Havells/Legrand/L& T
MCCB 400 Amp 4 pole 35/36 KA Make:Havells/Legrand/L& T
M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6.0mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connected to galvanized iron strip 32x6 .00 mm as earthing by means of bolts nuts and washers of galvanized iron including excavation and earth work and disposal of surplus soil including 40 mm GI tubing light grade and necessary fittings for protection of GI strip including laying of charcoal , dust and common salt , PCC 1:2: 4 Type B 1 using 20 mm graded aggregate with earth pit with 40 X 40 X 6.0 mm MS angle iron frame RCC cover 40mm thick (1:2: 4) Type C1 using 20 mm graded stone aggregate reinforced with 8 mm dia round bar @ 75 mm C/C both way with plastering 15 mm thick CM ( 1: 6) internally and up to 150 mm below ground level externally . PGI funnel with wire mesh, 20 mm dia medium grade GI pipe for watering complete all as shown on electrical plate No : 03 of SSR part - I 2009 and connected to earth test point including testing completed all specified and directed.
Supplying and fixing in replacement earth continuity conductor or main earthing lead of Galvanised iron strip of size 32 X 6 mm, fixed on Floor/ Wall with supporting insulators / laid in trench from existing earth test point complete all as specified and as directed by the Engineer - in - Charge.
M & L for cleaning the LT feeder pillar box indoor/ Outdoor type of size up to 3m X2m X0.5m of different rating bus bar, after dismantling the Incoming and outgoing connections from MCCB/ Bus bar and replacing the old unserviceable nut, bolts, supporting insulators etc. and check the serviceability of MCB/MCCB, earth continuity conductor, tightening the earth conductor and incoming and outgoing cables and removing existing old insulation of bus bar and MCCB/ MCB terminals and providing new insulation tape of standard quality applied to Bus bar and MCCB terminals and cleaning the feeder pillar box all as specified and directed by Engr in Charge. Note: (i) Contactor has to take the Shutdown of Transformer 11/0.433 KV from substation/ MRS before starting the execution of work and switch ON/OFF on the Transformer after completion of work all as as directed. (ii) Cost of T & P also included in quoted rate. (iii)The contractor should deploy the skilled electrician for handling the HT & LT feeder pillar smoothly without damaging/disturbing the existing HT & LT installation.
M & L for LT danger notice board readymade / printed on water proof sheet pasted on LT feeder pillar box with vitreous enameled white back ground, with letters figures and conventional skull and bones in signal red colour of Approved size up to 20 X 15 Cm all as directed by Engineer - in - Charge.
M & L for in replacement of copper earth strip of size 20 X 3 mm laid in trench/ wall/ floor with necessary supporting insulators in regular interval as directed from earth test point to terminal point with double nut bolt joint at starting terminal al as directed by Engineer - in - Charge.
M&L for writing feeder pillar No on feeder pillar with super enameled synthetic enamel paint of size 75x75 mm white colour on black background all as specified and directed by Engr-in-Charge.
Supply , Installation and Testing commissioning of 6 KVA / 4.8 KW 120 VDC online UPS 30 Minutes Back up inversion Technology, pure sine wave, LCD display, , Crest factor 3:1 with Protection of Output overvoltage/ Under voltage and over load with inbuilt Galvanic Isolation Transformer with the following components :-
*DSP/MCU Intelligent control *Inbuilt Isolation Transformer *High Efficiency *Generator Compatible *Pure sine wave *Output Voltage regulation +/-1% *Parallel Operation (Optional)
Certification :ISO9001:2015,rect ISO 45001:2018 Certified Company and CE ,Rosh Approved Products including Amaron/Exide make 75H fast recharging sealed maintenance free (SMF) Heavy duty alloy construction Battery of 16 Nos for 30 Min backup with battery interconnecting cable, Including disconnecting of existing UPS and reconnect with new UPS at same place with New connecting cables etc all as specified and directed By Engr-in-charge.
Supply and fix in replacement MCB of following rating , 50 Hz AC Supply 10 KA with necessary aluminium lugs up to 16 Sq mm complete ,all as specified and directed by engineer in charge .Make: L&T /Havell's/Legrand/Indo Asian/C & S
MCB TPN 4 Pole 32-40 Amp.-01
MCB TPN 4 Pole 63 Amp.-01
MCB TPN 4 pole 100 Amp.-01
M& L for preparation of old painted steel surface and applying two coats of synthetic enamel paint & priming with Zinc chrome and a final coat of black japan paint by spray paint (Using spraying Machine) at both sides ie, top and bottom of cable duct cover etc all as specified and as directed.
M&L for cable duct cover of steel plate, 6 mm thickness cut in required size including painting two coats of synthetic enamel paint & a coat priming with zinc chrome and a final coat of black japan paint by spray paint ( Using Machine) at both sides ie, top and bottom of cable duct cover as directed.
Supply, install, test and commissioning in replacement of Indoor type LT Feeder pillar box made out of 2.0 mm thick CRCA sheet outdoor type, CPRI Approved, totally enclosed weather dust and vermin proof as per IS with front and rear 300 Amp capacity for RYB and half for neutral and insulated with insulators, including connecting incoming and outgoing cables necessary made out of 50 X 50 X 6 mm angle iron grouted at Floor above 30 cm from ground level Comprising the following including taking down old unserviceable feeder pillar box, all as specified and as directed by the engineer - in- charge. Note: Cost includes necessary internal wiring for meters , CTs, indication lamps, etc and Rigid bus bar connections from bus bar to MCCB terminals connection Bus to MCCB/MCB connections. Note: Connection from HT Switch gears (Ringman system) to new LT panel board to be done and necessary fitting fixtures to be borne by the contractor without extra cost of the department.
Incoming (i) Provision of MCCB 250 Amp 4 pole manual change over -1 Nos . (ii) Digital multifunction meter, class 1 - 1 no (iii) LED type Indicating lamps -03 Nos [Make : C& S/ Neptune / L&T / Vaisnavo]
Outgoing (i) Provision of MCCB 100 Amp 4 pole 25 KA - 01 Nos (ii) Provision of MCCB 63 Amp 4 pole 25 KA - 03 Nos (iiI) Provision of MCB 63 Amp 4 pole 16 KA - 3Nos
WELTRONENGINEERINGSERVICES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .