Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.1 LAccepted-AOC HOUSE NO 01 B JANANA DODI OPP AKSHAY HOTEL RAI KA BAGH JODHPUR RAJASTHAN 342010 | 342010 | L1 | Accepted-AOC BEING LOWEST | |
| 2 | L2₹30.4 L+₹28,020 (0.93%)Rejected-AOC 61 ABHAY GARH SCHEME AIR FORCE JODHPUR 342001 RAJ | JODHPUR | JODHPUR | RAJASTHAN | 342001 | L2 | Rejected-AOC NOT BEING LOWEST | |
| 3 | L3₹30.6 L+₹44,885 (1.49%)Rejected-AOC | L3 | Rejected-AOC NOT BEING LOWEST | |
| 4 | L4₹32.4 L+₹2.3 L (7.78%)Rejected-AOC H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | L4 | Rejected-AOC NOT BEING LOWEST | |
| 5 | L5₹33.4 L+₹3.3 L (11.0%)Rejected-AOC | L5 | Rejected-AOC NOT BEING LOWEST |
Tender Value
₹34.3 L
EMD Value
₹68,600
Closing Date
23 Feb 2023, 6:00 pmClosed
GE (AF) Jodhpur
GE (AF) Jodhpur
REPAIR / MAINTENANCE TO LT CABLE AND LT PANEL AT AF STN JODHPUR
2023_MES_577603_1
8544/E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
GE (AF) Jodhpur
As per NIT
6 documents required · 6 mandatory
₹500
GE (AF) Jodhpur
₹68,600
Yes
28 Feb 2023
27 Jan 2023
25 Feb 2023
27 Jan 2023
23 Feb 2023
11 Feb 2023
Amount
Disconnecting transformer from exishting location by removal of HT and LT cable connection and shifting of transformer from one location to another inside the permises of air force station Jodhpur, of capacity upto 500 KVA including reconnecting at new location including all accessories and T&P complete all as directed by Engr-in-Charge.
Disconnecting the existing transformer by removal of HT and LT cable connection of capacity upto 400 KVA from premises of air force station jodhpur including removal of transformer from sub station bldg to CPH store, transformers shall be transported by suitable vehicle carefully without damage and deposited the same to MES store complete all as directed by Engr-in-Charge.
S&F in replacment of out door type LT Feeder Pillar box (Kiosk) of size not less than (L) 60 cm x (W) 45 cm x (H) 45cm made out of 3.15 mm thick CRCA sheet (CPRI approved) with openable Front door including locking arrangement, with and inluding Copper Busbar 400 amps rating and one MCCB 250 Amps, 04 pole, 25 KA thermal magnetic adjutable type for incoming and fixed on angle iron 40x40x6mm frame of suitable size and embedded in PCC plinth 45x45x60mm made of PCC 1:4:8 type D-1 using 40 mm graded stone aggregate complete all as specified and directed by the Engr-in-Charge.
S&F in replacment of out door type LT Feeder Pillar box (Kiosk) of size not less than (L) 60 cm x (W) 45 cm x (H) 45cm made out of 3.15 mm thick CRCA sheet (CPRI approved) with openable Front door including locking arrangement, with and inluding Copper Busbar 250 amps rating and one MCCB 125 Amps, 04 pole, 16 KA thermal magnetic adjutable type for incoming and fixed on angle iron 40x40x6mm frame of suitable size and embedded in PCC plinth 45x45x60mm made of PCC 1:4:8 type D-1 using 40 mm graded stone aggregate complete all as specified and directed by the Engr-in-Charge.
Supply, Laying, Testing and Commissioning in replacement of LT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables cross sectional area 50 Sqmm 3.5 core (heavy duty) 1100 Volts, grade with stranded Aluminium conductor complete all as specified and directed by Engineer-in-Charge.
Supply, Laying, Testing and Commissioning in replacement of LT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables cross sectional area 150 Sqmm 3.5 core (heavy duty) 1100 Volts, grade with stranded Aluminium conductor complete all as specified and directed by Engineer-in-Charge.
Supply, Laying, Testing and Commissioning in replacement of LT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables cross sectional area 95 Sqmm 3.5 core (heavy duty) 1100 Volts, grade with stranded Aluminium conductor complete all as specified and directed by Engineer-in-Charge.
Supply, Laying, Testing and Commissioning in replacement of LT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables cross sectional area 70 Sqmm 3.5 core (heavy duty) 1100 Volts, grade with stranded Aluminium conductor complete all as specified and directed by Engineer-in-Charge.
Supply, Laying, Testing and Commissioning in replacement of LT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables cross sectional area 185 Sqmm 3.5 core (heavy duty) 1100 Volts, grade with stranded Aluminium conductor complete all as specified and directed by Engineer-in-Charge.
Supply, Laying, Testing and Commissioning in replacement of LT cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables cross sectional area 300 Sqmm 3.5 core (heavy duty) 1100 Volts, grade with stranded Aluminium conductor complete all as specified and directed by Engineer-in-Charge.
Supply,installation, testing and commisioning of LT panel board floor mounted cubical type, outdoor double door type dust proof aesthetically designed. manufactured by CPRI approved and ISO certified manufactuter, with nine tank process, fabricated of 3.15 mm thick outer CRCA sheet and 2mm thick inner CRCA sheet,depth of panel not less than 45 cm, with front and rear opening confirming to IS-8623and including of bus bar chamber continuous GI strip earth bus bar din rail channels cable alley . danger notice board also including MS angle iron bas frame of size 40 x40 x6mm, 0.30 m above ground level and 0.30m grouted in ground/floor all including necessary excavation , PCC foundation in cement concrete 1:4;8 type D2 using 40mm graded stone aggregate complete with locking arrangement, powder coated rust proof paint connecting incoming and outgoing cable connections with suitable lugs nut bolts washers and cable glands prewired complete with suitable size PVC insulated fire retardant copper conductor cable, including for lifting 4 hook shall be provided at top of panel complete all as directed and shall consists of the following items:- INCOMING :- (a) Bus bars of aluminium strips of 600 Amp current rating capacity, mounted on epoxy/FRP bus bar insulator - 01 set (b) MCCB 400 Amps TPN 36KA, 415 V thermal megnatic adustable type - 01 (c) Multifunction meter with accuracy class 0.5 RS 485 enable to measure voltage, current , power with suitable size CT (d) Indicating lamp set of 03 R,Y,B OUTGOING :- (a) MCCB 160 A Amps TPN 16 KA 415 Volts thermal megnatic adustable type -03 (b) MCCB 40 A Amps TPN 16 KA 415 Volts thermal megnatic adustable type -01 Note:- All outgoing feeder shall be connected with suitable size of bus bar.
Material & labour for earthing complete with galvanised steel earth electrode 60cmx60cmx6mm buried directly in ground vertically to depth not less than 2.25m below normal ground level with top edge of the earth plate at a depth not less than 1.5m below ground level connected to and including GI earth strip 32mm x 6 mm, by means of nuts, bolts, check nuts and washer etc, made of GI and connected to test point and earth dolly all as shown in electrical plate No. 3 SSR Part-I 2009 and specified or indicated including excavation and earthwork in any type of soil PCC (1:3:6) Type C1 in chamber, precast RCC 50 mm thick in cement concrete (1:2:4) type B1, reinforced with welded steel wire fabric or XPM (Weight not less than 4.00 Kg/Square metre) with cast iron frame, funnel with wire mesh, 20mm bore medium grade GI watering pipe, lugs, 40 mm bore medium grade GI protection pipe, test point etc. complete all as specified and directed. NOTE :- The rate of above Item includes the cost of earth lead and GI protection pipe up to 7.5 Metres. GI strip beyond 7.5 Metre shall be measured and paid for separately.
Material & labour for boring of horizontal holes under road pavement, hard standing manually with suitable tools, with and including 100 mm bore HDPE protection pipe complete all as specified and directed by Engineer-in-Charge.
Excavation in trenches in soft/loose soil not exceeding 1.5 m deep and not exceeding 1.5 mtr wide and getting out for foundations/laying of cable etc all as specified and directed including taking out existing cable protection stone patti cover etc all as specified and directed by Engineer-in-Charge.
Returning, filling in, including spreading leveling, watering and well ramming the excavated soil in layers not exceeding 25 cm thick complete all as specified and directed by Engineer-in-Charge.
Removal of surplus excavated soil to a distance not exceeding 50 Mtr distance and depositing as directed at a level not exceeding 1.5 mtr above starting point complete all as specified and directed by Engineer-in-Charge.
Material & labour for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed by Engineer-in-Charge.
Material & labour for stone slab 40 mm to 50 mm thick rough dressed Jodhpur stone patties/ slab cover in trenches for protection of cable 25 cm to 30 cm wide and not less than 50 cm in length laid dry abutting each other with gap between adjacent slab not exceeding 10 mm over sand cushioning complete all as specified and directed by the Engineer-in-Charge.
SANJOLI CONSTRUCTION COMPANY
RISING ELECTRICALS
Shri Electrical Enterprises
M/S SHREE AAINATH ENTERPRISES
M/s R K Enterprises
L C ASSOCIATES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .