Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 CrAdmitted-Finance 25 A RR SAMY LANE KATTOOR COIMBATORE 641009 | COIMBATORE | COIMBATORE | TAMIL NADU | 641009 | ₹1.2 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.3 Cr+₹5.5 L (4.47%)Admitted-Finance 37 1634 IMPERIAL HOUSE KALOOR KATHRIKADAVU KATHRIKADAVU ERNAKULAM KERALA 682017 | ERNAKULAM | KERALA | 682017 | ₹1.3 Cr+₹5.5 L (4.47%) | L2 | Admitted-Finance |
| 3 | L3₹1.3 Cr+₹9.1 L (7.43%)Admitted-Finance 12 BHARTI AARTIST COLONY VIKAS MARG NEW DELHI 110092 | EAST | DELHI | 110092 | ₹1.3 Cr+₹9.1 L (7.43%) | L3 | Admitted-Finance |
| 4 | L4₹1.4 Cr+₹12.9 L (10.5%)Admitted-Finance 66 102 ARUN JYOTHI MULLASSERY CANAL ROAD ERNAKULAM KOCHI 682 011 | KOCHI | ERNAKULAM | KERALA | 682011 | ₹1.4 Cr+₹12.9 L (10.5%) | L4 | Admitted-Finance |
| 5 | L5₹1.5 Cr+₹24.2 L (19.6%)Admitted-Finance | ₹1.5 Cr+₹24.2 L (19.6%) | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | IMPERIAL ENGINEERING COMPANY L2 | rvelectricals L1 | devan enterprises L6 | Lucky Enterprises L7 | Vijaypower Generators Limited L3 | B5BUILDING SOLUTIONS L5 | NATIONAL ELECTRIC COMPANY L4 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing & commissioning of indoor type floor mounted metal clad,11 KV HT VCB 25 KA/3 Second panel with 10 Nos VCBs, totally enclosed and fully interlocked compatable to SCADA system in future, horizontal drawout, horizontal isolation type breaker as per IS 13118 as amended upto the date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, electrically and manually charged and auto closing breaker suitable for use on 11 KV 3 phase 50 Hz AC supply with short circuit fault level of 500 MVA, complete with self contained, fully inter locked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 1250 Amps capacity, breaker featured with mechanically ON/OFF indicator with hand trip device, spring release coil, shut trip coil and auxiliary switch of minimum 6 NO+ 6 NC and equipped with following switch gears and accessories i/c connections suitable for 3 x240 Sqmm XLPE 11 KV cable (cable entry from bottom) end termination with heat shrinkable jointing material etc as required complete all as specified and directed. | 1 | Each Set | 80,91,615 ₹80,91,615 | 73,00,000 ₹73,00,000 Lowest | 92,25,000 ₹92,25,000 | 1,03,40,000 ₹1,03,40,000 | 80,94,000 ₹80,94,000 | 89,00,000 ₹89,00,000 | 86,00,000 ₹86,00,000 |
| 1.01(a) Incoming- 2 Nos 1250 Amps capacity VCB and bus bar coupler-01 No 1250 Amps capacity VCB with electrical and mechanical interlocking system including castell key system having 3 locks and 2 keys. (b) 02 Nos 11 KV/110 Volts PT draw out dry type class 0.5 accuracy and 100 VA burden with Voltmeter 02 set (each one for each incoming feeders), 0-15 KV, digital type, selector switch for voltmeter and protection fuses/MCB for HT metering upto 15 KV on incomer. (c) 02 Nos (0-300 A) ammeter digital type, selector switches for ammeters. (d) 02 Nos Microprocessor based numerical relay with IDMTL + inst with O/L, E/F and S/C protection with multifunction digital energy communication port mode bus Rs 485 (e) 02 Nos Set of dual core dual ratio 3 CTs 300-150/5 +5A of 15 VA burden and accuracy class -0.5 for metering and class 5P10 for protection. (f) Outgoing-07 Nos HT VCB's of capacity 11 KV, 800 AMPS, 25KA / 03 sec. (g) 07 Nos (0-100 A) ammeters, digital type & selector switches for ammeters accuracy class 0.5. (h) 07 Microprocessor based numerical relays IDMTL + inst with O/L, E/F & S/C protection with multifunctional digital energy communication port mode bus Rs 485. (j) 07 Nos Set of dual core dual ratio 3 CTs 100-50/5+ 5A I/C for out going VCB's and 15 VA burden and accuracy class 0.5 for metering and class 5P10 for protection (k) Battery bank with 24 Volts (2 x 12V), 250 AH maintenance free batteries and with charger unit with capacitor bank for emergency delivering trip system complete with suitable capacity of Ammeter & Voltmeter incoming connections with sutable copper conductors 10.0 Sq mm FRLS insulted etc as required. (l) Master Tripping relay (Electrical & Mechanical) 09 sets complete system arranged in each HT VCB's panel. | ||||||||||
| 1.02(m) Emergency tripping push button (RED colour) system completely arranged in each one for each HT VCBs panel. (n) Multifunctional digital energy meter with demand controller communication port RS 485 warning alaram, tripping system completely arranged in each HT incoming feeder VCB's panel (02 sets) each one for each incoming feeders. (o) necessary control wiring colour coded, 2.5 sq mm for CT circuit & 1.5 sq mm for other circuit in each VCB's. (p) Degree of protection - IP4X (For Enclosure) in each VCBs (q) Power Coated, painting shade - RAL 7032 in each VCBs. (r) Shunt Trip/ Close coils -24 V DC in each VCBs. (s) Copper Earth Bus in each VCBs (t) Phase indication Lamps - Red/Yellow/Blue for incoming feeders in each VCBs. (u) Breaker ON - Red in each VCBs (v) Breaker OFF- Green in each VCBs (w) Auto Trip indicator - Amber in each VCBs (x) Trip Circuit Healthy White in each VCBs. (y) Spring Charged - Blue in each VCBs. (z) Push button for trip circuit Healthy check in eacg VCBs (aa) Trip neutral close switch, Non-lockable in each VCBs. (ab) Panel space heater with thermotat & switch in each VCBs (ac) Panel illumination lamp with switch in each VCBs (ad) 3 Pin plug with switch in each VCBs. (ae) Electrical interlock between incomer panels & bus coupler (3 Locks + 2 Keys for incoming bus coupler) (af) 8 window Annunciator in each VCBs in each VCBs NOTE:- The above HT VCB's and HT Panels and all connected systems of OEM make and factory fabricated, assembled and Tested at factory. | ||||||||||
| 2.00 | Supply, installation, testing and commissioning of indoor type floor mounted metal clad, 11 KV VCB 25 KA/ 3sec panel with 05 Nos VCBs, totally enclosed and fully interlocked, horizontal drawout, horizontal isolation type breaker as per IS 13118 as amended upto the date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, Electrically and Manually charged and auto closing breaker suitable for use on 11 KV 3 phase 50 Hz AC supply with short circuit fault level of 500 MVA, complete with self contained, fully inter locked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 1250 Amps capacity, breaker featured with mechanically ON/OFF indicator with hand trip device, spring release coil, shut trip coil and auxiliary switch of minimum 6 NO+ 6 NC and equipped with following switch gears and accessories i/c connections suitable for 3 x240 Sqmm XLPE 11 KV cable (cable entry from bottom) end termination with heat shrinkable jointing material etc as required complete all as specified and directed. | 1 | Each Set | 39,57,275 ₹39,57,275 | 37,95,000 ₹37,95,000 Lowest | 47,25,000 ₹47,25,000 | 54,20,000 ₹54,20,000 | 39,66,000 ₹39,66,000 | 45,70,000 ₹45,70,000 | 41,33,000 ₹41,33,000 |
| 2.01(a) Incoming - 01 No HT 11 KV VCB of 1250 Amps 25 KA /3 sec. (b) 01 Nos 11 KV/100 Volts PT draw out dry type class 0.5 accuracy and 100 VA burder with Voltmeter-01 set (each one for each) incoming feeders (0-15KV), digital type, selector switch for voltmeter and protection fuses/MCB for HT metering upto 15 KV on incomer. (c) 01 No (0-300 A) ammeter digital type, selector switches for ammeters. (for incoming) (d) 01 No Microprocessor based numerical relay IDMTL + inst with O/L,E/F and S/C protection with multifuntional digital energy communication port mode bus Rs 485. (e) 01 No Set of dual core dual ratio 3 CTs 300-150/5+ 5A of 15 VA burden and accuracy class -0.5 for metering and class 5P10 for protection. (f) Class -0.5 for metering and class 5P10 for protection. (g) Outgoing-04 Nos HT VCB's of capacity 800 AMPS, 25 KA / 03 sec. (h) 04 Nos (0-100 A) ammeters, digital type & selector switches for ammeters accuracy class 0.5. (j) Nos 04 Microprocessor based numerical relays IDMTL + inst with O/L, E/F & S/C protections with multifunctional digital energy communication port mode bus Rs 485. (k) Nos 04 Set of dual core dual ratio 3 CTs 100-50/5+ 5A for out going VCB's, 15 VA burden and accuracy class 0.5 for metering and class 5P10 for protection (l) Battery bank with 24 Volts (2 x 12V , 250 AH maintenance free batteries) and with charger unit with capacitor bank for emergency delivering trip system complete with suitable copper conductors 10.0 Sq mm FRLS insulated etc as required. (m) Master Tripping relay (Electrical & Mechanical) 05 sets Complete system arranged in each HT VCBs panel. (n) Emergency tripping push button (RED colour) system completely arranged in each one for each HT VCBs panel | ||||||||||
| 2.02(o) Multifunctional digital energy meter with demand controller communication port RS 485 warning alaram, tripping system completely arranged in HT incoming feeder VCB's panel - 01 set. (p) Necessary control wiring colour coded, 2.5 sq mm for CT circuit & 1.5 sq mm for other circuit in each VCBS (q) Degree of protection - IP4X (For Enclosure) in each VCBs (r) Powder Coated, Painting shade - RAL 7032 in each VCBs (s) Shunt Trip/Close coils - 24 V DC in each VCBS (t) Copper Earth Bus in each VCBS (u) Phase indication Lamps - Red/Yellow/Blue for incoming feeders in each VCBs (v) Breaker ON - Red in each VCBs (w) Breaker OFF - Green in each VCBS (x) Auto Trip indicator - Amber in each VCBs (y) Trip Circuit Healthy White in each VCBs (z) Spring Charged - Blue in each VCBs (aa) Push button for trip circuit Healthy check in each VCBS (ab) Trip Neutral close switch, Non-lockable in each VCBS (ac) Panel space heater with thermostat & switch in each VCBS (ad) Panel illumination lamp with switch in each VCBS (ae) 3 Pin plug with switch in each VCBS (af) 8 window Annunciator in each VCBs in each VCBs NOTE:- 'The above HT VCB's and HT Panels and all connected systems of OEM make and factory fabricated, assembled and Tested at factory" | ||||||||||
| 3.00 | Supply and laying cable XLPE insulated screened PVC bedded, galvanised steel strip of wire armoured, electric power cables (Heavy duty) 11000 Volts (E) grade with stranded aluminimum conductor of size 240 sqmm, 3.0 core UG cable complete all as specified and directed by Engr-in-Charge | 100 | RM | 2,530 ₹2,53,000 | 2,900 ₹2,90,000 | 2,700 ₹2,70,000 | 4,200 ₹4,20,000 | 3,027 ₹3,02,700 | 3,200 ₹3,20,000 | 2,450 ₹2,45,000 Lowest |
| 4.00 | Supply and laying cable XLPE insulated screened PVC bedded, galvanised steel strip of wire armoured, electric power cables (Heavy duty) 11000 Volts (E) grade with stranded aluminimum conductor of size 185 sqmm, 3.0 core UG cable complete all as specified and directed by Engr-in-Charge | 120 | RM | 2,072 ₹2,48,640 | 2,300 ₹2,76,000 | 2,180 ₹2,61,600 | 2,150 ₹2,58,000 | 2,412 ₹2,89,440 | 2,600 ₹3,12,000 | 2,060 ₹2,47,200 Lowest |
| 5.00 | Excavation in trenches n exc 1.5m wide and n exc 1.5m deep for laying /removing of cable/ erection of poles in soft loose soil complete all as specified and directed by Engr- in- charge. | 100 | Cum | 250 ₹25,000 Lowest | 360 ₹36,000 | 450 ₹45,000 | 380 ₹38,000 | 450 ₹45,000 | 300 ₹30,000 | 500 ₹50,000 |
| 6.00 | M&L for sand cushioning riddle earth in trenches/ducts for protection of UG Cables (below, above and around the UG cable laid) of 23 CM spread thickness (8 CM in depth before laying the cable and 15 CM in depth after laying the cable) and above sand shall be obtained through digging at site 500 mtrs distance and transporting to site for punned use to sand cushioning upto 18 CM thickness complete all as specified and as directed.
Note: Thickness of sand cusioning shall be measured after punning. | 16 | Cum | 130 ₹2,080 Lowest | 350 ₹5,600 | 600 ₹9,600 | 2,500 ₹40,000 | 900 ₹14,400 | 230 ₹3,680 | 500 ₹8,000 |
Tender Value
₹1.4 Cr
EMD Value
₹2.1 L
Closing Date
17 Aug 2026, 6:00 pmClosed
CWE NB KOCHI
CWE (NB) KOCHI, Kataribagh, Naval Base PO, Kochi-04
SPECIAL REPAIR AND REPLACEMENT OF BER OCB PANEL WITH VCBs AT SUBSTATIONS AT INS DRONACHARYA UNDER GE FORT KOCHI
2026_MES_777280_1
81271
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
fort kochi
AS PER NIT
7 documents required · 7 mandatory
₹1,000
GE FORT KOCHI
₹2.1 L
Yes
21 Sept 2026
8 Jul 2026
21 Aug 2026
8 Jul 2026
17 Aug 2026
4 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing & commissioning of indoor type floor mounted metal clad,11 KV VCB panel with 10 Nos VCBs, totally enclosed and fully interlocked compatable to SCADA system in future, horizontal drawout, horizontal isolation type breaker as per IS 13118 as amended upto the date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, mannually charged and auto closing breaker suitable for use on 11 KV 3 phase 50 Hz AC supply with short circuit fault level of 350 MVa, complete with self contained, fully inter locked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 800 Amps capacity, breaker featured with mechanically ON/OFF indicator with hand trip device, spring release coil, shut trip coil and auxiliary switch of minimum 6 NO+ 6 NC and equipped with following switch gears and accessories i/c connections suitable for 3 x240 Sqmm XLPE 11 KV cable (cable entry from bottom) end termination with heat shrinkable jointing material etc as required complete all as specified and directed. | 1 | Each Set | - | - |
| 1.01 | (a) Incoming- 2 Nos 1200 amps capacity VCB and bus bar coupler-01 No 1200 Amps capacity VCB.
(b) 02 Nos 11 KV/100 Volts PT class 0.5 accuracy and 100 burder with 1 No Voltmeter
(0-15KV), digital type, selector switch for voltmeter and protection fuses/MCB for HT metering upto 12 KV on incomer.
(c) 02 Nos (0-300 A) dual scale ammeter digital type, selector switches for ammeters.
(d) 02 Nos Microprocessor based numerical relay with O/L,E/F and S/C protection
(e) 02 Nos Set of dual core dual ratio 3 CTs 300/150/5 A of 15 VA burden and accuracy class -0.5 for metering and class 5P10 for protection.
(f) Outgoing-07 Nos VCB
(g) 07 Nos (0-100 A) ammeters, dual scale digital type & selector switches for ammeters.
(h) Nos 07 Microprocessor based numerical relays with O/L, E/F & S/C protections.
(j) Nos 07 Set of dual core dual ratio 3 CTs 100/50/5 of 15 VA burden and accuracy class 1.0 for metering and class 5P10 for protection
(k) Along with this supplying, installation, testing and commissioning of power pack with 220 Volt AC input & 24 Volt DC continous output suitable for closing tripping/indication of 10 Nos HT panel boards with 2 Nos 12 Volts each maintanance free batteries of 100 (suitable) AH each, charging unit, capacitor bank for emergency delivering for trip system complete with suitable capaity of Ammeter & Voltmeter i/c connections with 2.5 Sqmm FRLS insulated copper cable ets as required complete all as specified and directed. | - | - | - | - |
| 2 | Supply, installation, testing and commissioning of indoor type floor mounted metal clad, 11 KV VCB panel with 05 Nos VCBs, totally enclosed and fully interlocked, horizontal drawout, horizontal isolation type breaker as per IS 13118 as amended upto the date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, mannually charged and auto closing breaker suitable for use on 11 KV 3 phase 50 Hz AC supply with short circuit fault level of 350 MVa, complete with self contained, fully inter locked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 1200 Amps capacity, breaker featured with mechanically ON/OFF indicator with hand trip device, spring release coil, shut trip coil and auxiliary switch of minimum 6 NO+ 6 NC and equipped with following switch gears and accessories i/c connections suitable for 3 x240 Sqmm XLPE 11 KV cable (cable entry from bottom) end termination with heat shrinkable jointing material etc as required complete all as specified and directed. | 1 | Each Set | - | - |
| 2.01 | (a) Incoming - 01 No 800 Amps VCB
(b) 01 Nos 11 KV/100 Volts PT class 0.5 accuracy and 100 burder with 1 No Voltmeter (0-15KV), digital type, selector switch for voltmeter and protection fuses/MCB for HT metering upto 12 KV on incomer.
(c) 01 No (0-300 A) dual scale ammeter digital type, selector switches for ammeters. (d) 01 No Microprocessor based numerical relay with O/L,E/F and S/C protection (e) 2 Nos Set of dual core dual ratio 3 CTs 300/150/5 A of 15 VA burden and accuracy
(f) Class -0.5 for metering and class 5P10 for protection.
(g) Outgoing-04 Nos 600 AmpsVCB (h) 04 Nos (0-100 A) ammeters, dual scale digital type & selector switches for ammeters. (j) Nos 04 Microprocessor based numerical relays with O/L, E/F & S/C protections.
(k) Nos 04 Set of dual core dual ratio 3 CTs 100/50/5 of 15 VA burden and accuracy class 1.0 for metering and class 5P10 for protection
(l) Along with this supplying, installation, testing and commissioning of power pack with 220 Volt AC input & 24 Volt DC continous output suitable for closing tripping/indication of 10 Nos HT panel boards with 2 Nos 12 Volts each maintanance free batteries of 100 (suitable) AH each, charging unit, capacitor bank for emergency delivering for trip system complete with suitable capaity of Ammeter & Voltmeter i/c connections with 2.5 Sqmm FRLS insulated copper cable ets as required complete all as specified. | - | - | - | - |
| 3 | Supply and laying cable XLPE insulated screened PVC bedded, galvanised steel strip of wire armoured, electric power cables (Heavy duty) 11000 Volts grade with stranded aluminimum conductor of size 240 sqmm, 3.0 core UG cable complete all as specified and directed by Engr-in-Charge | 100 | RM | - | - |
| 4 | Supply and laying cable XLPE insulated screened PVC bedded, galvanised steel strip of wire armoured, electric power cables (Heavy duty) 11000 Volts earthed grade with stranded aluminimum conductor of size 185 sqmm, 3.0 core UG cable complete all as specified and directed by Engr-in-Charge | 120 | RM | - | - |
| 5 | Excavation in trenches n exc 1.5m wide and n exc 1.5m deep for laying /removing of cable/ erection of poles in soft loose soil complete all as specified and directed by Engr- in- charge. | 100 | Cum | - | - |
| 6 | M&L for sand cushioning riddle earth in trenches/ducts for protection of UG Cables (below, above and around the UG cable laid) of 23 CM spread thickness (8 CM in depth before laying the cable and 15 CM in depth after laying the cable) and above sand shall be obtained through digging at site 500 mtrs distance and transporting to site for punned use to sand cushioning upto 18 CM thickness complete all as specified and as directed.
Note: Thickness of sand cusioning shall be measured after punning. | 16 | Cum | - | - |
| 7 | Supply and lay sub class "B" burnt bricks of size 23x11.5x7.5 cm, laid length of brick perpendicular to length of cable complete all as specified and directed. | 1.6 | Per 1000 Nos | - | - |
| 8 | Returning filling in, including spreading, levelling, watering and well ramming in layers n exc 25mm thick in soil complete all as specified | 82 | Cum | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
BOQ_870517.xls
BOQ • 0.25 MB
tender81271.pdf
Tender Documents • 0.79 MB
amendment1.pdf
PDF • 0.43 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .