Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹75.8 LAccepted-AOC | L1 | Accepted-AOC Being L1 and reasonable | |
| 2 | L2₹98.6 L+₹22.5 L (29.5%)Rejected-Finance | L2 | Rejected-Finance Being other than L1 | |
| 3 | Rejected-Technical 202 NEW RAM VIHAR COLONY PINTO PARK MORAR GWALIOR 474005 | GWALIOR | GWALIOR | MP | 474005 | - | Rejected-Technical Due to not enlisted in requisite category |
Tender Value
₹73 L
EMD Value
₹1.4 L
Closing Date
10 May 2021, 6:00 pmClosed
Chief Enginner Bareilly Zone
Headquarters Chief Engineer Bareilly Zone Military Engineer Services Sarvatra Bhawan, Station Road Bareilly Cantt Bareilly - 243001
PROVISION OF INFILTERATION WELL NEAR DAM SITE AND SELF CLEANING SCREEN FILTER WITH SUCTION SCANNER CLEANING MECHANISM UNDER GE PITHORAGARH
2021_MES_433780_1
CEBZ/PGH/T-31 of 2020-21
Open Tender
Civil Works - Water Works
Item Rate
180 days
PITHORAGARH
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
GE Pithoragarh
₹1.4 L
Yes
5 Jun 2021
31 Mar 2021
11 May 2021
31 Mar 2021
10 May 2021
21 Apr 2021
1 Apr 2021 - 19 Apr 2021
Amount
SCHEDULE 'A' PART-I (SELF CLEANING WORK) UNDER PHASE-I
Excavation in trenches in hard/ dense soil, n exc 1.5m wide and n exc 1.5m in depth for foundation etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10sq m on plan and n exc 1.5m in depth and getting out complete all as specified and directed.
Returning, filling in, any type of soil and spreading in layers not exceeding 25cm thick each layer including watering & well ramming complete all as specified and directed.
Removal of surplus excavated soil to a distance exc50 m but not exc in 100 m and deposited wher directedat a leveln exc 50 m above the starting point complete all as specified and as directed.
Material and labour for clean dry sand in trenches/ducts for cushioning to cable including spreding and levelling in layers n.exc. 25 cm thick, well ramming including watering as required and consolidation complete all as specified and directed. (Note : For payment purpose punned thickness of 18cm shall be measured against spread thickness of 18cm as mentioned in para19.75 of SSR Part-I)
Supply and laying sub class 'B' bricks old size for protection of cables laid length wise perpendicular to the axis of cable, adjacent to each other complete all as specified and directed.
Supply and laying GI tubing 40 mm bore light grade for cable protection at road crossing/on poles and tubing sealed at both ends after laying of cables complete all as specified and as directed.
Supply, laying, jointing, connecting,testing & commissioning cable XLPE insulated, screened,PVC bedded galvanised steel strips or wire armoured electric power cable (heavy duty) cross sectional area 35 Sqmm 3.5 core, 1100 volts grade with standard aluminium conductor complete all as specified and directed.
Supply, laying, jointing, connecting,testing & commissioning cable XLPE insulated,screened,PVC bedded galvanised steel strips or wire armoured electric power cable (heavy duty) cross sectional area 35 Sqmm 3.5 core, 1100 volts grade with standard aluminium conductor including taking out old unserviceble cable all as specified and directed at site..
Supply, installations and testing of ONLINE SELF CLEANING SCREEN FILTER with suction scanner cleaning mechanism, filteration grade 100 microns of size 200 mm (8") with design flow rate 200 Cum/hr for raw water filteration in consisting following Parameters of Make- AMIAD SAF 6000/AZUD/PENTAIR:-
(i) Mounting Type: On Line Housing
(ii) Varient: Standard.
(iii) Net Filteration/Filter: 6000 Sq Cm
(iv) Min Flow Flushing: 25 Cum/hr
(v) Min Required Pressure: 3.0 Barg
(vi) Design Pressure: 10.0 Barg
(vii) Waste Water Per Cycle: 280 Ltrs
(viii) Flushing Cycle Time: 20 sec .
(ix) Est Weight: Empty 250 Kgs (Approx)
(x) Control Voltage: 24 Volt, DC
(xi) Electric Motor: 1/3 HP
(xii) Rated Operation Voltage: 3 Phase / 415 V / 50 Hz
(xiii) DP Type: DP Switch, IP 55
(xiv) Filter Housing Body: Carbon Steel 37-2, Epoxy Coated
(xv) Filter Element: SS 317 Multilayer Weave Wire Screen, Cleaning Mechanism SS 316 With Relay Control Panel AMIAD Standard Type D alongwith all plumbing and pipe fitting to better housing of system running including alteration, welding work as per site requirment in existing 150 mm bore pipe line all as specified and directed at site. (Make: AMIAD SAF 6000 / Pentair / Azud)
The quoted rate of item No 10 will be deemed to be included for maintenance during the defect liability period upto two years after completion of Phase-I.
Material and labour for 150 mm bore galvanized iron pipe, medium grade complete with all fittings laid in trenches / wall all as specified and as directed.
S&F 80 mm bore galvanized iron pipe, medium grade complete with all fittings laid in trenches / wall all as specified and as directed. (Note :- Pipe shall be used in the flushing system of filter at outlet of 50 mm by using reducer 50 to 80 mm and connected to the Dam with the filter and necessary fitting / welding / fabrication work to be inclusive in the quoted rate)
Supply, installation, connecting and testing sluice valve cast iron body (long body) Class-1 with flanged ends drilled suitable for 150 mm bore pipe, ISI marked (IS:14846:2000) having SS spindle with iron wheel at top with nuts bolts washers rubber gasket etc complete all as specified and directed.
Design, supply , install, testing and commissioning of factory made and tested outdoor type floor mounted LT panel board, double door, cubicle type suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with air insulated PVC sleeved copper bus bar of rating 200 Amps for phases and neutral installed on porcelain insulators. The panel shall be dust and vermin proof IP-54 class protection and made out of 2.0 mm CRCA MS sheet and 40 x 40 X 6mm thick MS angle iron frame work front opening type of adequate size for housing LT switchgear and measuring instruments duly powder coated after seven tank process on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS-694 marked or PVC sleeved copper trips of appropriate size but not less than 4.0 Sqmm and comprising of following of Make- Salabh/Adhunik Switch Gear with CPRI certification:-
INCOMINGS
(a) MCCB 415 Volts, 80 Amp, rating 4 Pole , Service Breaking Capacity 16 KA (Ics=100%Icu) - 01 No (Incoming) Make-Legrand (Cat No.4200 14)
(b) Digital multi function Panel Mounted Meters for Energy metering, monitoring and management system suitable for LT 3 phase 4 wire applications, using micro-controllers and non volatile memory and providing anti tamper features and communication facility at high accuracy with accuracy for active energy as per IS 13779:99/IEC 61036, CL 1.0, operating temperature -10 to +55 ˚C, relative humidity 95% non condensing, 96 X 96 X 86 mm or nearer size, 3 line backlit display of 6 digit each to display voltage, current, active power, reactive power, apparent power, power factor frequency and other parameters, digit height 8 mmX4.8 mm, Protection index IP54 with all necessary CTs, PTs and instrument fuses and wiring - 01 No (Make HPL SOCOMEC model CTemfA2/Siemens/Schenider)
OUTGOINGS
(a) MCCB 415 Volts, 63 Amp, rating 3 Pole , Service Breaking Capacity 16 KA (Ics=100%Icu) - 02 No (outgoing) Make-Legrand (Cat No.4200 03)/SIEMENS/SCHENIDER
Note: 1. The quoted rates shall be deemed to be included danger notice plate on the panel board. 2. Minimum height of panel from floor level shall be 300 mm. Platform shall be made out of PCC 1:2:4 type B-1 using 20 mm graded stone aggregate and external surface shall be finished even and smooth with cement plaster in CM 1:4, using extra cement finally applied with three coats of white wash.
Material and labour for earthing with galvanized steel earth plate electrode size 600x600x6.3mm thick buried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanized iron strip 32X6 mm earth lead by means of bolts, nuts, check nuts and washers of galvanized steel and 20mm bore GI pipe, light grade for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 5 connected to earthing test point all as specified or indicated including testing on completion.
Note: 1. The unit rate shall be deemed to be included for protection pipe and GI earth strip 32 x 6mm size from top of earth plate upto 5.00 meter above ground level.
SCHEDULE 'A' PART-II (ANNUAL MAINTENANCE) UNDER PHASE-II
Annual Comprehensive Maintenance for item No.10 after two year completion of PHASE-I for next 5 years including testing, Servicing and Periodical checking for serviceability of the filter mechanism alongwith replacement of all parts if required: Suction Scanner Cleaning Mechanism Inlet and Outlet Flange, Electric Motor, Panel, Filter Housing Body and Lid, Filter Element. Seals and 4 layers screen. Auto Sensor Relay, Electric wiring etc. with all necessary fitting arrangement of Filter all as specified and directed. (Note:- The quoted rate shall be deemed to be included for the following spares under annual maintenance comrehensive)
(a) Upper bearing insert SAF-6000
(b) O ring seal P2-128 sealing insert NBR "S"
(c ) Suction Scanner Nozzle SAF 6000
(d) Suction Scanner shaft SAF- 6000
(e) Pin 5 X 45 S/ST 316
(f) Lower bearing insert SAF- 6000
(g) Shaped seal Hyd. AM -03 NR (SAF - 6000)
(h) O ring seal P2-459 SAF-6000 Lid)NBR
(j) Centering sleeve housing Lid SAF
(k) Flat washer M6 Din 125 S/ST316
(l) Spring washer M6 Din 127 S/ ST 316
(m) O ring seal P2 443 (6' service lid) NBR
(n) O ring seal P2 448 SAF 6000 Drive shaft housing NBR
(o) O ring 60 x 4 SAF 6000 Flushing chamber NBR "S"
(p) Connecting Pin SAF 6000
(q) Split Pin 2 x 20 Din 94 S/ ST 304 Din 471
( r) Limit switch plate SAF HD
(s) External retaining ring 17 mmS/ ST 304 Din 471
(t) Motor 380 / 480 Volt A/C 50 / 60 Hz 0.25 KW
(u) Manometer Valve 1/4 " W / Drain
(v) Pressyre gauge 16 Bar 1/4" Back inlet
(w) Controle tube 5/16" PA Air break W / inserts
(x) L-Connector 5/16" x 1/4" 69 F brass
Quarterly :- Cleaning of all internal parts and servicing of electric motor incl relay testing complete smooth functioning of filter. (ii) Service report is to be generated for the above quarterly maintanence for all the systems and signature of concerned JE should be taken on the report before submitting to Engr- in-Charge. (iii) If any major breakdown occured in the filter system emergency call shall be atteneded by concerned contractor to rectified the break down within 48 Hours.
Note :- Minor spares if any required and labour / Technician /Engineer element like tools / equipment / cleaning agent etc. is deemed to be included in the quoted rate of item No 17 above and following spares shall be measured and paid seperately.
Supply only leading shaft SAF - 6000
Supply only tightening plug ( Leading shaft) SAF - 6000
Supply only plug threaded M8 for SAF- 6000 PRO
Supply only Coarse screen (SAF-6000)
Supply only Sealling Flange Flushing Chamber SAF
Raja enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .