Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.0 LAccepted-AOC | L1 | Accepted-AOC You are placed in L1 | |
| 2 | Rejected-Technical INS VALSURA JAMNAGAR | JAMNAGAR | GUJARAT | 360520 | - | Rejected-Technical Rate quoted is high hence rejected | |
| 3 | Rejected-Technical | - | Rejected-Technical Rate quoted is high hence rejected | |
| 4 | Rejected-Technical | - | Rejected-Technical Rate quoted is high hence rejected |
Tender Value
Refer Docs
Closing Date
1 Oct 2019, 9:00 amClosed
Maj V E Pawar, GE
Garrison Engineer (AF) Jamnagar No 2, Air Force Station -2, PIN - 361004
Repair/Maintenance of LT Panel board for motor control centre AC Plant (2 x 56 TR) at Mig 29 infrastructure Tech Area, Air Force Stn No.1 Jamnagar.
2019_MES_283670_1
3010/10/E3
Limited
Job Works
Works
30 days
GE(AF) Jamnagar No.2
Please refer Tender documents.
1 document required · 1 mandatory
₹0
Exempted
4 Sept 2020
20 Sept 2019
2 Oct 2019
20 Sept 2019
1 Oct 2019
20 Sept 2019
Repair/Maintenance of LT Panel board for motor control centre AC Plant (2 x 56 TR) at Mig 29 infrastructure Tech Area, Air Force Stn No.1 Jamnagar. 1. M&L for taking out old/unserviceable/defective LT indoor panel by disconnecting all incoming and outgoing cable connection, taking out cables, removing earthing connection and removal of old panel for undertaking repair/replacement at site complete all as specified and directd -01 Job. 2. Supply, fabricating, erecting and commissioning of LT Panel board Indoor type of suitable size, for motor control centre conform to CPRI approval, as per IS 8623 Part I (One) totally enclosed weather and vermin proof suitably ventilated for 3 Phase, 4 wire 415 Volts, 50Hz, AC supply, outer shell shall be made out of 3.15mm thick CRCA sheet & MS angle section of suitable size of frame, factory fabricated, compartmentalized inner shell shall be made of out of 2.00mm thick CRCA sheet for control gear. Front door opening with locking aggangement at front. Protection of enclosure IP 56 as per IS-2147 of 1962 with pr-treatment through 7 tank hot chemical process prior to powder coating and powder coated with minimum 50-70 micron of approved colour. The bottom of outer shell contains a detachable plate having provision for entry of armoured cable of adequate size. EPDM gasket of appropriate shape and size provided at all joints, doors and covers including suitable size angle iron/flat irom frame work/support, required at site and comprising of the following:- (i). TPN Aluminium electoytic grade busbar of capacity 750 Amps, 50KA for phases & 350 Amps for neutral, duly supported on SMC/DMC, busbar supports and insulated with colour coded heat shrinkable sleeve. (ii). Digital multifunction meter (V,A,KW,KWH), 415V, AC, C.T's of suitable ratio (set of three), class 1.0- 01. (iii).Indication lamps, LED type (RYB) - 01 Set of three. CT's 500/5A class 1.0, 15VA(Cast Resin) for metering - 03 Nos. (iv) Internal wiring with suitable size of copper cable,
jagdish machinery stores
Raj brothers
Trimurti Enterprise
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_318704.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .