Office of the Executive Engineer TLMD III Udhampur
Executive Engineer TLMD III Udhampur
Augmentation of grid station Katarsamna Kishtwar of 01 no 20 MVA Transformer with 50MVA Transformer and replacement of old outlived 20MVA Transformer at GSS NHPC with Transformer to be spared after augmentation and other associated works in Kishtwar
2026_PDD_327668_1
TLMD-III/Udh/14 of 2026-27 Dated 09-10-2026
Open Tender
Electrical Works
Turn-key
180 days
Kishtwar
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,000
Yes
Executive Engineer TLMD III Udhampur
₹17.1 L
Yes
Office of the Executive Engineer TLMD III Udhampur
10 Oct 2026
10 Oct 2026
31 Oct 2026
10 Oct 2026
30 Oct 2026
10 Oct 2026
21 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Design, Engineering. Manufacture,workshop testing, supply including packing, forwarding, insurance,transportation,delivery at site , Erection, testing commissioning as per approved design/drawings and in conformity to the relevant and applicable BIS/IEC and CEA standards | - | - | 1.25 | - |
| 1.01 | 50 MVA, 132/33 kV Three Phase Power Transformers with OLTC, SCADA Compatible RTCC, NIFPES , HV and LV connectors and other required accessories and fittings with online DGA monitoring Kit, online dehydration kit and maintenance free automatic breathers as per technical specifications with all mandatory spares as per SBD. 50 MVA, 132/33 kV Three Phase Power Transformers with OLTC, SCADA Compatible RTCC, NIFPES , HV and LV connectors and other required accessories and fittings including all mentioned manadatory spares including HV & LV Bushing with metal parts & gaskets (1 no each),Gasket sets complete,Buchholz relay (1 No.), Cooler fan with motor (2 nos) ,Silica Gel Breather, Inlet and Outlet valves & Gasket,Oil sampling bottles (Air tight stainless steel with capacity 01 (one liter and clocks fitted at both ends)** | 1 | No. | - | - |
| 2 | SITC of CONDUCTOR AND HARDWARE FITTINGS | - | - | 1.25 | - |
| 2.1 | 500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN | 0.6 | Kms | - | - |
| 2.2 | Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN. | 18 | No | - | - |
| 2.3 | Single Suspension Fittings For Single 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type suspension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN. | 18 | No | - | - |
| 2.4 | T Clamps 0.5 / 0.5 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) | 36 | No | - | - |
| 2.5 | pad clamps/CT clamp 0.5 made of Aluminium alloy and shall comply in all respects with IS:5561-1970 (latest edition) for isolator and breaker | 42 | No | 1.25 | ₹52.5 |
| 2.6 | Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia.Creepage total 430 mm and 260 mm protected. | 98 | No | 1.25 | ₹122.5 |
| 3 | SITC of POWER AND CONTROLCABLES | - | - | 1.25 | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.26 MB
Tendernotice_2.pdf
PDF • 2.85 MB
Tendernotice_3.pdf
PDF • 4.05 MB
Tendernotice_4.pdf
PDF • 9.89 MB
BOQ_1108676.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .