ELECT G
15 conditions · 3 needing a document upload
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
Similar nature of work for minimum eligibility criteria is as under: "Any electrical engineering work, provided that the tenderer has electrical contractor's license for the voltage that is the highest in the complete work."
3 conditions · 1 needing a document upload
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
1. I/We have visited the works site and I/We am/are aware of the site conditions. 2. We have read the tender Notice[NIT] details, Tender document along with all the conditions attached/referred to, in this tender document, and agree to abide by the said conditions. 3. We are aware of the fact that the railway reserves the right to amend the scope and value of the contract and to reject[or accept] this offer without assigning any financial liability.
Electrical work in connection with Construction of new wharf, Shed, Amenities, connectivity road, Office for Railway employees is required with water, urinal and toilet facility Lighting arrangement at Chainpur & Rakhitpur and Improvement of Goods shed & Provision of PC measures at Dughda (DPSC, DGSC,DBYC) goods sheds in DHN Division.
EL-46-OPEN-2025-26~ECR
EL-46-OPEN-2025-26
Open
Works - General
12 Months
Dhanbad, Jharkhand
₹0
₹2.4 L
28 Jan 2026
5 Jan 2026
14 Jan 2026
113 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 1,78,98,413.04 | ||
| (A) Supply, fixing and erection of 16Mtrs. long High Mast Tower for 09 nos. LED floodlight fittings of 160W/200W/240W suitable for wind pressure upto 180Km per hour. Materials construction: MSD IS-2002, make "BPP"/Bajaj/" comprising with following.(b) Supply, fixing and erection of mechanical components including head frame lantern carriage, ring, luminaries and C. G. Box Mfg. Arms, resting bracket, guide ring, compensating disc, lightning arrestor. (c) Supply, fixing and erection of steel ropes and nuts, bolts suitable for 16Mtrs.s. long High Mast.(d) Supply, fixing, connection and testing of control cable suitable for 9nos. LED floodlight fittings of 160W.(e) Supply and erection of foundation bolts, nuts & anchor plates etc.(f) Supply and erection of winch assembly suitable for 16-Mtrs.s. long High Mast. (g) Supply, fixing, connection and testing of power tools. (Motors, starters with control circuit board). Make:-BPP Surya, Orient, Bajaj & Utkarsh. | — | — | — | 23,68,782.92 | |
| — | 14.00 | — | — | ||
| Casting of high mast masonry foundation with earth excavation with RCC 1:3:6 cement, sand and stone as per relevant IS foundation shall be of approximate overall size 2.7 Mtrs. (L) X 2.7 Mtrs (B) X 2.3 Mtrs. (H) including muffing of size: 0.75Mtr (L) x 0.75Mtr (B) x 1.9 Mtr (H) or as per OEM manufacturer's drawing. The course aggregate should be granite stone 20 mm for muffing and foundation along with grouting of foundation bolts complete in all respect.(Cement and all other materials will be supplied by the contractor) | — | — | — | 5,48,101.12 | |
| — | 14.00 | — | — | ||
| Supply, fixing, connection, testing and commissioning of panel board complete with contractor, timer, selector switch, voltmeter, auto & manual switch indicator lamps etc. as required. (Make: Bajaj, BPP, L&T OEM} | — | — | — | 3,41,584.6 | |
| — | 126.00 | — | — | ||
| Installation, fixing, testing, commissioning & Supply of LED floodlight of 160W similar to BAJAJ Make, Turbo LED floodlight series Luminare type BARFEG 160W LED ordering code 169642 with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion with IP66 (Make-Surya, Havells, Bajaj, Philips, Policab, Orient, Cromption) | — | — | — | 14,82,584.04 | |
| — | 14.00 | — | — | ||
| Supply, installation, testing & commissioning of Neon spiral aviation fixture with 25W Neon spiral lamp (02 nos. fitting in the mast). (Make: Bajaj/ Philips/Surya, C&S). | — | — | — | 53,944.24 | |
| — | 255.00 | — | — | ||
| Supply of octagonal galvanised pole (dip galvanised in single dip average 70 micron), 7mtrs long, with required accessories, Make-Bajaj, Bansal, Surya,Orient, Jindal, Transrail lighting LTD, Gammon Group & Utkarsh. | — | — | — | 26,84,397.75 | |
| — | 255.00 | — | — | ||
| Erection and casting of foundation for octagonal/tubular pole with earth excavation, with cement concrete (1:3:6) and muffing of base foundation, as per manufacturers drawing and dimension as required under the supervision of site incharge. | — | — | — | 6,35,375.85 | |
| — | 255.00 | — | — | ||
| Fabrication, Supply and Fixing of GI Single Arm 1.5 mtr long suitable for 7 mtr GI octagonal pole. | — | — | — | 7,40,902.5 | |
| — | 290.00 | — | — | ||
| Installation, connection, testing and Supply of LED Street Light Fitting 72W (±5%), similar to Havells model OMNIPLUS, made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protection and impact resistance of IK07. Light source - High efficiency long life LED module with SMD LED package mounted on MCPCB. Lumen efficacy of LED >140 lm/W. System Lumen Efficacy 110Lm/W, Electronic driver-Powered by integral, isolated electronic LED driver (SMPS based constant current supply) with lower THD, Output Open / Short Circuit protection, Over Voltage protection, Surge Voltage protection 10KV with SPD & other safety test as per IS 15885 Part-2/Sec 13. Warranty 5 years. (Make- Surya, Havells, Bajaj, Philips, Policab, Orient, Cromption). Connection to be made with PVC insulated S/core stranded alum. FRLS Conductor 2.5mm2 with PG clamp of required size (including supply) | — | — | — | 16,53,000 | |
| — | 255.00 | — | — | ||
| Fixing & connection of St. Light fitting including supply of PVC wire 1.5 Sqmm. | — | — | — | 14,835.9 | |
| — | 35.00 | — | — | ||
| Supply of Bend GI pipe of 30mm dia x 4ft long (to suit the street light fitting) as per site requirement and fixing the same on pole with supply of suitable clamp, nut, bolt and washer. | — | — | — | 12,950 | |
| — | 3.70 | — | — | ||
| Erection and supply of Galvanised steel structure for Mast , dwarf mast etc. (9.5 mtr length) as per RDSO specification No. ETI/OHE/13(4/84) and IS:2062 | — | — | — | 3,27,697.31 | |
| — | 1.25 | — | — | ||
| Erection and supply of Galvanised steel structure other than mast as per RDSO specification No. ETI/OHE/13(4/84) and IS:2062 | — | — | — | 1,10,708.55 | |
| — | 27.75 | — | — | ||
| Concrete for foundation | — | — | — | 1,26,892.42 | |
| — | 5.00 | — | — | ||
| Erection and supply of No.TI/SPC/OHE/INS/ 0070(4/07) or latest. | — | — | — | 16,589.5 | |
| — | — | — | per | ||
| — | — | — | RDSO | ||
| — | 5.00 | — | — | ||
| Erection and supply of 25KV D.O. Fuse switch complete as per RDSO Spec. No.ETI/PSI/14(1/86)/ REV -1/Apr -87 or latest. | — | — | — | 54,928.25 | |
| — | 10.00 | — | — | ||
| Erection and supply of Post Insulator Spec. No. TI/SPC/OHE/INS/0070(04/2007) with A & C Slip no-1 & 2, RI 6090 | — | — | — | 49,045.9 | |
| — | 10.00 | — | — | ||
| Supply & erection of Anti climbing Device Spec. No.ETI/OHE/SK/106 | — | — | — | 23,323.3 | |
| — | 75.00 | — | — | ||
| Supply & erection of Jumper wire, 160 sq.mm (19x7x1.25 mm) as per RDSO Spec. No. ETI/OHE/3(2/94) Rev.1 (4/95) or latest | — | — | — | 58,338.75 | |
| — | 20.00 | — | — | ||
| P.G. Clamp (1030) as per Drg. No.ETI/OHE/ P/1030-3 & or latest | — | — | — | 5,249.8 | |
| — | 5.00 | — | — | ||
| Supply & fixing of Number Plate | — | — | — | 2,165.15 | |
| — | 50.00 | — | — | ||
| Drilling of hole for bonding | — | — | — | 2,276.5 | |
| — | 0.50 | — | — | ||
| M.S Flat 40x6mm | — | — | — | 35,471.92 | |
| — | 5.00 | — | — | ||
| Supply& fixing of Busbar Chamber, Current Rating 200A, 4-way, similar to Havells Cat: no: IHBB020004,(Make: Havells/Siemens/ Standards/L&T (Fixing with proper excavation and refilling the wall with proper re-plastering of the wall) | — | — | — | 40,476.15 | |
| — | 5.00 | — | — | ||
| Testing, commissioning, installation and supply of MCCB,320A, 35KA, four pole, with thermal magnetic release with suitable MCCB enclosure. Fixing to be done as per the site requirement under supervision of site incharge including connection with crimping of cable ends with aluminium lugs of required sizes (Make -Indo asian, C&S, Havells, L&T, HPL & BCH) | — | — | — | 2,10,701.8 | |
| — | 50.00 | — | — | ||
| Supply of GI pipe 4" dia, Medium gauge 'B' class including fixing with suitable clampnuts, bolts etc as per requirement (Make-Tata, Jindal & Bansal) | — | — | — | 29,409 | |
| — | 5.00 | — | — | ||
| Installation, testing commissioning & Supply of Submersible Pump set 3000 GPH x 250ft head (5 star) Similar to KSB Model UQD+UMA 1/G150, 182/10+6/22 (S/D), Motor Rating- 7.5 HP, 5.5KW, 3-phase, including installation, testing, commissioning and lowering of the pump in the bore well with clamping of pump & motor with black steel pipe by tag welding and clamping of submersible cable throupgh out the length of the lowering (Acceptable Make: Shakti PUMPS (INDIA) Ltd. /KSB/CRI | — | — | — | 3,09,627.7 | |
| — | 5.00 | — | — | ||
| Installation, testing ,commissioning & Supply of 20HP Automatic Star/Delta starter with (1)Pump protection relay(C & S mpro-200 - 60 - E) (2)Programmable time switch(Automatic ON/OFF purpose) (3)LVM with SPP and phase Seq. complete with other electrical accessories e.g voltmeter(0-500V), Ammeter(0-50A),selector switches etc. including wiring. (Make- L&T, Siemens, C&S) | — | — | — | 2,36,895.8 | |
| — | 10.00 | — | — | ||
| Supply of GI long bends 2" dia, heavy gauge 'C' class, 90 degree, including fixing (Make: TATA/JINDAL/BANSAL) | — | — | — | 2,550.1 | |
| — | 450.00 | — | — | ||
| Supply of GI pipe 2" dia heavy gauge 'C' class, with socket including fixing (Acceptable make: Tata, Jindal, Bansal) | — | — | — | 2,26,246.5 | |
| — | 1000.00 | — | — | ||
| Installation, testing commissioning & Supply of submersible copper cable, insulated, sheathed, flat type 3-core 4mm2, Water Proof conforming to IS: 694 (Make: Polycab/Havells/Finolex) | — | — | — | 1,76,240 | |
| — | 5.00 | — | — | ||
| Supply TATA/JINDAL/BANSAL ) | — | — | — | 5,022.3 | |
| — | — | — | 2"/2.5" | ||
| — | — | — | dia | ||
| — | — | — | (Make: | ||
| — | 5.00 | — | — | ||
| Supply of sluice valve 2"/2.5" dia including fixing (Acceptable make: ISI approved) | — | — | — | 4,518.55 | |
| — | 13200.00 | — | — | ||
| Trenching, laying and back filling of XLPE cable as per Sr.DEE(G)/DHN's drg. No. EL/486-01 (cable will be supplied by the Railway/Contractor as applicable) | — | — | — | 8,34,900 | |
| — | 500.00 | — | — | ||
| Trenching, laying and back filling of XLPE cable on pucca/concrete road or concrete/tiled floor through making a trench of 6 inchs depth and 6 inches wide on the road / floor and refilling the trench with cement concrete (1:3:6) and finished to smooth surface in a manner as directed by Section Engineer in charge at site. (cable will be supplied by the Railway/Contractor as applicable) | — | — | — | 57,460 | |
| — | 100.00 | — | — | ||
| Cable crossing across railway track/pucca road by boring hole at depth of 01 mtr by using 01(one) nos 100mm dia GI pipe(medium grade) with accessories.GI pipe with accessories will be supplied by the contractor. (cable will be supplied by the Railway/Contractor as applicable) | — | — | — | 1,70,333 | |
| — | 48.00 | — | — | ||
| Provision (Supply and erection) of Earthing station (RI-7021) as per Drg.No. ETI/ OHE/P/ 7020 or latest (The price shall cover supply and erection of an earth electrode (RI 7021) as per drawing no. ETI/OHE/P/7020. The price shall also cover the provision of a protective concrete Box with removable MS cover. The material should confirm to ACTM vol. II Part II Para 7.1.1 with figure A 3.01. The price shall cover the testing of earth value and painting the value on the earth pit. The earth electrode shall normally be of mild steel galvanized perforated pipe of not less than 44 mm nominal bore and about 3 meter length provided with a spike at one end and welded lug suitable for connecting directly Earth wire/MS flat of required size at other end. The connection of Earth wire/M S flats to each electrode shall be made through M S links by bolted joints, fasteners to be supplied by the contractor. The earth surrounding the electrode shall be chemically treated by alternate layers of fine charcoal and salt at least 150 mm all around. The item should be procured from approved supplier of CORE or RDSO, duly inspected by either RITES or Railway Representative deputed by Sr. Div. Elect. Engineer (G)/ Dhanbad.) | — | — | — | 1,55,906.88 | |
| — | 350.00 | — | — | ||
| Fixing, connection, testing & Supply of LED Batten, Box type luminaire, with CRCA body, Pre wired for LED tube with supply of Retrofit LED tubular lamp 1X20W,T-8, 4' long, complete with inbuilt LED driver, Make - Surya, Havells,Bajaj, Philips, Polycab, Orient, Cromption (LED Luminarie of the makes as specified above should be as per RDSO's specification for Energy efficient LED based luminaire unit for indoor lights to be used in Indian Railway offices and buildings. (Fixing of fitting to be done with proper clamping arrangement as per the site requirement and connection to be done with1.5 sqmm single core copper conductor FRLS by tapping from sub main line including supply of ceiling rose and wires and PVC flexiable pipe) ( The complete system of LED lights (including Driver etc) shall be guaranteed for satisfactorily performance and manufacturing defects for period of 60 months from the date of commissioning or 72 months from the date of supply, whichever is earlier.(Reference: Railway Board's letter no.2006/Elect(G)/150/5 dated 27.03.15). | — | — | — | 3,70,338.5 | |
| — | 350.00 | — | — | ||
| Wiring of light point with PVC insulated, sheathed & stranded single core copper conductor( FRLS) 1.5mm2 (Wire Make-Havells, anchor, Finolex, Polycab, Mescab) with ECC in PVC pipe in concealed with proper excavation and refilling the wall with proper plastering of the wall with supply & fixing of switch, ceiling rose/angular batten holder etc(.make Havells, anchor,Legrand, Slemens, L&T,or C&S) | — | — | — | 78,634.5 | |
| — | 10.00 | — | — | ||
| Supply & fixing of Air circulators Wall fan 600mm sweep, single phase (Make - HAVELLES, crompton, Bajaj) including supply fabrication of suitable clamping arrangement made of M.S Flat 40X5 mm size, with supply of suitable bolts, nuts and washers as per the site requirement and connection to be done with1.5 sqmm single core copper conductor by tapping from sub main line including supply of ceiling rose and wires and other accessories. | — | — | — | 80,106.7 | |
| — | 10.00 | — | — | ||
| Supply,& fixing of Metal body Exhaust Fans (non-capacitor type) No of poles -4 & sweep size 300 mm (Make-Usha, Havells/crompton, Bajaj ) (fixing of exhaust fan to be done by cutting the hole of required size along with supply and grouting of required nut, bolt & washer to suit the Ex-fan as per site requirement, including connection. ) | — | — | — | 14,166.7 | |
| — | 45.00 | — | — | ||
| Wiring of C- Fan/Ex-Fan point with PVC insulated, sheathed & stranded single core copper conductor FRLS 1.5mm2 (Wire Make-Havells, anchor, Finolex, Polycab, Mescab ) with ECC in PVC pipe in concealed with proper excavation and refilling the wall with proper plastering of the wall with supply & fixing of switch, ceiling rose .(make-Havells, anchor,Legrand, Slemens, L&T or C&S) on surface of wall with ECC including supply and fixing of switch and ceiling rose. | — | — | — | 14,647.05 | |
| — | 300.00 | — | — | ||
| Wiring of plug point with PVC insulated, sheathed & stranded single core copper conductor FRLS 1.5mm2 (Wire Make-Havells, anchor, Finolex, Polycab, Mescab) with ECC in PVC pipe in concealed with proper excavation and refilling the wall with proper plastering of the wall with supply & fixing of 5Amp plug & socket switch (make-Havells, Anchor, Legrand, L&T, Seimens or C&S) | — | — | — | 45,759 | |
| — | 50.00 | — | — | ||
| Wiring of power plug point 15 Amp with PVC insulated, sheathed and stranded single core, copper conductor FRLS 4mm2 (Wire Make-Havells, anchor, Finolex, Polycab, Mescab) with ECC in PVC pipe in concealed with proper excavation and refilling the wall with supply & fixing of 15Amp Power Plug & Socket flush type, 5 in 1 including controlling switch.(make-Havells, Anchor, Legrand, L&T, Seimens or C&S) | — | — | — | 11,915 | |
| — | 2000.00 | — | — | ||
| Wiring of sub-Main Line with FRLS copper wire single core size 6mm2 multistrand with PVC pipe concealed with proper excavation and refilling the wall with proper plastering. (Wire Make-Havells,anchor, Finolex, Polycab Mescab) | — | — | — | 1,23,260 | |
| — | 700.00 | — | — | ||
| Wiring of Main Line with FRLS copper wire single core size 10mm2 multistand with PVC pipe in concealed with proper excavation and refilling the wall with proper plastering. (Wire Make-Havells,anchor, Finolex, Polycab, Mescab) | — | — | — | 57,652 | |
| — | 20.00 | — | — | ||
| Fixing, connection, testing & Supply of MCB Distribution Board 8-way (2-incomer ,6- outgoing),double door,IP-43-protection conforms to IS:8623-1&3, MCB 32A, DP, 10 KA, B-Curve, conforms to IS:60898 - 1 No as incoming, MCB 10A, DP, 10 KA, C-Curve, conforms to IS:60898 3 Nos as outgoing. Make - L&T, Havells, Legrand ,C&S, HPL & BCH (Fixing of Distribution Board to be done with proper clamping arrangement as per the site requirement and connection to be done with suitable conductor including supply of PVC flexiable pipe) | — | — | — | 71,133.4 | |
| — | 5.00 | — | — | ||
| Supply, installation, testing & commissioning of LT panel consist of: (1) dsine MCCB- 400A-4 Pole, 50kA-01no. (Incoming) (2) dsine MCCB-200A-4 Pole, 50kA-01 no. (3) dsine MCCB-100A- 4 Pole, 50kA-04 no (Outgoing) (4) 01 No. Voltmeter (0-500V), (5) 01 nos-Ammeter(0-150A), (6) Selector switch-02 nos. (7) Ind. lamp-03 nos. (8) Cu.busbar-25KG, (9) MS sheet metal 4'x3'x1.5' = 18Cu.ft etc. ' (Acceptable make: MCCB-SIEMENS,HAVELLS,L&T, HPL,BCH & C&S. Ammeter/Voltmeter/Sel. Switch make: Essma/Shruti Associates, HRC fuse-HPL/Hager) | — | — | — | 5,53,486.1 | |
| — | 4.00 | — | — | ||
| Fixing, connection, testing & Supply of Off load Change Over switch 400 A, 4 Pole. (Fixing of Change over switch to be done as per the site requirement and connection to be done with suitable supply of PVC flexible pipe) make-HAVELLS, Standard, Indoasian | — | — | — | 1,05,422.52 | |
| — | 4.00 | — | — | ||
| Testing, commissioning, installation and supply of MCCB,100A, 35KA, four pole, with thermal magnetic release with suitable MCCB enclosure. Fixing to be done as per the site requirement under supervision of site incharge including connection with crimping of cable ends with aluminium lugs of required sizes (Make -Indo asian, C&S, Havells, L&T, HPL & BCH) | — | — | — | 44,138.68 | |
| — | 4.00 | — | — | ||
| Installation, Connection, commissioning and Supply of Automatic changeover CLS panel, Capacity - 300Amps for 3 source single phase supply suitable for 50 kVA AT as per RDSO specification No.-TI/SPC/PSI/CLS/0020 with A&C slip no: 01 to 04 or latest, CORE approved drawing no. ASCOS/25 KVA/CORE/2007/01 Rev.01, Make- SUNTRON, MATRIX or CORE approved. Signaling panel should be fixed on the wall / floor with proper grouting as per the site requirement including connection with crimping of cable ends as required under the supervision of site incharge. | — | — | — | 16,04,513.84 | |
| — | 3200.00 | — | — | ||
| Providing and fixing 06 SWG / 5.0 MM dia GI wire on surface or in recess for loop earthing of street light poles, connection from earth pit to main junction board/panel, connecting different earth pits etc. Connection and Looping of earth wire to be done with suitable fasteners, nuts bolts and washer as required. | — | — | — | 24,960 | |
| — | 5.00 | — | — | ||
| Supply of 25 KVA , 25KV/240V single phase oil filled Auxiliary transformer as per latest RDSO Specification no-ETI/PSI/15(8/2003) Make-RDSO/Core approved vendor. | — | — | — | 8,35,845 | |
| — | 5.00 | — | — | ||
| Installation, Testing and commissioning of 25 KVA , 25KV/240V single phase oil filled Auxiliary transformer (fixing to be done by As per site reqirement) | — | — | — | 53,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .