| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹85.1 LAccepted-AOC 00 BALITIKURI BALITIKURI NASKARPARA HOWRAH WEST BENGAL 711113 | HOWRAH | WEST BENGAL | 711113 | L1 | Accepted-AOC LOWEST BID | |
| 2 | L2₹85.6 L+₹54,546 (0.64%)Rejected-Finance | L2 | Rejected-Finance NOT LOWEST | |
| 3 | L3₹98.5 L+₹13.4 L (15.8%)Rejected-Finance 14 SURI LANE KOLKATA 700 014 | KOLKATA | KOLKATA | WEST BENGAL | 700014 | L3 | Rejected-Finance NOT LOWEST | |
| 4 | L4₹1.1 Cr+₹28.5 L (33.5%)Rejected-Finance | L4 | Rejected-Finance NOT LOWEST | |
| 5 | L5₹1.2 Cr+₹30.2 L (35.5%)Rejected-Finance | L5 | Rejected-Finance NOT LOWEST |
Tender Value
Refer Docs
EMD Value
₹1 L
Closing Date
28 Sept 2021, 5:00 pmClosed
SE PWD CEC
184, C.R.Das Road, Berhampore, Murshidabad, PIN-742101
Construction of Nurses Hostel in Front of existing Nurses Hostel at Gandhi Memorial Hospital ,Kalyani Nadia Augmentation of Sub Station SITC 2X 500 KVA SUBSTATION AND EI Work
2021_WBPWD_341319_1
WBPWD/CEC/eNIQ/03/Q/SECONDCALL
Open Tender
ELECTRICAL WORKS ORG
Item Rate
90 days
Gandhi Memorial Hospital, Kalyani Nadia
Please refer Tender documents.
4 documents required · 4 mandatory
₹1 L
VIRTUAL WEB PLATFORM
6 Dec 2021
24 Aug 2021
30 Sept 2021
24 Aug 2021
28 Sept 2021
4 Sept 2021
3 Sept 2021
Amount
SUB HEAD I: SITC OF 11KV VCB PANEL & TRANSFORMERS Supply & Delivery Indoor-type, floor mounted,metal clad, single tier, fully compartmentalized,free standing, 11 kV VCB Panel with 3 Nos VCBs (1 Incomer + 2 Outgoing), totally enclosed and fully interlocked , horizontal drawout, horizontal / vertical isolation type breaker as per IS 13188, as ammended upto date and as per detail specification attached ( uploaded in the specification section) , suitable for use on 11 KV, 3 Phase,50 Hz AC supply to energise 2 X 500 KVA Dry Type Transformers. [ Make : ABB / Siemens / CGL].
Installation & commissioning of the above 11 kV VCB Panel with P.T & all the accessories, incl. carriage, by placing in position, assembling, lining up, levelling and checking all instruments, relays, correctly set according to requirement.
Supply & Delivery of Cast Resin Dry Type 11KV/415V 500 KVA, 3 Phase,50Hz, Dyn11,copper wound, Class F insulation associated with winding temperature indicator/controller,having cable end box in the HV & LV sides and all accessories and conforming to IS 11171-1985 & IS - 2026 with latest modification (if any) & CBIP Specification and as per detail specification attached ( uploaded in the specification section) [ Make: ABB/Voltamp ( Vadodara)/CGL/Raychem ].
Installation & commissioning of 11 KV/ 415 volt, 500 KVA distribution transformer incl. carriage to the substation building within a lead of 30mtr by placing in position and fixing after leveling fitting all components, connecting, checking & set of all instrument, relays according to requirement as instructed by the EIC incl. S&F base channels etc.
SITC of floor mounted Indoor type extensible cubical MV switchboard,fabricated by CPRI approved panel maker having compartmentalized design, fabricated out of 14 SWG ( 2.0 mm ) nominal thickness CRCA sheet steel,front and back openable, hinged, single shuttered, with incoming ACBs & Outgoing MCBS and all accessories as per size, design & drawing to be approved by EIC and conforming to IS with latest modification and as per detail specification attached ( uploaded in the specification section)[LT MAIN PANEL IN THE SUBSTATION]
Making testing arrangement and submitting the test report for high voltage testing of specified voltage incl. checking & testing of all HT / LT equipments by authorized firm of Directorate of Electricity & commissioning the installation after obtaining the Approval of Directorate of Electricity.The scope shall be also included the necessary approval from Authority also.
SUB HEAD II - HT/ LT CABLING IN SUBSTATION Supplying and laying of 1 No. 11KV (E/UE) Grade XLPE Aluminium conductor, PVC sheathed, armoured cable confirming to IS 7098, of earthed system of following size in the existing Masonary Open Duct as required.[ From Supplier HT Gear to Consumer HT Gear and to Transformer]. [ Make : Nicco / Gloster ] a) 3 Core x 240 Sq.mm
Making heatshrinkable joints to the ends of the following XLPE HT cable at the transformer end as well as at the VCB ends supplying with necy. jointing kits, sockets, sleeves, anti-corrossive paste, wires, solders, jointing compounds, rubber sheets etc. incl. supplying of necy. tools & tackeles for crimping the end sockets, soldering irons & making of glands at the both end of the cable as per directions of EIC a) 3 Core x 240 Sq.mm
Supplying and Laying of following size PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing Masonary Open Duct. [ From TR & DG set to main panel].[ Make : Nicco / Gloster ] a) 3.5 Core x 185 sq.mm (3 NO Cable Transformer to LT Panel )
Supplying and making end termination with Brass compression gland and aluminium lugs for the following sizes of PVC insulated and PVC sheathed aluminium conductor cable of 1.1 KV Grade as required a) 3.5 Core x 185 sq.mm.
Supply & Drawing 1.1 KV Grade 7 Core 1.5 sq.mm PVC Armoured Copper Cable from Transformer WT relay to VCB WT relay for Power & Control Supply as per direction of EIC
SUB HEAD III - EARTHING FOR SUBSTATION Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By TATA-Medium GI pipe.
Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 no 65 mmx 8mm galvanised (Hot Dip) steel strip (4 mtr long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including fonishing at both ends by making hole etc and S & F 80 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground to an average depth of 3.65 Mts
Excavation of soil for installation of Earth Electrode and filling & ramming. For Soft Soil
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos.12 mm dia holes on the GI pipe
Extra treatment of soil by using salt & charcoal for plate electrode as to G.S.
Supply & fixing earth busbar of galvanized (Hot dip) MS flat 65 mm x 8 mm on wall having clearence of 6 mm from wall incl. providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
Insulating the 65 x 8 mm M.S. flat incl. S&F black heat shrink PVC sleeves etc. The PVC tube sleeve to be inserted on the GI flat and heat shrinked by heating apparatus by skilled technician carefully without damaging the PVC sleeve as per direction of the EIC (for transformer neutral earth bus bar).
S&Laying Single core 25 sq. mm. unsheathed FR PVC insulated cu.wire from TR.Neutral to neutral Basbar including. S&F of alu socket end finishing (2nos)
Connecting the equipments body to earth bus bar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor drilling holes, with nuts, bolts, washers etc.
SUB HEAD IV - SAFETY EQUIPMENT Providing & fixing danger plates made of mild steel at least 2mm thick & vitreous enameled white on both sides & with inscription in signal red colour on front side as required. a) High Voltage - size 200mm x 300mm
b) Medium Voltage - size 200mm x 300mm
Providing and fixing carbon dioxide (CO2) type fire extinguishers confirming to IS 2878 - 1976 and cylinders fully charged of following capacity(4.5 Kg )
Supply and fixing safety instruction chart in word duly framed with 5mm thick glass as required (approx. Front area 1.20 sq.mt.)
Providing of set of 4 nos. 9.5 litre capacity GI bucket painted in post office red colour with prior coat of red-oxide paint and written with white paint 'FIRE' and mounted on MS angle iron frame with bracket and suitable base of appropriate size & capacity I/c filling sand etc.
Providing First Aid Box as approved by St. John Ambulance Brigade / Indian Red Cross conforming to IS 2217-1963.
Supply and fixing shock treat chart duly mounted on a wooden frame with 5mm thick glass as reqd. (approximate front area 1.20 sq.metre).
Providing of rubber mat 2 mtrs Length x 1 m. wide and 12mm thick to withstand 15 KV dielectric strength as per IS 5424-1969.
Providing of rubber mat 2 mtrs Length x 1 m. wide and 6mm thick to with stand 3.3 KV dielectric strength as per IS: 5424-1969.
S/F of 860 mm wide and 8 mm thick M.S checker plate including painting for covering the trench.
SUB HEAD V- LT CABLING FROM SUBSTATION Supplying of one number 1.1 KV Grade XLPE insulated and PVC sheathed aluminium conductor cable ( Armoured ) conforming to IS: 7098 / 1988 with its latest amendment of following size. [ Make Nicco / Fort Gloster ] 3.5 Core 240 Sq. mm [ New SUBSTATION To Old Substation BUILDING LT Panel ]
4 Core 120 Sq. mm [ LT PANEL TO Feeder pilar box ]
4 core 50 Sq. mm [ LT PANEL TO VTPN ]
Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed.
Laying of one No. cable above 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed.
Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below including finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials 3.5Core 240 Sq. mm
4Core120 Sq. mm
4Core50Sq. mm
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required 80mm dia
100mm dia
SUB HEAD VI--DISTIBUTION WIRING Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [only PVC Rigid Conduit on ceiling and remaining portion concealed] Av run 10mt. E-15, 5(e)
Distribution wiring in 1.1KV grade 2X1.5sq.mm. single core stranded "FR" PVC insulated & unsheathed copper wire (Approved make) in 20mm. Size PVC rigid conduit 'FR' (Precision make), with 1X1.5sq.mm. single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 5A, 3pin flush typr plug socket & piano key switch fixed on MS CRC sheet metal (16SWG) switch board cum JB on wall incl. bakelite top cover 3mm. thick and incl. painting the MS box and mending good the damages to original finish On Board E-15, 4(a)
Separate plug. (Average Run 7.5mt.) E-15, 4(a)
SUB HEAD VII-- PLUGS & SOCKETS S/F of 240V, 3nos. 6A & 1no 20A plug socket with separate 3nos. 6A & 1no. 20A piano key type switch with indicator & 16A kit-kat fuse unit on sheet metal switch board embedded in wall incl. S/F of 240X200X65mm. MS (16SWG) switch board and bakelite top cover of 3mm. thick by brass screw and making necessary connection as required E-7, 25
Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x 100x 65 mm MS (16SWG) switch board and bakelite /erspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/erspex cover and making necessary connections as required E-6 , 22
SUB HEAD VIII---BDB,PDB,VTPN ETC Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall as per GS. 2+10Way[ Legrand ] [ 13 / D- 9 ]
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall as per GS.( Make - Legrand ) 4 Way [ 14 / D- 10 ]
Supplying and fixing double-door VTPN Distribution Board with IP-42/43 protection, on angle iron frame wall as per GS. 4 Way ( Make - Legrand 5077 20 )
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection as perGS [Make-Legrand ] 40 A DP [ 6 / D- 5 ]
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [ Make -Legrand ] 6-32 A SP [ 7 / D- 6]
SUB HEAD IX-- POLY THENE PIPE AND WIRES Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire of the following sizes in the prelaid polythene pipe as per GS. 2x(1.5sqmm)+1x(1.5sqmm) (For Separate plug)) [1(b),E-9 ]
2x(2.5sqmm)+1x(1.5 sqmm) (For Power plug & Computer Plug) [ 1(s) / E-9 ]
2x(6sqmm) +1x (4sqmm) (For TPNDB to SPNDB) [1(iv) / E 9]
4x(16sq.mm.)+2x(10sq.mm.) ( From panel to TPNDB) [NS ]
Cutting Channel of size (31 mm x 31 mm)/(40 mm x 40 mm)/(43 mm x 43 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 13/19/25 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles as per GS. 19 mm dia 3 mm thick [ 6 (a)/ E- 3 ]
25 mm dia 3 mm thick [ 7 (b) / E- 3 ]
SUB HEAD X - SUPPLY OF LIGHT FITTINGS Supply of 4ft LED type single batten with end cap complete with all accessories [Philips make, Cat. No. TMC 501 P1 XT-LED2200 P 3241]. [NS]
S/F of 18W LED T-8 lamp (type - MAS LED tube STD 1200mm 15W840 T8 I) on fittings. N.S.
Supply 9W LED lamp to the lamp point. [PHILIPS make] N.S.
SUB HEAD XI -FIXING OF LIGHT FITTINGS Fixing only single /twin fluorescent light fitting complete with all accessories directly on wall/ceiling/HW round block and suitable size of MS fastener C-2, 14(b)
Fixing only lamp [11/ C-2 ]
SUB HEAD XII -- FIXING OF FANS S/F of 250V, 400W step type (4 step) Electronic fan regulator (Anchor make) on bakelite sheet after cutting the board as per G.S. E6/18a
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc as per GS [ 21 (a) / C-3 ]
Fixing only exhaust fan after making holes in wall as per GS (12") [ 28(b)/C-4 ]
Supply & Fixing louver shutter ( Aluminum)on wall with necy. bolts & nuts (6 mm dia x 62 mm long) as per GS (12") [ 32(a)/D-14 ]
Engraving the deptt. number with 10 mm lettering on the body of fan upto 10 letters incl. hifen, stroke or stop [ 24 (a) / C-3 ]
Extra for additional one letter incl. hifen, stroke and stop as per GS [24 (b) / C-3 ]
Painting upto 10 letters of the engraved number with approved black /red paint as required as per GS [ 26 (a) / C-3 ]
Extra painting for additional one letter of the engraved number as per GS [ 26 (b) / C-3 ]
SUB HEAD XIII -- SUPPLY OF FANS Supply of ceiling fans complete with all accessories having the following Model / Cat No. ( Make -Crompton Greaves ) a. 1200 mm Sweep ( High Speed ) [ NS ]
Supply of Exhaust fans complete with all accessories having the following Model / Cat No. ( Make -EPC ) 12"( 300mm ) Speed 920 RPM
Supply of Air circulator Stand fans complete with all accessories having the following Model / Cat No. ( Make -EPC ) 24" Speed 1420 RPM
S&F 300mmX300mmX100mm sheet metal (2mm thick) box with hinge type glass window door & locking arrangement fixed on wall. Consisting of DIN Rail, 1nos 2A sliding fuse & 1 nos 12 way 10A bakelite connector & necessary connection by suitable size copper wire. The box will be painted as per GS. [NS] For Stand Fan
S&F digital time switch on din rail on existing box incl. necessary connection. L&T make crono time switch [cat no 67DDT0] [NS] For Stand Fan
S&F25A 3pole power contactor on din rail on existing box incl. necessary connection. L&T make MNX 25-2P [cat no CS 90240 [NS] For Stand Fan
Supplying and fixing 240V 32A SP MCB of Breaking capacity 10kA & C characteristics on din rail of existing box and necessary connection L&T make.[N/S] For Stand Fan
SUB HEAD XIV --- COMPOUND LIGHT Supply of 4 Core PVC/XLPE Insulated Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [ Make Polycab / Havells/Gloster/Currency/Mescab] 6 Sq. mm [ NS ]
Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish From 2.5 sqmm to 35 sqmm at an average depth of 75 mm in floor/pavement/wall etc. [5(a)/F-3]
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below.
Upto 6 Sq mm For 4 core [7(a)/F-4]
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials
Upto 6 Sq mm For 4 core [8b/F-5]
S&F 300mmX300mmX100mm sheet metal (2mm thick) box with hinge type glass window door & locking arrangement fixed on wall. Consisting of DIN Rail, 1nos 2A sliding fuse & 1 nos 12 way 10A bakelite connector & necessary connection by suitable size copper wire. The box will be painted as per GS. [NS] COMPOUND LIGHT
S&F digital time switch on din rail on existing box incl. necessary connection. L&T make crono time switch [cat no 67DDT0] [NS]COMPOUND LIGHT
S&F25A 3pole power contactor on din rail on existing box incl. necessary connection. L&T make MNX 25-2P [cat no CS 90240 [NS]COMPOUND LIGHT
Supplying and fixing 240V 32A SP MCB of Breaking capacity 10kA & C characteristics on din rail of existing box and necessary connection L&T make.[N/S]COMPOUND LIGHT
Supplying and Fixing GI water proof looping cable box having hinged GI Top Cover having 4 mm thick with rubber gasket lining, railway type mechanical locking arrangement, earthing terminal with lug etc. of the following sizes as indicated below, Comprising of one 250 V, 15 A Kit-Kat fuse unit, one NL on porcelain insulator etc. and housing the same in pole muffing incl. addition and alteration to the existing CC muffing (6:3:1) after dismantling the damaged looping cable box etc. where necy. incl. painting. ( 250 x 250 x 100mm ) [16(b)/I-2]
Fixing only outdoor / street light type fluorescent light fitting complete with all accessories to be fixed/projected from the wall of the building incl. making holes to building, S&F 40 mm dia GI pipe (ISI-Medium) 1.50 mts. average length, with GI socket at one end and thread at the other end & suitable bend to house the fitting & making necy. connections with S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall and painting[19/C-3]
Supply & delivery of 40 Watt LED STREET Iight fittings with aesthetically designed roadway with execellent thermal management and IP65 protection [ make- Crompton Greaves , cat no- LSTS-40-CDL-M).
Supply & delivery of 90 Watt LED STREET Iight fittings with aesthetically designed roadway with execellent thermal management and IP66 protection [ make- Crompton Greaves , cat no- LSTP-100-CDL-M).
Supplying & fixing earth busbar including Connecting the equipments of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall as per GS [4(a)/G-2 ]
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages
Solid GI wire No 6 S.W.G wire [5(a) ii /G-2 ]
JADOB ELECTRIC CO.
T.D.K. ENTERPRISE
SIKDER ENTERPRISE
M/S N. C. HORE
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .