BID DOCUMENTS FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 100 KVA SILENT DIESEL GENERATOR SET WITH AUTOMATIC CONTROL PANEL INCLUDING ELECTRICAL CONNECTIONS, AND ALL ASSOCIATED WORKS AT CHHAYA BUILDING FOR PORBANDAR MUNICIPAL CORPORATION.
317372
02 of 24 june 2026
Open
Electrical Generators
Works
Porbandar
3 documents required · 3 mandatory
₹1,062
Municipal Commissioner, PORBANDAR MUNICIPAL CORPORATION
₹14,342
25 Jun 2026
25 Jun 2026
25 Jun 2026
9 Jul 2026
25 Jun 2026
Total Amount Rs.
Sr. No. Description Qty Unit Rate Amount
Supplying and erecting, commissioning and testing of Diesel Generating set
confirming to IS: 4722:1968 & BS:5514 having continuous rating, 3 phase,
volts, 50 cycles A.C. supply comprising of a totally enclosed air/water cooled
diesel engine with multi-cylinders developing suitable BHP not less than
following capacity at 1500 RPM with 10% overload for one hour in 24 hours
with standard accessories like fly wheel, lubricating oil cooler, "A" class
governor, heavy duty fuel wheel and lubricating oil filter, oil bath air filler,
lubricating oil pressure gauge, end exhaust manifold, standard set of tools with
adjustable spanners, screw drivers, cylinder head to cover, joint cylinder head to
exhaust, element lube oil filter, 12 / 24 volts electric starting equipment
complete with standard heavy duty battery, dynamo, cut-outs, ammeter,
necessary wiring, pressure gauge, starter etc and heavy duty Residential type
exhaust silencer (With DEF System) and vertical hot air duct both logged with
asbestos rope, save oil trays, exhaust piping of required length, standard
wall/floor mounted fuel with level indicator and piping and drip proof
alternator, self excited, self regulated, screen protected, with excitation system,
capable of delivering the rated system output at 415 volts, 3 phase, 0.8 PF,
Hz, 4 wire, running at 1500 RPM, conforming to IS-4722- 1968 with voltage
regulation +/- 5% of rated voltage from no load to full load. Both the engine
and alternator fitted on a common fabricated steel base plate with antivibration
mounting engine and alternator both connected to each other by flexible
1 flange coupling and with floor/wall mounted control panel box comprising of 1.00 Each 968209.23
voltmeter ammeter, selector switches, ACB / MCCB / MCB of adequate
capacity, indicator lamps duly wired with HRC fuses. The alternator & control
panel shall be connected with provided suitable capacity armoured cable and
complete with Acoustic enclosure (canopy) made out of 16 SWG CRCA Sheet,
sound absorbing material Rockwool of 64 density & 100 mm thick conforming to
IS:8183 / PU Foam of 40 Density - at least 40 mm. The resin bonded rockwool
covered from inside the canopy by perforated sheet with 3/4 mm holes, sound
level not more than 75 dB at a distance of 1 mtr, as per PVCT norms.DG set
should have in built fuel tank capacity of minimum 8 hrs of continous running
capacity on full load . Erection, commissioning and satisfactory testing as per
requirement with first filling of fuel (minimum up to the 80% of fuel tank
capacity), oil, etc. with guarantee / Warrantee of complete system for Two
years. & with obtaining all necessary certificate from Electrical Inspector. The
Capacity and Ratings of DG sets are as below. (As per new CPCB4+ Emission
norms Engine With - Turbo Charger, EGR (Exhaust Gas Recirculation), CRS
(Common Rail Fuel System), DOC (Diesel Oxidation Catalyst), SCR (Selective
Catalytic Reduction), Integrated wiring harness connected to ECU .) (L)
Continuous rating of 100 KVA ,BHP not less than 126 BHP
PORBANDAR MUNICIPAL CORPORATION - PORBANDAR
BID DOCUMENTS FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 100 KVA SILENT DIESEL GENERATOR SET WITH
AUTOMATIC CONTROL PANEL INCLUDING ELECTRICAL CONNECTIONS, AND ALL ASSOCIATED WORKS AT CHHAYA BUILDING FOR PORBANDAR
MUNICIPAL CORPORATION.
Providing & erecting approved make AMF control panel suitable for following
size of 3 phase, 415 V., 50 cycles, A.C. diesel generating set complete of scope
as detailed below:
1) Power module: A pair of electromechanically interlocked contactors (for
mains & generator) Overload relay for generator contactor Neutral contactor
for mains and generator Power socket for connections.
2) Control and metering module: Line voltage monitor. Generator voltage
monitor Ammeter 3 items attempt start facility. Air circuit breakers/MCB/MCCB
of suitable rating for auto/manual operation. Auto/manual switch. Emergency
2 stop push buttons. Manual start push button. frequency meter. Engine hour 1.00 Each 121201.01
meter. Two earthing studs. 3) Protection module: The engine shutdown in the
unlikely event of Low lube oil pressure High cylinder head temperature. V belt
4) Indicators with alarm Load on generator.
5) Indicators Load on mains Engine fails to start . Emergency stop battery
The AMF Panel of following capacity (C) AMF Control Panel for100 KVA/125
KVA3 phase DG Set
Supply, installation, testing and commissioning of 100 KVA, 3-Phase, Oil Cooled
Automatic Servo Voltage Stabilizer suitable for indoor installation, complete
with microprocessor based control system, input MCCB protection, bypass
changeover switch, digital LCD display for input/output voltage and load current
indication, over voltage, under voltage, overload, short circuit and single phasing
protections, AC synchronous stepper motor driven servo mechanism, individual
phase dimmers and buck boost transformers, busbar connection arrangement,
3 shunt trip cut-off facility, earthing bolt, powder coated enclosure conforming to 1.00 unit 210948.60
IS:9815, suitable for input voltage range 330–500 Volt AC and output 415 Volt
AC ±1%, frequency 47–63 Hz, oil cooled with first filling of transformer oil
conforming to IS:335, including all accessories, internal wiring, mounting
arrangement, labour, testing and commissioning, Online Support will be
provided (24 X 7) without any extra cost, complete as directed by the Engineer-
in-Charge. Transportation, loading, unloading, installation, and all incidental
works complete.
Supplying and erecting triple pole & neutral 440V / 500V panel mounting Copper
Busbars with four equal Nos. of electrolyte bus having current density not more
than 1.6 Amp. / sq.mm (Rated current / cross section area) duly wrapped with
colour insulating tape for phase sequence of following current carrying capacity,
erected with necessary bus bar supports /insulators, main cable socket to each
bar, erected in existing cubical panel with necessary connections. (B) Suitable
for 200 Amp. capacity
5 Providing and erecting Annealed bare Copper wire 8 to 16 SWG. 3.00 kg 794.87
Providing and erecting HOT deep Galvanised iron strip wire 8 to 16 SWG.
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand
Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in
existing trench / pipe of following size of cables (E) 3 1/2 core 95 Sq. mm (
Sq. mm 1/2 core)
PORBANDAR MUNICIPAL CORPORATION - PORBANDAR
BID DOCUMENTS FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF 100 KVA SILENT DIESEL GENERATOR SET WITH
AUTOMATIC CONTROL PANEL INCLUDING ELECTRICAL CONNECTIONS, AND ALL ASSOCIATED WORKS AT CHHAYA BUILDING FOR PORBANDAR
MUNICIPAL CORPORATION.
Supplying & erecting in earthpit of minimum bore dia. 225mm size approved
make Safe Earthing Electrode consisting Pipe-in-Pipe Technology as per IS 3043-
1987 made of corrosion free hot dipped G.I.Pipes having Outer pipe dia of
mm having 80-200 Micron galvanising, Inner pipe dia of 40 mm having 200-250
Micron galvanising, connection terminal dia of 14 mm with constant ohmic
value surrounded by highly conductive compound with high charge dissipation
suitable for following type of applications with chamber and heavy duty cover
(A)(approved make OEM has to submit test certificate including value of earth
resistance of installation duly stamped and signed by agency and officer
Incharge has to ensure the value of earthing resistane mentioned in test
Certificate) & having back filling compound of (B) Inner chemical (CCM
Compound)- Resistivity:- 0.2 ohm / meter testing as per IEC 62561-2017,
Voltage drop:- < 1 volt at no load & dry form, Sulphar content:- <2%(C) Back fill
Compound :- Earthing compound should be capable to retain moisture for long
time Necessary test report must be submitted by Agency.
[C] For Electrical Installation covering Transformer Neutrals, Lightning
arrester Earthing, A.C.Plant & Sensitive Computer System(like Automation,
SCADA)i.e. independent Earthing located in other than normal soil i.e. Soft
Rock, Marshy Soil etc..
-Length of Pipe : 3 Mtrs.
-Back filling Compound :2 nos Bags of 25 Kg.
Making trench in soft soil of suitable width of 90 cm deep for laying cable or
9 locating the fault all over the run and back filling the same and making the 40.00 Mtr. 55.55
surface as normal ground.
Providing & laying approved make Double walled corrugated pipes (DWC) of
polyethylene(conforming to IS 14930 II )with necessary connecting accessories
10 of same material at required depth in existing trench for laying of cable. below 40.00 Mtr. 137.36
ground / road surface for enclosing cable (D)120 mm outer dia.
Total Amount Rs.
Total Amount Rs.
Consultant City Engineer
DD(OPC) PVT. LTD. Porbandar Municipal Corporation
Ahmedabad Porbandar
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
01_SBD_DG SET.pdf
02_SCHEDULE B.pdf
03_TECHNICAL SPECIFICATION.pdf
04_DMO 2799 11-Mar-2024 662.pdf
05.00_P-1_GENERAL TECHNICAL SPECIFICATION _ELECTRICAL -1-33.pdf
05.00_P-2_GENERAL TECHNICAL SPECIFICATION _ELECTRICAL -34-63.pdf
06.00_Electrification Specification Work.pdf
06_GOVERNING CONDITION.pdf
07_MAKE LIST.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .