Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.6 LAccepted-AOC | L1 | Accepted-AOC Lowest valid tender | |
| 2 | L2₹9.2 L+₹54,902.50 (6.36%)Rejected-AOC | L2 | Rejected-AOC Second lowest valid tender |
Tender Value
Refer Docs
EMD Value
₹24,981
Closing Date
6 Mar 2025, 6:00 pmClosed
Assistant Executive Engineer
O/o the Assistant Executive Engineer, PWD Electrical Sub Division, Kozhikode
AYURVEDA DISPENSARY BEYPORE-ANNUAL PLAN -2024-25- Balance work for Ayurveda Dispensary Beypore-SL No 1036-Electrification-General Electrical Work
2025_PWD_743580_1
PWD/BLDG/TR/183/2025
Open Tender
Electrical Works
Item Rate
240 days
Kozhikode
Please refer Tender documents.
8 documents required · 8 mandatory
₹2,205
₹24,981
5 Apr 2025
28 Feb 2025
10 Mar 2025
28 Feb 2025
6 Mar 2025
28 Feb 2025
Amount
Electrification
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.11:Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
90.3.21.3:Supply & installation of light fittings on 'C/U' shaped flat iron bracket <br> Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture
OD217743/2024-2025:Supply, installation, testing and commissioning of 1200 lumen round/ square surface mount down light fitting made of diecast aluminium, having efficacy not less than 100l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea directly on ceiling including giving connections with required length of 16/0.20 mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, making good the damages, colour washing etc as required.
OD217742/2024-2025:Supply, installation, testing and commissioning of 1800 lumen round/ square surface mount down light fitting made of diecast aluminium, having efficacy not less than 100l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea directly on ceiling including giving connections with required length of 16/0.20 mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, making good the damages, colour washing etc as required.
OD259123/2024-2025:Supply,installation,testing and commissioning of 1500 lumen round/ square(1X1) recessed fitting made of diecast aluminium, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea pre-wired light fitting of all types complete with all accessories and fluorescent lamps etc. suspended from ceiling using 2 nos steel chain (16 SWG or nearest available size) of length not exceeding 30 cm properly hooked to steel hooks anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.
OD265491/2024-2025:Supply and Installation of LED Well Luminaire having power consumption not more than 25W and light output not less than 4000 Lumens with System efficacy> 150 Lumen/Watt with housing made up of noncorrosive LM6 grade Pressure die cast aluminium body & polycarbonate Diffuser with IP66 and IK10 protection. The Luminaire should be having Minimum 50000 Burning hours(L70B50) with CRI ≥80 and co-related color temperature (CCT) of 5700K.The luminaire must have 4KV surge protection integrated in potted driver with 90% driver efficiency, PF≥0.95, operating voltage range 120-270V with High voltage cutoff@325 ± 15V with Auto restart feature, 440V Phase 2 Phase protection and total harmonic distortion THD≤10% with class B serviceability. Luminaire and driver shall be separately BIS approved of same make equivalent to Philips/Osram/Lighting technologies .
OD265630/2024-2025:Supply, conveyance, installation, testing and commissioning of single head wall light white & silver colour, Metal 100 x 126 x 201 mm size directly on wall/ ceiling including 12W LED bulb and giving connections with required length of 16/0.20 mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring,making good the damages, colour washing etc as required.(Make Philips Model No 31453/Techno commercial equivalent)
OD266661/2024-2025:Supply, conveyance, installation, testing and commissioning of 10W LED 2 way wall washer light and light output not less than 950 Lumens WW, black color (Dimensions 145 x 87 x 43 mm) with IP65 directly on wall including giving connections with required length of 16/0.20 mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, making good the damages, colour washing etc as required. (Make: Phillips Radiant 2 way or Techno commercial equivalent approved by engineer in charge)
OD266953/2024-2025:Supply, conveyance, installation, testing and commissioning of 7W LED mirror light bronze colour( Dimensions 355 x 180 x 95 mm) directly on wall / ceiling including giving connections with required length of 16/0.20 mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, making good the damages, colour washing etc as required. (Philips make Muziris model No. 31402 or Techno commercial equivalent.)
OD217745/2024-2025:Supply and fixing LED bulkhead fitting on wall / ceiling includes giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS. ((Philips make WT140W VistaGlow or Techno commercial equivalent)
OD266037/2024-2025:Supply and fixing pressure die cast housing LED Bulkhead with IP66 protection and IK09 impact resistance suitable for surface and wall mounting applications including giving connection with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS or extending the Original wiring and making good the surface as required. (Philips Endura WT202W LED6s NW/CW PSU S2 PC or Equivalent )
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
1.48:Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
OD265496/2024-2025:Supply, conveyance, installation, testing and commissioning of Metal body Wall mounting fan of 450 mm(18") sweep using mounting brackets supplied along with the fan and giving necessary connections as required.(Make Almonard Tempest Mark- II)
OD259369/2024-2025:Supply, conveyance, installation, testing and commissioning of fans 380 mm, single phase Heavy duty exhaust fan in metal frame in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 24/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS.
OD259371/2024-2025:Supply, conveyance, installation, testing and commissioning of the following sizes of exhaust fans in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS. 300/305 mm sweep Light Duty Exhaust fan in metal frame working on 230 V A/C
OD259370/2024-2025:Supply, conveyance, installation, testing and commissioning of the following sizes of exhaust fans in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS. 250 mm sweep Light Duty Exhaust fan in plastic body with self-opening lowers working on 230V single phase A/C
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
90.4.9:Charges for cutting holes suitable for accommodating exhaust fans above 305mm sweep and up to 450mm sweep including plastering colour washing etc. as required.
1.51:Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes
1.38:Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required.
90.5.1.3:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell
90.5.1.4:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Musical bell with bird sound
1.22.5:Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.180 mm X 100 mm X 60 mm deep
OD264237/2024-2025:SITC of high-quality integrated LED Post top Luminaire having power consumption not more than 25 W and light output not less than 2800 Lumens with a nominal efficiency 115 lumen/watt. The housing should be of non-corrosive ADC12Grade high pressure die-cast to withstand extreme environments and should have corrosion resistant coating to pass Natural salt spray test of 500 Hrs. The Luminaire total dimension must be a minimum of 450mm for larger area coverage. The Luminaire should be having Minimum 50000 Burning hours(L70B50) with CRI ≥70, SDCM< 5 and corelated color temperature (CCT) of 5700K. The Ingress protection should be minimum IP 66 with an IK rating of 10. The LED used in the luminaire shall be SMD type only of make LGIT, Lumileds, Osram, Nichia, and CREE & no other make. The luminaire should be capable of withstanding voltage stress of 440V for 8 Hrs , should have an auto shutdown at 325V and have an auto recovery feature, Under Voltage protection with Input Voltage Stress of 100V for 48 Hrs and EMI/EMC compliant. The Luminaire should have a 10 KV SPD duly bolted in the Luminaire. The SPD should be able to sustain a minimum 15 hits of 10KA rating i.e., Total of 45 hits across all the three modes as per IEEE 62.41.2 The Drivers should be a potted driver not a printed circuit board without casing, mounted inside the luminaire with PF>0.95 and THD<10% Luminaire and driver shall be separately BIS approved (Philips make BGP300 LED 28 757 PSU PC IN S1/Techno- Commercial or Equivalent make)
90.3.17.2:Supply, conveyance and erection of the following sizes of 'B' class GI pipe in single section for post top lantern of all types on concrete base (excluding charges for concrete base and excavation) and painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer etc. as required.40 mm dia GI pipe
OD264246/2024-2025:Supply and fixing Sintex junction box GS-JB- 1414 with provision for fixing SP/DP MCB for terminating street light cable.
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.3:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.28.4:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module
90.10.1.5:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )6 module moulded plastic box on surface
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
90.10.3.15:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator
90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
OD263194/2024-2025:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.9:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
1.14.10:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 10 sq. mm + 2 X 6 sq. mm earth wire
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
90.6.6.1:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.1.50 sq mm
OD264228/2024-2025:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation 40/32mm or nearest size
90.12.7.42:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
90.11.1.11:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
90.11.1.15:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
OD264254/2024-2025:Supplying and fixing 40 amps to 63 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.15.1:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
OD264107/2024-2025:Supplying and fixing following rating, double pole, Centre off MCB Change over in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
OD264108/2024-2025:Supplying and fixing 24Hours Digital Time Switch for operating ON-OFF function in the existing MCB DB/enclosure complete with connections, testing and commissioning etc. as required. (L&T make Digital Time switch 2 module cat no 67DDT0 or Techno Commercial equivalent approved by engineer in charge)
OD266061/2024-2025:Supplying and fixing 25A 2Pole AC-1 contactor complete with connections, testing and commissioning etc. as required. (L&T make AC-1 contactor cat no MNS25,product code CS90240 or Techno Commercial equivalent approved by engineer in charge)
90.16.1.9:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.64 mm GI conductor (12 SWG)
90.16.1.10:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.25 mm GI conductor (10 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD218050/2024-2025:Supply and providing 25x3mm brass nut and bolt etc. as required
OD218049/2024-2025:Supply and providing 25x6mm brass nut and bolt etc. as required
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD218051/2024-2025:Providing and fixing 25 mm X 3 mm G.I. strip earth lead from the test joint to the earth plate
OD218052/2024-2025:Providing and fixing 2 X 25 mm X 3 mm G.I. strip test joint for earthing system
90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class)
90.14.10.3:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
OD266075/2024-2025:Supply and fixing suitable type Spreader/Terminal adapter Kit Extended terminal for 4 pole MCCB of rating upto 250 A (8 pcs)
OD266625/2024-2025:Supply and fixing panel mounted type Earth leakage relay with CBCT and giving connections as required.( Make:L&T /Techno Commercial equivalent)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm
90.6.5.9:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 0.75 sq mm
OD266873/2024-2025:Supply and wiring with ISI marked, FRLS PVC insulated following size single core copper conductor cables for interconnecting the control devices/ equipments including the wiring firm by suitable tie/ tie mounts/ PVC duct etc with sockets as required. 16 sq. mm 4 run
OD266941/2024-2025:Supply and laying of 20mm corrugated flexible PVC conduit with all required accessories as required.
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
OD266708/2024-2025:supply and fixing LED indicators for all voltage ranges - Blue Colour
OD266709/2024-2025:supply and fixing LED indicators for all voltage ranges - Red, Green, Black, Yellow or Orange Colour
OD266710/2024-2025:Supplying and fixing 2 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
OD264010/2024-2025:Supply and fixing 63A, 415 V, 2 way neutral link mounted on DMC/ SMC base in the existing meter board and giving connections etc.
OD264011/2024-2025:Supply and fixing 63A Fuse base with HRC fuse link in the existing meter board and giving connections etc.
OD264009/2024-2025:Supply and providing suitable Iron Hook grouted on wall for binding the service wire
OD266076/2024-2025:Supply and Installation of ABC type Fire extinguisher of 5Kg.capacity with stored pressure type complete with installation brackets with ISI mark IS:15638
OD266077/2024-2025:Painting letters or figures with enamel paint as identification mark to SB, DB, panel board etc as required
OD266078/2024-2025:Supply and fixing Danger notice board of size, 125 x 75 mm
OD266678/2024-2025:Supply and fixing 50mm dia 6Kgf/cm2 PVC pipe including fixing the pipe at 60cm spacing. etc on wall with all required accessories and clamps etc. including cutting and making good the walls, painting the exposed portions etc. as required. (KSEB Service pipe)
OD267506/2024-2025:Supply,installation,testing and commissioning of 2KVA UPS single phase in and out with pf>=0.95 pure sine wave with automatic /manual bypass IGBT rectifier and inverter with battery over/under charge cutoff with Exide/equivalent battery of 2 hr backup.Numeric/Hycon/V Guard
OD267803/2024-2025:Supply, conveyance, installation, testing and commissioning of 10Ltr, 240V, 50Hz, vertical storage water heater 5 star rated in the position by suitable size nut and bolts as required. ( Racold CDR Dlx/ Venus/Havells or equivalent make )
OD270462/2024-2025:Din Rail (4+0) Surge Protection Device Class B+C/ Type 1+2 Tested as per IEC 61643 Part 11:2016 . Total Impulse current-10 KA (10/350&micro; sec) Total Max Discharge current 200 KA (8/20&micro; sec), Voltage protection level &lt;1.5 kV . The Surge Protection Devices should have TOV safefail for 120 Min : 442 V . Protective Elements are MOV &amp; GDT &amp; the Protection Modes for : L &amp; N to PE . Short- Circuit Current rating (Isccr) ? 25kA/50 kA Back up fuse required more than 200AgG/gL. Health Status Indication required in all cartridge. Total Response time &lt;25 nano sec . Make : Raycap / Erico / Weidmuller
MOHANAN T (BID ID -2131587)
Bidder Name
RAMAKRISHNAN A P
MOHANAN T
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1199187.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .