Loading…
Loading…
Tender ID
Tender Value
₹83.6 Cr
EMD Value
₹3.0 Cr
Closing Date
22 Apr 2026, 6:00 pmClosed
The Registrar, Gujarat Biotechnology University, Giftcity, Gandhinagar
Construction of InCITE Building at Gujarat Biotechnology University
292023
2025-26/InCITE BUILDING
Open
Civil - All
Works
Gandhinagar
2 documents required · 2 mandatory
₹17,700
The Registrar, Gujarat Biotechnology University
₹3.0 Cr
1 Apr 2026
1 Apr 2026
1 Apr 2026
22 Apr 2026
1 Apr 2026
BILL OF QUANTITIES
Construction of Incite Building - Package C at GBU Gandhinagar Gujrat
Suresh Goel & Associates
C-85, Shivalik,
Abstract of Cost
GBU Gujrat - BOQ for Construction of Incite Building - Package C
Sl. No.Description Total Amount
Sl. No.Description Total Amount
2 Concrete Work
6 Wood Work & PVC Work
11 Aluminium Work
12 Waterproofing
13 Ext development
14 Plumbing Work
15 Fire Fighting Work
16 Electrical Work
18 Integrate BMS
Total (Excluding GST But including
Bill Of Quantities
GBU Gujrat - BOQ for Construction of Incite Building - Package C
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Sub- Head - I , Earth Work
Clearing and grubbing road including uprooting rank vegetation grass
bushes, shrubs , sapling and trees girth upto 300mm removal stumps of
trees cut earlier and disposal of unserviceable (D) By mechanical means
in area of thorny jungle.
Excavation for foundation upto 1.5m depth including sorting out and
stacking of useful materials , back filling in sides of sides of foundations
2 etc. in layers not exceeding 20cm .in depth consolidating each deposited 7153.00 cum 174.00 1.74 175.74
layer by ramming and watering etc and disposing off the excavated stuff
upto any lead and lift. Dense or hard soft soil
Excavation for foundation for a depth from 1.5m to 3.0m depth including
sorting out and stacking of useful materials back filling in sides of sides
of foundations etc. in layers not exceeding 20cm .in depth consolidating
3 each deposited layer by ramming and watering etc and disposing off the 6458.00 cum 186.58 1.87 188.45
excavated stuff upto any lead . (D)Dense or hard soft soil . Quantity for
excavation shall be paid based on actual dimensions in the drawings
Excavation for foundation for a depth from 3.0m to 5.0m depth including
sorting out and stacking of useful materials back filling in sides of sides
of foundations etc. in layers not exceeding 20cm .in depth consolidating
4 each deposited layer by ramming and watering etc and disposing off the 7977.00 cum 198.31 1.98 200.29
excavated stuff upto any lead . (D)Dense or hard soft soil . Quantity for
excavation shall be paid based on actual dimensions in the drawings
Excavation for foundation for a depth from 5.0 m to 6.0m depth including
sorting out and stacking of useful materials back filling in sides of sides
of foundations etc. in layers not exceeding 20cm .in depth consolidating
5 each deposited layer by ramming and watering etc and disposing off the 347.00 cum 219.21 2.19 221.40
excavated stuff upto any lead . (D)Dense or hard soft soil . Quantity for
excavation shall be paid based on actual dimensions in the drawings
Filling in plinth with (good quality) sand under floors including watering,
ramming, consolidating and dressing etc. complete.
Carring out plinth treatment to post construction / during construction by
spraying chemical solution for termite control treatment including labour
and material consistment with I.S.I specification. Using Chlordene and
Chiorpurfiles 20 EC. As Per 6131_paret-II Concentration Weight one
7 percent is recommended i.e one litre 20EC chemical emulsion with 19 liter 5430.88 sqm 104.90 1.05 105.95
give 1% concentration inclusive of one litre chemical emulsion appication
at the rate of 5Litre chemical / Sqm of surface is recommended as per I.S.
Plinth area only shall be measured for payment purpose.
TOTAL 0.00 0.00
Sub - Head - II , Concrete Work 0.00
Providing & laying cement concrete 1:3:6 (1: cement: 3 coarse sand:
machine crust stone aggregates 40 mm nominal size) for all depths below
8 and up to plinth level in foundations and curing etc. complete including 64.00 cum 3084.72 30.85 3115.57
cost of formwork in Footings & Ground, Plinth Beams & below Floors
Providing and laying cement concrete 1:4:8 (1- Cement : 4- coarsesand : 8-
hand broken stone aggregates 40 mm nominal size) and curing complete
including cost of formwork in (A) Foundation and Plinth
Providing and laying cement concrete 1:2:4 (1-Cement : 2- Coarse sand :4-
10 graded stoneaggregates 20 mm nominal size) and curing complete 16.00 cum 3661.30 36.61 3697.91
excluding cost of formwork in (A) Foundation and Plinth
Providing and laying damp proof course 100 mm thick cement concrete
1:2:4 (1- Cement: 2coarse sand: 4stone aggregate 10 mm nominal size)
11 and curing complete including providing and mixing water proofing 60.00 sqm 1249.77 12.50 1262.27
material in cement concrete in mix proportion recommended by the
Providing and filling in Aereated block bats (broken pieces ) in single or
multiple layers in super structure , filling the joints with sand mortar ( not
more than 20%)20mm thick cement sand mortar screed in proportion of
1:6 shall be laid asper drawing. Crushing strength of aerated concrete
block /bats shall not be less than 40 kg/sqcm, minimum density in dry oven
12 condition between 651 to 750 kg /cum, thermal conductivity shall not 88.00 cum 1675.00 16.75 1691.75
exceed 0.3W / mk, fire resistance 4 hours , in line and plumb , cleaning
the surface with tools and tackles , at all level, all height , all floors
including curing , scaffolding , complete as per specifications , drawings
and directed by engineer in charge.
Making plinth protection 50mm thick of cement concrete 1:3:6 (
1cement:3 coarse sand:6 graded stone aggregate 20mm nominal size
over 75mm thick bed of dry brick ballast 40mm nominal size , well
rammed and consolidated and grouted with fine sand , including
necessary excavation, levelling and dressing & finishing the top smooth,
including toe wall 230mm wide and 450mm deep on the edge to plinth
protection with common burnt clay bricks including grouted with cement
mortar 1:4 (1cement:4 fine sand)
Sub - Head - III , RCC Work
Providing TMT Bar FE 500D reinforcement for RCC work including
bending, binding with G.I Binding wire and placing in position complete at
all heights, all lifts and all levels as shown in the drawing
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 410 kg ) for
Footing/Raft /grade slab upto plinth.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 410 kg ) for
Beam upto Plinth.
Providing and laying in position machine batched and machine mixed
design mix M-450grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 480 kg ) for
Columns, pillars Post Struts upto Plinth.
Providing and laying in position machine batched and machine mixed
design mix M-450grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 480 kg ) for
Shear wall upto Plinth.
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 440 kg ) for
basement Wall upto Plinth.
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering
20 shuttering(height upto 4.2M) finishing and excluding reinforcement 531.04 cum 6379.25 63.79 6443.04
including cost of admixtures in recommended proportions as per IS:
to accelerate/ retard setting of concrete, improve workability without
impairing strength and durability as per direction of the Engineer - in -
charge. Without Fly Ash (Min cement level as per latest IS 456 shall be
maintained) (Cement level 410 kg ) for Slab /Shelves/ landing balconies,
access platform , staircase at Basement Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant including the cost of centering shuttering (height
upto 4.2M) finishing and excluding reinforcement including cost of
21 admixtures in recommended proportions as per IS: 9103 to accelerate/ 328.98 cum 6951.41 69.51 7020.92
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for beams/Cantilevers Girders Bressumers at Ground
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
22 (height upto 4.2M) finishing and excluding reinforcement including cost of 322.90 cum 6986.17 69.86 7056.03
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for beams/Cantilevers Girders Bressumers at First Floor
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
23 (height upto 4.2M) finishing and excluding reinforcement including cost of 322.90 cum 7021.10 70.21 7091.31
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for beams/Cantilevers Girders Bressumers at Second
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
24 (height upto 4.2M) finishing and excluding reinforcement including cost of 322.90 cum 7056.21 70.56 7126.77
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for beams/Cantilevers Girders Bressumers at Third Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
25 (height upto 4.2M) finishing and excluding reinforcement including cost of 322.90 cum 7091.49 70.91 7162.40
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for beams/Cantilevers Girders Bressumers at Fourth
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
26 (height upto 4.2M) , finishing and excluding reinforcement including cost 163.35 cum 7126.94 71.27 7198.21
of admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410kg ) for beams/Cantilevers Girders Bressumers at Fifth Floor
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
27 (height upto 4.2M) finishing and excluding reinforcement including cost of 163.35 cum 7162.58 71.63 7234.21
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for beams/Cantilevers Girders Bressumers at Sixth Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
28 (height upto 4.2M) finishing and excluding reinforcement including cost of 163.35 cum 7198.39 71.98 7270.37
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for beams/Cantilevers Girders Bressumers at seventh
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
29 (height upto 4.2M)finishing and excluding reinforcement including cost of 163.35 cum 7234.38 72.34 7306.72
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 475 kg ) for beams/Cantilevers Girders Bressumers at Eightth
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
30 (height upto 4.2M) finishing and excluding reinforcement including cost of 163.35 cum 7270.56 72.71 7343.27
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for beams/Cantilevers Girders Bressumers at Ninth Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering
31 shuttering(height upto 4.2M) finishing and excluding reinforcement 135.30 cum 7306.91 73.07 7379.98
including cost of admixtures in recommended proportions as per IS:
to accelerate/ retard setting of concrete, improve workability without
impairing strength and durability as per direction of the Engineer - in -
charge. Without Fly Ash (Min cement level as per latest IS 456 shall be
maintained) (Cement level 410 kg ) for beams/Cantilevers Girders
Bressumers at Terrace Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering
shuttering(height upto 4.2M) finishing and excluding reinforcement
including cost of admixtures in recommended proportions as per IS:
to accelerate/ retard setting of concrete, improve workability without
impairing strength and durability as per direction of the Engineer - in -
charge. Without Fly Ash (Min cement level as per latest IS 456 shall be
maintained) (Cement level 410 kg ) for Sill/ Lintels for all Floors.
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering
shuttering(height upto 4.2M) finishing and excluding reinforcement
including cost of admixtures in recommended proportions as per IS:
to accelerate/ retard setting of concrete, improve workability without
impairing strength and durability as per direction of the Engineer - in -
charge. Without Fly Ash (Min cement level as per latest IS 456 shall be
maintained) (Cement level 410 kg ) for RCC Band for all Floors.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and laying in position machine batched and machine mixed
design mix M-450 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 480kg ) for
Columns, pillars Post Struts at Ground Floor
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and laying in position machine batched and machine mixed
design mix M-450 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 480kg ) for
Columns, pillars Post Struts at First Floor
Providing and laying in position machine batched and machine mixed
design mix M-450 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 480kg ) for
Columns, pillars Post Struts at Second Floor
Providing and laying in position machine batched and machine mixed
design mix M-450 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 480kg ) for
Columns, pillars Post Struts at Third Floor
Providing and laying in position machine batched and machine mixed
design mix M-450 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 480kg ) for
Columns, pillars Post Struts at Fourth Floor
Providing and laying in position machine batched and machine mixed
design mix M- 400 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 460 kg ) for
Columns, pillars Post Struts at Fifth Floor
Providing and laying in position machine batched and machine mixed
design mix M-400 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 460 kg ) for
Columns, pillars Post Struts at Sixth Floor
Providing and laying in position machine batched and machine mixed
design mix M-400 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 460 kg ) for
Columns, pillars Post Struts at Seventh Floor
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and laying in position machine batched and machine mixed
design mix M-400 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 460kg ) for
Columns, pillars Post Struts at Eightth Floor
Providing and laying in position machine batched and machine mixed
design mix M-400 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 460 kg ) for
Columns, pillars Post Struts at Ninth Floor
Providing and laying in position machine batched and machine mixed
design mix M-400grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 460kg ) for
Columns, pillars Post Struts at Terrace Floor
Providing and laying in position machine batched and machine mixed
design mix M-450 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 480kg ) for
Wall / shear wall Ground Floor
Providing and laying in position machine batched and machine mixed
design mix M-450grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 480kg ) for
Wall / shear wall First Floor
Providing and laying in position machine batched and machine mixed
design mix M-450 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 480kg ) for
Wall / shear wall Second Floor
Providing and laying in position machine batched and machine mixed
design mix M-450 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 480kg ) for
Wall / shear wall Third Floor
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and laying in position machine batched and machine mixed
design mix M-450 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 480kg ) for
Wall / shear wall Fourth Floor
Providing and laying in position machine batched and machine mixed
design mix M-400 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 460kg ) for
Wall / shear wall Fifth Floor
Providing and laying in position machine batched and machine mixed
design mix M-400 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 460kg ) for
Wall / shear wall Sixth Floor
Providing and laying in position machine batched and machine mixed
design mix M-400 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 460kg ) for
Wall / shear wall Seventh Floor
Providing and laying in position machine batched and machine mixed
design mix M-400 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 460kg )for
Wall / shear wall Eightth Floor
Providing and laying in position machine batched and machine mixed
design mix M-400 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 460kg )for
Wall / shear wall Ninth Floor
Providing and laying in position machine batched and machine mixed
design mix M-400 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
finishing and excluding reinforcement including cost of admixtures in
recommended proportions as per IS: 9103 to accelerate/ retard setting of
concrete, improve workability without impairing strength and durability as
per direction of the Engineer - in - charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be maintained) (Cement level 460kg ) for
Wall / shear wall Terrace Floor
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering
54 shuttering(height upto 4.2M) finishing and excluding reinforcement 458.48 cum 6379.25 63.79 6443.04
including cost of admixtures in recommended proportions as per IS:
to accelerate/ retard setting of concrete, improve workability without
impairing strength and durability as per direction of the Engineer - in -
charge. Without Fly Ash (Min cement level as per latest IS 456 shall be
maintained) (Cement level 410 kg ) for Slab /Shelves/ landing balconies,
access platform , staircase at Ground Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering
55 shuttering(height upto 4.2M) finishing and excluding reinforcement 408.08 cum 6411.15 64.11 6475.26
including cost of admixtures in recommended proportions as per IS:
to accelerate/ retard setting of concrete, improve workability without
impairing strength and durability as per direction of the Engineer - in -
charge. Without Fly Ash (Min cement level as per latest IS 456 shall be
maintained) (Cement level 410 kg ) for Slab /Shelves/ landing balconies,
access platform , staircase at First Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
56 (height upto 4.2M) finishing and excluding reinforcement including cost of 414.33 cum 6443.20 64.43 6507.63
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for Slab /Shelves/ landing balconies, access platform
staircase at Second Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
57 (height upto 4.2M) finishing and excluding reinforcement including cost of 409.33 cum 6475.42 64.75 6540.17
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for Slab /Shelves/ landing balconies, access platform
staircase at Third Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
58 (height upto 4.2M) finishing and excluding reinforcement including cost of 409.33 cum 6507.80 65.08 6572.88
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for Slab /Shelves/ landing balconies, access platform
staircase at Fourth Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
59 (height upto 4.2M) finishing and excluding reinforcement including cost of 202.25 cum 6540.33 65.40 6605.73
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for Slab /Shelves/ landing balconies, access platform
staircase at Fifth Floor
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
60 (height upto 4.2M) finishing and excluding reinforcement including cost of 202.25 cum 6573.04 65.73 6638.77
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for Slab /Shelves/ landing balconies, access platform
staircase at Sixth Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
61 (height upto 4.2M) finishing and excluding reinforcement including cost of 202.25 cum 6605.90 66.06 6671.96
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for Slab /Shelves/ landing balconies, access platform
staircase at Seventh Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
62 (height upto 4.2M) finishing and excluding reinforcement including cost of 202.25 cum 6638.93 66.39 6705.32
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for Slab /Shelves/ landing balconies, access platform
staircase at Eightth Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
63 (height upto 4.2M) finishing and excluding reinforcement including cost of 202.25 cum 6672.13 66.72 6738.85
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for Slab /Shelves/ landing balconies, access platform
staircase at Ninth Floor
Providing and laying in position machine batched and machine mixed
design mix M-300 grade concrete for reinforced cement conctere work
using cement content as per approved Design Mix manufactured in fully
automatic batching plant and transported to site of work in transit mixer
for any lead having continuous agitated mixer , manufactured as per mix
design of specified grade for RCC work including pumping of RMC from
transit mixer to site of laying including the cost of centering shuttering
64 (height upto 4.2M) finishing and excluding reinforcement including cost of 120.68 cum 6705.49 67.05 6772.54
admixtures in recommended proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve workability without impairing strength
and durability as per direction of the Engineer - in - charge. Without Fly
Ash (Min cement level as per latest IS 456 shall be maintained) (Cement
level 410 kg ) for Slab /Shelves/ landing balconies, access platform
staircase at Terrace Floor
Extra for Additional height of proping and centering where the height of
65 propping and centering exceeds 4.2 m between supporting floor to ceilling 3338.00 sqm 573.30 5.73 579.03
Providing and fixing in position Stainless steel Grade 304 plate-1.0 mm
thick as per design for expansion joints.
Providing and fixing of expansion joint system related with floor
location as per drawings and direction of Engineer-In-Charge. The joints
system will be of extruded aluminum base members, self aligning / self
centering arrangement and support plates etc. as per ASTM B221-02. The
system shall be such that it provides floor to floor /floor to wall expansion
control system for various vertical localtion in load application areas that
accommodates multi directional seismic movement without stress to it’s
67 components. System shall consist of metal profiles with a universal
aluminum base member designed to accommodate various project
conditions and finish floor treatments. The cover plate shall be designed of
width and thickness required to satisfy projects movement and loading
requirements and secured to base members by utilizing manufacturer’s
pre-engineered self-centering arrangement that freely rotates / moves in
all directions.
The Self – centering arrangement shall exhibit circular sphere ends that
lock and slide inside the corresponding aluminum extrusion cavity to allow
freedom of movement and flexure in all directions including vertical
displacement. Provision of Moisture Barrier Membrane in the Joint System
to have watertight joint is mandatory requirement all as per the
manufactures design and as approved by Engineer -in- Charge . (Material
shall confirm to ASTM 6063.)
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Floor Joint of 100 mm gap 244.00 metre 5364.00 53.64 5417.64
Providing and fixing of expansion joint system related with wall joint
(internal/ external) location as per drawings and direction of Engineer-In-
Charge.The joints shall be of extruded aluminum base members, self
aligning / centering arrangement and support plates as per ASTM B221-
02. The material shall be such that it provides an Expansion Joints System
suitable for vertical wall to wall/ wall to corner application, both new and
existing construction in office Buildings & complexes with no slipping down
tendency amongst the components of the Joint System. The Joint System
shall utilize light weight aluminum profiles exhibiting minimal exposed
aluminum surfaces mechanically snap locking the multicellular to facilitate
movement.(Material shall confirm to ASTM 6063.)
Wall Joint of 100 mm gap 372.00 metre 4452.00 44.52 4496.52
Providing and fixing of expansion joint system of approved make and
manufactures for various roof locations as per approved drawings and
direction of Engineer-In-Charge. The joints shall be of extruded aluminum
base members with, self aligning and self centering arragement support
plates asper ASTM B221-02. The system shall be such that it provides
watertight roof to roof/roof to corner joint cover expansion control system
that is capable of accommodating multidirectional seismic movement
69 without stress to its components. System shall consist of metal profile that
incorporates a universal aluminum base member designed to
accommodate various project conditions and roof treatments. The cover
plate shall be designed of width and thickness required to satisfy
movement and loading requirements and secured to base members by
utilizing manufacturer’s pre-engineered self-centering arrangement that
freely rotates / moves in all directions.
The Self centering arrangement shall exhibit circular sphere ends that lock
and slide inside the corresponding aluminum extrusion cavity to allow
freedom of movement and flexure in all directions including vertical
displacement. The Joint System shall resists damage or deterioration from
the impact of falling ice, exposure to UV, airborne contaminants and
occasional foot traffic from maintenance personnel. Provision of Moisture
Barrier Membrane in the Joint System to have water tight joint is
mandatory requirement.Material shall confirm to ASTM
Roof Joint of 100 mm gap 22.00 metre 5022.00 50.22 5072.22
Constructing cast-in situ RCC diaphragm wall by providing and laying
machine batched, machine mixed, self compacting, ready mix reinforced
cement concrete, tramie controlled, of M 30 grade using minimum 400 kg.
cement per cum of concrete including providing and mixing required
admixtures in recommended proportions as per IS : 9103, as approved by
the Engineer-in-charge, for achieving 150- 200mm slump, for diaphragm
wall having thickness as per approved structural design not exceeding
mm, in pannels of required depth and lengths as per approved drawing,
including constructing necessary guide walls as required and as specified
including boring in all kinds of soils and rocks,including working in or
under water and / or liquid mud, in foul conditions and pumping or bailing
out of water and removing slush, including disposal of earth/ rock / slush
etc. for all leads and all lifts, including preparing,providing and re-
70 circulating bentonite slurry in the trench as and when required for all 207.00 cum 17168.00 171.68 17339.68
depths, including agitating bentonite slurry during trenching etc., providing
and fixing stop ends or form tubes, upto the required depth of diaphragm
wall including extracting the same after casting,including chipping off the
bentonite adulterated concrete or unsound concrete up to the cut off level
for obtaining the sound concrete, dressing undulations on the exposed
face of diaphragm wall after excavation by chipping / chiseling etc.
including filling the depression/ cavities with sound concrete etc. complete
and as directed by the Engineer-in-charge, including providing recess for
bearing plates and fixing insert boxes for inclined rock anchors etc.
complete as per the specifications and approved design and as directed
by the Engineer-in-charge, but excluding the cost of reinforcement and
Sub- Head IV - Brick Work
Brick work using common burnt clay building bricks having minimum
71 crushing strength not less than 35 kg/ sq cm in foundation and plinth in 135.00 cum 3981.21 39.81 4021.02
cement mortar 1 : 6 (1 cement : 6 fine sand)
Masonary work using Aerated light weight concrete block having crushing
strength not less than 35 kg/sqcm for super structure above plinth level
72 laid with approved block laying polymer modified adhesive mortar all 701.94 cum 4483.73 44.84 4528.57
complete as per direction of engineer in charge and Technical
Specification . Ground Floor
Masonary work using Aerated light weight concrete block having crushing
strength not less than 35 kg/sqcm for super structure above plinth level
73 laid with approved block laying polymer modified adhesive mortar all 586.94 cum 4528.57 45.29 4573.86
complete as per direction of engineer in charge and Technical
Specification. 1st Floor
Masonary work using Aerated light weight concrete block having crushing
strength not less than 35 kg/sqcm for super structure above plinth level
74 laid with approved block laying polymer modified adhesive mortar all 586.94 cum 4573.85 45.74 4619.59
complete as per direction of engineer in charge and Technical
Specification. 2nd Floor
Masonary work using Aerated light weight concrete block having crushing
strength not less than 35 kg/sqcm for super structure above plinth level
75 laid with approved block laying polymer modified adhesive mortar all 586.94 cum 4619.59 46.20 4665.79
complete as per direction of engineer in charge and Technical
Specification. 3rd Floor
Masonary work using Aerated light weight concrete block having crushing
strength not less than 35 kg/sqcm for super structure above plinth level
76 laid with approved block laying polymer modified adhesive mortar all 586.94 cum 4665.79 46.66 4712.45
complete as per direction of engineer in charge and Technical
Specification. 4th Floor
Masonary work using Aerated light weight concrete block having crushing
strength not less than 35 kg/sqcm for super structure above plinth level
77 laid with approved block laying polymer modified adhesive mortar all 324.63 cum 4712.45 47.12 4759.57
complete as per direction of engineer in charge and Technical
Specification. 5th Floor
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Masonary work using Aerated light weight concrete block having crushing
strength not less than 35 kg/sqcm for super structure above plinth level
78 laid with approved block laying polymer modified adhesive mortar all 324.63 cum 4759.57 47.60 4807.17
complete as per direction of engineer in charge and Technical
Specification. 6th Floor
Masonary work using Aerated light weight concrete block having crushing
strength not less than 35 kg/sqcm for super structure above plinth level
79 laid with approved block laying polymer modified adhesive mortar all 324.63 cum 4807.17 48.07 4855.24
complete as per direction of engineer in charge and Technical
Specification. 7th Floor
Masonary work using Aerated light weight concrete block having crushing
strength not less than 35 kg/sqcm for super structure above plinth level
80 laid with approved block laying polymer modified adhesive mortar all 324.63 cum 4855.24 48.55 4903.79
complete as per direction of engineer in charge and Technical
Specification. 8th Floor
Masonary work using Aerated light weight concrete block having crushing
strength not less than 35 kg/sqcm for super structure above plinth level
81 laid with approved block laying polymer modified adhesive mortar all 324.63 cum 4903.79 49.04 4952.83
complete as per direction of engineer in charge and Technical
Specification. 9th Floor
Masonary work using Aerated light weight concrete block having crushing
strength not less than 35 kg/sqcm for super structure above plinth level
82 laid with approved block laying polymer modified adhesive mortar all 25.60 cum 4952.83 49.53 5002.36
complete as per direction of engineer in charge and Technical
Specification. Terrace
Provinding and fixing chicken wire mesh of gauge 0.18mm and 200 mm
wide with necessary screws and nail at joints cracks of brick work R.C.C
work as per drawing and specification and direction of Engineer incharge.
TOTAL 0.00 0.00
Sub Head - V Marble/stone Work 0.00
Providing and fixing 18mm thick gang saw cut mirror polished
premoulded and prepolished) Granite of any colour and shade as per
selection of client for wall lining (veneer work), /bands 200mm wide
backing filled with a grout of average 12 mm thick in polymer modified
adhesive mortar including secured to the backing by means of cramps,
hold fastners ,copper pins 7.5 cm long 6 mm diameter for securing
adjacent stones in stone wall lining in adhesive mortar including making
the necessary chases complete in all respect.
Providing and fixing 18mm thick gang saw cut mirror polished premoulded
and prepolished) machine cut Granite of any colour and shade as per
selection of client for kitchen platforms, vanity counters, window sills
facias and similar locations of required size of approved shade, colour and
texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse
sand) with joints treated with white cement, mixed with matching pigment,
epoxy touch ups, including rubbing, curing, moulding and polishing to
edges to give high gloss finish, providing opening of required size & shape
for wash basin/sink etc. complete at all levels.
Design, Supply & Fixing Marble stone sculptures with Size 6ft x 3.5ft x 2ft .
Providing & making individual pieces using laser cutting machine desired shape
and profile. All components of origami figure to be developed in 3d model hollow
from inside, thenlaser cut with proper dimensions and edges. Smoothening by
using machine and tools to get edge finish. using necessary tools and machinery
to get even and mirror like finishing in all respects. Designing, making and
86 approval of shop drawings of the entire ser good to be fabricated and assembled 1 each 349612.00 3496.12 353108.12
at site. Providing and finishing the sculptural Marble stones with mirror finish and
balanced flat surface to be kept at the site..Hardware items and Footing
Arrangement with plinth top Granite Finishing required in proper fixing of the mural
as per direction of Engineer-in-charge
87 Item Deleted 0.00
TOTAL 0.00 0.00
Sub- Head - VI Wood Work & PVC Work 0.00
Flush Door (Laminated ) Providing and fixing of 35mm solid cored flush
door with 1mm thick laminate in approved shade as per selection on
both side as shown in the drg. All exposed edges covered with wooden
liping of min 4mm th duly painted and finished matching shade of
laminate. Rate shall Include Frame of WPC 100x50 mm size comprising of
virgin PVC polymer of K value 58- 60 (Suspension Grade), , SS Handle,
Lock , Door Stopper, Door Closer, S.S. heavy duty hinges etc. all
materials and labour etc. complete as per detail drawing and instruction of
engineer‐in charge and consultant.
Flush Door (Laminated ) Providing and fixing of 35mm solid cored flush
door with 1mm thick laminate in approved shade as per selection on
both side as shown in the drg. All exposed edges covered with wooden
liping of min 4mm th duly painted and finished matching shade of
laminate. Rate shall Include SS Handle, Lock , Door Stopper, Door
Closer, S.S. heavy duty hinges etc. all materials and labour etc. complete
as per detail drawing and instruction of engineer‐in charge and consultant.
Providing and fixing M.S. grill of required pattern of windows etc. with
M.S.. flats at required spacing and frame alround square or round headed
90 bolts and nuts or by screws.including applying a priming coat of red lead 24949.00 kg 100.17 1.00 101.17
paint and two coats of oil painting etc complete (A) Plain grill
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Restroom Cubical: providing and installing premium Series Restroom
Cubicles with all necessary tools hardware, labour, as per the company
specs.Providing & Fixing Cubicle partition system for toilet by using
following Materials 12mm thick compact laminate with core of phenol resin
treat papers with black color top layer treated with special melamine resin.
Adjustable legs with bottom cap of SS 316, door lock with, gravity hinges
with cover – combination of mild steel and Nylon PA6And used following
Accessories Accessories Include: 1. AlumuniumTop Rail (Stainless Steel
Grade 304 with Satin Finish)2. SS Coat Hook with Door Stopper Option
(Stainless Steel Grade 304 with Satin Finish)3. SS Gravity Hinges
(Stainless Steel Grade 304 with Satin Finish)4. SS Latch cum Occupancy
Indicator (Stainless Steel Grade 304 with Satin Finish)5. SS “U” Channel
(Stainless Steel Grade 304 with Satin Finish)6. SS “F” Channel (Stainless
Steel Grade 304 with Satin Finish)7. SS Palm Design Adjustable Foot
(Stainless Steel Grade 304 with Satin Finish)8. SS Screws &
Inserts(Stainless Steel Grade 304 with Satin Finish) 9.Rubber Lining for
Door Stopper Brand.
Providing and fixing Hollow metal fire rated doors shutter with frame and
hardware fittings etc complete as per specifications.Door frame shall be
double rebate profile of minimum size 154mm X 77 mm made out of
1.60mm minimum thick galvanized steel sheet. The frames should be
finished with Thermosetting Powder Coating in desired RAL Shade. All
provision should be mortised, drilled and tapped for receiving appropriate
hardware. Frames should be provided with back plate bracket and anchor
fasteners for installation on a finished plastered masonry wall opening.
Door leaf shall be minimum 49mm thick fully flush double skin door with or
without vision lite. All doors NSD 12049 shall be factory prepped for
receiving appropriate hardware and provided with necessary
reinforcement for hinges, locks, and door closers. For pair of doors
astragals has to be provided on the meeting stile for both active and
Providing and fixixng of 6mm thick decorative compact HPL laminate as
per EN 438-6Type EDS ( Exterior Durable Standard)/ EGS(External
General Standard) external wall clading using specially treated acrylic
resins under high pressure and temperature and hardened into sheets,
93 thus providing all weather protection and UV resistance on an aluminium 590.00 sqm 4646.00 46.46 4692.46
powder coated sub structure of aluminium cube chanel having thickness
50x25x1.6mm at corner and 75x25x1.6mm at junction of two panels
complete as per manufacturers specifications and direction of engineer in
Providing and fixing of approximately 8.0mm thick Laminated wooden
flooring, classification of use 31/23 with a surface abrasion resistance of
class AC3 (average 3800 cycles), impact resistance of 7.7 mm,resistance
to cigarette burn with a rating of 4(EN 438-2:05), swelling after 24 hrs in
water of 8.22%, Modulus of rupture of 53.3 newton/mm2, Internal bond
1.78 newton/mm2, surface soundness 2.62 newton/mm2(EN 13329:2000)
with a 0.2 mm thick wear layer on top of a High Density Fiber substrate
core (density ~ 948.3 Kgs/M3) of plank size 1285/1215 mm X 191/192 mm
having locking arrangement (lock strength > 670 lbs/ft) with an
underlayment made of natural colour foam , with accessories like End
profile, Transition profile, reducer, Stair nosing etc. complete.
Providing and fixing GI Gyp steel ultra frame work for wall panelling as
per design drawing consisting of floor channel of size 50x32x32 x0.5mm
thick at bottom and top fixed with 35 mm nylon sleeves and 35 mm screw.
Further fixing GI stud 48x34x36x0.5 mm thick @600mm C/C vertically. The
framework to be filled with 50mm 1000GSM non-woven thermal bonded
polyester wadding ( Make Dupont/ mikasha/vibrant) held in position with
18 mm GI checken mesh of 24SWG with drive all screws and oversize
95 washers. Finally fixing over it horizontally 80x26x51x0.5 mm thick G.I. Gyp 2413.00 sqm 1640.00 16.40 1656.40
ceiling section placed @600mm C/C or wherever required as per design
drawings. The frame to be fixed to the walls by means of angle holdfasts
or cleats of required size complete with expandable anchor fasteners of
65x10mm dia fixed on each vertical member @1000mm C/C .The work
shall be executed as per drawings ,specifications & instructions of
engineer in charge.
Providing & fixing at all heights on walls Wood based slats laminated
panels having NRC upto 0.75 with lineal perforations . The size of lineal
panels is 2400 x 128x 16mm with a pitch of 16 mm. The slats to have a
groove of 2mm. The back panels to have circular perforations (8-10mm)
dia randomly with a non wooven fabric covering of 0.2mm. The lineal
96 panels to have tounge & groove joints and fixing arrangements for 2413.00 sqm 4293.00 42.93 4335.93
seamless continuity . The panels to be fixed on the GI framework with
impalers as per manufacturers recommendations ( The GI framework to
be payable Separately ). The work to be done complete as per detail
drawing and instruction of engineer‐in charge and consultant.
Providing and fixing 12 mm thick frameless toughened glass door shutter
of approved brand and manufacture, including providing and fixing top &
bottom pivot & spring type fixing arrangement and making necessary holes
etc. for fixing required door fittings, all complete as per detail drawing and
instruction of engineer‐in charge and consultant.
TOTAL 0.00 0.00
Sub- Head - VII , Steel Work 0.00
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing, supplying, fixing, fabricating, erecting, aligning the structural
steel like pivot ,tubular 'T','I" section, angle, plate ,beam, channel section,
Bar , hollow box or Z purlins , for built up purlins, roof trusses, columns,
side runners, tie beams, sag rods, base plates gusset plates, cap plates,
bearing bracing, gantry girders, rails, require support,pipes, including all
welded or bolted steel structures of various types with approved I.S.I.mark
electrodes, bolts, anchor bolts including cost of thread, Anchor plate cleats
etc. in RCC or masonry work, including cutting, bending, welding ,fixing,
supplying , Fabricating Decorative fevisted section or any structured
98 member required to complete the job for Trusses, Canopy, doors, Frame, 371820.81 kg 83.33 0.83 84.16
Railing, Entrance gate, pergola, Decorative hanging light , for Electrical,
water supply and HVAC structure New window, parking shed or space
frame or any other required specified area as shown on drawing and
detailed specification or as per design incl. three coats of approved brand
primer and two coats of paints, necessary scaffolding, tools tolerance etc.
complete as directed by Engineer In Charge. (Payment will be made for
weight of metal used in the work) (Work for all the floors/all heights)
Design, manufacture and installation of 12 mm dpi system, a complete
assembly of extruded Multi / Micro cellular profile UV extruded/protected
polycarbonate panels incorporated into a complete system. The
Polycarbonate panel system consists coextruded UV protected Multi /
Micro cellular structure polycarbonate panel with width of 1040 mm to
ensure best performance for wind uplift, vibration, oil canning and visual
appearance. Panels shall be manufactured with vertical standing seam
with standing seam height of 10 ‐ 15mm at both sides of the panel. Panels
shall be fixed on Purlins with the Z ‐ Type Stainless Steel
Fastener/retention clips and connectors. Each fastener shall be min 1mm
thick of SS 304 Grade and secured to supporting frame/structure with min
99 3 numbers of self‐drilling screws so that the Pull Out Load of Fastener 82.00 sqm 2255.00 22.55 2277.55
exceeds 7000 N (7 KN) when tested as per ISO 6892: 1998 and IS 1608:
2005. Snap‐on connectors to interlock the panels shall have 2‐4 teeth
grip‐lock locking mechanism to ensure maximum uplift capability. Panel
shall be fixed with additional End cap/Aluminum U / F Profile / Glazing Bar
(mill finish) for ends as required. Panel shall be fixed over structural steel /
MS purlin (paid separately) by trained & factory authorised installer under
direct supervision to complete entire project installation according to the
detail technical specifications as per approved architectural drawings all
complete as per detail drawing and instruction of engineer‐in charge and
Providing and fixing stainless steel ( Grade 304) railing made of Hollow
tubes, channels, plates etc., including welding, grinding, buffing, polishing
and making curvature (wherever required) and fitting the same with
necessary stainless steel nuts and bolts complete, i/c fixing the railingwith
necessary accessories & stainless steel dash fasteners , stainless steel
bolts etc., of required size, on the top of the floor or the side of waist slab
with suitable arrangement as per approval of Engineer-in charge, (for
payment purpose only weight of stainless steel members shall be
considered excluding fixing accessories such as nuts, bolts,fasteners etc.
TOTAL 0.00 0.00
Sub- Head - VIII Flooring 0.00
Providing and laying mirror polished Kota stone slab flooring over 20mm
(Average ) thick base of cement mortar1:6 (1-cement:6-coarse sand)laid
101 over and jointed with grey cement slurry mixed with pigment to match the 1243.00 sqm 982.83 9.83 992.66
shade of slab including rubbing and mirror polishing etc.complete.(A)
25mm thick(work for all the floors)
Providing and laying mirror polished kota stone slab 25mm thick in risers
of steps,skirting Dado and pillars laid on10mm thick cement mortar 1:3 (1-
102 Cement :3 coarses and) and jointed with gray cement slury mixed with 168.00 sqm 1176.03 11.76 1187.79
pigment to match the shade of slab including rubbing and mirror polishing
etc. complete.(work for all the floors)
Providing & laying Light & Dark Colored Polisehd Granite slab (18mm
thick) flooring For Staircase Tread,Landing over 20 mm (average) thick
base of Cement Mortar (1‐Cement : 6‐Sand) using cementitious Adhesive
Materials as per EIC instruction. Granite slab shall be laid and jointed with
103 grey cement slurry. The size of granite should be in full leght of Riser and 11333.00 sqm 2577.00 25.77 2602.77
Tread as per design. Rates are including rubbing, polishing Moulding
/Rounding of edges, making two lines of Grooves on each tread for
antisleep, laying and removing of floor protection sheet etc. complete.
(work for all the floors)
Providing & laying Granite slab (18mm thick ‐ river wash) in riser of steps
dedo, Skirting and pillars laid 15 mm thick Cement Mortar 1:3 (1Cement:3
Coarse Sand) using cementitious Adhesive Materials as per EIC
104 instruction. Granite slab shall be jointed with the Grey Cement Slurry 1960.00 sqm 2577.00 25.77 2602.77
Rates are including rubbing, polishing Moulding / Rounding of edges,
laying and removing of floor protection sheet etc. complete.(work for all the
Providing and laying minimum 8-9 mm thick Double Charged Vitrified
tiles Matt/Antiskid finish of size 600mmx600mm in floor / skirting
(thickness to be specified by the manufacturer) with water absorption less
than 0.08%and conforming to IS:15622, of approved brand &
manufacturer, in all colours and shade, laid with cement based high
polymer modified quick set tile adhesive (water based) conforming to IS :
15477, in average 6 mm thickness, including grouting of joints The tiles
must be cut with the zero chipping diamond cutter only . Laying of tiles will
be done with the notch trowel, plier, wedge, clips of required thickness,
leveling system and rubber mallet for placing the tiles gently and easily.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and laying minimum 8-9 mm thick Double Charged Vitrified tiles
Matt/Antiskid finish of size 800mmx800mm in floor / skirting (thickness to
be specified by the manufacturer) with water absorption less than
0.08%and conforming to IS:15622, of approved brand & manufacturer, in
all colours and shade, laid with cement based high polymer modified
quick set tile adhesive (water based) conforming to IS : 15477, in average
6 mm thickness, including grouting of joints The tiles must be cut with the
zero chipping diamond cutter only . Laying of tiles will be done with the
notch trowel, plier, wedge, clips of required thickness, leveling system and
rubber mallet for placing the tiles gently and easily.
Providing and laying Ceramic tiles 6mm thick in flooring treads of steps
107 and landing laid on a bed of 12mm thick cement mortar 1:3 (1- cement : 3- 266.00 sqm 908.17 9.08 917.25
coarse sand ) finishing with flush pointing in white cement.
Providing and laying Ceramic tiles 6mm thick in skrting risers of steps and
108 dedo on 10mm thick cement plaster 1:3 (1-cement : 3- coarse sand) and 8357.00 sqm 1044.23 10.44 1054.67
jointed with white cement slurry
Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate) finished with a floating coat of neat cement, including cement
slurry, but excluding the cost of nosing of steps etc. complete. i)40 mm
thick with 20 mm nominal size stone aggregate
Providing and laying C.C. pavement of mix M-25 with ready mixed
concrete from batching plant. The ready mixed concrete shall be laid in
panels and finished with screed board vibrator , vacuum dewatering
process and finally finished by floating, brooming with wire brush etc.
complete as per specifications and directions of Engineer-in
charge.Cement content considered in this item is @ 380 kg/cum.
Providing & laying of ITF Certified Acrylic Synthetic sports surfaces
including 7MM SBR with single component PU binder, manually laying on
the existing concrete surface, sealer of PU material for sealing of vide in
SBR layer, 2 layers of top coat ITF classified Techno Court, White Line
marking complete as per detail drawing and instruction of engineer‐in
charge and consultant.
Providing and fixing Glass mossaic tiles on finished plain floor surface and
wall surface of size 20 mm x 20 mm x 4 mm in all colour, design , fixing in
customize design as per direction of Engineer-in- Charge. The glass
mosaic tiles to be fixed on the wall surface with the help of approved
adhesive applied at the rate of 2.5 kg per sqm and grouting of the same.
The rate is inclusive of all operation, material and required pattern
complete as per detail drawing and instruction of engineer‐in charge and
Cutting holes in RCC wall , slab by diamond core cutting machine upto
113 150mm dia for passing drain pipes etc and repairing the hole after 150 each 379.00 3.79 382.79
insertion of drain pipe etc with GP2 grout.
TOTAL 0.00 0.00
Sub- Head - IX Roofing 0.00
Providing and fixing eco-friendly light weight calcium silicate false ceiling tiles having Tegular
edge & 15 mm Thick Densified edges on the Tile Periphery for Extra Strength The Light weight
calcium silicate ceiling tiles shall have , light reflection 85% non-combustible as per B.S.
part IV, 100% humidity resistance and also having thermalconductivity0.043° w/m KC.for the
best thermal Insulation . The Light weight calcium Silicate tile shall be of approved texture Fine
fissured/ Spintone /Cosmos having NRC value of 0.5 & Globe having NRC value of 0.75 NRC
or equivalent of size 595 X 595 mm to be laid on true horizontal level suspended inter locking
metal grid of hot dipped galvanized steelsections (galvanizing @120 grams per sqm including
both side) consisting of main ‘T’runner suitably spaced at joints to get required length and size of
24X38mm made from 0.30 mm thick (minimum) sheet, 1200mm centre to centre, and cross ‘T’
of size 24X28mm made out of 0.33mm (Minimum) sheet spaced 1200mm along space etc. An
additional 4mm thick PVC strip of 40mm width is to be stuck on the interior side of the C
channel using PVC solvent adhesive complete as per direction of Engineer in
charge,manufactures.s at the back side so that ‘L’ shape outer PVC beading can be removed
whenrequired for replacement of broken glass etc. complete as per direction of etc. complete
as per direction of Engineer in charge and manufactuture’s specification.icationntre with 25mm
long dry wall screws @ 230mm interval and laying 15mm thick Densified edges light weight
calcium silicate ceiling tiles of approved texture (Fine Fissured /Cosmos /Spintone) in the grid
including, cutting /making opening for services like diffusers, grills, light fittings, fixtures, smoke
114 detectors etc., wherever required, Main ‘T’ runners to be suspended from ceiling using G.I. 9415.80 sqm 1632.63 16.33 1648.96
slotted cleats of size 25X35X1.6mm fixed to ceiling with 12.5mm dia and 50mm long dash
fasteners, 4mm G.I. adjustable rods with galvanized steel level clips of size 85X30X0.8mm,
spaced at 1200mm centre to centre long main ‘T’bottom exposed with 24mm of all T-sections
shall be pre-painted with polyester baked paint, for all heights, as per specifications, drawings
and as directed by engineer-in charge.Note:- Only calcium silicate false ceiling area will be
measured from wall to wall. No deduction shall be made for exposed frames/opening (cut outs)
having area less than 0.30 sqm. The calcium silicate ceiling tiles shall have NRC. Value of
(Minimum) for Fine fissured/Spintone/Cosmos and 0.75 NRC for Globe, light reflection 85% non-
combustible as per B.S. 476 part IV, 100% humidity resistance and also having thermal
conductivity.0.043° w/m KC.for the best thermal Insulation
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing & fixing false ceiling at all height including providing & fixing of
framework made of special section, power pressed from M.S. sheets and
galvanised with zinc coating of 120 gms/ sqm (both side inclusive) as per IS :
and consisting of angle cleat of size 25mm wide x 1.6mm thick with flanges of
27mm and 37mm, at 1200mm c/c, one flange fixed to the ceiling with dash
fastener 12.5mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to
the angle hangers of 25 x10 x0.50mm of required length with nuts & bolts of
required size and other end of angle hanger fixed with intermediate G.I chanels
x15 x 0.90mm running at the spacing of 1200 mm c/c, to which the ceiling section
0.5mm thick bottom wedge of 80mm with tapered flanges of 26 mm each having
lips of 10.5mm, at 450mm c/c, shall be fixed in a direction perpendicular to G.I
intermediate channel with connecting clip made out of 2.64mm dia x 230mm long
G.I wire at every junction, including fixing perimeter channels 0.50mm thick 27mm
high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall/
partitions with the help of Rawl plugs at 450mm centre, with 25mm long dry wall
screws @ 230mm interval, including fixing of Calcium Silicate Board to ceiling
115 section and perimeter channels with the help of dry wall screws of size 3.5 x25mm 6277.20 sqm 1501.00 15.01 1516.01
at 230mm c/c, including jointing & finishing to a flush finish of tapered and square
edges of the board with recommended jointing compounds, jointing tapes,finishing
with jointing compounds in three layers covering up to 150mm on both sides of
joints and two coats of primer suitable for boards, all as per manufacture's
specification and also including the cost of making opening for light fittings, grills,
diffusers, cut outs made with frame of perimeter channels suitably fixed, all
complete as per drawings, specificaton and direction of the Engineer in charge but
excluding the cost of painting with: 8 mm thick Calcium Silicate Board made with
Calcareous & Siliceous materials reinforced with cellulose fiber
manufactured through autoclaving process.
Providing & fixing Armstrong Vertical Linear Baffle Ceiling made out of
Aluminum Extrusion in Aluminum alloy grade 6063. The baffle blade shall
be in size of 100x 50mm in WHITE/BLACK/WOOD GRAIN finish –
Pradoo & Cabrueava. The baffle blade shall be suspended using Slotted
116 U-profile at on-center spacing . Longer lengths of Baffle to be connected by 1156.00 sqm 5085.00 50.85 5135.85
Baffle Joiner and the ends to be fixed with End caps.
Baffle Ceiling 200mm c/c.complete as per detail drawing and instruction of
engineer‐in charge and consultant.
Providing and fixing mineral fibre false ceiling tiles at all heights of size
595X595mm of approved texture, design and pattern. The tiles should
have Humidity Resistance (RH) of 99%, Light Reflectance ? 85%,Thermal
Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt -
6 &7)in true horizontal level suspended on interlocking T-Grid of hot
dipped all round galvanized iron section of 0.33 mm thick (galvanized
@120 gsm) comprising of main T runners of 15x32 mm of length
mm, cross T of size 15x32mm of length 1200 mm and secondary
intermediate cross T of size 15x32 mm of length 600 mm to form grid
module of size 600x600 mm suspended from ceiling using galvanized mild
steel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash
fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length
and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm
centre to centre along main ‘T’. The system should rest on periphery walls
/partitions with the help of GI perimeter wall angle of size24x24X3000 mm
made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic
rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws.
The exposed bottom portion of all T-sections used in false ceiling support
system shall be pre-painted with polyester baked paint, for all heights. The
work shall be carried out as per specifications, drawings and as per
directions of the engineer-in-charge. With 20 mm thick beveled tegular
mineral fibre false
ceiling tile (NRC 0.7)
TOTAL 0.00 0.00
Sub- Head - X Finishing 0.00
Providing 10 mm thick Cement Plaster in single coat on brick/concrete
Ceiling for interior plastering finished even and smooth in(i) Cement
118 mortar 1:3 (1‐cement :3‐ sand) as required to receive specified 5049.27 sqm 152.15 1.52 153.67
architectural finish (like Grooves, pattern if any, drip mould etc.) to correct
line, plumb .etc - Basement Floor
Providing 10 mm thick Cement Plaster in single coat on brick/concrete
Ceiling for interior plastering finished even and smooth in(i) Cement
119 mortar 1:3 (1‐cement :3‐ sand) as required to receive specified 5542.24 sqm 159.76 1.60 161.36
architectural finish (like Grooves, pattern if any, drip mould etc.) to correct
line, plumb .etc - Ground Floor
Providing 10 mm thick Cement Plaster in single coat on brick/concrete
Ceiling for interior plastering finished even and smooth in(i) Cement
120 mortar 1:3 (1‐cement :3‐ sand) as required to receive specified 4873.24 sqm 167.75 1.68 169.43
architectural finish (like Grooves, pattern if any, drip mould etc.) to correct
line, plumb .etc - First Floor
Providing 10 mm thick Cement Plaster in single coat on brick/concrete
Ceiling for interior plastering finished even and smooth in(i) Cement
121 mortar 1:3 (1‐cement :3‐ sand) as required to receive specified 4573.24 sqm 176.14 1.76 177.90
architectural finish (like Grooves, pattern if any, drip mould etc.) to correct
line, plumb .etc - Second Floor
Providing 10 mm thick Cement Plaster in single coat on brick/concrete
Ceiling for interior plastering finished even and smooth in(i) Cement
122 mortar 1:3 (1‐cement :3‐ sand) as required to receive specified 4605.68 sqm 184.95 1.85 186.80
architectural finish (like Grooves, pattern if any, drip mould etc.) to correct
line, plumb .etc - Third Floor
Providing 10 mm thick Cement Plaster in single coat on brick/concrete
Ceiling for interior plastering finished even and smooth in(i) Cement
123 mortar 1:3 (1‐cement :3‐ sand) as required to receive specified 4605.68 sqm 194.20 1.94 196.14
architectural finish (like Grooves, pattern if any, drip mould etc.) to correct
line, plumb .etc - 4th Floor
Providing 10 mm thick Cement Plaster in single coat on brick/concrete
Ceiling for interior plastering finished even and smooth in(i) Cement
124 mortar 1:3 (1‐cement :3‐ sand) as required to receive specified 2487.50 sqm 203.91 2.04 205.95
architectural finish (like Grooves, pattern if any, drip mould etc.) to correct
line, plumb .etc - 5th Floor
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing 10 mm thick Cement Plaster in single coat on brick/concrete
Ceiling for interior plastering finished even and smooth in(i) Cement
125 mortar 1:3 (1‐cement :3‐ sand) as required to receive specified 2437.50 sqm 214.11 2.14 216.25
architectural finish (like Grooves, pattern if any, drip mould etc.) to correct
line, plumb .etc - 6th Floor
Providing 10 mm thick Cement Plaster in single coat on brick/concrete
Ceiling for interior plastering finished even and smooth in(i) Cement
126 mortar 1:3 (1‐cement :3‐ sand) as required to receive specified 2437.50 sqm 224.82 2.25 227.07
architectural finish (like Grooves, pattern if any, drip mould etc.) to correct
line, plumb .etc - 7th Floor
Providing 10 mm thick Cement Plaster in single coat on brick/concrete
Ceiling for interior plastering finished even and smooth in(i) Cement
127 mortar 1:3 (1‐cement :3‐ sand) as required to receive specified 2437.50 sqm 236.06 2.36 238.42
architectural finish (like Grooves, pattern if any, drip mould etc.) to correct
line, plumb .etc - 8th Floor
Providing 10 mm thick Cement Plaster in single coat on brick/concrete
Ceiling for interior plastering finished even and smooth in(i) Cement
128 mortar 1:3 (1‐cement :3‐ sand) as required to receive specified 2437.50 sqm 247.86 2.48 250.34
architectural finish (like Grooves, pattern if any, drip mould etc.) to correct
line, plumb .etc - 9th Floor
Providing 10 mm thick Cement Plaster in single coat on brick/concrete
Ceiling for interior plastering finished even and smooth in(i) Cement
129 mortar 1:3 (1‐cement :3‐ sand) as required to receive specified 189.00 sqm 260.25 2.60 262.85
architectural finish (like Grooves, pattern if any, drip mould etc.) to correct
line, plumb .etc - Terrace Floor
Providing 15 mm thick Cement Plaster in single coat on brick/concrete
wall/ for interior plastering finished even and smooth in(i) Cement mortar
130 1:4 (1‐cement :4‐ sand) as required to receive specified architectural finish 2045.25 sqm 155.61 1.56 157.17
(like Grooves, pattern if any, drip mould etc.) to correct line, plumb .etc -
Providing 15 mm thick Cement Plaster in single coat on brick/concrete
wall/ for interior plastering finished even and smooth in(i) Cement mortar
131 1:4 (1‐cement :4‐ sand) as required to receive specified architectural finish 9030.66 sqm 163.39 1.63 165.02
(like Grooves, pattern if any, drip mould etc.) to correct line, plumb .etc -
Providing 15 mm thick Cement Plaster in single coat on brick/concrete
wall/ for interior plastering finished even and smooth in(i) Cement mortar
132 1:4 (1‐cement :4‐ sand) as required to receive specified architectural finish 7275.66 sqm 171.56 1.72 173.28
(like Grooves, pattern if any, drip mould etc.) to correct line, plumb .etc -
Providing 15 mm thick Cement Plaster in single coat on brick/concrete
wall/ for interior plastering finished even and smooth in(i) Cement mortar
133 1:4 (1‐cement :4‐ sand) as required to receive specified architectural finish 7275.66 sqm 180.14 1.80 181.94
(like Grooves, pattern if any, drip mould etc.) to correct line, plumb .etc -
Providing 15 mm thick Cement Plaster in single coat on brick/concrete
wall/ for interior plastering finished even and smooth in(i) Cement mortar
134 1:4 (1‐cement :4‐ sand) as required to receive specified architectural finish 7275.66 sqm 189.15 1.89 191.04
(like Grooves, pattern if any, drip mould etc.) to correct line, plumb .etc -
Providing 15 mm thick Cement Plaster in single coat on brick/concrete
wall/ for interior plastering finished even and smooth in(i) Cement mortar
135 1:4 (1‐cement :4‐ sand) as required to receive specified architectural finish 7275.66 sqm 198.61 1.99 200.60
(like Grooves, pattern if any, drip mould etc.) to correct line, plumb .etc -
Providing 15 mm thick Cement Plaster in single coat on brick/concrete
wall/ for interior plastering finished even and smooth in(i) Cement mortar
136 1:4 (1‐cement :4‐ sand) as required to receive specified architectural finish 4024.10 sqm 208.54 2.09 210.63
(like Grooves, pattern if any, drip mould etc.) to correct line, plumb .etc -
Providing 15 mm thick Cement Plaster in single coat on brick/concrete
wall/ for interior plastering finished even and smooth in(i) Cement mortar
137 1:4 (1‐cement :4‐ sand) as required to receive specified architectural finish 2012.05 sqm 218.97 2.19 221.16
(like Grooves, pattern if any, drip mould etc.) to correct line, plumb .etc -
Providing 15 mm thick Cement Plaster in single coat on brick/concrete
wall/ for interior plastering finished even and smooth in(i) Cement mortar
138 1:4 (1‐cement :4‐ sand) as required to receive specified architectural finish 2012.05 sqm 229.92 2.30 232.22
(like Grooves, pattern if any, drip mould etc.) to correct line, plumb .etc -
Providing 15 mm thick Cement Plaster in single coat on brick/concrete
wall/ for interior plastering finished even and smooth in(i) Cement mortar
139 1:4 (1‐cement :4‐ sand) as required to receive specified architectural finish 2012.05 sqm 241.42 2.41 243.83
(like Grooves, pattern if any, drip mould etc.) to correct line, plumb .etc -
Providing 15 mm thick Cement Plaster in single coat on brick/concrete
wall/ for interior plastering finished even and smooth in(i) Cement mortar
140 1:4 (1‐cement :4‐ sand) as required to receive specified architectural finish 2012.05 sqm 253.49 2.53 256.02
(like Grooves, pattern if any, drip mould etc.) to correct line, plumb .etc -
Providing 15mm thick Cement Plaster in single coat on brick/concrete wall/
for interior plastering finished even and smooth in(i) Cement mortar 1:4
141 (1‐cement :4‐ sand) as required to receive specified architectural finish 128.00 sqm 266.16 2.66 268.82
(like Grooves, pattern if any, drip mould etc.) to correct line, plumb .etc -
20mm thick Double coat Sand Faced / Mala cement plaster on Exterior
walls at for various floors, levels and height as below and shown in the
drawing consisting of 12mm thick backing coat of C.M. 1:3 (1‐cement
142 :3‐sand) and 8mm thick finishing coat of C.M. 1:2 (1‐cement :2‐sand) etc. 8735.55 sqm 297.68 2.98 300.66
complete. as required to receive specified architectural finish like Vata,
Grooves, pattern if any, drip mould etc. to correct line, level and plumb .
Providing 20mm thick cement plaster in single coat on single wall for
basement wall/ under plinth exterior surface in cement mortar 1:3 (
143 1cement: 3sand) including providing and mixing water proofing material in 100.00 sqm 226.92 2.27 229.19
cement mortar work in doses by weight of cement as per manufacturer
Applying two coats of putty & two coats of primer of approved brand and
manufacture on new wall surface to give an even shade including
thoroughly brushing the surface free from mortar dropping and other
foreign matter and sand papered smooth.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Wall painting (Three coats) with plastic emulsion paint of approved brand
& manufacture on under coated wall surface to give an even shade
including thoroughly brushing the surface free from mortar dropping and
other foreign matter and sand papered smooth.
Painting two coats (excluding priming coat) on new steel and other metal
surface with syntheticenamel paint, brushing to give an even shade
including cleaning the surface of all dirt, dust and other foreign matter.
Providing and applying acrylic aggregate textured non pigmented wall
finish coating in 100% natural/ non pigmented Crushed Stone finish,
dispersed in a pure acrylic binding medium, incorporating anti cracking,
anti rusting, defoamers, antifungal compound followed by trowel/ spray
gun application in approved shade and pattern or brick pattern with an
average thickness of 1.75-2.0 mm, product finally sealed with protective
top coat as per sample approved by Engineer-in-charge on the exterior
walls of the building.
TOTAL 0.00 0.00
Sub- Head - XI , Aluminium Work 0.00
Providing and fixing of Anodised Aluminium (Matt finish) frame work as per IS
1868 (1996)(Horizontal and verticals , Styles and rails, ball bearing) for Doors/
window/ventilation/alluminum partition with required Domal sections including
fixing all items and hinged / pivoted arrangements for operation of shutters and
labour cost for fixing of door fittings and locks including all items and
contingencies described above complete (Aluminium beadings and glazing clips &
section measured under this item only) NOTE : All fitting works shall be carried
out as per I.S. specifications including cost of necessary rivets, screws, lugs,
scaffolding, rubber gaskets etc., complete all generally as per drawings. The sizes
of the components should confirm as per details in drawings. Providing and fixing
at all heights / in all floors with all leads. Colour Anodised Aluminium doors /
windows / partitions manufactured from best extruded Aluminium sections
confirming to ISI cut to length, joints mitred and corners grinded with joints water
proof the outer frame and shutter frame stiffened with corner angle and strips
provided for in the frame for fixing the frame to R.C.C Columns / masonry/Granite
Frame on sides, R.C.C lintels/Granite Frame on top and P.C.C sills or floor at
148 bottom, the frame work fixed with standard approved fastenings all generally as 18732.15 kg 415.00 4.15 419.15
per details shown in drawings and specification with all the sections pretreated for
removal of any rust & scales and prevention of further rust/scale formation and
coated with greasy materials for non-adherence of mortar or any other sticky
materials and this coat to be removed after installations 1)Sheet metal screws,
wool pile and aluminium angle corner cleat of required thickness and of full width,
etc. for assembling the frame and shutter; 2)Glazing clips for receiving infill panel
for Double Glazed Unit (DGU), any type of Glass, Compact Sheet, Louvers; 3)
Best quality wool pile where ever shutter touches the frame; 4) Anchor fasteners
for fixing the frame assembly to the RCC or Granite or masonry surfaces etc.
Note:-As per drawings and design supplied by architect and instruction given by
authority and E.I.C.
Providing and fixing double glazed hermetically sealed glazing in
aluminium windows, ventilators and partition etc. with 6 mm thick clear
float glass both side, having 12 mm air gap, including providing EPDM
gasket, perforated aluminium spacers, desiccants, sealant (Both primary
and secondary sealant) etc. as per specifications, drawings and direction
of Engineer-in-charge complete
Providing and fixing fly proof stainless steel grade 304 wire gauge, to
windows and clerestory windows using wire gauge with average widthof
150 aperture 1.4 mm in both directions with wire of dia. 0.50 mm all 1235.31 sqm 1030.00 10.30 1040.30
complete.with Aluminium beading
Supply of Aluminium Ventilated Façade / Louver System of approved
colour consisting of panel 50 mm wide x 50mm depth x 0.6mm thick panel
length up to 5mtrs coil coated on a continuous paint line double baked and
roll formed from enameled corrosion Resistance Aluminum Alloy AA3005 /
AA5050 for higher strength and good Roll forming characteristics. Panels
shall be mounted in a module of 100 mm on a mullion profile grooved
(Slotted Fastening Profile) by means of Clamp, Locking Pop and Pop Rivet
(Gap will be 50 mm between two panels). Slotted Fastening Profile shall
be fixed at 150 mm from panel ends and at a distance of maximum
mm center to center across the panel span and in any height and Slotted
Fastening Profile shall be fixed to a suitable sub-structure by means of
Square Brackets.Paint Finish:Panel shall be stove enamelled and finished
with Luxacote, a patented special three layered coating system (consisting
of first a conversion layer of thickness 800-2000mg/sq mtr, a polyurethane
basecoat of 16-20 microns, and a special top coat of polyamide particles
of 8-12 microns thick to provide excellent abrasion and damage
resistance) in a continuous coil coating process of the approved colour on
the exposed side and the reverse side with epoxy.
152 Item Deleted
Designing, fabricating, testing, protection, installing and fixing in position
semi(grid) unitized system of structural glazing with IGUs comprising of
hermetically sealed 6-12-6 mm insulated glass (double Glazed) and
Aluminium section complete as per specification
TOTAL 0.00 0.00
Sub- Head - XII , Water Proofing 0.00
Providing and laying of minimum 1.5 mm thick SBS modified self adhesive
Samshield XL or equivalent waterproofing membrane topped with samshield
HDPE valeron film, having tensile strength of L/T 3.5N/mm2 as per ASTM D412
and with minimum elongation L/T of 180% (as per ASTM D 412). The membrane
shall have puncture resistance of >200 N (as per ASTM E154). Hydrostatic
pressure > 60 m (6BAR) No leakage as per DIN 1048, including cleaning the
surface,priming the surface with cold applied bituminous primer@4-6 sqmtr/litre,
154 properly sealing the joints & maintaining 75 mm overlap between the membrane 1713.00 sqm 630.00 6.30 636.30
selvedge & 100 mm overlap on the end joints of the membrane over the slab etc.
The system includes base preparation of cleaning, brushing and removal of flacky
materials, grouting the porous area with cementitious grout, proper coving
between slab and wall junctions. The waterproofing system should be applied
directly by the manufacturer approved applicator with 10 years of warranty against
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Supplying and laying composite 1.5mm thick, pre-applied, fully bonded HDPE
membrane with double side adhesive which results in adhesive-to-adhesive bond -
Prebond Pro or equivalent over P.C.C. conforming to BS 8102 & IS 16471:2017,
requirements of UG waterproofing structures, with the turnkey execution to be
done by the manufacturer through its in-house subsidiary execution company and
with 10 years composite warranty against leakages, to be provided by the principal
manufacturer. The system should be fully bonded to the Raft and consists of highly
resilient HDPE film, self-adhesive polymer layer and weather protective layer.
Typical application includes surface preparation by removing loose aggregates
from PCC, foreign material, cleaning the surface etc., cutting membrane to
convenient length, carefully aligning the membrane over blind concrete and rolling
it out with print coated side facing up, laying adjacent sheets by keeping overlap of
75 mm, end overlaps to be treated using double sided tape and sealed tape
etc.The membrane shall be continued over the vertical surface upto top of the Raft
and fixed to shutter using double side adhesive tape. For application on confined
retaining walls membrane shall be continued over the vertical surface and fixed by
PVC roundels / shot guns at selvedge portion. The membrane shall have Tensile
strength > 25 Mpa as per ASTM D 412 Modified, Elongation > 500% as per ASTM
D 412 Modified, Puncture resistance > 1000 N as per ASTM E 154, Hydrostatic
head resistance > 70m head of water as per ASTM D 5385,Low Temperature
Flexibility: -25 deg C, Lap Peel Adhesion-880 N/m as per ASTM D1876, Peel
Adhesion to Concrete > 1500 N/m as per ASTM D 903 Modified, UV Exposure >
Providing and laying water proofing treatment to vertical and horizontal
surfaces of depressed portions of W.C kitchen and the like consisting of :
i) Ist course of appying cement slurry @ 4.4 Kg/sqm mixed with water
proofing compound conforming to IS 2645in recommended proportions
including rounding off junction of vertical and horizontal surface.ii) IInd
course of 20 mm cement plaster 1: 3 (1 cement :3 coarse sand) mixed
with water proofing compound in recommended proportion including
roudnign off junction of vertical and horizontal surface. iii) IIIrd course of
applying blown or residual bitument applied hot at 1.7 kg. per sqm of
area.iv) IVth course of 400 micron thick PVC sheet. ( Overlaps at joints of
PVC sheet should be 100 mm wide and pasted to each other with bitument
Terrace Waterproofing Works : Providing and applying single
component PU based cold applied seamless waterproofing membrane
over the primed surface with PU/Epoxy primer Layer on RCC mother slab,
Insulation Layer: Spray applying an average minimum 65mm thick GRIHA
enlisted CFC & HCFC free spray applied polyurethane foam and 2 coats
of a single component PU based cold applied seamless waterproofing
membrane over PU foam , 150 gsm Geotextile (non-woven polyester)
over the entire membrane on horizontal areas maintaining proper overlaps
and an avg of 100 mm thick M20 grade PP fiber reinforced concrete
screed with Min. 75 mm thick at the rain water outlets, laid to a slope of 1 :
120, including saw cuting (approx 6mm W x 30mm D) at 3MX4M pannels
within 24 hours of concrete placement and filling the groove with
Expanded Polytheylene backer rod keeping the top approx 10 mm depth
open and sealing the groove on the top after 28 days of concrete
placement with PU sealant or equivalent, and making angle fillet of
100mmX100mm using M20 grade concrete at the corners, compaction
curing for 7 days etc complete
TOTAL 0.00 0.00
Sub Head XIII - External development 0.00
Preparation and consolidation of sub grade with power road roller of 8 to
12 tonne capacity after excavation earth to an average of 22.5cm depth
158 dressing to camber and consolidating with road roller including making 2969.00 sqm 184.00 1.84 185.84
good the undulations etc. and re-rolling the sub grade and disposal of
surplus earth lead upto any lead.
Construction of granular Sub base providing coarse graded material,
spreading in uniform layers with motor grader on prepared surface mixing
by mix in place method with front end loader at OMC and compacting with
159 vibratory roller to achieve the desired density, complete as per 625.00 cum 2336.00 23.36 2359.36
specification and direction of engineer in charge- With material
conforming to Grade - I (size range 75mm to 0.075mm ) having CBR
Construction of dry lean cement concrete sub base over a prepared sub-
grade with coarse and fine aggregate conforming to IS:383, the size of
coarse aggregate not exceeding 25 mm, aggregate cement ratio not to
exceed 15:1, aggregate gradation after blending to be as per
specifications, cement content not to be less than 150 Kg/cum, optimum
160 moisture content to be determined during trial length construction, 445.00 cum 3481.00 34.81 3515.81
concrete strength not to be less than 10 Mpa at 7 days, mixed in a
batching plant, transported to site, for all leads & lifts, laid with a
mechanical paver, compacting with 8-10 tonne vibratory roller, finishing
and curing etc. complete as per direction of Engineer in- charge.
Providing and fixing pre-cast Rubber Dye/ steel Dye interlocking concrete
block 60mm thick with grade of concrete M300 pnumatic compressed/
vibrated mechanically and as per approved design Confirming to
IS15658:2006 including 35mm Sand layer for levelling and filling the joint
with sand in proper line and level as per guidlines of IRC : SP 63-2018 etc.
Providing and Fixing pre-cast concrete kerb stone of gray cement based
concrete block 30cm length,30cm height and 15cm thick of M200 grade
162 concret as per approved design and including excavation for fixing in 1212.00 metre 376.43 3.76 380.19
proper line and level ,filling the joint with C:M 1:3(1cement:3 fine sand) etc
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and laying design mix cement concrete of M-30 grade, in roads/
taxi tracks/ runways, using cement content as per design mix, using
coarse sand and graded stone aggregate of 40 mm nominal size in
appropriate proportions as per approved & specified design criteria,
providing dowel bars with sleeve/ tie bars wherever required,laying at site,
spreading and compacting mechanically by using needle and surface
vibrators, levelling to required slope/ camber finishing with required
texture, including steel form work with sturdy M.S. channel sections,
curing, making provision for contraction / expansion, construction &
longitudinal joints (10 mm wide x 50 mm deep) by groove cutting machine,
providing and filling joints with approved joint filler and sealants, complete
all as per direction of Engineer-in-charge (Item of joint fillers, sealants,
dowel bars with sleeve/ tie bars to be paid separately). Cement content
considered in M-30 is @ 410 kg/cum. Cement concrete manufactured in
automatic batching plant (RMC plant) i/c transportation to site in transit
Parking Signs :-Providing and fixing sing boards made out of 2mm
aluminium sheet; size 60 x 60cms. sequare plus 60 x 20cms rectangular
additional plate as as per the design of IRC-67-1977 pre treated with
phospheting process & acid etching; coated with one coat of epoxy primer
and two coats of best quality epoxy paint;reflectorised with retro refiective
sheeting as per latest M.O.S.T.Specifications; 3.1m long stand post and
frame fabricated from suitable size iron angle of 35 x 35 x 3mm
75x75x6mm as required;painted with best quality epoxy coatings in black
and white bends.the details of symbol for each board shall be as per the
instruction of engineer in charge. The fixing at site shall be in 1:2:4 CC
block of size 45 x 45 x 60cms. for each leg. including excavation curing
etc.complete under the supervision of engineer in charge.(A) Engineer
Providing and fixing retro Reflective Engineering grade Board using
C.R.C. (M.S.) Sheet 2mm, angle iron 75 x 75 x 6mm. Descaling and
degreasing the board as per requirement using epoxyprimer epoxy paint
and carrying retro reflactive process by screen painting as directed etc.
complete including transporting and fixing in C.C. 1:4:8 with necessary
excavation curing etc. complete as per I.R.C type design.(A) Engineer
Facility Informatory Sign :-Providing and fixing sign boards made out of
2mm aluminium sheet / 4mm ACP (Aluminum composite Panel); size 80 x
60 cms rectangular as per design of IRC-67-2012.Pre treated with
phospheting process & acid etching; coated with one coat of epoxy primer
and two coats of best quality epoxy paint ;reflectorised with Micro
Prismatic Grade retro refiectivesheeting of Type-11 as per ASTM D-4956
and latest M.O.S.T.Specifications; 3.6mtr long stand post of 75 x 75 x 6mm
/ 65NB Circular MS Pipe
as required and frame fabricated from suitable size iron angle of 35 x 35 x
166 3mm; painted with bestquality epoxy coatings in black and white bends. 6 each 5848.00 58.48 5906.48
The details of symbol foreach board shall be as per theinstruction of
engineer in charge. The fixing at site shall be in 1:2:4 CC blockof size 45 x
45 x 60 Cms. for each leg.including excavation, curing etc.complete under
the supervision of engineer in charge. A warranty for 10 years for the
Retro reflective sheeting from original manufacturer & a certified copy of
year outdoor exposure test report from third party test lab for the product
offered shall be submitted by contractor. (A) Class-C Type-11 Retro
Reflective sheeting
Painting road surface marking with adequate nos of coats to give uniform
finish with ready mixed road marking paint conforming to IS : 164, on
167 bituminous surface in white/yellow shade, including cleaning the surface of 59.00 sqm 158.00 1.58 159.58
all dirt, scales, oil, grease and foreign material etc.complete. New work
(Two or more coats)
Earthwork for embankment including breaking clods,dressing with all lead
and lift and including watering rolling and consolidation of subgrade in
168 layers at O.M.C.to required dry density including filling the depression 4500.30 cum 171.95 1.72 173.67
which occur during the process using power roller 8Tto10T. (E) From
Borrow area within all lead.
Supplying and stacking at site dump manure from approved source,
169 including carriage (manure measured in stacks will be reduced by 8% for 87.00 cum 254.15 2.54 256.69
payment) : Screened through sieve of I.S. designation 20mm
170 Fine dressing of the ground 2321.00 sqm 3.70 0.04 3.74
Spreading of sludge, dump manure and / or good earth in required
171 thickness as per direction of Engineer -in-charge (Cost of sludge, dump 783.00 cum 52.35 0.52 52.87
manure and / or good earth to be paid separately).
Mixing earth and sludge or manure in the required proportion specified or
directed by the Engineer -in-charge.
Grassing with selection No.1 grass including watering and maintenance of
the lawn for 30 days or more till the grass forms a thick lawn, free from
weeds and fit for mowing including supplying good earth, if needed -With
Preparation of beds for hedging and shrubbery by excavating 60 cm deep
and trenching the excavated base to a further depth of 30 cm, refilling the
excavated earth after breaking clods and mixing withsludge or manure in
the ratio of 8:1 (8 parts of stacked volume of earth after reduction by 20% :
one part of stacked volume of sludge or manure after reduction by 8%),
174 flooding with water, filling with earth if necessary, watering and finally fine 50.00 cum 222.85 2.23 225.08
dressing, leveling etc.including stacking and disposal of materials
declared unserviceable and surplus earth by spreading and leveling as
directed, within a lead of 50 m, lift up to 1.5 m complete (cost of sludge,
manure or extra earth to be paid for separately).
Supplying & Stacking of Selection No.1 doob grass turf at site fresh & free
from weeds having proper roots in green including loading, unloading,
carriage and all taxes paid etc.and as per direction of Engineer - in -
Demolition including stacking of serviceable materilas and disposal of
unserviceable materials with all lead and lift. (i) R.C.C. work
Demolition of Brick work and stone masonry including stacking of
177 serviceable materilas and disposal of unserviceable materials with all lead 94.00 cum 544.95 5.45 550.40
and lift.(ii) In Cement Mortar.
Dismentaling tiled of stone floors laid in mortar including stacking of
178 serviceable materilas and disposal of unserviceable materials with all lead 2374.00 sqm 47.25 0.47 47.72
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Dismentling steel work including distempering and stacking the materials
with all lead and lift.
Dismentling doors, windows, ventilators etc. (wood or steel) shutters
including chowkhats architraves, holdfasts and other attachment etc.
complete and stacking them within all lead and lift.(i) Not exceeding
Dismentling doors, windows, ventilators etc. (wood or steel) shutters
including chowkhats architraves, holdfasts and other attachment etc.
complete and stacking them within all lead and lift.(ii) Exceeding 3 Sq.M.
Carefully removing the existing interlocking paver blocks of any thickness,
including stacking the serviceable paver blocks at site; disposing of
unserviceable materials; preparing the sub-base including dressing,
182 leveling, compacting, and relaying/re-fixing the paver blocks in proper line 2374.00 sqm 350.23 3.50 353.73
and level with required compaction; filling joints with sand; and completing
the work as directed by the Engineer-in-Charge.
Shifting relocating and re-routing of existing building services falling within
the proposed building construction area, including Diesel Generator (DG)
sets, Transformers, HT/LT panels,pump room equipment, UGT/Panel
rooms, and other associated MEP services; complete in all respects. The
183 work includes safe shutdown, disconnection, transportation, re-installation 1 LS 500000.00 5000.00 505000.00
at the designated location, , supply of required hardware, supports,
accessories, testing and commissioning, and restoration of affected
surfaces; all as per direction of the Engineer-in-Charge
Sub Head – Plumbing Work
Providing and fixing white vitreous china wall mounting water closet of size
64X35.5X38.5 cm of approved shape including providing & fixing cistern
184 with dual flush fitting, of flushing capacity 2 litre/ 4 litre (adjustafle to 4 95 each 10629.00 106.29 10735.29
litre/8 litres), including seat cover, and cistern fittings, nuts, bolts and
gasket etc complete Make -20151-Hindware.
Providing and fixing water closet squatting Pan (Indian type W.C. Pan)
185 size 580mm (Earthwork, bed concrete, foot reste and trap to be measured 2 each 926.10 9.26 935.36
and paid for separately) (A) Vitreous China.(I) Long pattern = White colour
Providing and fixing Handicap toilet consisting of 1 no. EWC with vitreous
10 litre capacity dual flushing system cistern with 1 no. hinged rail of
186 cm, 1 no. wash basin with all fittings and bottle trap, with one pair of 11 each 39697.00 396.97 40093.97
mounting brackets and 4 nos. grab rails, 1 no. tower ring and 1 no. paper
holder all complete as per the manufacturer's specification
187 Providing and fixing toilet paper holder.(A) C.P. Brass 106 each 414.53 4.15 418.68
Providing and fixing white vitreous china battery /Electice based infrared
sensor operated urinal of approx. size 29X 32.5X 57.5 cm having pre &
post flushing with water (250 ml & 500 ml consumption), having water inlet
from back side, including fixing to wall with suitable brackets all as per
manufacturers specification and direction of Engineer-in-charge. ( cat No
Hindware- 60021)
Providing and fixining frameless urinal partition with 8 mm glass , full
189 height upto 3 feet, 1 feet deep & SS fittings approved make all complete 21 each 4767.00 47.67 4814.67
as directed by the Engineer-in-Charge.
Providing and fixing white vitreous china wash basin under counter basin
of size 630x450mm, with including 32 mm CP brass waste coupling,
including painting of fittings and brackets, cutting and making good the
walls wherever required all complete
Providing and fixing CP brass auto closing system basin pillar tap of
Jaquar PRS - 031 or Equivalent as approved by Engineer- In Charge
Providing and fixing chromium plated, bottle trap with necessary couplings
of approved quality for wash basin
Providing and fixing Kitchen sink with C.I. or M.S. brackets, painted white
193 including cutting holes in walls and making good the same but excluding 6 each 2257.69 22.58 2280.27
fittings. (C) Vitreous China Sink.(i) 600mm x 450mm x 150mm size
Providing and fixing white vitreous china laboratory sink with C.I. brackets,
C.P. brass chain with rubber plug, 40 mm C.P brass waste and 40mm C.P.
194 brass trap with necessary C.P. brass unions complete, including painting
of fittings and brackets, cutting and making good
the wall wherever required :
195 Providing and fixing C.P. brass waste for washbasin or sink. (A) 32mmdia. 87 each 67.24 0.67 67.91
196 Providing and fixing C.P. brass waste for washbasin or sink. (B) 40mm dia. 46 each 88.94 0.89 89.83
197 Providing and fixing M.I. fisher union for washbasin or sink. (A) 32mm dia. 87 each 77.97 0.78 78.75
Providing, laying and jointing in true line and level 110 diametre U.P.V.C
(TypeB) conforming to IS13592-1992 with one end plain and othe rend
socketed with rubberring, & fittings conforming to ISI14735-1999 of
approved make for drainage system pipe line, pipe shall be jointed with
each other with rubber lubricant, pipe shall be fixed on wall using of PVC
clamp of the size 110 mm diametre x149mm length x145mm heigh at
every 2000 mm center to center or shall be concealed in walls as directed
including necessary fittings such as bends, shoes etc.including testing of
pipes and joints and jointed with adhesive solvent cement including cost of
Providing, laying and jointing in true line and level 75 diametre U.P.V.C
(TypeB) conforming to IS13592-1992 with one end plain and othe rend
socketed with rubberring, & fittings conforming to ISI14735-1999 of
approved make for drainage system pipe line, pipe shall be jointed with
each other with rubber lubricant, pipe shall be fixed on wall using of PVC
clamp of the size 75 mm diametre x149mm length x145mm heigh at every
2000 mm center to center or shall be concealed in walls as directed
including necessary fittings such as bends, shoes etc.including testing of
pipes and joints and jointed with adhesive solvent cement including cost of
Providing and fixing cast iron spigot and socket soil, waste and ventilating
pipes of the following nominal size.(B) 75mm dia.
Providing and fixing cast iron spigot and socket soil, waste and ventilating
pipes of the following nominal size.(C) 100mm dia.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
202 Providing and fixing in position cowel went to pipes.(B) 75mm dia. 18 each 385.88 3.86 389.74
203 Providing and fixing in position cowel went to pipes.(C) 100mm dia 27 each 496.90 4.97 501.87
Providing and fixing SWR floor drain consisting of 100x63mm PVC
204 elbow (grating and SWR pipe to be paid separately), complete as per 85 each 144.00 1.44 145.44
instructions.(C) 100mm dia.
Supply and fixing of SWR Plain / Multi Floor Trap of `P' , "S" or `Q' type
and 110 mm outlet complete, including cost of materials, labour, HOM of
machinery & equipments with all lead and lifts, loading and unloading
charges, transportation cost and conveyance, all other incidental charges
etc. complete for successful completion of work as per specifications, and
as directed by Engineer -in- Charge. 110mm inlet and 110 mm outlet
Painting two coats (excluding priming coat) on external surface of new rain
water, soil, waste and vent pipes and fittings with ready mixed bituminous
brushing, black, anticorrosive to give an even shade including cleaning of
all dirt, dust and other foreign matter. (B) 75mm dia.
Painting two coats (excluding priming coat) on external surface of new rain
water, soil, waste and vent pipes and fittings with ready mixed bituminous
brushing, black, anticorrosive to give an even shade including cleaning of
all dirt, dust and other foreign matter. (C) 100mm dia.
Providing and fixing 125 mm square S/S grating (with or without
hole)for floor or Nahani trap.
Providing and fixing C.P soap dispenser with all complete as directed by
the Engineer-in-Charge.
Providing & fixing C.P. brass towel ring all complete with required
210 acceessories as directed by the Engineer-in-Charge. Towel Ring Round 17 each 750.13 7.50 757.63
with Round Flange (Make -Jaquar Cat no- ACN-1121BN).
Providing and fixing concealed center point to wall ceiling & floor CPVC
(SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for
potable water of following dia. nominal bore tube fittings and clamps
including making good the wall, ceiling and floor etc. complete. [D] 32mm.
Providing and fixing concealed center point to wall ceiling & floor CPVC
(SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for
potable water of following dia. nominal bore tube fittings and clamps
including making good the wall, ceiling and floor etc. complete. [E] 40mm.
Providing and fixing concealed center point to wall ceiling & floor CPVC
(SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for
potable water of following dia. nominal bore tube fittings and clamps
including making good the wall, ceiling and floor etc. complete. [F] 50mm.
Providing and fixing stainless steel hand dryer (Heavy Traffic ) all
complete as directed by the Engineer-in-Charge.
Providing and fixing concealed center point to wall ceiling & floor CPVC
(SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for
potable water of following dia. nominal bore tube fittings and clamps
including making good the wall, ceiling and floor etc. complete.[A] 15 mm.
Providing and fixing concealed center point to wall ceiling & floor CPVC
(SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for
potable water of following dia. nominal bore tube fittings and clamps
including making good the wall, ceiling and floor etc. complete. [B] 20 mm.
Providing and fixing concealed center point to wall ceiling & floor CPVC
(SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for
potable water of following dia. nominal bore tube fittings and clamps
including making good the wall, ceiling and floor etc. complete. [C] 25 mm.
Providing and fixing concealed center point to wall ceiling & floor CPVC
(SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for
potable water of following dia. nominal bore tube fittings and clamps
including making good the wall, ceiling and floor etc. complete. [D] 32mm.
Providing and fixing concealed center point to wall ceiling & floor CPVC
(SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for
potable water of following dia. nominal bore tube fittings and clamps
including making good the wall, ceiling and floor etc. complete. [E] 40mm.
Providing and fixing concealed center point to wall ceiling & floor CPVC
(SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for
potable water of following dia. nominal bore tube fittings and clamps
including making good the wall, ceiling and floor etc. complete. [F] 50mm.
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having
thermal stability for hot & cold water supply, including all CPVC plain &
brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m
spacing.This includes jointing of pipes & fittings with one step CPVC
solvent cement and the cost of cutting chases and making good the same
including testing of joints complete as per direction of Engineer in Charge.
Internal work - Exposed on wall
a 65 mm dia nominal bore 145.00 metre 1491.00 14.91 1505.91
b 80 mm dia nominal bore 20.00 metre 1893.00 18.93 1911.93
Providing and fixing 600mm x 450mm bevelled edge mirrror of superior
222 glass mounted on 6mm thick A.C. sheet or plywood sheet and fixing to 107 each 825.48 8.25 833.73
wooden pluge with C.P. brass screws and washers.
Providing and fixing gun metal gate valve with C.I. wheel of approved
quality (screwed end) :
Providing and fixing Gun metal check or non-return fullway wheel valve.(B)
Providing and fixing Gun metal check or non-return fullway wheel
valve.(C) 25mm dia.
Providing and fixing Gun metal check or non-return fullway wheel
valve.(D) 32mm dia.
Providing and fixing Gun metal check or non-return fullway wheel valve.(E)
Providing and fixing gun metal gate valve with C.I. wheel of approved
quality (screwed end) :
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
a) 50 mm dia. nominal bore 3 each 861.43 8.61 870.04
b) 65 mm dia. nominal bore 2 each 1461.78 14.62 1476.40
Supply ,Erection , Testing & Commissioning of Automatic water level
control panel & related accessories for pumping automation with
228 consisting of automatic water level controller , level sensor with stainless
steel probe, motorized butterfly valve, motorized valve controller with
complete in all respect.
upto 50 mm dia. nominal bore 5 each 67496.00 674.96 68170.96
Providing and fixing Stainless steel braided connection pipe with brass
unions :45 cm length and 15 mm dia
230 Providing and fixing C.P. Angle stop cock 15 mm Heavy duty with cap 304 each 504.00 5.04 509.04
Providing and fixing hand held ablution fitting (health faucet) with one
231 meter long flexible tube and wall hook, all complete approved engineer-in- 95 each 705.00 7.05 712.05
Supply and fixing of 15mm CP brass 2 -Way Bib Cock with wall flange and
232 suitable length CP brass extension pipe all of approved engineer-in- 97 each 1276.00 12.76 1288.76
Providing and fixing Sink Cock with swinging casted spout ( cat. No. LYR
38347 equivalent ) of approved quality
Supply Installation Testing Commissioning of water Cooler with all
required accessories to complete the job including appropriate Prefilter
with its housing and Pipe at the inlet of water cooler appropriate Level
Sensor for Water Cooler for switching UV Lamp as direction of
Engineering in charge.The details as below:
Minimum Storage Capacity 80L, Minimum Cooling Capacity 150L/Hr,No of
faucets 01+01 nos ( 1 Normal,1 Cool),Front Tray drain pipe system,
Hermetically sealed reciprocating compressor having R-134 a
refrigerant,Cabinet Material Stainless steel AUG J1 grade,Stainless Steel
Water Tank with float type sensor, Warranty on Cooler and other parts:
Minimum 1 years,Supply Volatge-230 V AC,Make of the water Cooler-
Voltas/ Blue Star/ Aquaguard / Usha
After installation the agency should submit the test report of functioning of
all its parts like Float Sensor,Cooling etc. The Unit and its accessories
should be leackage free during the warranty period,any leackages found
during warranty period agency should attend it on their own cost.
Providing and fixing Stainless Steel pipe and fitting of grade 316L as per
IS 6911:2017 and conforming to EN-10312 standards complete with press
type fitting (fitting shall be paid for separately) i/c fixing of the pipe with
235 clamps at 1.00 m spacing including cutting and making good the walls
including testing of joints complete as per direction of Engineer-in-charge.
(The pipe length inserted in the fitting shall not be measured for payment)
Inernal work - Exposed on wall
a 22 mm outer dia pipe 20.00 metre 719.88 7.20 727.08
b 28 mm outer dia pipe 16.00 metre 897.05 8.97 906.02
c) 35 mm outer dia pipe 16.00 metre 1244.84 12.45 1257.29
d 42 mm outer dia pipe 50.00 metre 1498.62 14.99 1513.61
Providing and fixing Stainless Steel pipe and fitting of grade 316L as per
IS 6911:2017 and conforming to EN-10312 standards complete with press
type fitting (fitting shall be paid for separately) i/c fixing of the pipe with
236 clamps at 1.00m spacing and also including cutting of chases and making
good the walls including testing of joints complete as per direction of
Engineer -in-charge. (The pipe length inserted in the fitting shall not be
measured for payment)
Internal work - Concealed Pipe
a 15 mm outer dia pipe 20.00 metre 639.37 6.39 645.76
b 22 mm outer dia pipe 20.00 metre 863.36 8.63 871.99
Providing and fixing required Stainless Steel Fitting of press fit design of
grade 316L as per IS 6911:2017 and conforming to EN-10312 standards
with V-profile and with O-ring sealing gasket of EPDM material of required
dia as per direction of Engineer-in-charge.
Coupling/Socket
a For 22 mm outer dia pipe 10 each 303.11 3.03 306.14
b For 28 mm outer dia pipe 8 each 353.62 3.54 357.16
c) For 35 mm outer dia pipe 8 each 443.45 4.43 447.88
d For 42 mm outer dia pipe 25 each 600.60 6.01 606.61
Providing and fixing required Stainless Steel Fitting of press fit design of
grade 316L as per IS 6911:2017 and conforming to EN-10312 standards
with V-profile and with O-ring sealing gasket of EPDM material of required
dia as per dirction of Engineer-in-charge.
For 22mm x 15 mm outer dia pipe 10 each 286.25 2.86 289.11
Providing and fixing required Stainless Steel Fitting of press fit design of
grade 316L as per IS 6911:2017 and conforming to EN-10312 standards
with V-profile and with O-ring sealing gasket of EPDM material of required
dia as per direction of Engineer-in-charge.
Female Thread Connector/ Adapter
For 15 mm outer dia x 1/2" mm nominal dia threaded 10 each 493.96 4.94 498.90
Providing and fixing required Stainless Steel Fitting of press fit design of
grade AISI 304 conforming to JWWA G116 standard with V-profile or M-
profile and with O-ring sealing gasket of EPDM material of required dia as
per direction of Engineer-in-charge.
Valve Connector
a For 22.22 mm outer dia x 15 mm nominal dia threaded 20 each 314.31 3.14 317.45
b For 22.22 mm outer dia x 20 mm nominal dia threaded 20 each 348.00 3.48 351.48
c For 28.58 mm outer dia x 25 mm nominal dia threaded 10 each 477.09 4.77 481.86
Supply and fixing HDPE double wall corrugated ( DWC ) I.S 16098 ( Part -
2 ) 3013 for soil / waste pipe under ground drainage system with jointed
241 with rubber ring with good quality lubricant for fittings, inclusive of all
necessary specials like bends, tees, offsets, junctions, etc complete.
a 150 mm diameter 80.00 metre 496.00 4.96 500.96
b 200 mm diameter 263.00 metre 665.00 6.65 671.65
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and fixing S.W. gully trap with C.I. grating brick masonry
chamber and water tight C.I. cover with frame of 300mm x 300mm size
(inside) with standard weight.(i) Square mouth traps.(B) 150mm x 100mm
size P or R type
Providing laying (to level or slopes) and jointing reinforced concrete Light
duty non-pressure pipes I.S. class NP2 of the following internal diameter
with collars and butt ends prepared for collar joints including testing of
joints complete.(B) 150mm
Providing laying (to level or slopes) and jointing reinforced concrete Light
duty non-pressure pipes I.S. class NP2 of the following internal diameter
with collars and butt ends prepared for collar joints including testing of
joints complete.(C) 250mm
Constructing Manhole with R.C.C. top slab in 1:2:4 mix (1- cement :2-
coarse sand : 4-graded stone aggregate 20mm nominal size) foundation
concrete 1:3:6 mix (1-cement : 3- coarse sand :6-Brick bats 40 + 50mm
size) inside plastering 15mm thick with Cement Mortar 1:3 (1-Cement : 3-
coarse sand) finished with a floating coat of neat cement and making
channels in cement concrete 1:2:4 mix (1-Cement :2-Coarse sand :4-stone
245 aggregate 20mm nominal size) finished smooth complete including curing 20 each 10920.76 109.21 11029.97
and festing (i) Inside size 900mm x 1200mm and 1.5M. deep including C.I.
cover with frame size 560mm diameter total weight of cover and frame to
be not less than 128 kgs. (Wt. of cover 64 Kg. and Wt. of frame 64 Kg.)(A)
With 230mm thick walls of brick msonry using brick having crushing
strength not less than 35Kg. / Sq.cm. in Cement Mortar 1:5 (1- Cement: 5-
Coarse sand) (1) A type depth 0.90 Metre for 150mm diameter sewer.
Constructing Manhole with R.C.C. top slab in 1:2:4 mix (1-cement :2-
oarse sand : 4-graded stone aggregate 20mm nominal size) foundation
concrete 1:3:6 mix (1-cement : 3- coarse sand :6-Brick bats 40 + 50mm
size) inside plastering 15mm thick with Cement Mortar 1:3 (1-Cement : 3-
coarse sand) finished with a floating coat of neat cement and making
channels in cement concrete 1:2:4 mix (1- Cement :2-Coarse sand :4-
stone aggregate 20mm nominal size) finished smooth complete including
curing and festing (i) Inside size 900mm x 1200mm and 1.5M. deep
including C.I. cover with frame size 560mm diameter total weight of cover
and frame to be not less than 128 kgs. (Wt. of cover 64 Kg. and Wt. of
frame 64 Kg.)(A) With 230mm thick walls of brick msonry using brick
having crushing strength not less than 35Kg. / Sq.cm. in Cement Mortar
1:5 (1- Cement: 5-Coarse sand) (2) B type depth 1.50 Metre for 150mm
diameter sewer.
Constructing Manhole with R.C.C. top slab in 1:2:4 mix (1-cement :2-
coarse sand : 4-graded stone aggregate 20mm nominal size) foundation
concrete 1:3:6 mix (1-cement : 3- coarse sand :6-Brick bats 40 + 50mm
size) inside plastering 15mm thick with Cement Mortar 1:5 (1-Cement : 5-
coarse sand) finished with a floating coat of neat cement and making
channels in cement concrete 1:2:4 mix (1- Cement :2-Coarse sand :4-
stone aggregate 20mm nominal size) finished smooth complete including
curing and festing (i) Inside size 900mm x 1200mm and 1.5M. deep
including C.I. cover with frame size 560mm diameter total weight of cover
and frame to be not less than 128 kgs. (Wt. of cover 64 Kg. and
Wt. of frame 64 Kg.)(A) With 230mm thick walls of brick msonry using
brick having crushing strength not less than 35Kg. / Sq.cm. in Cement
Mortar 1:5 (1- Cement: 5-Coarse sand) (3) C type depth 2.25 Metre for
150mm diameter sewer.
(A) With 230mm thick walls of brick msonry using brick having crushing
248 strength not less than 35Kg. / Sq.cm. in Cement Mortar 1:5 (1- Cement: 5- 3 each 29952.74 299.53 30252.27
Coarse sand) (4) D type depth 3.15 Metre for 150mm diameter sewer
(I) Extra rate for constructing B.B. masonry for every additional depth of
0.1M. or Part thereof over item No.24.27 (I) for depth from 0.9M to 1.5M.
Providing and fixing cast iron steps of size 500mm x 150mm x 22.5mm and
painting with two coats of Anti-corrosive paint etc. complete.
Constructing Brick masonry road gully chamber 500mm x 450mm x
251 600mm including 500mm x 450mm C.I. horizontal grating wih frame 26 each 1997.22 19.97 2017.19
Constructing brick masonry chamber for underground C.I. Inspection
chamber and bends with bricks having crushing strength not less than
35Kg/Cm2 in C.M. 1:5 C.I. cover with frame (Light duty) 455mm x 610mm
intenal dimensions total weight of cover with frame to be not less than
38Kg. (Wt. of cover 23 Kg.) and Wt. of frame 15Kg. ) (R.C.C. top slabe
with 1:2:4 mix (1-cement :2- coarse sand :4-graded stone aggregate 20mm
size) foundation concrete 1:5:10 inside plaster 15mm thick with cement
mortar 1:3 finished smooth with a floating coat of neat cement on walls
and bed concrete etc. complete.(i) Inside dimensions 455mmx 610mm and
450mm deep for single pipe line.
External water supply
Providing and fixing brass ferrule with C.I. mouth cover including boring
and tapping the main :
25 mm nominal bore 3 each 408.46 4.08 412.54
Providing and fixing of cast iron sluice valves ( with cap ) complete with
254 bolts, nuts, rubber insertions etc. ( the tail pieces if required will be paid
a 100 mm diameter
b 150 mm diameter
Providing and fixing C.I. double acting air valve of approved quality with
255 bolts, nuts, rubber insertion etc. complete ( The tail pieces, tapers etc if
required will be paid separately) :
Providing and fixing G.I. pipes complete with G.I. fittings including
trenching and refilling etc.
a 65 mm dia nominal bore 35.00 meter 752.31 7.52 759.83
b 80 mm dia nominal bore 36.00 meter 874.06 8.74 882.80
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and fixing HDPE pipes,PE-63 8kgf/cm2 to IS confirming IS 4984-
1995 having thermal stability for hot & cold water supply including all
257 threaded fittings. This includes jointing of pipes & fittings with one step
HDPE solvent cement, trenching, refilling & testing of joints
complete as per direction of Engineer in Charge.
25 mm nominal outer dia pipe 35.00 metre 137.00 1.37 138.37
32 mm nominal outer dia pipe 20.00 metre 164.00 1.64 165.64
50 mm nominal outer dia pipe 20.00 metre 267.00 2.67 269.67
75 mm nominal outer dia pipe 10.00 metre 484.00 4.84 488.84
100 mm nominal outer dia pipe 20.00 metre 925.00 9.25 934.25
Constructing masonry Chamber 30x30x50 cm inside, in brick work in
cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I.
surface box 100x100 x75 mm (inside) with hinged cover fixed in cement
concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone
258 aggregate 20 mm nominal size), i/c necessary excavation, foundation
concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate
40mm nominal size ) and inside plastering with cement mortar 1:3 (1
cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat
cement complete as per standard design :
With common burnt clay F.P.S.(non modular) bricks of class designation
Rain Water Harvesting & Tubewell
Boring/drilling fore well of required dia for casing/ strainer pipe, by suitable
method prescribed in IS: 2800 (part I), including collecting samples from
difberent strata, preparing and submitting strata chart/ fore log, including
hire & running charges of all equipments, tools, plants & machineries
required for the job, all complete as per direction of Engineer -in-charge,
upto 90 metre depth below ground level.
All types of soil
Boring/drilling fore well of required dia for casing/ strainer pipe, by suitable
method prescribed in IS: 2800 (part I), including collecting samples from
difberent strata, preparing and submitting strata chart/ fore log, including
hire & running charges of all equipments, tools, plants & machineries
required for the job, all complete as per direction of Engineer -in-
charge,beyond 90 metre depth below ground level.
All types of soil
Supplying, assembling, lowering and fixing in vertical position in bore well,
ERW (Electric Resistance Welded) FE 410 mild steel screwed and
socketed/plain ended casing pipes of required dia, conforming to IS:
261 of reputed & approved make, including painted with outside surface with
two coats of anticorrosive paint of approved brand and manufacture,
including required hire & labour charges, fittings & accessories, all
complete, for all depths, as per direction of Engineer-in-charge.
200 mm nominal size dia having minimum wall thickness 5.40 mm 425.00 metre 2049.63 20.50 2070.13
Supplying, assembling, lowering and fixing in vertical position in bore well,
ERW (Electric Resistance Welded) FE 410 plain slotted (having slot of
size 1.6/3.2 mm) mild steel threaded and socketed/ plain bevel ended pipe
(type A) of required dia, conforming to IS: 8110, of reputed and approved
262 make, having wall thickness not less than 5.40 mm, including painted with
outside surface with two coats of anticorrosive bitumestic paint of
approved brand and manufacture, ncluding hire & labour charges, fittings
& accessories, all complete, for all depths, as per direction of Engineer -in-
200 mm nominal size dia 425.00 metre 2157.28 21.57 2178.85
Supplying, filling, spreading & leveling stone boulders of size range5 cm to
263 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all 7.95 Cum 1266.82 12.67 1279.49
complete as per direction of Engineer-in-charge.
Supplying, filling, spreading & leveling gravels of size range 5 mm to
mm, in the recharge pit, over the existing layer of foulders, in required
thickness, for all leads & lifts, all complete as per direction of Engineer-in-
Supplying, filling, spreading & leveling coarse sand of sizerange 1.5 mm to
265 2 mm in recharge pit, in required thickness over gravel layer, for all leads 7.95 Cum 1290.69 12.91 1303.60
& lifts, all complete as per direction of Engineer -in-charge.
Gravel packing in tubewell construction in accordance with IS:
including providing gravel fine/ medium/ coarse, in required grading &
sizes as per actual requirement, all complete as per direction of Engineer-
Providing and fixing factory made precast RCC perforated drain covers,
having concrete of strength not less than M-25, of size 1000 x 450x50 mm,
reinforced with 8 mm dia four nos longitudinal & 9 nos cross sectional
T.M.T. hoop fars, including providing 50 mm dia perforations @ 100 to
mm c/c, including providing edge finding with M.S. flats of size 50 mm x
1.6 mm complete, all as per direction of Engineer-in-charge.
Development of tube well in accordance with IS : 2800 (part I) and IS:
11189, to establish maximum rate of usable water yield without sand
content (beyond permissible limit), with required capacity air compressor,
running the compressor for required time till well is fully developed,
measuring yield of well by “V” notch method or any other approved
method, measuring static level & draw down etc. by step draw down
method, collecting water samples & getting tested in approved laboratory,
i/c disinfection of tubewell, all complete, including hire & labour charges of
air compressor, tools & accessories etc., all as per requirement and
direction of Engineer-in-charge.
Providing and fixing M.S. clamp of required dia to the top of
269 casing/housing pipe of tubewell as per IS: 2800 (part I), including
necessary bolts & nuts of required size complete.
Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of
pipe assemfly of tubewell as per IS:2800 (part I).
STP / WATER TREATEMENT EQUIPMENT & SUPPLY PUMPS
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Design, Construction ,Supplying, installing, testing & commissioning of
Sewage Treatment Plant of 50m3/day based on MBR technology
(Excluding excavation, back filling & disposal of surplus earth MS / Civil
construction work) for the following duty:
Nature of Sewage - Domestic Sewage from Kitchen, Pantry and human
waste for STP and from lab fro ETP.
The sewage treatment plant shall include the following items: Screen
Chamber,Oil & Grease Trap,Reaction Tank,Clear Water Tank,Sewage
equalization tank/sump,,Aeration Tank,,Sludge Holding Tank,Air Blowers,
Pump sets & other equipment including submersible pumps in the
drainage sump,Effluent,Sludge,,Tertiary Treatment,Irrigation, Flushing &
Soft water pumpsets,Inlet and Outlet connection to Treated water storage
Tanks,Electrical Control Panel & Cabling, earthing etc.,Piping, valves and
Instrumentation including level controllers, pressure gages, sensors,
rotameters and indicating cum recording meters for incoming sewage and
outgoing treated effluents etc.,Contractor shall ensure submission of
detailed GA drawings (Plan & Section), P&I diagram, schematic diagram
for the above said components and equipment and additional component if
so required for the complete working of the STP /ETP. The following list of
civil units shall be in Client's Scope. However the size and design of the
civil constructions required shall be given and guaranteed for its efficacy
by the contractor for which the contractor shall take full responsibility, Bar
screen pit, Oil & Grease Chamber,Equalisation Tank,Sewage
equalization tank/sump, Anoxic Tan,Aeration Tank,Sludge Holding Tank,
Final Traeted water tank,Drain Sump for STP room,The STP shall consist
of following units but not limited to these unit as may be required by the
manufacturer's design.
The STP shall be designed based on the following parameters:
Daily average flow : 50 m3/Day
BOD5 : 50- 80 mg/l
S. Solids : 50- 80 mg/l
COD : 50- 80 mg/L
Oil & Grease : 20-30mg/L
ELECTRICAL INSTALLATION FOR SEWAGE TREATMENT PLANT
Note : The mentioned ratings are for estimation purpose it may change as
per final technical submittal. The Vendors are advised to quote as per
actual. Design, fabrication, assembling, wiring, supply, installation, testing
and commissioning of motor control centre shall be fabricated out of
gauge CRCA sheet steel in form in 3b formation with reinforcement of
suitable size angle iron, channel ‘T’ sections irons and /or flats wherever
necessary. Cable gland plates shall be provided on top as well as at the
bottom of the panels. Panels shall be treated with all anticorrosive process
before painting as per specifications with 2 coats of red oxide primer and
final approved shade of powder coated paint. 2 Nos. earthing terminals
shall be provided for 3 phase, 4 wire, 50 Hz supply system. Lifting hooks
shall also be provided in case of large panels. Approval shall be taken for
each panel before fabrication. Cadmium Plated hardware shall be used in
fabrication of panels. Quoted rates shall inclusive of cables, cable trays,
control cabling, earthing (in accordance to specification) with earthing from
panel to each motor / equipment. MCC –1 (Sewage Treatment Plant)
Incoming 100 amps TPN MCCB with the following accessories: - 1 No
STP Describe as above item with complete in all respect.
Sub Head XX : Fire Fighting System
Supplying, installing, testing and commissioning of flooded Vertical Inline
cetrifugal pump set with stainless steel body , stainless steel impller and
SS shaft capable to deliver of following capacity and head. given by TFC
squirrels induction motor suitable for operation on 415 volt , 50 HZ AC
power supply running speed 2900 RPM .The installation shall be complete
with all necessary ancillaries & accessories including base plate , coupling
guard etc complete as required.
Flow rate : 150 LPM
Required for : UG T ( Domestic Water & Flusing Water ) 4 set 80557.98 805.58 81363.56
Supply, installation, testing and commissioning of continuous duty
submersible centrifugal non-clogging drainage pumps complete with
phase motor with all necessary protection and mechanical seal etc.
complete with all ancillaries etc required.
Flow rate : 100 LPM
Solid Handling : 10 – 12 MM
Purpose : Drainage
Supply, installation, testing & commissioning of electric driven main fire
274 pump suitable for automatic operation and consisting of following:
complete in all respect as required.
Horizontal type, multistage, centrifugal, split casing pump of cast iron body
& bronze impeller with stainless steel shaft, mechanical seal to ensure a
minimum pressure of 3.5 kg/sp.cm. at highest and farthest oulet at
specified flow of 2850 lpm at 88M. head conforming to IS
Suitable HP SQ cage induction motor, TEFC, synchronous speed
RPM, suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP
protection for enclosure, horizontal foot mounted type with Class-'F'
insulation, conforming to IS-325.
M.S. fabricated Common base plate, coupling, coupling guard, foundation
bolts etc. as required.
Suitable cement concrete foundation duly plastered with anti vibration
Supplying, Installation, Testing and Commissioning of diesel engine driven
275 main fire pump suitable for automatic operation and consisting of
following: complete in all respect as required.
Horizontal type, multistage, centrifugal, split casing pump of cast iron body
& bronze impeller with stainless steel shaft, mechanical seal to ensure a
minimum pressure of 3.5 kg/sp.cm. at highest and farthest oulet at
specified flow of 2850 lpm at 88M. head conforming to IS
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Suitable HP, 1500 RPM water cooled with radiator, diesel engine
conforming to relevant BS & IS standard complete with auto starting
mechanism, 12 volts/24 Volts electric starting equipment, sealed
maintenance free batteries, Diesel Tank, exhaust pipe extended upto 1 m.
outside pump house duly insulated with 50 mm. thick glass wool with
mm. thick aluminium sheet cladding, residential silencer, instruments and
protection as per specification, stop solenoid for auto stop in the event of
fault with audio indications, painted with post office red colour etc. as
M.S. fabricated Common base plate, coupling, coupling guard, foundation
bolts etc. as required.
Suitable cement concrete foundation duly plastered with anti vibration
Supplying, Installation, Testing and Commissioning of electric driven
276 pressurisation pump suitable for automatic operation and consisting of
following: complete in all respect as required.
Horizontal type, multistage, centrifugal pump of cast iron body and
bronze impeller with stainless steel shaft, mechanical seal and flow of
lpm, at 88M head conforming to IS:1520.
Suitable HP SQ cage induction motor, TEFC, synchronous speed
RPM, suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP
protection for enclosure, horizontal foot mounted type with Class-'F'
insulation, conforming to IS-325.
M.S. fabricated Common base plate, coupling, coupling guard, foundation
bolts etc. as required.
Suitable cement concrete foundation duly plastered with anti vibration
Fabrication, Supplying, Installation, Testing & Commissioning of electrical
control panel of cubical construction, floor mounted type, fabricated out of
2mm thick CRCA sheet, compartmentalised with hinged lockable doors,
dust and vermin proof, powder coated of approved shade after 7 tank
277 treatment process, cable alley, inter-connection, having switchgears and
accessories mounting and internal wiring, earth terminals, numbering etc.
complete in all respect, suitable for operation on 415 V, 3 phase, 50 HZ.
AC supply with enclosure protection class IP 42 as required.
COMMON PANEL IN FIRE PUMP HOUSE
a) 630 Amps. TP & MCCB 50 KA
b) Voltmeter (0-500 Volts) with selector switch
c) Ameter (0-300 Amps.) with selector switch & CT's etc
d) Set of 3 Phase indicating lamp.
e) Set of Al. bus bar 500 Amps.
OUTGOING : ( Electrical Fire / Sprinkler Pump )
2 Nos Electrical Driven fire Pump. 250 Amps. TP& MCCB-35K with
suitable HP fully automatic star/delta starter with over load protection,
current sensing type single phase preventor complete with all accessories
and internal wiring required for automatic operation, selector switch for
local/remote, auto/manual/OFF operation.
2 Nos Jockey pump. 100 Amps. TP & N MCCB-25 KA with suitable HP
fully automatic star/delta starter with over load protection, current sensing
type single phase preventor complete with all accessories and internal
wiring required for automatic operation, selector switch for local/remote,
auto/munual/OFF operation.
DIESEL ENGINE CONTROL
Control for Diesel Engine comprising:-
Auto/Manual selector switch & 3 attempt starting device, timers and relays
as required, push buttons, start/stop in manual mode.
Indication lamp for High/Low Lub. Oil pressure, High Water Temp. and
Engine ON indication.
Battery charger suitable for 12 V/24V DC with boost and tickle selector
switch, 0-15 V/ 0-30 V Dcvolt merer, 0-20A DC Ammeter.
All standard relays and accessories for automatic operation of diesel
SYSTEM CONTROLLER
Designing, Supply, Installation, Testing and Commissioning of system
controller to control operation of Main Electric Fire Pump, Diesel Pump,
278 Pressurisation Pump, in sequence as per specification consisting of 1 Set 393980.53 3939.81 397920.34
relays, times, sensors, annunciation window for fault indication, complete
as per specification.
Suitable cement concrete foundation duly plastered with anti vibration
Supplying and making end termination with brass Compression Gland &
279 Al.lugs for following sizes of PVC insulated, PVC sheathed/XLPE
Al.conductor cables of 1.1 KV grade as required
Supplying and installing following size of perforated painted with powder
coating M.S. cable trays with perforation not more than 17.5%, in
280 convenient sections, joined with connectors, suspended from the ceiling
with M.S. suspenders including bolts & nuts, painting suspenders etc. as
150 mm width x 50mm depth x 1.6 mm thickness. 15.00 Meter 575.60 5.76 581.36
Supplying & laying one number XLPE insulated PVC sheathed Aluminium
Conductor armoured UG cable of 1.1 KV grade Conforming to IS
281 7098/1988 with upto date ammendment of following size in the existing
RCC/HUME/ METAL /GI /CI /Stoneware/DWC pipe/ masonary Open Duct/
cable tray/ open in air etc. as requred.
4 core, 25 sq.mm. Aluminium Armoured 120.00 Meter 384.00 3.84 387.84
3.5 core, 50 sq.mm. Aluminium Armoured 100.00 Meter 576.00 5.76 581.76
3 core, 120 sq.mm. Aluminium Armoured 50.00 Meter 1006.00 10.06 1016.06
3.5 core, 300 sq.mm. Aluminium Armoured 75.00 Meter 2723.00 27.23 2750.23
Earthing with GI Earth plate 600 mm x 600 mm x 6 mm th.including
accessories and providing masonry enclosure with cover plate having
locking arrangement and watering pipe with charcoal or coke and salt
complete as required.
Providing & fixing 25 mm x 5 mm G.I. Strip in 40 mm dia GI pipe from
283 earth electrode including connections with GI nut, bolt, spring, washer 75.00 metre 633.50 6.33 639.83
excavation and re-filling etc. as required.
Providing & fixing 25 mm x 5 mm G.I. Strip in on surface or in recess for
connections etc as required.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and fixing 6 SWG dia G.I wire on surface or in recess for loop
earthing as required.
Supplying and installing following size of perforated painted with powder
coating M.S. cable trays with perforation not more than 17.5%, in
286 convenient sections, joined with connectors, suspended from the ceiling
with M.S. suspenders including bolts & nuts, painting suspenders etc. as
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe
conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers,
nuts bolts, gaskets etc. in ground including excavation & providing cement
concrete blocks as supports, anticorrosive treatment with coaltar/asphalt
tape as per IS 10221, refilling the trench etc. of following sizes complete
Providing, laying, testing & commissioning of 'C' class heavy duty MS
pipe conforming to IS 3589 and 1239 including fittings like elbows, tees,
flanges, tapers, nuts bolts, gaskets etc., fixing the pipe on the wall/ceiling
with suitable clamps and painting with two or more coats of synthetic
enamel paint of required shade complete as required.
Supplying and fixing single headed internal hydrant valve with
instantanous Gun metal couplings of 63mm dia with cast iron wheel ISI
marked conforming to IS 5290 (Type-A) with blank Gunmetal cap and
chain as required
Supplying and fixing Single headed external yard hydrant valve with 1 No.
63 mm dia instantaneous FM Gun metal coupling and cast iron wheel, ISI
marked, conforming to IS 5290 (type A) with blank Gunmetal cap and
chain as required.
Supplying, fixing, testing and commissioning of following size butterfly
291 valve (manual) with CI body SS disc nitrile sheet & O-ring & PN
pressure rating as specified.
Supplying, fixing, testing and commissioning of double flanged sluice
valve of rating PN with non rising spindle, bronze/gun metal seat, ISI
marked complete with nuts bolts washers, gaskets and conforming to IS
780 of following size asrequired:
Supplying and fixing orifice plate made out of 6 mm thick stainless steel
(Grade 304) with orifice of required size to be fitted between flange &
landing valve of external and internal hydrants to reduce pressure at the
outlet to the level of 3.5 kg/cm2 complete as required.
Supplying, fixing, testing and commissioning, of following sizes of non
return valve with C I body
Supplying, fixing, testing and commissioning of following size Y-Strainer of
295 ductile CI body flanged ends with stainless steel strainer as specified.
Supplying and fixing 63mm dia, 15mtr. Long RRL hose pipe with 63mm
296 dia Male and Female Gun metal couplings duly binded with GI wire, rivets 76 each 4577.11 45.77 4622.88
etc. conforming to IS 636 (type-A) as required.
Supplying and fixing First-Aid-Hose Reel with MS construction spray
297 painted in Post office Red, conforming to IS 884 with upto date
amendments, complete with the following as required.
30 m long 20mm (nominal internal) dia water hose Thermoplastic (Textile
reinforced) Type-2 as per IS:
20 mm (nominal internal) dia gun metal globe valve & nozzle.
Drum and brackets for fixing the equipments on wall.
Connections from riser with 40 mm dia stop valve (gun metal) & M.S. Pipe
Supplying and fixing fire hose cabinet fabricated from 16 gauge M.S.
Sheet with single or double glazed front door (with 4 mm thick glass) and
298 locking arrangement, painted fire red with stove enamelled paint "FIRE
HOSE" written on front including necessary supports approximate size.
a)750mm x 600mm x 250mm deep. (External) 7 each 10520.00 105.20 10625.20
Providing and fixing Fire hose cabinet door (40mm x 40mm x 5mm) angle
depth fabricated with 2100mm x 1200mm MS sheet. Complete in all
respect with 25mmx25mmx3mm angle frame all around and stiffened in
between i/c hinges, handle, locking arrangement, painting with approved
synthetic enamel paint i/c sign writing on glass at internal hydrant
including providing & fixing S.S. sheet 2mm thick on remaining portion
above door to close opening i/c painting etc. as required. Glass shall be
Supply and fixing 63mm dia Gun Metal branch pipe with 20mm (nominal
internal diameter) size Gun Metal nozzle conforming to IS 903, suitable for
instantaneous connection to interconnect hose pipe coupling as required.
Supplying and fixing following fire brigade connection of cast iron body
with Gun metal male instantaneous inlet couplings complete with cap and
chain as required for 150mm dia MS pipe connection, conforming to IS
904 as required.
2 Way FBC of Cl body 3 each 6093.30 60.93 6154.23
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
4 Way FBC of Cl body 1 each 12434.97 124.35 12559.32
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet,
1200 mm in height with Air release valve on top and flanged connection
302 to riser, drain arrangement with 25 mm dia Gun metal wheel valve, with 4 each 16279.58 162.80 16442.38
required accessories, pressure gauge and painting with synthetic enamel
pain of approved shade as required.
Providing fixing testing & commissioning of 15 mm size quartzoid bulb type
303 sprinklers, of rating 68 degree C. pendent / upright with required
Sprinkler (Pendent / Upright) 4003 each 502.60 5.03 507.63
Side Wall Speinkler 220 each 502.60 5.03 507.63
Providing & fixing of pressure switch in M.S. pipe line including
connection etc. as required.
Providing & fixing Auto Air release valve for fire hydent and sprinkler,
suitable for pressure not less than 15 Kg/Sq.cm.
Providing & fixing flow switch in following sizes M.S. pipe including
connection etc as required.
Providing and fixing in position the industrial type pressure gauges with
gun metal / brass valves complete as required
Providing and fixing stainless steel standard Fireman's Axe with heavy
308 insulated rubber handle tested to 20000 volts as per IS : 926 complete. 31 each 711.00 7.11 718.11
Supply, installation, testing and commissioning of 150 mm dia Installation
Control Valve inclusive of 2 nos 150 mm dia Butterfly Valve, strainer,
Alarm Valve with Water Motor Gong, Pressure Gauges, Test Lines with
309 Ball Valves with necessary MS Class "C" piping with threaded fittings of 1 each 42628.80 426.29 43055.09
required sizes. It should be complete as per manufacturer's specifications
& as directed by Engineer- in-charge.
Providing, installing, testing & commisioning of fire brigade draw out
connection (fire department connection) with suction pipe MS class 'C'
mm dia. & 100 mm dia. foot valve & steel chain including wall mounted box
M.S. construction made out of 16 gauge MS Sheet with glass door to
310 house the above mentioned componenets. It should be complete as per 1 each 7699.00 76.99 7775.99
manufacturer's specifications & as directed by Engineer- in-charge. (to be
connected to static water tank) It should be complete as per
manufacturer's specifications & as directed by Engineer- in-charge.
Providing and fixing mechanical foam type(ISI marked) fire extinguishers
consisting of welded M.S. cylindrical body squeeze lever discharge valve
30 cm long high pressure discharge hose, discharge nozzle suspension
bracket ISI marked as per IS 933 finished externally with red enamel paint
and fixed to wall with brackets complete with internal charger.
Capacity 6 kg. I.S.I. Marked. 45 each 2947.00 29.47 2976.47
Providing and fixing Carbon-di-oxide fire extinguishers consisting of
welded M.S cylinderical body,squeeze lever discharge valve fitted with
internal dischargetube, 30cms long high pressure discharge hose,
discharge nozzle, suspension bracket, confirming to IS : 934 finished
externally with red enamel paint and fixed to wall with brackets with rawl
plug/dash fasteners complete with internal charge.
Capacity 4.5 kg. I.S.I. Marked. 45 each 8537.00 85.37 8622.37
Sub Head - I - Point Wiring
Point wiring for light/bell with 2X1.5 sq. mm & earth wire of 1.5 sq.mm
(Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi
strand copper wires up to 10 mtr length in below type of pipe erected with
6A Modular type switch/bell push & accessories and earth continuity of
313 following type erected on PVC/metallic/wooden Box single mounting base
frame, covered with textured/metalic white front plate modules erected on /
in wall / ceiling as per pipe erected with necessary lamp holder/ ceiling
rose/ H.D Connector as directed.
(f) with medium class Rigid PVC pipe and accessories erected concealed
in wall/ceiling complete
Point wiring for Tissino / Modular secondary light point with 2-1.5 sq.mm
& earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade
FRLS PVC insulated multi strand copper wires, in below type of pipe to be
erected complete with earth continuity and necessary connection with
primary light with accessories erected on Metal / PVC / wooden box
covered with 3 mm thick PC(Polycarbonate) / Acrylic sheet for open /
concealed wiring. with necessary Lamp holder / ceiling rose /
H.D.Connector as directed.
Note:- Maximum up to 6 mtrs length, excess will be considered as Mains
for Secondary Point.
(f) with medium class Rigid PVC pipe and accessories erected concealed
in wall/ceiling complete
Point wiring for Fan with 2X1.5 sq. mm & earth wire of 1.5 sq.mm (Green)
both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand
copper wires up to 10 mtr length in below type of pipe erected with 6A
Modular type switch and num free EME four or more step type electronic
fan regulator with separately mounted and accessories with earth
continuity of following type erected on PVC/ metallic /wooden Box single
mounting base frame, covered with textured/ metalic white front plate
modules erected on / in wall / ceiling as per pipe erected with necessary
ceiling rose/ H.D Connector as directed.
(f) with medium class Rigid PVC pipe and accessories erected concealed
in wall/ceiling complete
Providing following type of Modular type Accessories mounted with
PVC/metallic.wooden box, single mounting base frame covered with
textured / metallic / white front plate, modules erected with necessary
connections as per site situation directed by Engineer in charge.
(1)One No. SP 6 Amp.
(9) 16 Amp. SP one way switch
(10) 6/16Amp. Universal socket
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Supplying and fixing suitable size GI box with modular plate and cover in
front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6
317 A modular socket outlet and 2 nos. 5/6 A modular 1524 each 642.00 6.42 648.42
switch, connections etc. as required. (For light plugs to be used in non
residential buildings).
Providing & erecting insulated socket 3P+N+E with Plug 32A rating which
318 is comprised of Four pole MCB slot and insulated socket IP40 cat-III 139 each 2169.00 21.69 2190.69
Providing & erecting Mains with 1.1 KV grade FRLS PVC insulated ISI
marked standard copper conductor wire in following type of pipe to be
319 erected concealed in / flushed on wall / ceiling, with 1.5 sq.mm copper
conductor FRLS PVC insulated standard wire of green colour for earth
continuity of following size.
(A) With medium class Rigid PVC pipe and accessories
Providing & erecting Mains with 1.1 KV grade FRLS PVC insulated ISI
marked standard copper conductor wire in following type of pipe to be
320 erected in / on wall / ceiling, with 2.5 sq.mm copper conductor FRLS PVC
insulated standard wire of green colour for earth continuity of following
(A) with medium class Rigid PVC pipe and accessories
providing and erecting Mains with ISI marked, 1.5KV grade electrolyte
multi stranded, annealed copper conductor with heat resistant PVC
insulated conforms to IS 694, IEC - 227 erected in existing pipe of
following size (Specifically for control panel, relays, power switchgears,
motor starters & control wiring) with required size of copper lugs, nuts and
bolts if required.
Providing and erecting ISI mark Medium class RIGID PVC PIPES of
following size complete to be erected on/in wall or ceiling erected with
322 necessary PVC fittings & Junction boxes fixed with adhesive solution &
Clamps with following dia of pipes, in approved manner as directed
Supply & installation of surface mounted U PVC snap-on adaptable
trunking raceways, fabricated out of U-PVC to Off-White or approved
shade as per IS 733 of thickness 2.0mm for the base and sides with all
323 accessories like removable covers, joints ,height spacer,angles complete
with necessary bends, suitable sized junction boxes and tees etc,
(b)Size: 50x130 mm PVC Raceways for Power & Data with
compartments above specifications.
Supplying under floor pregalvanised corrosion proof rectangular sheet
steel cable trunking of 1.6 mm thick having with stand point load up to
Ton & free from seepage of concrete of screed water with all
324 accessories,Junction Box, Joints as required and demanded by engineer-
incharge and laying /erecting as per OEM guidelines and as per
instruction of engineer incharge having following size of dimensions and
No of compartments (W x D x T) Cat-III
[1] 50mm x 25mm x 1.6 mm with One Compartment 400.00 Mtr 295.00 2.95 297.95
[10] 150mm x 38mm x 1.6mm with Three Compartments 800.00 Mtr 758.00 7.58 765.58
[4] 225mm x 25mm x 1.6 mm with Three Compartment 600.00 Mtr 1084.00 10.84 1094.84
Providing & fixing approved make Perforated C type Cable tray, made
from sheet steel. The cable tray should be single or double bended as per
required and as per IS 2062 / 1079 and shall be coated with hot dip
325 galvanizing as per IS 2629/4759 with max 17.5% perforation with coupler
plate / fish plate and GI hardware like nut - bolt and washers etc. erection
with necessary support included) as per specification and as per
instruction of Engineer In charge.
Sub-Head - II - Panels & DB'S
Fabrication, supply, installation, testing and commissioning of wall/floor
maounted cubicle type LT panels suitable for 415 V 3 phase, 4 wire, 50 Hz
AC supply system (IP 42 degree of protection) fabricated in
compartmentalized design from CRCA sheet made out of 2 mm thick for
frame work & covers 3mm thick for gland plates including cleaning &
finishing complete with 7 tank process for powder coating in approved
shade, having TPN Al alloy bus bars of high conductivity, DMC/SMC bus
326 bar supports with short circuit withstand capacity of 31 MVA for 1 sec,
bottom base channel of MS section. Entire panel shall have a common
copper earth bar of size as per CPWD specification at the rear with 2 Nos
earth stud, interconnections from main busbar to switch gears with
required size of AL bus bar and control wiring with PVC insulated FRLS
copper conductor single core cable, cable alleys, cable gland plates etc.
providing following switch gears:
Note: All the MCCBs of capacity more than 250 Amp should be
Microprocessor based and below 250Amp it should be Thermal
1000 A, FP ACB 50 KA - 1 No.
1250 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
400 A FP MCCB, 35 KA - 2 Nos.
200 A FP MCCB, 35 KA - 3 Nos.
100 A TPN MCCB, 25 KA - 2 Nos.
63 A TPN MCCB, 25 KA - 2 Nos.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 1 each 480099.00 4800.99 484899.99
FDB- Light Panel -
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
125 A, FP MCCB 25 KA - 1 No.
200 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
63 A FP MCB, - 4 Nos.
40 A FP MCB, - 8 Nos.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 1 each 81650.00 816.50 82466.50
FDB- Light Panel -
125 A, FP MCCB 25 KA - 1 No.
200 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
40 A FP MCB, - 6 Nos.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 4 each 50378.00 503.78 50881.78
FDB- Light Panel -
160 A, FP MCCB 25 KA - 1 No.
200 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
63 A FP MCB, - 17 Nos.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 1 each 108185.00 1081.85 109266.85
FDB- Light Panel -
125 A, FP MCCB 25 KA - 1 No.
200 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
63 A FP MCB, - 10 Nos.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 2 each 78654.00 786.54 79440.54
FDB- Light Panel -
160 A, FP MCCB 25 KA - 1 No.
200 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
63 A FP MCB, - 7 Nos.
40 A FP MCB, - 7 Nos.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 1 each 95741.00 957.41 96698.41
FDB- Light Panel -
125 A, FP MCCB 25 KA - 1 No.
200 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
63 A FP MCB, - 3 Nos.
40 A FP MCB, - 7 Nos.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 5 each 76906.00 769.06 77675.06
1600 A, FP ACB 50 KA - 1 No.
2000 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
800 A, FP ACB 50 KA - 2 No.
400 A FP MCCB, 35 KA - 1 Nos.
200 A FP MCCB, 35 KA - 1 Nos.
100 A TPN MCCB, 25 KA - 2 Nos.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 1 each 790361.00 7903.61 798264.61
FDB- Power Panel -
125 A, FP MCCB 25 KA - 1 No.
200 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
63 A FP MCB, - 7 Nos.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 2 each 54373.00 543.73 54916.73
FDB- Power Panel -
125 A, FP MCCB 25 KA - 1 No.
200 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
63 A FP MCB, - 5 Nos.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Indication lamp RYB with Fuses/MCB etc. as req. 2 each 49380.00 493.80 49873.80
FDB- Power Panel -
250 A, FP MCCB 36 KA - 1 No.
300 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
63 A FP MCB, - 3 Nos.
100 A, FP MCCB 25 KA - 6 No.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 6 each 162832.00 1628.32 164460.32
FDB- Power Panel -
200 A, FP MCCB 25 KA - 1 No.
300 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
63 A FP MCB, - 2 Nos.
63 A, FP MCCB 25 KA - 4 No.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 10 each 98115.00 981.15 99096.15
400 A, FP MCCB 36 KA - 1 No.
500 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
400 A, FP MCCB 36 KA - 1 No.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 1 each 126156.00 1261.56 127417.56
Lift Panel - 4 Lifts
200 A, FP MCCB 25 KA - 1 No.
300 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
32 A DP MCB, - 3 Nos.
63 A, FP MCCB 25 KA - 5 No.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 1 each 109504.00 1095.04 110599.04
Lift Panel - 1 Lifts
63 A, FP MCCB 25 KA - 1 No.
100 A TPN AL. bus bar with coloured heat shrinkable PVC sleeve -1 Set
32 A DP MCB, - 2 Nos.
63 A, FP MCCB 25 KA - 2 No.
Multi Function Meter (MFM) with CTs & Fuses/MCB/Selecter Switch -1 Set
Indication lamp RYB with Fuses/MCB etc. as req. 1 each 68899.00 688.99 69587.99
Providing and erecting approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 25 KA at 415 V, having normal
327 current rating up to 25A to 100A, with fixed thermal & magnetic release
suitable to work on AC supply 50c/s with all internal connections &
cpomplete erected in existing 16 G.M.S housing.
ICS=100% of ICU only Cat III 64 each 6112.00 61.12 6173.12
Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 35 KA. at 415 V. having normal
current rating 125A. with Fixed thermal & magnetic release suitable to
work on A.C.supply 50 c/s. with all internal connections, spreader tinned
copper & complete erected in existing 16 G.M.S. housing.
ICS=100% of ICU only Cat III 14 each 7976.00 79.76 8055.76
Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 35 KA. at 415 V. having Normal
current rating 200A.with variable Thermal & magnetic release suitable to
work on A.C.supply 50 c/s. with all internal connections, spreader tinned
copper & complete erected in existing 16 G.M.S.housing
ICS=100% of ICU only Cat III 18 each 16061.00 160.61 16221.61
Providing and erecting Approved make Four pole moulded case
circuit breaker having breaking capacity ICU of 35 KA. and above at
415 V . having normal current rating 250A. with variable thermal
330 & magnetic release suitable to work on A.C.supply 50 c/s. with all
internal connections, spreader tinned copper & complete erected
in existing 16 G.M.S. housing.
ICS=100% of ICU only Cat III 6 each 20739.00 207.39 20946.39
Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 50 KA and above at 415 V
having Normal current rating 400A. with variable Thermal & magnetic
release suitable to work on A.C.supply 50 c/s. With all internal
connections, spreader tinned copper & complete erected in existing
G.M.S. housing.
ICS=100% of ICU only Cat III 2 each 24979.00 249.79 25228.79
Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 50 K.A. and above at 415 V
having normal current rating 800A.with variable thermal & magnetic
release suitable to work on A.C.supply 50 c/s. with all internal
connections, spreader tinned copper & complete erected in existing
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
ICS=100% of ICU only Cat III 2 each 30429.00 304.29 30733.29
Providing & erecting sheet steel powder coated MCB distribution board -
flush / surface mounted fitted with busbar, neutral link, earth bar and DIN
333 rail, confirms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house
appropriate nos. of MCBs.(The DBs should be used of same company of
MCB to be used) suitable for
(A) single phase incoming and horizontal single phase outgoing
(b) sheet steel double door (IP-43)
Three phase incoming and single phase horizontal type outgoing per
phase isolation type (PPI)
(b) sheet steel double door
Providing and erecting Sheet Steel powder coated Vertical MCB
distribution board (VTPN) - flush / surface mounted double door (IP54)
fitted with copper insulated busbar, isolated neutral bar, earth bar and DIN
334 rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3, suitable for 250 AMP
TPN MCCB + RCCB as incomer and three phase outgoing as per
following .(The DBs should be used of same company of MCB to be used)
(C)8 way outgoing 30 each 11709.00 117.09 11826.09
(D)12 way outgoing 24 each 14247.00 142.47 14389.47
supplying & erecting sheet steel powder coated cable end termination Box
to be mounted on Top or Bottom of MCB Distribution Box for housing /
Covering Extra wires & cables suitable for following size of MCB Db Box.
(C) Single Phase 8 Way 3 each 323.00 3.23 326.23
(F) Three Phase 6 Way 2 each 577.00 5.77 582.77
(G) Three Phase 8 Way 51 each 683.00 6.83 689.83
(H) Three phase 12 way 54 each 789.00 7.89 796.89
Providing & erecting Miniature circuit breaker single pole 6A to 25A
suitable to operate on 240 V A.C system and having breaking capacity
KA to be erected in existing box confirming to IS 8826/1996 with ISI mark.
Providing & erecting 240 V MCB double pole switch for motor & inductive
337 load (C Curve) having 10 KA breaking capacity & confirms to IS :
in existing box having following capacity
(A) 6 to 32 Amp. Cat III 3 each 297.00 2.97 299.97
Providing & erecting 415 V MCB three Pole for Motor & Inductive
338 Load (C Curve) having 10KA breaking capacity & confirms to IS
:8828 in existing box having following capacity
(b) for 40 amps
(c) for 63 amps
Providing & erecting Four pole Miniature Isolator A.C.22 duly confirms to
IS 13947-3 in existing box.
(a) for 40 amps
(b) for 63 amps
Providing & erecting approved make ELCBs / RCCBs confirming to IS :
12640 and having sensitivity of 30 mA and short circuit withsatnd capacity
of 10KA and suitable for operation on single phase 240 V, 50 Hz having
characterstic of quick action & tripping with all advance feature & do not
incorporate any electronic component for following Max rating erected as
Providing & erected metallic vitrified danger notice board as per language
341 suggested by Engineer Incharge for MEDIUM VOLTAGE installation to be 164 each 69.00 0.69 69.69
erected as per IS-2551.
Rising Mains & Cables
Providing and erecting sandwitched type bus duct having following
specification : Sandwich type busbar for use as Feeder Busbar for
interconnection between separate electrical equipment/ load centers, and
342 for use as Plug in busbar risers.
The busbar shall be suitable for operation in a 690V / 1000 V system with
frequency of 50 Hz .System can be either earthed or unearthed. Impulse
voltage should be 12 KV. Standards:
The busbar shall be designed and manufactured in accordance with the
following international standards for busbar trunking.
-IS 8623/ 1993 Part I & II : Particular requirements of busbar trunking
-IEC 61439 Part I & VI : Particular requirements of busbar trunking System
-IEC- 60529 : Degree of protection TESTING
The busbars shall be type tested at a reputable national / International test
laboratory (ASTA or CPRI) for short circuit withstand. The test shall be for
a minimum duration of one second.
• Degree of ingress protection (IP rating) shall also be tested at any
reputed independent laboratory. This test shall be for IP 55 for Indoor and
IP 65 for Outdoor application.
• Short circuit and Degree of protection type test reports will be submitted
for vThe bsubars shall be of high conductivity Copper of 99.9% pure ETP
grade and high conductivity Aluminium of 99.59% pure 19501 grade.
Where as earth conductor is required, it shall be separate external earth
conductor, of high conductivity aluminium. Cross section of Earth
Conductor shall be as per IEC
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
It should be possible to provide a 200% Neutral where specified.
Phase cross over box should have busbars crossing over each other not
cables.The busbars shall be individually insulated with 2 layers of
insulating film. Layers of POLYSTER material class ‘F’, 155ºC. The
housing shall be made of 1.6 mm electrogalvanised sheet steel, with an
epoxy powder coated paint finish of RAL 7032 grade. Alternatively
Aluminum casing of 2.5mm may also be provided. The housings shall be
profiled, to provide higher strength and efficient heat dissipation. The
width of the housings shall be same for all ratings of busbars, in order to
provide interchangeability of tap off boxes. The joints between sections
shall be made so as to provide flexibility during installation and expansion
/ contraction of busbar during operation. The joints shall be of the single
bolt type. The joint construction must have the following features.
a) Thermal expansion of Busbars at joint of at least 4 mm per joint.
b) The joint insulation must be of one piece moulded design and not have
any cut edges which can absorb moisture.
c) Joint assembly shall be removable as separate sub-assembly so that it
can be inserted or removed without disturbing the adjacent sections.
d) The joint system must be designed in a way that the installer cannot
insert the busduct length too far and damage the bolt insulator.
e) The busbars ends shall not have any holes or slots at the joints – the
electrical continuity shall be through pressure plates, achieving a high
area of joint cross section and expansion capability.
a) Plug in boxes will be draw out type, contacts shall be silver plated and
b) The front operating handle will be interlocked with the plug-in boxes
cover so that MCCB can be operated only with suitable cover in close
c) The door shall be provided with the door knobs.
d) When the MCCB is in ‘ON’’ position, even with the door knobs
unlocked, the operator should not be able to remove the box or open the
tap off location cover.
e) During insertion, the earth conductor shall make contact first before the
phase conductors. This should follow the sequence of first in last out
f) When the box is open the live conductors shall be safe guarded by a
transparent insulator plate which allows for visible inspection but does not
allow touching of the live conductors.
g) The tap off unit arrangement must achieve IP 54 without requiring any
additional sealing at site.
h) The tap off boxes will be suitable for accommodating MCCBs or other
accessories, as required. The tap off units should allow the flexibility of
accommodating different, reputed MCCB makes, to be mutually agreed
depending on the tender requirements.
(A) Aluminium Bus
1.1 KV XLPE CABLES
Providing and erecting XLPE (IS:7098) - BB ISI armoured cable
multistrand aluminium conductor for 1.1 KV . To be laid on wall with
necessary clamps or in existing trench / pipe of following size of cables.
Providing and erecting XLPE (IS:7098) - BB ISI armoured cable
multistrand aluminium conductor for 1.1 KV . To be laid on wall with
necessary clamps or in existing trench / pipe of following size of cables.
END TERMINATIONS :
Providing & fixing heavy duty flange type brass double compression type
cable gland with rubber ring for PVC insulated armoured cable complete
with outgoing tails insulating tape etc. for following size of cables.
Solder less crimping type Aluminium lugs confirming to IS suitable for
cable of following size evenly climped with high pressure tool & connected
to switchgear terminals with brass / cadmium plated nut bolts in an
approved manner.
SITC of Light Fitting, Fans and Fixtures
Installation, testing and commissioning of prewired, LED fittings of all
types , complete with all accessories and tube etc. directly on ceiling/wall,
including connections with 1.5 sq.mm. PVC insulated, copper conductor,
single core cable etc. as required.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Supplying and erecting LED Indoor fittings with LEDs of wattage 0.2 watt
to 0.5 watt assembled on single MCPCB, with housing used as a heat sink
shall be made of thick sheet steel confirming to IS: 513/CRCA/aluminium
pressure die cast powder coated and high U.V. & corrosion resistance with
diffuser housed in aluminium casted body with company mark/name 120 to
300 V, power factor more than 0.9, THD< 10%, CCT 3000 K to 65 K.
348 Luminiare efficacy > 85 lumens/watt. LED efficiency 110 lumens/watt, LED
driver efficiency > 85%. CREE/OSRAM/PHILIPS Lumileds/ NICHIA/
SEOUL/ Bridgelux make LED used for luminiare (fitting required LM-79 &
LM-80 certificates )( Note: below description have shown ranges of
wattage capacity of LED fittings. The Engineer Incharge may select any
wattage capacity between the ranges shown).
(A) Square/ Circular shaped Surface/Recessed Mount Downlight with
provision for spring loaded mounting clips complete.IP20
(a) 5-9 watts, surge-2 KV
(b) 11-15 watts, surge-2 KV
(B) LED Panel light with provision for plane front frame with translucent
cover fixed to housing complete IP
(vi) 36 watts, 24" x 24", Surge- 2KV
Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt
to 0.5 Watt assembled on single MCPCB, with housing used as a heat
sink shall be made of thick sheet Steel conforming to IS: 513/CRCA/
aluminium die cast powder coated and high U.V. & corrosion resistance
with diffuser with company mark/name 160V to 270V, Power Factor more
350 than 0.95, THD < 15%, CCT 3000 K to 6500K, Luminaire efficacy>
lumens/watt ,LED , LED driver efficiency > 85 % ( fitting required LM-79 &
LM-80 Certificates)(NOTE: Below description have shown ranges of
Wattage capacity of LED fittings.The Engineer incharge may select any
wattage capacity between the ranges shown.)
(A) Tube light with integral driver
(i) 5-10 Watts, Surge-2 KV, IP-20, conventional 1 to 2 feet
(iii) 18-20 Watts, Surge - 2KV,IP-20, conventional 4 feet
(v) 36-40 Watts, Surge-2 KV, IP-20, conventional 4 feet
Supply of 5-6 W LED Exit & matter at per site requirement Light with
inbuilt battery backup of 2 hours, including drivers, fixing accessories
complete as required. The fixture should have sufficient intensity and all
fixing arrangement complete as required at site. Bajaj : BESL 03 LED DSD
WBB Red/Green or equivalent of Decon and Insatpower
Providing and erecting PVC body surface or pendant mounting LED Bulk
type 9 watt Lighting fitting with electronic driver and lumen output from
352 luminiare 720 lm, input voltage range 90-300 VAC, 50 Hz cool white (3000 53 each 780.00 7.80 787.80
to 6500 K), inbuilt driver, 20 degree C to + 60 deg C working temperature,
AL frame with Beam Angle 120 deg.
Supply, Installation, Testing and Commissioning of 1200 mm (48")
sweep, BEE 5 Star rated, Ceiling fan with Brush Less Direct Current
(BLDC) permanent ferrite magnet Motor, class of insulation: B, Rust
free 3 nos.Aluminium blades, 2 nos. canopies, shackle kit with
earthing provision, copper winding, Power factor not < 0.9, Service
Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM,
350 RPM,230v (tolerance as per IS : 374-2019), THD < 10%, with
353 remote unit for Speed Control and all remaining accessories 1272 each 2857.00 28.57 2885.57
including safety pin, nut bolts, washers, temperature rise =
degree C (Max.), suitable for 140 to 285 Voltage and rectifier
circuit with surge, over current and overload protection , 50 Hz,
Single phase AC Supply, earthing etc. Complete as required.[ Make
shall be approved by Engineer in Charge]
Supplying & erecting Single phase approved make industrial exhaust fan
suitable for medium duty ring mounted low noise operation suitable for
medium duty having following dia size and maximum speed in RPM
(D) 450 mm dia. 900 RPM, Cat II 7 each 3899.00 38.99 3937.99
355 Providing suitable M.S. louver shutter of the Exhaust Fan. 121 each 365.00 3.65 368.65
Earthing & Lightning Conductor
Supplying & erecting funnel type earthing having earth plate of following
size burried in specifically prepared earth pit 3 mtr, below ground with
kg charcoal and salt with alternate layers of charcoal & salt, 20 mm dia GI
pipe with funnel with a wire mesh for watering & bricks masanory block CI
cover complete as per para 7.3 of IS 3043 with necessary length of double
Galvanized Iron / copper earth wire no. 6 SWG bolted with lug to the plate
and covered in 12 mm dia. G.I pipe 2.5 mtr long complete connected to the
nearest switch gear with end socket as per direction & duly tested by earth
tester confirming to IS (As per drawing) with following Specification.
(B) with 45 x 45 x 0.35 cms. G.I. earth plate 16 each 2543.00 25.43 2568.43
(C) with 60 x 60x 0.315 cms. Copper earth Plate 12 each 7797.00 77.97 7874.97
Providing and erecting required size HOT deep galvanized iron strip for
357 earthing of H.T, OCB/ACB/Transformer LT panel board, motors etc. using 530.00 Kg 77.00 0.77 77.77
Providing and erecting required size Copper strip for earthing of H.T,
358 OCB/ACB/Transformer LT panel board, motors etc. using copper clamp. 600.00 Kg 787.00 7.87 794.87
359 Providing and erecting Annealed bare Copper wire 8 to 16 SWG. 350.00 Kg 787.00 7.87 794.87
Providing and erecting Hot deep Galvanized Iron strip wire 8 to 16 SWG.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
SITC of Vertical Air Terminal Solid aluminium with base-10 mm dia and
3000 mm long. Air Termination base tested for conditioning, ageing test &
Lightening impulse current withstand test: 100 KA of 10/350 Us waveform
in an accerdited third party laboratory as per 6.3 & 6.4 of IEC 62561-1
2017 protocol with MAST 34 mm dia 3000 mm long-Cold Galvanized.
SITC of 8 mm dia solid Aluminium Conductor for roof top mesh grid and
tested as per IEC 62561- 2 conducted in the Govt. accredited thirty party
laboratory to meet the requirement of IS/IEC 62305 with Required
Accessories - Aluminium Holding clamp at every 1 mtr distance,
Aluminium/SS cross splicer at every crossing of Alu. conductor, Expansion
piece with connectors at every 20 mtr distance, Aluminium straight Splicer
to connect conductors. All Accessories should be tested as per IEC
62561-1 2018 Cl. 6.3 for conditioning & Ageing Test & 6.4 for Lightning
impulse current withstand test: 100 kA of 10/350µs waveform(Ageing &
Electrical test ) conducted in a sequence manner & tested in the Govt.
accredited Third party laboratory to meet the requirements of IS/IEC
SITC of 10 mm MS Round solid conductor having smooth surface should
be tested and use exclusively for lightening protection (vertical Riser /
down conductor which shall be concealed in column) to meet the
requirement of IS IEC 62305 with accessories. Earthing stud of
dimensions SS-75 mm OD plate with 10 mm dia tail connector used in
structural steel ring earthing system to meet the requirement of IS / IEC
62305. (For interconnecting the column and Terrace AL Conductor / strip/
flat SS cross connector to connect Earth fixing oint to vertical raiser / down
conductor. SS straight splicer at every 4 mtr to connect MS conductor in
363 column. Bonding / Rehar clamp at every 3 mtr suitable for innerconnecting 500.00 metre 721.00 7.21 728.21
round conductor with reinforcement inside the concrete for structural
earthing system, SS connector - To connect external conductor 8-10 mm
with earth fixing point. All accessories shall be test as per IEC 62561 I
2018 CI.6.3 for conditioning & ageing test & 6.4 for lightening impulse
current withstand test:100 KA of 10/350 Us waveform (Ageing & Electrical
test) conducted in a sequence manner & tested in the Govt. accerdited
Third party laboratory to meet the requirements of IS/IEC6230.
SITC of Galvanized steel flat 25X6 mm thickness from earth electrode
directly in ground as required. Zinc coating 500 g/m square (approx
micron coating) tested used exclusively for lightening protection earthing
system and ring equipment bonding.
SITC of 14.2 mm dia 3 mtr long earth electrode of high tensile steel
electrode with 250 micron copper bonding & 1 bag of carbon fill based
environment friendly backfill tested as per IEC 62561-7 in NABL
365 accerdited Laboratory and suitable stainless steel double sided clamp. 8.00 Per Set 5933.00 59.33 5992.33
Eco friendly rust proof heavy duty weather proof polythylene earth pit
chamber with following dimensions: 254 mm dia (top) 330 mm dia (bottom)
& 260 mm (height).
Passive Cabling & LAN System
Note: Wiring/Fiber installation shall include numbering, Ferruling,
termination and testing of cables at both ends.
Fiber Splicing, Testing with OTDR etc. shall be the part of installation of
Test Reports of Passive Items with dully authorized by OEM shall be
submitted for 25 years warranttee.
All Active devices shall have minimum 5 years of support from the date of
Providing & erecting ISI mark Medium class RIGID PVC Pipes of following
size complete to be erected on / in wall or ceiling erected with necessary
366 PVC fittings & junction boxes fixed with adhesive solution & clamps with
following dia of pipes, in approved manner as directed.
Supplying, drawing, Testing and commissioning of Cat6A UTP 4 pair,
AWG solid copper cable in existing conduit/ on surface, U/FTP, LSZH,
Non- Plenum, Horizontal (solid) Cable suitable for high speed data
networking application supporting upto 10Gbps over a 100 meter channel.
The 4 Unshielded Twisted Pairs (UTP) cable with color coded insulation
367 for easy indentification should have FLAME PROPERTIES i.e.
Flammability Test - IEC 60332-1, Smoke Density - IEC 61034, LSZH
standards compliance: ANSI/TIA-568 C.2, ISO/IEC 11801, IEEE 802.3an,
RoHS. Delay Skew should be < 45NS. The outer Cable Diameter should
be 7.5 + 2 mm. Cable should have been tested and verified by UL/ ETL
etc. complete as required.
1 Run of cable 40000.00 metre 63.00 0.63 63.63
2 Run of cable 35000.00 metre 105.00 1.05 106.05
Supplying, Installation, Testing and commissioning of CAT6A Copper
Information Outlet (IO) with face plate of color as per site requirement,
should have ETL/UL verification program certificate for compliance with
ANSI/TIA-568.2-D. All copper Cable and Components should be from
same OEM to maintain compatibility and interoperability etc. complete as
Supplying and fixing of 15U size Wall Mount Rack having Fixed Structure
with 0.8mm CRCA Sheet, completely knocked-down condition (CKD)
Shape, Vertical Mounting Rail 1.6 mm with 'U'Marking, Minimum 2 cable
entry/exit provision at Top and bottom with rubber protection, Front 5mm
369 Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- 4 each 11297.00 112.97 11409.97
7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution
units, 3 numbers closed cable organizer, Hardware mounting screws
packet of 20 x 1 number, etc. complete as required.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Supplying and fixing 24U Rack with 4 inch Castor wheels and front brake
Floor Standing Rack with Main Frame Pillar of 1.25mm Powder Coated
CRCA Sheet with removable side panels, L- Shape adjustable Vertical
Mounting Rail of 2mm with 'U'Marking completely knocked-down condition
(CKD) Shape, fitted with 4 number cooling fans, minimum
5nos two line cable entry/exit provision at top and bottom with rubber
370 protection, Front door 5mm Toughened Glass with MS frame or MS 12 each 17967.00 179.67 18146.67
perforated with lock, Rear MS vented or perforated door, Powder coated
Color- RAL- 7035 or black, complied with UL & RoHS, 2 x 6 sockets 16A
power distribution units, 3 numbers closed cable organizer, Hardware
mounting screws packet of 20 x 1 number, etc. complete as required.
Supplying and fixing 42U Rack with 6 inch Castor wheels and front brake
Floor Standing Rack with Main Frame Pillar of 1.6mm CRCA Sheet with
removable side panels, L- Shape adjustable Vertical Mounting Rail of 2mm
with 'U'Marking completely knocked-down condition (CKD) Shape, fitted
with 4 number cooling fans, minimum 8nos two line cable entry /exit
provision at top and bottom with rubber protection, Front door 5mm
Toughened Glass with MS frame or MS perforated with lock, Rear MS
vented or perforated door, Powder coated Color- RAL- 7035 or black,
complied with UL & RoHS, 2 x 6 sockets 16A power distribution units,
numbers closed cable organizer, Hardware mounting screws packet of
x 1 number, etc. complete as required.
Supplying, Installation, Testing and commissioning of following CAT6A
Patch Cord should have ETL/UL verification program certificate for
compliance with ANSI/TIA-568.2-D etc. complete as required.
Copper Patch Cords of length 1m (3ft) 2043 each 147.00 1.47 148.47
Copper Patch Cords of length 3m (10ft) 2043 each 343.00 3.43 346.43
Supply, Installation, Testing & Commissioning of Staggred 24 Port
Unshielded, Loaded with Category 6A RJ45 Unshielded Modular Jack,
Keystone information outlet (I/O) in accordance with ANSI/TIA 568.2-D,
IEC 60603-7-4 2nd Edition, ISO/IEC 11801, ROHS Compliant. The I/O
373 should have minimum 750 mating cycle and 200 insertion cycle and ETL 91 each 7917.00 79.17 7996.17
04-Connector Channel Verified, 1U height, Black with integrated cable
support bar, clear label marks and earthing plug for UTP cable termination
at rack end complete etc as required.
SITC of O. F. Cable 06F Outdoor - Armoured Unitube SM - HDPE Sheath
374 [Approved by Competent Authority i.e. not Below the rank of Executive 3800.00 Mtrs. 50.00 0.50 50.50
SITC of LIU 12 PORT Rack Mount - Loaded (LC) SM
375 [Approved by Competent Authority i.e. not Below the rank of Executive 32 each 6833.00 68.33 6901.33
SITC of PIGTAIL LC SM SIMPLEX LENGTH- 1m
376 [Approved by Competent Authority i.e. not Below the rank of Executive 192 each 772.00 7.72 779.72
SITC of PATCH CORD LC-LC SM DUPLEX LENGTH- 3m
377 [Approved by Competent Authority i.e. not Below the rank of Executive 32 each 1883.00 18.83 1901.83
ACTIVE LAN SYSTEM
SITC of 20 x SFP ports
4 x Combo 10/100/1000BASE-T/SFP ports
4 x 10G SFP+ ports
6 kV surge protection on all RJ-45 access ports
Switch Resource Management (SRM) for flexible management of system
378 Redundant Power Supply (RPS) support 2 each 641524.00 6415.24 647939.24
MPLS L2VPM/L3 VPN support
Full L3 routing protocol support including OSPF, BGP, and ISIS for
SDN-enabled switch, compatible with Openflow
10-GbE SFP+ to SFP+ 1M Direct Attach Cable [Approved by Competent
Authority i.e. not Below the rank of Executive Engineer ]
SITC of 24 x 10/100/1000BASE-T PoE ports 4 x Gigabit RJ45/SFP Combo
ports Advanced L2 switching and security features L2+ Static Routing
379 Optional “standard mode” or “surveillance mode” management user 91 each 31680.00 316.80 31996.80
interface 193 W PoE budget Approved by Competent Authority i.e. not
Below the rank of Executive Engineer ]
SITC of Maximum distance of up to 10 km Hot-pluggable Single-mode
fiber 1000BASE-LX (IEEE 802.3z standard) Duplex LC connector MSA,
RoHS-compliant [Approved by Competent Authority i.e. not Below the rank
of Executive Engineer ]
SITC of Digital / PCM / TDM EPABX System having SMT design, system
with flexible universal slots. Inbuilt Auto attendant facility, Minimum
Nos. conference, Analog extension line, Calling GSM, E&M line, PRI / EI &
VOIP program me through Analog telephone digital key from Ethernet,
public address cord, shall have unrestricted simultaneous dialing facility,
QSIG protocol on PRI, 95 / STD / ISD / Local-Locking, Class of Service,
Quick Dial-Single Digit dialing of any two external number, Once only ring
device, Chairman / Secretary - Do not disturb Facility, Power Down Mode,
381 Hot Line, Hot Outward Dialing, Day Night Mode, Auto Call Back, Barge-in,
Call Pick Up & Call Transfer, Call transfer while Ringing with Voice Guide
System, (DISA), Caller ID (CLI), CLI Base ECF, CLI Base routing Internet
Ready Port, External Music Port, Call Budgeting, Call Most Calculation
(ASMDR), DID Direct Inverse Dialing, External Music Input, Fax Homing,
Global Directory Printing with following capacities [[Approved by
Competent Authority i.e. not Below the rank of Executive Engineer ]
[E] No of Extension 128, No of Junctions 24, No of expandable ports :
512, Operators Console - 01 Compatible : ISDN and Networking
Providing and erecting IP Phone with display with all IP system supported
382 [[Approved by Competent Authority i.e. not Below the rank of Executive 435 each 5594.00 55.94 5649.94
Fire Detection & PA System 0.00
Supplying, installation, testing & commissioning of intelligent analog
383 addressable photothermal detector complete with mounting base complete 1453 each 2546.00 25.46 2571.46
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Supplying, installation, testing & commissioning of intelligent
384 addressable thermal detector with rate of rise cum fixed temperature 133 each 2429.00 24.29 2453.29
thermistor complete with base as required.
Supplying, installation, testing & commissioning of addressable fire
control module complete as required.
Supplying, installation, testing & commissioning of fire fighter
telephone handset complete as required.
Supplying, installation, testing & commissioning of fire fighter
phone jack complete as required.
Supplying, installation, testing & commissioning of addressable horn cum
strobe complete as required.
Supplying, installation, testing & commissioning of addressable manual
call point complete as required.
Supplying, installation, testing & commissioning of intelligent interface unit
BACnet/ Modbus protocol i.e. supplying communication links between
building management system and fire alarm control panel complete as
Supplying, installation, testing & commissioning of response
391 indicator on surface/recessed MS Box having two LED, metallic cover 645 each 259.00 2.59 261.59
complete with all connections etc as required.
Supplying, installation, testing & commissioning of fault isolator complete
with base as required.
Supplying, installation, testing & commissioning of central graphical fire
393 alarm management system to centrally monitor and operate the fire alarm 1 each 178190.00 1781.90 179971.90
system complete as required.
Supplying, installation, testing and commissioning of micro processor
based intelligent addressable main fire alarm panel, central processing
unit with the following loop modules and capable of supporting not less
than 240 devices (including detectors) and minimum 120 detectors per
loop and loop length up to 2 km, network communication card, minimum
320 character graphics/ LCD display with touch screen or other keypad
and minimum 4000 events history log in the non volatile memory
(EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with
volt sealed maintenance free batteries with automatic charger. The panel
shall have facility to connect printer to printout log and facility to have
seamless integration with analog/digital voice evacuation system (which is
part of the schedule of work under SH: PA System) and shall be complete
with all accessories . The panel shall be compatible for IBMS system with
open protocol BACnet/ Modbus over IP complete as per specifications.
Ten Loop Panel 2 each 404147.00 4041.47 408188.47
SITC of Controller Heart of the Plena Voice Alarm System EN 54‐16
certified Built-in message manager and 240 W amplifier Six‐zone outputs
6 emergency and 6 business triggers [Approved by Competent Authority
i.e. not Below the rank of Executive Engineer]
SITC of Ceiling speaker, 6W, metal
396 [Approved by Competent Authority i.e. not Below the rank of Executive 304 each 643.00 6.43 649.43
SITC of Power amplifier, 2x500W 2 ✕ 500 W class-D power amplifier
(70/100 V output) Low power consumption in standby mode
397 Excellent sound quality, high signal-to-noise ratio EN 54-16 and ISO 7240- 4 each 217686.00 2176.86 219862.86
16 system certification [Approved by Competent Authority i.e. not Below
the rank of Executive Engineer ]
SITC of Call station for 6-zone Stylish six-zone call station, intended for
LBB 1925/10 system pre-amplifier Unidirectional condenser microphone
on flexible stem Six zone selection keys, all-call key, and momentary PTT-
key for calls Selectable gain, speech filter, and limiter for improved
intelligibility Selectable priority levels and different pre and post-call
chimes LED indications for zone selection, system activity, and call station
status [Approved by Competent Authority i.e. not Below the rank of
Executive Engineer ]
Providing & erecting 16 gauge HGS conduit pipe (as per IS) painted
black surface/concealed of following size complete to be erected on/in wall
399 or ceiling with erected with necessary saddles, screws, bends, junction
boxes etc. with following (Nominal Bore) dia of pipes, in approved manner
Supplying and drawing of cable Fire Retardant PVC insulated copper
conductor cable in the existing surface /recessed steel conduit of following
pairs, cores and size including connections and interconnections etc. as
speaker cable Single pair, 2-core, 1.5 sqmm 4500 each 52.00 0.52 52.52
Supplying and drawing following sizes of FR PVC insulated copper
401 conductor, single core cable in the existing surface/ recessed steel/PVC
Supplying Installation Testing and Commissioning of 5/6MP IP IR Dome
Camera having following specifications and features etc :-
1)Type of Camera: Dome Camera
2) Image Sensor: 1/2.8" or better progressive Scan CMOS get color image
even at night condition
402 3) Signal System: PAL/NTSC
4) Minimum Illumination: 0.008Lux@ F1.4, AGC ON, 0 lux with IR or better
5) Imaging: 1/3s to 1/30000s Shutter Support, Auto Gain Control, White
Balance- Auto, Back Light Compensation, Multi zone Privacy Masking,
HLC, Digital Watermarking.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
6) On Screen Display: Camera should display Camera title, Date & Time in
live & recorded video both.
7) Signal to Noise Ratio: > 50 dB
8) Day & Night: True Day & Night High Performance Mechanical IR cut
filter with auto switch, IR Source- Inbuilt IR LED's with effective distance
upto 50 Mtrs integrated IR 30 Mtrs for colour view in night.
9) Video Compression (Minimum): H.265 or better, Audio:- G.711U/A,
G.711Mu, G.726, AAC, G.723
10) Wide Dynamic Range: WDR (120dB or more)
11) Digital Noise Reduction: DNR (2D/3D) On/Off
12) Streaming: Triple streaming, configurable
13) Video Streaming & Frame Rates: Triple streaming configurable Main
stream: 5/6MP @25/30 fps, Sub streams: D1@25/30 fps or better
14) Image Setting: Rotate Mode, saturation, brightness, contrast,
sharpness adjustable through client software or web browser
15) Profile Management: User configuration import, export
16) Security: User Authentication, Water Marking
17) Onboard Storage: Camera should support built-in Micro SD/SDHC/
SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB
18) Recording Management: Format SD, overwrite, storage management,
video to NAS device,
19) Edge Analytics : Tripwire, Intrusion, Motion Detection
20) Alarm Trigger : Motion/tampering detection; network disconnection
detection; IP conflict detection; memory card state detection; memory
space detection
21) Alarm Support: It should have 1/1 Alarm In/ Out Port
22) Audio Support: It should have 1x Built-In Mic and 1/1 Audio In/ Out
Port for external Mic. and Speaker (As per site requirement) with
G.711U/A/ G.711Mu/ AAC/ G.726 audio compression
23) Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP,
HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL, DHCP, SMTP,
RTSPS, unicast,
24) System Capability: ONVIF
25) VMS: Camera shall support open source VMS
26) Cyber Security: trusted boot, AES 256-bit Encryption, Configuration
encryption, trusted execution, Digest, security logs, , account lockout,
video encryption, IP/MAC filtering, HTTPS, trusted upgrade.
27) Ethernet: 1 RJ 45 10/100 Ethernet port
28) Power Input: The camera should support simultaneous dual power
input—12 VDC (via power adapter) and PoE—to ensure continuous
operation in the event of a failure in one power source.
29) Power Requirement: 12VDC/24VDC/PoE (802.3af)/ePoE
30) Enclosure: IP67 weather proof, IK10
31) Operating Condition: Ambient Temperature:- (-) 05°C to 50°C,
humidity 95% (max) (non-condensing)
32) IR life: 40000 hours or higher
33) Video Bit rate: 32 KBPS - 8 MBPS or better
34) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS
5MP/6MP IP IR 2.7 to 4 mm ~12 to 13.5mm or better Varifocal Motorized
lens Dome Camera.
Supplying Installation Testing and Commissioning of 5MP/6 MP IP IR
Bullet Camera having following specifications, type of lens and features
1) Type of Camera: Bullet Camera
2) Image Sensor: 1/2.8" or better progressive Scan CMOS get color image
even at night condition
3) Signal System: PAL/NTSC
4) Minimum Illumination: 0.006Lux@ F1.4, AGC ON, 0 lux with IR or better
5) Imaging: 1/3s to 1/30000s, Auto Gain Control, White Balance- Auto,
Back Light Compensation, Multi zone Privacy Masking, HLC, Digital
6) On Screen Display: Camera should display Camera title, Date & Time in
live & recorded video both.
7) Signal to Noise Ratio: > 50 dB
8) Lens Type & Focus: as given below.
9) Day & Night: True Day & Night High Performance Mechanical IR cut
filter with auto switch, IR Source- Inbuilt IR LED's with effective distance
upto 50 Mtrs integrated IR and 30 Mtrs for colour view in night.
10) Video Compression (Minimum): H.265 or better, Audio:- G.711U/A,
G.711Mu, G.726, AAC, G.723
11) Wide Dynamic Range: WDR (120dB or more)
12) Digital Noise Reduction: DNR (2D/3D) On/Off
13) Streaming: Triple streaming, configurable
14) Video Streaming & Frame Rates: Triple streaming , configurable Main
stream: 5MP/6MP @25/30 fps, Sub streams: D1@25/30 fps or better
15) Image Setting: Rotate Mode, saturation, brightness, contrast,
sharpness adjustable through client software or web browser
16) Profile Management: User configuration import, export
17) Security: User Authentication, Digital Water Marking
18) Onboard Storage: Camera should support built-in Micro SD/ SDHC/
SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB
19) Recording Management: Format SD, overwrite, storage management,
video to NAS device,
20) Edge Analytics: Tripwire, Intrusion, Motion Detection
21) Alarm Trigger : Motion/tampering detection; network disconnection
detection; IP conflict detection; memory card state detection; memory
space detection
22) Alarm Support: It should have 1/1 Alarm In/ Out Port
23) Audio Support: It should have 1x Built-In Mic and 1/1 Audio In/ Out
Port for external Mic. and Speaker (As per site requirement) with
G.711U/A / G.711Mu/ AAC/ G.726 audio compreesion
24) Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP,
HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL, DHCP, SMTP,
RTSPS, unicast,
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
25) System Capability: ONVIF
26) VMS: Camera shall support open source VMS
27) Cyber Security: trusted boot, AES 256-bit Encryption, Configuration
encryption, trusted execution, Digest, security logs, account lockout,
video encryption, IP/MAC filtering, HTTPS, trusted upgrade.
28) Ethernet: 1 RJ 45 10/100 Ethernet port
29) Power Input: The camera should support simultaneous dual power
input—12 VDC (via power adapter) and PoE—to ensure continuous
operation in the event of a failure in one power source.
30) Power Requirement: 12VDC/24V DC/PoE (802.3af)/ePoE
31) Enclosure: IP67 weather proof, IK10
32) Operating Condition: Ambient Temperature:- (- )05°C to 50°C,
humidity 95% (max) (non-condensing)
33) IR life: 40000 hours or higher
34) Video Bit rate: 32 KBPS - 8 MBPS or better
35) Standards: BIS with ER, STQC Certified, CE, FCC and RoHS
5MP/6MP IP IR 2.7 to 4 mm ~12 to 13.5mm or better Varifocal Motorized
lens outdoor Bullet Camera
Supplying Installation Testing and Commissioning of following Channel
Network Video Recorder (NVR) with camera licenses to record for all
channels having specifications and features etc as mentioned below :
1) Network Video Recorder Embedded/ Installed OS (Linux) along with
Camera Licenses to record per NVR and to provide a live view, storage
and simultaneously Multi-channel playback of all IP camera or more and
must be ONVIF with minimum support of 384 Mbps incoming Bandwidth.
2) NVR should support video compressions : H.265 or better, H.264,
3) Must support 1 channel RCA Input, 2 channel RCA Output for Two-way
Talk with G.711U/A, G.711u, PCM, G726 audio compressions.
4) Intelligent auto power on when power resumes after power outage.
5) Storage: It should support minimum 8 SATA Slots with 20TB capacity/
Slot and RAID support of RAID 0/1/5/6/10.
6) Connectivity Interface : 2 Nos. x 10/100/1000 Mbps Ethernet Ports, 1x
RS485, 1x RS232, 1x eSATA Port
7) Backup Interface : Its should have 4 Nosx USB port (2x USB3.0,
8) Video Output Ports: 2x HDMI and 2 VGA
9) Alarm Ports: It should have 16/8 Ch In/ Out ports to connect various
type of external sensors and output devices like hooter/ Siren etc.
10) Email & SMS Altert options: Option for SMS/ Email Alerts to minimum
5 designated mobile number for power failure, HDD failure, vandalism,
tempring, network disconnection and panic
11) Web & Mobile Application: Web, Mobile app ( For iPhone, iPad,
Android Phone) for alerts and viewing.
12) Protocols: HTTP, HTTPS, TCP/IP, IPv4/IPv6, UDP, DHCP, DNS,
SMTP, UPnP, IP Filter, PPPoE, FTP, DDNS, Alarm Server, IP Search,
Multicast, Auto Registration, ONVIF (Profile T, Profile S, Profile G), CGI,
SDK and OEM Cloud for remote monitoring without any public IP need.
13) Standards: CE, FCC, RoHS, BIS Certified
14) Power Supply : Should support AC100-240V, 50/60Hz Power supply.
15) Operating Condition : -5°C to 50°C, humidity 90% (max) (non-
16) The VMS application shall support all the features & functionalities of
the offered cameras.
17) VMS should consist Licenses for all channels to record Cameras with
General, motion detection, intelligent, alarm and POS recording modes.
VMS should be provided with Camera Licenses, with no dependency of
VMS licenses by binding with the MAC address of the cameras to achieve
the functionality.
18) The NVR OEM shall be responsible for providing a mobile application
compatible with both Android and iOS devices, enabling remote
monitoring and playback of cameras/NVR footage.
19) The OEM must provide its own DDNS server hosted in India,
eliminating the need for a public IP address for remote monitoring over the
20) Must support Continuous, Alarm, Motion, Instant, Panic Recording
21) It should support Resolution: 32MP; 24MP; 16MP; 12MP; 8MP; 5MP;
4MP; 1080p; 720p; D1; CIF; QCIF
22) When alarm recording is enabled and an event occurs, you can click
the alarm icon on monitoring page to view the alert details. The snapshot
function is supported on monitoring and playback page
23) The Network Video Recorder (NVR) shall be configured to send email
whenever a system message is created or an alarm event occurs. The
email server shall be a valid SMTP server. Each recipient email address
shall be configured to receive any combination of critical, warning, or
informational messages or alarm notifications. When an alarm occurs, the
email message includes the NVR name, time of alarm and a list of camera
that is configured to record upon alarm
24) It should have Web and GUI interface.
25) Built-In Artificial Intelligence: NVR should have built-in AI :-
- 2 Channel face detection and recognition, - Minimum
4 Channel perimeter protection, - Minimum 8 Channel Smart Motion
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
26) Face Recognition Database Capacity: It should support total Blacklist
and Whitelist capacity of Minimum 20,000 Faces or more with Face
Detection speed of 12 face images/sec and facility to add Name, gender,
birthday, address, credential type, credential No., countries & regions and
state to each face image.
27) Face & Human Attributes Search: Search Pictures/ Video by Gender,
age group, glasses, expressions, face mask, beard, Top color, top type,
hat, bag, age, gender and umbrella.
28) ANPR Capability: It should support ANPR Camera with License plate,
plate color, vehicle body, vehicle model, vehicle logo, calling, seatbelt,
vehicle registration location etc vehicle attributes.
29) Alarm Notifications based on: Motion detection, video tampering, video
loss, scene changing, PIR alarm, Camera external alarm, Face detection,
face recognition, perimeter protection (intrusion and tripwire), ANPR,
people counting, stereo analysis, crowd distribution, heat map, Disk Full,
Storage Error, IP Conflict and abnormal behavior of fan, cybersecurity
30) Alarm Notification should be linked with Recording, snapshots,
Camera external alarm output, buzzer, logs, presets and email.
31) General AI Based Search: Search Pictures by channel, time, event
type, target classification (Fall Detection, People Approach Detection,
People No. Exception Detection, People Staying Detection, Violence
32) Smart playback function: Should support smart search for the selected
area in the video and smart playback to improve the playback efficiency
33) VCA (Video Content Analytic): Should support multiple video
contented analytics based on camera analytics
34) Analytics by NVR: Perimeter protection and face recognation
32 Channel Network Video Recorder (NVR) having display split :- Main
64 Channel Network Video Recorder (NVR) having display split :- Main
Supply, Installation, Testing and commissioning of Monitor, 55" LED high
resolution monitor with high performance 240VAC, 50 Hz. 24x7 for spot
display including all accessories as per specifications and as required to
complete the system.
Supply, installation, testing & commissioning of Client Workstation as per
following specifications:Intel Core i7-8700K or better, 4.2GHz, OS -
Genuine Microsoft Microsoft® Windows 10 Enterprise/IOT 64 Bit, RAM -
16GB, OS - 480 GB SSD/SATA, Graphic Card - In-built Processor
Graphics (GPU):Intel® HD Graphics 630 or Intel Q470 Processor,
supporting 2 Monitors, 01 LAN 01GBPS, Audio IN & Out, USB3.0,
Keyboard and Mouse, associated cables etc complete.
Approved Makes : Pelco / Avigilon / Axis / Allgovision / Dell / HP
Supplying, Installation, Testing and Commissioning following capacity
Serveillance grade Hard Disk with upto 256MB/s Transfer Rate, 256 MB
407 Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface,
BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI,
CB-Scheme, TUV, UL Certifications.
10TB (Terabytes) 30 each 21015.00 210.15 21225.15
Supply, Installation Testing & Commissioning 15 Mtr. HDMI Interface
408 Cable as per the detailed Specifications supports transmission of 4K 4 each 1760.00 17.60 1777.60
Signals as per the detailed Specifications
Supplying, Erecting, Testing & Commissioning the passenger / stretcher
lift having following main features:The Rates of the following items are for
the lift without Machine room (MRL type)
(A) GENERAL DESCRIPTION OF LIFTS.
[1] GEAR LESS LIFT DRIVE (MRL) comprising of High Starting torque Lift
3 phase 440 V A. C. Permanent Magnet Synchronous motor of proper
rating with high efficiency shall be used.[2] Micro processor based / PLC,
ACVVVF, vector control drive with encoder feedback closed loop system
shall be used for lift car and door operation which shall be full collective
selective operation hall call demand response, UP/DOWN hall stops,
Main, Up/ Down Contactor with overload and phase reversal relay and
safety controls.[3] Car with M S platform with bracings of adequate size
and to sustain the impact load cabin + passenger with safety factor of fire
for steel and side panels of Stainless steel of sheet of grade 304 duty. Car
ceiling will be S.S. finishes with aesthetic appearance with LED ceiling
lights. Car flooring shall be of anti skid PVC with choice of colour of
engineer in charge. Car doors shall be of stainless steel grade
hairline finish with centre opening / telescopic automatic doors. Car panel
will also be S.S. 304 finished with emergency stop device, mechanical
door safety device, facility of auto/ attended mode.
All car panel buttons and all floor switches must be with brail language as
per lift act.[4] All landing doors must be fire rated for 2 hour shall be fully
automatic centre opening/ telescopic opening made of hairline finish steel
grade of 304 with key holes and infrared curtains with Unlocking facility
from outside [5] Appropriate battery operated emergency light in the car
along with alarm switch shall be provided. Also, Emergency Light & Fan
should start immediately without any Time Delay as soon as power fails.
[6] Digital scrolling indicator system for up-down arrow along with floor
position indicator shall be provided inside the car and at all floors.[7] Full
height infra red curtain with multiple cross / crossing light beams shall be
provided.[8] Automatic Rescue Device (ARD) shall be provided
accordingly of passenger capacity with Manual Rescue Operation (
Manual Cranking Facility).[9] Audio visual indication in the lift car showing
over loading shall be provided such that doors kept open till excess load is
removed.[10] Spring buffers/PU Buffers shall be provided.[11] Car fan as
per passenger capacity with automatic sleep timer shall be provided.[12]
Voice annunciator with suitable music shall be provided in lift car. [13] Self
diagnostics system for operational and safety parameters shall be
provided in control panel.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
[14] Mechanical over speed governor with governor calibration as per
actual site parameters and submission of calibration certificate
submission, door key holes in the floor doors, fireman switch shall be
provided.[15] Lift machine hoisting arrangement in the lift machine room
and monkey ladder for lift pit should be provided by the lift agency, along
with the other steel structure works, foundations for the machine etc…[16]
In the hoist way fascia plate shall be provided without any extra cost,
where ever required as / if directed by engineer in charge.[17] Permanent
wiring with necessary safety devices like RCCB in all circuit, Over Voltage
Under Voltage protection and THD eliminator in circuit for lift machine
room and lift well with proper numbers of light points, with fixtures, exhaust
fan and plug points shall be provided by the agency. Only 3 phase Power
Supply shall be made available by department in lift machine room.
Necessary Earthing as per Lift Act/Rules shall be arranged by Lift Agency.
[18] Any civil/ electrical works for additional and alteration in lift shaft and
machine room related to erection of lift shall be made by lift agency
without any extra cost. (granite/marble fixing around all landing door
openings are not in lift agency’s scope.)
[19] Agency has to provide all working drawings and documents and
liaison services for obtaining all necessary permission from lift inspector
and other authorities.[20] acrylic transparent licence/display A4 size holder
in lift car[20A] As per statutory requirement of Govt. Of Gujarat lift &
escalator act 2000, lift agency has to provide 1. Car top safety barricade
2. Push & talk communication system.3. Fireman's switch operation at
Ground Floor. 4.carrying out third party lift inspection during/after lift
erection and provide report by third party authorized by concern licensing
authority 5.agency has to provide third party insurance upto completion
of free maintenance period and submit the document for the same.[21] Car
Panel Operating Buttons with floor position indicator/buttons must be of
Auto Glow type clearly visible when view from inside cabin. [22] For
Physically Handicapped person Full Length Handrails of hairline finish
steel grade of 304 should be provided at appropriate height on the Rear &
Side Wall Panels in Lift Car.
20 passengers Basement, Ground plus 9 upper floors with Rated Speed
409 of 2.0 /2.5 m/sec with micro price/PLC control and ACVVVF. drive
(B) With General PLUS ADDITIONAL SPECIAL FEATURES attached
herewith. Prem. Cat.
13 Passengers, Basement, Ground plus 9 upper floors with Rated Speed
of 2.0 / 2.5 m/sec.,
(B) With General PLUS ADDITIONAL SPECIAL FEATURES attached
herewith. Prem. Cat.
1 Ton Goods Lifts, Basement, Ground plus upper 4 floor with rated speed
411 of max 1 MPS with all necessary asccesories complete as required. 1 each 2690322.00 26903.22 2717225.22
1 Ton Goods Lifts, Basement, Ground plus upper 9 floor with rated speed
412 of max 1 MPS with all necessary asccesories complete as required. 1 each 3128486.00 31284.86 3159770.86
SUB HEAD-XI - SUBSTATION EQUIPMENTS
Design, manufactuer, Supply, installation, testing and commissioning of
Oil type transformer ONAN cooling Type 2500 KVA 11/0.433 KV,3 phase,
50Hz, Dyn 11 vector group, double wound copper, class A insulation,
indoor type Transformer with approximately 6.25% impedence subject to
tolerance as per IS, ON Load tap changer, operationon HV side in steps of
± 5% to -7.5%, @1.25%, having cable end boxes on HV side suitable for
3x300 Sq mm XLPE cable of 11KV (E) grade and 4000 Amp TPN
Sandwitch Bus Duct arrangement on LV side with neutral brought out
separately, Marshelling Boxes and other safety equipments etc. & suitable
for ambient 50˚C temprature. All Relays, Contacts & CT Terminal to be
wired upto marshelling Box suitably mounted on M.S. channel i/c
supplying and grouting of suitable M.S. Channel with all accessories and
confirming to Latest IS/IS:1180Part-1/2026 & complete in all respects as
required at site. Transformer losses shall be as per Latest ECBC Norms.
Main L.T. PANEL IN ESS
Design, manufacture, testing at works, supply, installation, testing and
commissioning of MODBUS ready SCADA Compatible 415V LT Panel
Tested Assembly – TTA, CPRI /Independent international test house
tested for all the tests as per IEC61439-1 & 2 and internal arc tests as per
IEC 61641, 50kA for 0.3 SEC. Copies of the test reports & certificates
shall be submitted with the tender. LT Panel shall also be tested of design
414 as per Seismic Zone 4 of IEC 60068-3-3 requires compliance against 0.4g
acceleration. Panel shall be rated for Impulse withstand capability as per
IEC-61439. For operator safety IP2 X (touch proof) protection to be
available even after opening the feeder compartment door. The
compartmentalization to be achieved by using metal separators, use of
PVC sheet / Hylem sheets shall not be allowed.
Main LT Panel shall be form 4b, for form of separation and rest with form
3b ,only metallic covers shall be used, Hylem / PVC sheets shall not be
allowed. The panel shall be FRONT operated, suitable for bus duct entry
for transformer incomings. Outgoing panels shall be suitable for cable
entry from the top/bottom. The type tested design of the Switchboard shall
be proven design from the main switchgear manufacturer (OEM). All
switchboards shall be supplied by authorized system integrator and
design, design warranty, including performance warranty on the switch
boards shall be from original equipment (switchgear) manufacturers.
Note : ALL the Panels should be SCADA Compatible for Monitoring &
Control on Ethernet and should include all accessories as required.Each
breaker in Main LT Panel & Emergancey panel shall have Zone Selective
Interlocking feature.
INCOMING FROM TRANSFORMER (2500 KVA)
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
1 No. 4000A, 4-pole EDO type ACB having release with following
functions :Protection for O/C, S/C, E/F and Metring for Current-
I1,I2,I3,In,Iavg,Imax, Voltage- Vph, Vline,Power- KW, KVA, KVAR, Power
factor, Maximeters /minimeters Energy –KWh,KVAh, KWArh, Demand
current- Ph & Neutral, Demand power-KWh, Under & over frequency,
current unbalance, reverse power, phase seq. reversal, Last 10 faults with
date and time stamping,Last 10 alarms with date and time stamping,
Current and Voltage Harmonics till 31st multiple with Waveform capture.
All release data should be available over MODBUS.
TNC breaker control switch.
ON, OFF, Trip, Ready to close and RYB indication lights with backup
96 x 96 sq.mm display module mounted on panel door directly connected
from release to display all parameters of ACB/MCCB.
1 No. 4000A, 4-pole EDO type ACB having microprocessor release with
following functions :Protection for O/C, S/C, E/F and Last 10 faults with
date and time stamping,Last 10 alarms with date and time stamping, All
release data should be available over Modbus.
ON, OFF, Trip, Ready to close and RYB indication lights with backup
Set of 4000 Amps rating TPN copper Bus Bars of suitable length shall be
provided for entire length of panel board. Busbar Design suitable for
Temperature rise 40 degree over & above ambient temp. of 45 degrees
Outgoing Panels
All ACB shall have release with following functions :Protection for O/C,
S/C, E/F and Metring for RMS values of highest current, Bargraph for %
loading, Ammeter, Current- I1,I2,I3, In,Iavg,Imax, Voltage- Vph, Vline,
Power- KW,KVA, KVAR, Power factor, Maximeters/minimeters, Energy
–KWh, KVAh, KWArh, Demand current- Ph & Neutral, Demand power-
KWh. The electrical endurance of ACB shall be 10000 operations upto
1600 AMP ACB and 6000 operation upto 3200 AMP ACB. All release data
should be available over MODBUS. All MCCBs shall have Microprocessor
release with following inbuilt functions :Protection for O/C, S/C, E/F.
Bus Section - C
2000 amp, 50KA FP ACB - EDO---------------1 Nos.
1600 amp, 50KA FP ACB - EDO---------------1 Nos.
800 amp, 50KA FP ACB - EDO---------------6 Nos.
400 amp, 36 KA FP MCCB ---------------2 Nos.
200 amp, 36 KA FP MCCB ---------------2 Nos.
Metering & Indication for each outgoing feeders.
96 x 96 sq.mm display module mounted on panel door directly connected
from release to display all parameters of ACB/MCCB.
Set of ON/OFF/Trip/Trip Circuit healthy/ready to close(for ACB) lamp with
control MCBs of 2A.
Main LT Panel ESS (TTA Type) as per specifications and details
above complete as required.-
Supply, Installation, testing and commissioning of HYBRID APFC Panel,
phase 4 wire, 415 V, 50 Hz AC System for Ambient temperature -5°C to
+40°C of following capacity with passive solution of 60% capacity and
active solution of 40% capacity, 3Phase 4 wire Hybrid Power Factor
Correction Solution (with arrangment for neutral current balance) to
achieve >0.99 lag and TDDI/THDV values within IEEE recommended
limits.APFC should be designed as per IS 16636 Or IEC 61921. The
active section and passive section shall work in sync to give optimized
output. The degree of protection of passive section should be IP 42, and
of active section should be minimum IP 21.The switching device for APFC
passive section should be through capacitor duty contactor and for the
active compensation system shall be IGBT based with 3 level topology
having 12 IGBT in inverter circuit. The active compensation system should
filter harmonics from 2nd to 50th individual harmonic order and shall be
selectable for the entire range. The active compensation system should
have feature to improve PF correction and harmonic filtration having
response time < 100 Micro second.
The hybrid panel shall be indoor type floor mounted free standing totally
enclosed, extensible, fabricated in compartmentalised designed made of
CRCA sheet steel of 2.0mm thick for framework & covers, 3 mm thick for
gland plate i/c cleaning & finishing complete with 9 tank process for
powder coated of approved shade ( RAL 7032-Siemens gray or as
approved by Engineer-in-Charge), having front section (switch gear and
control accessories) and rear section (capacitor and reactor), front and
rear access, having suitable current carrying capacity, extensible TPN
Aluminium alloy bus bar of high conductivity, DMC/SMC bus bar
supports,bottom base channel of MS Section,
fabrication shall be done in transportable section, entire panel shall have
common copper earth bar of minimum size of 25mm x 5mm with 2 nos.
earth studs, the earth terminals provided on the body
of capacitor bank shall also be bonded to the main capacitor panel earth
bus with 2 nos. 8 SWG or 6 SWG GI earth wires/ equivalent size of copper
conductor cable, forced ventilation for maintaining
temperature rise not more than 5°C from ambient, interconnections,
connections with 14% detuned reactor and heavy duty 525 V ISI marked
Impregnated MPP(Metalized Polypropylene) Capacitor (IS 13340 Part -1 &
2) APFC Panel shall be in compliance with
IS :16636 & CPWD Specifications etc. as per below details.
Suitable capacity MCCB/ACB (Upto 300 KVAR, MCCB and above
KVAR, ACB ) Microprocessor base with O/C, S/C, E/L release of TPN
50KA breaking capacity (Ics=Icu), ON, OFF, Trip, R, Y, B - LED Indicating
Lamp set alongwith required Instruments and accessories with extended
rotary handel and door interlocking arrangment. Current rating of the
Incomer in ampere shall be APFC Panel rating in KVAR x 1.4 x 1.5 or
Nearest higher standards rating.
(B) Instruments & Indications
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
a)For Passive Section :
i) 3-Phase current sensing APFC microprocessor relay/controller
advance 12/16 stages (12 stages for over all capacity of panel (active +
passive) below 500 KVAR and 16 stages 500 KVAR & above) and having
display of Phase wise V, A, PF, Cos-Phi, KW, KVA,KVAR, THD-V , THD-I,
harmonics up to 31 level.
ii) Auto Manual Selector switch, auxiliary contactors with timer for delay in
iii) Digital Multi function meter with LED Display for VA, PF, KW, KVA,
KVAR, THD-V & I, Frequency.
iv) Suitable rating control transformer shall be provided for control and
indication circuit.
v) All components like control transformer, meter, relay and indicating
lamp shall be protected by using suitable rating individual MCB's.
vi) Wiring of the control circuit shall be done by using 2.5 sq mm,
FRLS/HFFR 1100 V grade, PVC insulated multi stranded copper control
vii)Communication Ethernet/RS485/SNMP port open protocol for BMS
integration as per approved by Engineering in charge.
b) For Active Section : Dedicated HMI (Human Machine Interface)
(Minimum 7 inch display) for controlling and communication and having
display of Phase wise V, A, PF, Cos-Phi, KW, KVA, KVAR, THD-V , THD-I,
harmonics up to 50th level. Communication Ethernet /RS485/SNMP port
open protocol for BMS integration as per approved by Engineering in
BUS DUCT INDOOR TYPE-(As per IEC 61439-6)
Providing & erecting sandwitched type bus duct having following
specification: sandwich type busbar for use as feeder busbar for
interconnection between separate electrical equipment / load centers and
416 for use as plug in busbar risers. The busbar shall be suitable for operation
in a 690V / 1000V system with frequency of 50 Hz system can be either
earthed or unearthed, impulse voltage should be 12 KV; Standard
(A) Aluminium Bus
(j) 4000 A, Capacity (TR to LT PANEL) 30.00 RM 33348.00 333.48 33681.48
H.T. / L.T. CABLES, CABLE TERMINATIONS AND CABLE TRAY
Supply of following size of 11 KV XLPE insulated aluminium conductor
417 earthed and armoured cable conforming to IS 7098 complete as required.
3 Core, 300 sq.mm (from HT Panel to Transformer) 40.00 RM 3292.00 32.92 3324.92
Laying of one number additional PVC insulated and PVC sheathed / XLPE
power cable of 11 KV grade of following size direct in ground in the same
418 trench in one tier horizontal formation including excavation, sand
cushioning, protective covering and refilling the trench etc as required.
Above 120 sq. mm and upto 400 sq. mm 30.00 mtr 422.00 4.22 426.22
Laying of one number PVC insulated and PVC sheathed / XLPE power
419 cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL
pipe as required.
Above 120 sq. mm and upto 400 sq. mm 10.00 mtr 144.00 1.44 145.44
supplying and making indoor cable end termination with heat shrinkable
jointing kit complete with all accessories including lugs suitable for
following size of 3 core, XLPE aluminium conductor cable of 11 kV grade
Supplying, Fixing with End Terminations of 400 sqmm single core 1.1 KV
421 XLPE insulated copper conductor earthed and armoured cable conforming
to IS 7098 complete as required.
Providing and erecting XLPE (IS:7098) - BB ISI armoured cable
multistrand aluminium conductor for 1.1 KV . To be laid on wall with
necessary clamps or in existing trench / pipe of following size of cables.
END TERMINATIONS OF 1.1KV CABLES
Providing & fixing heavy duty flange type brass double compression type
cable gland with rubber ring for PVC insulated armoured cable complete
with outgoing tails insulating tape etc. for following size of cables.
Solder less crimping type Aluminium lugs confirming to IS suitable for
cable of following size evenly climped with high pressure tool & connected
to switchgear terminals with brass / cadmium plated nut bolts in an
approved manner.
CABLE TRAY / RCC PIPE
Providing & fixing approved make Perforated C type Cable tray, made
from sheet steel. The cable tray should be single or double bended as per
required and as per IS 2062 / 1079 and shall be coated with hot dip
425 galvanizing as per IS 2629/4759 with max 17.5% perforation with coupler
plate / fish plate and GI hardware like nut - bolt and washers etc. erection
with necessary support included) as per specification and as per
instruction of Engineer In charge.
Providing & laying RCC Hume pipe for cables to be laid at 90 cm below
ground across the road crossing on or floor with necessary material in an
approved manner and making the ground as per original.
Providing & laying approved make ISI marked HDPE 6kg/cm2 (Class-3) as
per IS:4984:1995 PE-80 to be erected at road crossing on or floor as
directed for laying of cable. The pipes as following size of dia & weight per
63 mm inner dia For Fiber & Power cables 100.00 RM 247.00 2.47 249.47
110 mm inner dia For Fiber & Power cables 100.00 RM 725.00 7.25 732.25
Fire Suppression system
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Supplying, installation, testing and commissioning of pre-engineered
Automatic Clean Agent 3M Novec 1230 (UL Listed/ FM approved) Direct
Low Pressure (DLP) System complete With DOT/PESO approved cylinder
fitted with Automatic Valve. Complete System shall be Tested and
Certified to LPCB/VDS/UL. (Makes : FireTrace / Kidde /Minimax)
Supply, installation, testing and commissioning of 10LB. Novec-1230 DLP
428 Assembly with automatic valve mounted on DOT/PESO approved cylinder, 2 Nos. 77650.00 776.50 78426.50
push in connector for tube, Mounting bracket etc.
Supply, installation, testing and commissioning of 5LB. Novec-1230 DLP
429 Assembly with automatic valve mounted on DOT/PESO approved cylinder, 2 Nos. 63900.00 639.00 64539.00
push in connector for tube, Mounting bracket etc.
Supplying, installation, testing and commissioning of 2.5LB. Novec-1230
430 DLP Assembly with automatic valve mounted on DOT/PESO approved 4 Nos. 41950.00 419.50 42369.50
cylinder, push in connector for tube, Mounting bracket etc.
Supply, installation, testing and commissioning of UL listed Linear
431 Pneumatic Heat Detection Tube ( operating temp at 120 Degree 70.00 mtr. 2000.00 20.00 2020.00
Centigrade, Colour-Red) For Automatic Fire Detection & Suppression.
432 Supply, installation, testing and commissioning of tee connection. 5 Nos. 2800.00 28.00 2828.00
433 Supply, installation, testing and commissioning of elbow connection. 5 Nos. 2800.00 28.00 2828.00
Supply, installation, testing and commissioning of end of line adapter with
Pressure Gauge For charging & monitoring.
Supply, installation, testing and commissioning of Low pressure switch for
monitoring system activation.
Supply, installation, testing and commissioning of Master control Unit with
436 LED Flasher, Electronic Hooter, LED Indicator with provision for 8 Nos. 8750.00 87.50 8837.50
Integration with Fire Alarm Control Panel complete as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including
accessories, and providing masonry enclosure with cover plate having
locking arrangement and watering pipe of 2.7 metre long etc. with
charcoal/ coke and salt as required.
Providing and erecting HOT deep Galvanised iron strip wire 8 to 16 SWG.
Providing and erecting required size Copper strip for earthing of H.T,
439 OCB/ACB/Transformer LT panel board, motors etc. using copper clamp. 200.00 kg 787.00 7.87 794.87
SUB HEAD-XII - SOLAR POWER GENERATION SYSTEM
Supply, Installation, Testing & Commissioning of following size of Grid
Tied Solar Power Plant with Integrated, Input Reverse Polarity Protection
Integrated, Insulation Resistor Detection Integrated, Residual Current
Monitoring Unit Integrated, Output Over Current Protection Integrated,
Output Short Circuit Protection Integrated, Output Over Voltage Protection
Integrated, Protection Degree: IP65, User Interface LCD &
APP,Datalogger & Communication: GPRS / Wi-Fi, Module Mounting
Structure: The mounting (Rectangular pipe / square pipe / circular pipe)
with requisite cross bars, nuts and bolts, etc. shall be Hot deep
galvanized with minimum 80micron coating. The Rectangular / square
/circular hollow pipe section used for the structure should have a minimum
thickness of 2.0 mm. other than above, the material thickness should be
minimum 2.5 mm. A certificate of a structural engineer certifying the
strength and stability of the mounting structure to withstand the weight and
wind speed of 150 km/hour throughout the life span of 25 years of the
system, shall be submitted by the vendors. Hot Dipped Galvanized steel
coils. suitable arrangement for base plate for foundation , solar panel
mounting, the structure should be suitable for carry the load of solar
panel,wiring, sprinkler system etc. with necessary foundation work/wall
mount, j bolt, anchor fastner etc. the nut bolt used for installtion of stucture
should be (SS 304) quality.
Solar Panels (ALMM approved): Frame Material : Anodized Aluminum
alloy Frame With Twin Wall Profile, Front Cover : High Transmission Low-
Iron Tempered Glass (AR Coated), High efficency and positive power
tolerance Pmax: 0/+5, Module Efficiency should be approx. 19.5%-22%,
Normal operating temperature 45'C, Junction Box with Waterproof IP67 &
MC4 Compatible and Enclosed with Bypass diodes, 100%
Electroluminescence test to ensure error free Modules, Thep. temp. co-
efficient of the PV module shall equal or better than -0.45%/degree C.
Solar PV modules of minimum fill factor 75% to be used. Unit Production:-
More than 4.5 Unit /kw /day (Actual)(1Year Avg) With 10 year Product
warranty and 25 year Linear Power Warranty includes all mechanical and
electrical parameters of the Solar panel. Modules must be complied to the
DCR(Domestic content requirements). The Ration of AC to DC is 5:6 for
the Installation capacity which are given in AC KW.
Solar Inverter: MPPT Range: MPPT Range: 80-1000 V , Max efficiency:
97.5% - 98.9%, O/p Frequency: 50/60Hz, Operating Altitude (m) ≤4000,
O/p Power Factor: ~1, O/P THDi: <3%, Operating Tempreture Range: -
25~60°C, Integrated protection of Inverter are Anti-islanding Protection,
Input Reverse Polarity Protection, Insulation Resistor Detection, Ground
fault protection, Residual Current Monitoring Unit, Output Over Current
Protection, Output Short Circuit Protection, Output Over Voltage
Protection, PV array string fault Protection. Protection Degree: IP65, User
Interface LCD & APP, Datalogger & Communication: GPRS / Wi-Fi. The
ground clearance of the bottom most edge of solar panel shall not be less
than 300 mm to 1200 mm or as per site’s technical/feasibility requirement.
a. Column –The minimum section (thickness) should be 60MM*40MM
b. Rafter - The minimum section (thickness) should be 60MM*40MM
c. Purlin - The minimum section (thickness) should be 40MM * 40MM
Balane of System with necessary Swichgears (Suitabel size and protection
of ACDB & DCDB), inter connecting wiring, earthing system as per the
CEIG drawing approval, lightining arrester system as per the CEIG
drawing approval, all liasoning work with various gov. dipartment like state
nodal agency,DISCOM & CEIG is included in agency scope
(Excluding All charges namely GEDA Application fees, Solar connectivity
Charges, Meter connectivity Charges, Meter testing Charges and system
stability/strenthning charges.)
(E) Grid Tied Solar Power System: 51 - 100 kW (3 - phase) 100.00 Per KW 40256.00 402.56 40658.56
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
The all inclusive comprehencive annual maintance contract cost covers
yearly maintanance of solar Pv Modules, Inverter, wiring, earthing,
switchgears, etc with material and labour cost including preventive
maintanance.The cost covers entire installation. AMC also includes
441 monthly site visit and inspection of project with submission of inspection
and solar generation report. All parts should be replaced/ repaired if found
faulty within specified time. Agency has to provide necessory licening work
for warranty,power,Bidirectional meter etc .
(D) 51KW-100KW System
Supply, installation, Testing & Commissioning of 'Silent Type Diesel
Generating set as per CPCB IV + or better norms along with having Prime
Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power
factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor,
including testing at factory and site with fuel, load for test and other
necessary arrangements Complete as per CPWD specifications, should
have QR code which should contain drawing, test report OEM manual,Geo-
Tag of manufacturing location, rating plate as per relevant IS Code etc.
and consisting of the followings:
(A) Diesel Engine:
Turbocharged Diesel engine 4 stroke water cooled, multi cylinder,
cynamically balanced fly wheel, electric start of suitable BHP at 1500 RPM
suitable for above output of alternator at 40 Degree C, 50% RH & at
Meter MSL, capable of taking 10% over loading for one hour after
hours of continuous operation. The engine will be with Electronic
governor, Dry type Air filter with service indicator, first filling of engine fuel
(after commissioning) lubricating Oil, Coolant and other consumables
complete with all the required accessories, the Electronic governor shall
be as per ISO 8528.The engine shall comply to the latest CPCB norms
(CPCB IV + or better) and Conforming to BS 5514, BS 649, IS 10000, IS
10002, IS 13018 and as per CPWD specifications.
(B) Engine mounted Instrument Panel fitted with and having digital display
(i) Start-stop switch with key
(ii) Water temperature indication
(iii) Lubrication oil pressure indication
(iv) Lubrication oil temperature indication
(v) Battery charging indication and Voltage indication
(vi) RPM indication
(vii) Over speed indication
(viii) Low lubricantion Oil trip indication
(ix) Engine Running Hours indication
(C) Alternator:
Synchronous alternator rated of appropriate KVA, 415 volts at 1500 RPM,
3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C,
50% RH & at 1000 Meter MSL. The alternator shall be having Screen
Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty,
dynamically balanced rotor, capable of taking 10% over loading for one
hour after 12 hours of continuous operation, self cooled,self-excited and
self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS
2613 suitable for tropical conditions and with class- H insulation.
(D) Base Frame & Foundation:
Both the engine and alternator shall be mounted on suitable base frame
made of MS channel with necessary reinforcement which shall be installed
on suitable cement concrete foundation and vibration isolation
arrangement as per recommendations of manufacturer.
Daily service fuel tank of suitable liters capacity as per CPWD
Specifications, fabricated out of 3 mm thick M.S. sheet complete with all
standard accessories and fuel piping between fuel tank and diesel engine
with MS class 'C' pipes of suitable dia. Complete with valves, level
indications & accessories as required as per specifications.
(F) Exhaust System:
Dry exhaust manifold with hospital type exhaust silencer and catalytic
(G) Starting System:
12V/24V DC starting system comprising of starter motors: voltage
regulator and arrangement for initial excitation complete with suitable
numbers of batteries (180 AH capacity lead acid SMF type) as required as
per specifications. The battery shall be housed inside the acoustic
enclosure of DG Set.
(H) Acoustic and weather proof enclosure with arrangement for fresh air
intake for cooling of the engine & alternator, extraction, discharging hot air
in to the atmosphere and the temperature rise inside the enclosure, noise
level outside enclosure. The acoustic enclosure should be suitable for
cable connection /connection through bus-trunking. Such arrangements on
acoustic enclosure should be water proof & dust-proof conforming to IP-65
protection. The enclosure shall be as per CPCB IV + or better norms etc.
and as per CPWD specifications.
Free standing floor mounted IP 42 automatic mains failure control panel
including auto by-pass, suitable for KVA as below for silent type DG set
complete with relays, timers, set of CTs for metering & protection and
energy analyser to indicate currents, phase and line voltages, frequency,
power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase
& Total), KW & provision for overload, short circuit, restricted earth fault,
under frequency, power (aluminum) and control (copper) cabling of
suitable size upto 15 meter between AMF panel, LT Panel and DG Set
including connection interconnection etc. as required, all complete and
inter locking and communication/ Ethernet /RS485/SNMP port open
protocol for BMS integration including suitable software, the panel shall be
of DG Set OEM make etc. as per approved by Engineering in charge and
including the following:
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
1. Suitable numbers and appropriate capacity 4 pole motorised electrically
operated draw out with cradle type 3 position ACB/ MCCB with electronic
release for O/C & E/F and shunt trip.
2. Auto/Manual/Test/Off selector switch
3. Protection for under and over voltage phase reversal (2 nos Over
voltage relay, 2 Nos. reverse power relay and 2 Nos. under voltage relay).
4. 3 Sets of current transformers 15 P 10 accuracy for protection and
VA class-I for metering
5. Energy analyser unit to indicate current, Voltage( L-N & L-L), kW, kVA
(Phase & Total), Frequency, KWH, PF
6. LED Indicating lamps for load on mains and load on set.
7. Fuse/ MCB for instruments.
8. Battery charger, complete with transformer/ rectifier, D.C. voltmeter and
ammeter, selector switch for trickle, off and boost and current adjustment.
9. Main supply failure monitor.
10. Supply failure timer.
11. Restoration timer
12. Control unit with three impulse automatic engine start/stop and failure
to start lockout.
13. Impulse counter with locking and reset facility.
14. ON/OFF/Control circuit switch with indicator
15. Audio/Video annunciation for
(i) High water temperature
(ii) Low lubricating oil pressure
(iii) Engine over speed
(iv) Engine fails to start
(v) Full load/maximum load warning
16. Protection for over/under Frequency, Loss of AC sensing, Over
Current, Unbalancing load with suitable number of relays and accessories
17. Maintenance notification based on Engine Run Hour & due date
18. Load Management through PLC to achieve auto opening and closing
of incomer breakers, bus coupler switching of essential panel , interlocking
providing signal to AMF Panel for load status and AMF shall give
command to DG Set to auto start / auto stop depending upon load status
and requirement etc. and necessary hardware and software required to
perform the operation shall be provided by the contractor including all
SITC of DG SET - 750 KVA, as described above and complete as per
specifications.
Emergency L.T. PANEL IN ESS for INCITE Block
Design, manufacture, testing at works, supply, installation, testing and
commissioning of MODBUS ready SCADA Compatible 415V LT Panel
Tested Assembly – TTA, CPRI /Independent international test house
tested for all the tests as per IEC61439-1 & 2 and internal arc tests as per
IEC 61641, 50kA for 0.3 SEC. Copies of the test reports & certificates
shall be submitted with the tender. LT Panel shall also be tested of design
443 as per Seismic Zone 4 of IEC 60068-3-3 requires compliance against 0.4g
acceleration. Panel shall be rated for Impulse withstand capability as per
IEC-61439. For operator safety IP2 X (touch proof) protection to be
available even after opening the feeder compartment door. The
compartmentalization to be achieved by using metal separators, use of
PVC sheet / Hylem sheets shall not be allowed.
Main LT Panel shall be form 4b, for form of separation and rest with form
3b ,only metallic covers shall be used, Hylem / PVC sheets shall not be
allowed. The panel shall be FRONT operated, suitable for bus duct entry
for transformer incomings. Outgoing panels shall be suitable for cable
entry from the top/bottom. The type tested design of the Switchboard shall
be proven design from the main switchgear manufacturer (OEM). All
switchboards shall be supplied by authorized system integrator and
design, design warranty, including performance warranty on the switch
boards shall be from original equipment (switchgear) manufacturers.
Note : ALL the Panels should be SCADA Compatible for Monitoring &
Control on Ethernet and should include all accessories as required.Each
breaker in Main LT Panel & Emergancey panel shall have Zone Selective
Interlocking feature.
SOURCE -1 INCOMING FROM ESS LT PANEL
1 No. 1600A, 4-pole EDO type ACB having release with following
functions :Protection for O/C, S/C, E/F and Metring for Current-
I1,I2,I3,In,Iavg,Imax, Voltage- Vph, Vline,Power- KW, KVA, KVAR, Power
factor, Maximeters /minimeters Energy –KWh,KVAh, KWArh, Demand
current- Ph & Neutral, Demand power-KWh, Under & over frequency,
current unbalance, reverse power, phase seq. reversal, Last 10 faults with
date and time stamping,Last 10 alarms with date and time stamping,
Current and Voltage Harmonics till 31st multiple with Waveform capture.
All release data should be available over MODBUS.
TNC breaker control switch.
ON, OFF, Trip, Ready to close and RYB indication lights with backup
96 x 96 sq.mm display module mounted on panel door directly connected
from release to display all parameters of ACB/MCCB.
SOURCE - 2 INCOMING FROM DG SET (750 KVA)
1 No. 1600A, 4-pole EDO type ACB having release with following
functions :Protection for O/C, S/C, E/F and Metring for Current-
I1,I2,I3,In,Iavg,Imax, Voltage- Vph, Vline,Power- KW, KVA, KVAR, Power
factor, Maximeters /minimeters Energy –KWh,KVAh, KWArh, Demand
current- Ph & Neutral, Demand power-KWh, Under & over frequency,
current unbalance, reverse power, phase seq. reversal, Last 10 faults with
date and time stamping,Last 10 alarms with date and time stamping,
Current and Voltage Harmonics till 31st multiple with Waveform capture.
All release data should be available over MODBUS.
TNC breaker control switch.
ON, OFF, Trip, Ready to close and RYB indication lights with backup
96 x 96 sq.mm display module mounted on panel door directly connected
from release to display all parameters of ACB/MCCB.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Set of 1600 Amps rating TPN copper Bus Bars of suitable length shall be
provided for entire length of panel board. Busbar Design suitable for
Temperature rise 40 degree over & above ambient temp. of 45 degrees
Outgoing Panels
All ACB shall have release with following functions :Protection for O/C,
S/C, E/F and Metring for RMS values of highest current, Bargraph for %
loading, Ammeter, Current- I1,I2,I3, In,Iavg,Imax, Voltage- Vph, Vline,
Power- KW,KVA, KVAR, Power factor, Maximeters/minimeters, Energy
–KWh, KVAh, KWArh, Demand current- Ph & Neutral, Demand power-
KWh. The electrical endurance of ACB shall be 10000 operations upto
1600 AMP ACB and 6000 operation upto 3200 AMP ACB. All release data
should be available over MODBUS.
All MCCBs shall have Microprocessor release with following inbuilt
functions :Protection for O/C, S/C, E/F.
Bus Section - A
1000 amp, 50KA FP ACB - EDO---------------1 Nos.
400 amp, 50KA FP MCCB ---------------1 Nos.
200 amp, 36 KA FP MCCB ---------------2 Nos.
100 amp, 36 KA FP MCCB ---------------2 Nos.
Metering & Indication for each outgoing feeders.
96 x 96 sq.mm display module mounted on panel door directly connected
from release to display all parameters of ACB/MCCB.
Set of ON/OFF/Trip/Trip Circuit healthy/ready to close(for ACB) lamp with
control MCBs of 2A.
Main LT Panel (Incite Block) in ESS (TTA Type) as per specifications
and details above complete as required.-
SUB HEAD-XIV - UPS SYSTEM
Supplying, installation, Testing & Commissioning of of following capacity
at full load (Unity Power Factor) at operating temperature 0 to 40 deg C,
Relative humidity 0 to 95%, Online double conversion true sine wave
Uninterrupted hot swappable (allow for the replacement or addition of
battery modules without shutting down the entire system) modular Power
Supply (UPS) system with N+1 modules (N denotes total number of
moduels requird for rated capacity). The UPS shall include a Rectifier,
inverter, battery bank suitable for 30 minutes back up (Battery VAH
capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour
backup time) on full load (Battery shall be VRLA, SMF in ABS Container)
and Static Bypass switch alongwith provision for manual bypass, suitable
isolation transformer for additional protection against neutral faults etc.
UPS shall have inbuilt phase sequence correction.
The UPS systems offered are to be of the latest technology with Digital
Control Microprocessor based for reliable operation using Insulated Gate
Bipolar Transistor (IGBT)'s both for the rectifier & inverter (3 Level) with
PWM (Pulse Width Modulation). The quality of design,manufacturing and
inspection process should confirm to the relevant International standards
such as IEC/EN/VDE. The operating efficiency of the UPS systems shall
be >96% while operating on battery mode and delivering quality power to
the 100% non-linear loads. Current total harmonic effect (ITHD) on the
input grid shall be < 5% at 50 %load. (The required LC (inductor (L) and a
capacitor (C)) filters shall be included in UPS cost), extreme power factor
kit to be included to limit the input power factor (PF) to 0.99 and output
power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x
), however UPS shall be suitable to take load at 0.7 laging to 0.7 leading
power factor loads.
UPS shall be suitable for incoming supply AC : 3Phase 400V +/-20%,
Hz +/-5 Hz, AC Output voltage: 3Phase 415 Volt, 50 Hz +/- 0.2Hz,
Overload capacity of 120% for 10 mins, Sine wave output. Non
condensing, noise level less than 60db at 1 meter distance, protections:
Input Under voltage over voltage, abnormal out voltage, battery over
charging, output over current, short circuit protection, battery deep
discharge protection, 10KV surge. UPS must comply with low voltage
electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204
Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI)-
Communication RS232/RS485/SNMP port open protocol for BMS
integration, all hardware & software for iOT Communication as per
approved by Engineering in charge. Required battery racks and
interconnecting copper conductor cables of suitable size and connectors
and all required accoseries are inclusive of the cost). This system must
provide a means for logging and alarming of all monitored points plus
email notification. Forced air-cooling with integral inbuilt fans with
redundancy (if one fan fail UPS should be able to handle at least 80% of
the load, Noise Level 65 DB at 1 meter distance. The system shall be in
compliance IEC 62040- 1,2 & 3, IS: 16242 and CPWD Specification.
Display Panel (minimum) (In-build 5 inch or more LC Display / LED ) to
display : a) Input: Voltage, current, Frequency. b) Bypass: Voltage,
Frequency. c) Output: Voltage, frequency, Current.
d) Battery: Voltage, Capacity. e) Load: KVA, KW, Percentage.
f)Temperature: STS, Inverter, PFC. g) Event Logging & Statistical Data
(On LCD/LED): UPS should capture and display up to 3000 events like:
Over temperature / DC Bus Fail / Fan Fail / Fuse Fail / Overload / Short-
circuit / Device Fail / Inverter Fail / Rectifier Fail / Bypass Fail, etc. h)
Statistical Data: No. of power failures / Transfers to Bypass / Total
Running time, etc. i) Mains Mode of Operation /Battery Mode of Operation
/ Bypass feeding the load / UPS Fault /Battery charging and discharging,
overload, battery voltage and battery capacity. j) Audible Alarms : Mains
Failure, Battery Low Alarm, UPS Overload, Fault, Shutdown, Input Over,
Under Voltage, Output Over, Under Voltage, Battery Over, Under Voltage,
Over Load and short circuit, Over Temperature. The UPS should have QR
code which should contain drawing, test report OEM manual,Geo- Tag of
manufacturing location etc.
30 KVA (Each Power module shall be < 10 KVA) 1 set 428600.00 4286.00 432886.00
200 KVA (Each Power module shall be < 50 KVA) 1 set 2013065.00 20130.65 2033195.65
SUB HEAD - ESS Shifting
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and erecting XLPE (IS:7098) - BB ISI armoured cable multistrand
aluminium conductor for 1.1 KV . To be laid on wall with necessary clamps
or in existing trench / pipe of following size of cables.
END TERMINATIONS OF 1.1KV CABLES
Providing & fixing heavy duty flange type brass double compression type
cable gland with rubber ring for PVC insulated armoured cable complete
with outgoing tails insulating tape etc. for following size of cables.
Solder less crimping type Aluminium lugs confirming to IS suitable for
cable of following size evenly climped with high pressure tool & connected
to switchgear terminals with brass / cadmium plated nut bolts in an
approved manner.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick
including accessories, and providing masonry enclosure with cover plate
having locking arrangement and watering pipe of 2.7 metre long etc. with
charcoal/ coke and salt as required.
Providing and erecting HOT deep Galvanised iron strip wire 8 to 16 SWG.
Providing and erecting required size Copper strip for earthing of H.T,
450 OCB/ACB/Transformer LT panel board, motors etc. using copper clamp. 200.00 kg 787.00 7.87 794.87
Sub Head - External Lighting
Supplying & erecting approved make Octagonal pole made from HR Sheet
steel. The pole should be made as per IS and shall be coated with hot dip
galvanizing as per IS 2629/2633/4759, suitable suspend local wind speed
with integral junction box consist of terminal plate of min 6 mm Hylam
sheet, standard profile 35mm x 7.5 mm Din-Rail for MCB mounting, stud
451 type terminal and arrangement for cable termination to be erected on 10 each 8111.00 81.11 8192.11
foundation as per details given by manufacturer considering site
requirement.-(D) 6 Mtr. Long 70 mm Top X 135 mm bottom dia, 3 mm
thickness with 200mmX200mmX12mm base plate, 4-M20 Bolts and
600mm long J-Bolt.
Supplying & erecting approved make Octagonal pole made from HR Sheet
steel. The pole should be made as per IS and shall be coated with hot dip
galvanizing as per IS 2629/2633/4759, suitable suspend local wind speed
with integral junction box consist of terminal plate of min 6 mm Hylam
sheet, standard profile 35mm x 7.5 mm Din-Rail for MCB mounting, stud
452 type terminal and arrangement for cable termination to be erected on 5 each 15550.00 155.50 15705.50
foundation as per details given by manufacturer considering site
requirement.-(H) 9 Mtr. Long 70 mm Top X 155 mm bottom dia, 3 mm
thickness with 260mmX260mmX16mm base plate, 4-M24 Bolts and
750mm long J-Bolt.
Providing 1:2:4 cement concrete foundation & 70 % PCC from bottom
including excavation for the pole of size 45 X 45 X 100 cm, deep in below
453 ground level with plinth of 45 cm X 45 cm ( or 45 cm dia X 45 cm ) high 15 each 801.00 8.01 809.01
upper ground level with necessary curing and finishing in approved
manner. ( for 4 & 6 mtr pole)
Supplying & erecting approved make SMC press moulded composite FRP
loop in, loop out approx 2 mm thick box complete with backelite connector
strip 5 way (3P+N+E) DIN rail for mounting mob & hanged doors as per
454 requirement having locking arrangement with mounting clamp with nuts, 15 each 2987.00 29.87 3016.87
bolts & washers suitable for erection on pole with cable clamp & earth built
of following size of box. including 6A SP MCB 10 KA rating Cat-III).-(g)
250mm X 220mm 135mm (deep)
Providing and erecting Street Light pole bracket comprising main B Class
GI pipe of 4.2 cm/require outside dia. complete with suitable B Class G.I.
sleeve tubing of approx. 45cms.length and suitable for 76.5 mm /80mm /
required size of pole top having sufficient fasteners for fixing the brackets
455 and having spread of 1.5.mtr. length with 110 deg.with vertical plane & 2 each 677.00 6.77 683.77
suitable welded stays, reducer and with check nuts complete painted with
one coat of Red oxide / PU base primer and two coats of Aluminium / PU
paint. paint with following nos of arms. (For 9 Mtr Pole)-[A] Single Arm
Bracket 1.5 Mtr
Providing and erecting Street Light pole bracket comprising main B Class
GI pipe of 4.2 cm/require outside dia. complete with suitable B Class G.I.
sleeve tubing of approx. 45cms.length and suitable for 76.5 mm /80mm /
required size of pole top having sufficient fasteners for fixing the brackets
456 and having spread of 1.5.mtr. length with 110 deg.with vertical plane & 3 each 993.00 9.93 1002.93
suitable welded stays, reducer and with check nuts complete painted with
one coat of Red oxide / PU base primer and two coats of Aluminium / PU
paint. paint with following nos of arms. (For 9 Mtr Pole)-[B] Double Arm
Bracket 1.5 Mtr
Providing and erecting street light pole bracket comprising main B Class
MS pipe of 4.2 cm/require outside dia. complete with suitable B Class M.S.
sleeve tubing of approx. 45cms.length and suitable for 76.5 mm / 80mm. /
require size pole top having sufficient fasteners for fixing the brackets and
457 having spread of 1 mtr. length with suitable rise as per site condition & 8 each 556.00 5.56 561.56
suitable welded stiffener reducer and nipple with check nut complete
painted with one coat of Red oxide / PU base primer and two coats of
Aluminium / PU paint. paint with following nos of arms.-[A] Single Arm
Providing and erecting street light pole bracket comprising main B Class
MS pipe of 4.2 cm/require outside dia. complete with suitable B Class M.S.
sleeve tubing of approx. 45cms.length and suitable for 76.5 mm / 80mm. /
require size pole top having sufficient fasteners for fixing the brackets and
458 having spread of 1 mtr. length with suitable rise as per site condition & 2 each 751.00 7.51 758.51
suitable welded stiffener reducer and nipple with check nut complete
painted with one coat of Red oxide / PU base primer and two coats of
Aluminium / PU paint. paint with following nos of arms.-[B] Double Arm
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Street Light (IP-65), surge protection-4 KV integral and 10 KV non
Integral, light must have 440 V AC line supply protection. It should
withstand 48 hours for 440 v AC line supply.(iii) Above 60 to 90 watts-Cat -
Providing and erecting XLPE (IS:7098)(I)-88 ISI armoured cable
multistrand Aluminium conductor for 1.1 KV. to be laid on wall with
necessary clamps or in existing trench / pipe of following size of cables-
(A) 4 core 16 Sq. mm
Providing & fixing heavy duty flange type brass cable gland with rubber
ring for PVC insulated armoured cable complete with outgoing tails
insulating tape etc. for following size of cables.-(d) 2 to 4 core 16 sq. mm
Solder less crimping type Aluminium lugs confirming to IS suitable for
cable of following size evenly climped with high pressure tool & connected
462 to switchgear terminals with brass / cadmium plated nut bolts in an 160 each 15.00 0.15 15.15
approved manner.-(c ) 16/25 sq. mm
Providing & laying approved make ISI marked HDPE 6kg/cm2 (Class-3) as
per IS:4984:1995 PE-80 to be erected at road crossing on or floor as
463 directed for laying of cable. The pipes as following size of dia & weight per 1000.00 RM 247.00 2.47 249.47
6mtr.-63 mm dia (OD-63 mm & ID-51 mm nominal) For Fiber & Power
Providing & laying RCC Hume pipe for cables to be laid at 90 cm below
ground across the road crossing on or floor with necessary material in an
approved manner and making the ground as per original.-150 mm dia
Supplying & erecting funnel type earthing having earth plate of following
size burred in specifically prepared earth pit 3 mtr. below ground with
kg. charcoal and salt with alternate layers of charcoal & salt, 20mm.dia.
G.I. pipe with Funnel with a wire mesh for watering & bricks masonry
block, C.I. Cover complete as per para 7.3 of IS 3043 with necessary
465 length of double Galvanised Iron / copper earth wire No 6 SWG bolted 2 each 2543.00 25.43 2568.43
with lug to the plate and covered in 12 mm dia. G.I. pipe 2.5 mtr long
complete connected to the nearest switch gear with end socket as per
direction & duly tested by earth tester confirming to IS (As per drawing)
with following specification -(B) With 45 x 45 x 0.35 cms. C.I. earth plate
Providing and erecting Hot deep Galvanized Iron strip wire 8 to 16 SWG.
Smart 4G Timer, Supply of IoT based 4G Smart Streetlight Control & Monitoring System having
a Smart Panel comprising of 3 Phase IoT Streetlight Smart 4G Timer with 16x2 LCD to display
RSSI, relay status, RTC time & diagnostics., Controller works on 3-phase & also on any
available 1-Phase., Controller with 8-hour battery backup during external power failure. External
power failure alert immediately to cloud., 110-630 V AC @ 50-60 Hz – 3 phase operating
range., Standby power consumption <3W., Smart 4G Timer with RS232 port for DLMS Energy
meter., Smart 4G Timer must be compatible with any make / brand of DLMS (RS232) Energy
Meter., DI: 4 Nos. (3 Contactor / Latch detection, 1 for Door Sensor.)., DO: 3 Relays for
Independent control each phase (R, Y, B) with 1 extra spare relay., Smart 4G Timer with dual
SIM functionality for connectivity backup., 4G M2M SIM 3-Year communication included., Local
configuration via WiFi / BLE for maintenance or during force majeure., GPS chip inbuilt of
467 Smart 4G Timer for auto location tracking & astronomic schedule location., 50 programmable
schedules., Astronomic scheduling with monthly offsets., Smart 4G Timer has inbuilt timer
stores schedules locally & also stores schedule execution logs locally, syncs to cloud whenever
connected to cloud., Auto-scheduler overrides manual operations., Monitoring & alerts for MCB
trips., Over/under voltage, current, overload, power factor & short circuit protections with alerts
via Dashboard, App, SMS, WhatsApp & Email., Contactor / Latch chattering protection &
alerts., Smart 4G Timer with neutral failure protection and alert., Bulit-in Watchdog for anti-
jamming., Smart 4G Timer must send Regular "heartbeat" on software for CCMS status.,
Accelerometer for tamper & panel movement detection & alerts., Smart 4G Timer must be
tested from an NABL Lab for Surge Test @ 6 KV (IEC 61000-4-5), ESD Test @ 4 KV (IEC
61000-4-2), EFT @ 2 KV (IEC 61000-4-4), Conducted Emission @ 150 KHz-30 MHz
(CISPR11), Damp Heat Test (40 Deg C @ 95% RH) 2 cycles of 12+12 hours (IS: 9000 (Part
5/Sec.2):1981 latest) with all test passing criteria as “Temporary degradation or loss of function
or performance which is self-recoverable”., FOTA functionality required for upgrades., Smart 4G
Timer sends & stores online/offline data of controller & load for lamp burn hours analysis.,
It stores & syncs connectivity logs for configuration of network connections & analytics., PANEL
& SWITCHGEAR, The panel includes a Class 1 DLMS energy meter NABL approved with 1-2
months of stored data of daily, hourly, monthly, load survey, instantaneous, events, tamper data
& with power events stored in meter memory for audit purpose., Must monitor V, I, KWH, KVA,
PF, KVAH, etc., Panel made with 2 mm CRCA sheet with ground mountable stand complete
with gland plate, waterproof glands, earthing bolt., IP55, weatherproof panel with RAL7035
powder-coated., Smart 4G Timer must be fitted on removable terminal sockets for easy
maintenance., Switchgear includes 3 Nos. 3 pole Contactor / Latch having minimum 50 A Load
carrying capacity per phase, all other switchgear & wires: 40 A load carrying capacity., 1 Nos.
4P MCB 10 kA for Incomer & 6 Nos. 1P MCBs 10 kA for Outgoing., Phase-Wise Bypass MCBs
required., 4P RCCB 100 mA., door sensor. Also, provide lock & key facility., Panel mount
outdoor antenna for GSM, GPS., Canopy design for draining down water., CCMS SMART
SOFTWARE, OAuth 2.0 APIs for sending data to Government clouds/software, etc., CCMS
Web dashboard with secure password & OTP login., Hosted on trusted cloud, data security,
antivirus & attack protection., HTTPS., AES256-bit encryption., Vulnerability Assessment and
Penetration Testing (VAPT) certificate for CCMS Software.,
Streetlight management software for load status, live analytics & reports.,
Energy meter data tables (kW, kWh, PF, I, V, etc.) available., Utility
monthly bill reconciliation & Class 1 accuracy reports for billing, energy
monitoring & auditing for streetlight load., Fault detection., Light fault 99%
analysis on dashboard using energy monitoring., WhatsApp integration.,
Hierarchy-wise reporting & alerts., GIS mapping of live connected
streetlight control panels, poles & streetlights., MQTT protocol.,
Smartphone app with local configuration & navigation., Monitoring &
reporting of lighting parameters., Facility for media attachments for site 1 each 99433.00 994.33 100427.33
photos/videos/work permits/checklists, etc. per Feeder Panel for remote
verification., Asset management module for streetlight infrastructure data.,
Complaint/service task management with history & escalation must be
available., Android & iOS App for dashboard analytics, graphs, energy
data, alerts., 3 Years CCMS Web Software & Cloud Server Hosting
subscription included., Customizable, user-friendly dashboard.,
Total of Sub Head-XV
SUB HEAD 'A' - EQUIPMENTS
Water Chilling Unit
Water Cooled SCREW Chiller
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Supplying, Installation, Testing and Commissioning of following capacity
floor-mounted VFD (Variable Frequancy Drive) Operated water cooled
screw-type chiller machine complete with single/multi semi-hermatic
mono/multi screw type compressor, with independent circuits, water-
cooled Shell & Tube type condenser, Shell & Tube horizontal flooded type
evaporator with carbon steel shell and seamless copper tubes with 19 mm
nitrile rubber insulation i/c suitable foundation/mounting structure made of
RCC/MS Structure i/c anticorosive paint, anti vibration pad, power control
cable and connection inter connection etc. as per design approved by
engineer-in-charge, common base frame, interconnected copper
refrigerant piping and wiring, vibration Isolators, gauge panel, automatic
safety controls, flow switch at evaporator and condenser and ozone
friendly Chlorofluorocarbons (CFC)-free refrigerant gas R- 134A. The
refrigerant flow control shall use an electronic expansion valve. The chiller
shall be designed for a Water Side working pressure of 150 psig and
hydraulically tested at 1.5 times of design pressure . A number of properly
spaced baffles shall be provided for maintaining optimum water velocity
and heat transfer and the tubes shall be adequately supported. The chiller
shall be Building Management System (BMS) compatible The system shall
be in confirmation to IS : 16590 and CPWD Specification as amended
upto date. BEE Star labeling and CPWD Specification as amended upto
date and tested as per IS
Chilled water Leaving Temp. (6.67 0C)
Chilled water Entering Temp. (12.2 0C)
Evaporator fouling factor = 0.018 m2. 0C/kW
Condenser water Entering Temp. (32.2 0C)
Condenser water Leaving Temp. (36.4 0C)
Suitable for Seismic Zone and Altitude as per location/site.
Microprocesser based controller.
Minimum COP at AHRI Conditions = 6.7 min.
IKW/TR at Full Load = 0.64 max.
NPLV at design conditions not exceeding 0.32 IKW/TR
IPLV at AHRI conditions not exceeding 0.32 IKW/TR
Manufacturer’s AHRI Certified Selection Performance Sheet to be
submitted to evaluate and verify the specified performance parameters
Supply, Installation, testing & commissioning of water chilling m/c
including transit insurance, transportation, loading & unloading, lifting &
Chiller should be tested on the load - 100 % / 75% / 50% / 25 % / 15% @
Capacity : 390 TR Actual (2 # Working 1 # Standby) BEE 4 Star Rating
Chiller Plant Optimization
Intel Quad Core processor (Latest Technology), Windows® 2010 SP2 or
above operating System, 1 TB HDD, 8 GB RAM, Enhanced graphic Card,
DVD Combo Drive, Ethernet Port with 32" color monitor flat screen LED
display, multimedia keyboard & optical mouse and microsoft office
and anti virus as per Specification.
Chiller Plant Optimizer(CPO) should have algorithm to match the real time
damand load with the chiller maximum COP operating condition. CPO
should be capabile of operating VFD's to maintain optimal water flow on
evaporator and condensor side of the chiller. It should also optimize the
470 machine run time and the machine sequencing/scheduling to get the best 1 Nos. 2859543.00 28595.43 2888138.43
system efficiency. It should also generate alarms in case of abnormal
operating range. CPO should be complete with software, enclosure/Panel.
Note- CPM shall not be accepted.
Field Devices 0.00
471 Immersion temp sensor 45 Nos. 3491.00 34.91 3525.91
473 Water Pressure transmitter 1 Nos. 9241.00 92.41 9333.41
474 Water Level Switch 1 Nos. 8728.00 87.28 8815.28
2 x 1 sq.mm Copper Shielded unarmoured cable for signal and power as
per specification. (for I/O points hard wired to DDC).
476 25 mm thick PVC conduit. 450 Nos. 123.00 1.23 124.23
CAT 6 A unarmoured cables with required accessories like RJ45
3 x 1.5 sq.mm Shielded unarmoured cable for signal and power as per
specification. (power Cable).
Primary Chilled Water Pumps
Supply, Installation, Testing and Commissioning of vertical inline Split
coupled chilled water circulating pump set capable of delivering water
against a head of 12 meters complete with motor, .as per specifications
1 No. Vertical Inline Long Coupled type pump
1 No. suitable HP, TEFC squirrrel cage induction motor with class "F"
insulation, 1450 rpm sunchronous speed, operating on 415 ±10% volt,
phase, 50 htz A.C supply,Suitable for outdoor application.
2 Nos. 200 mm dia. Dail type pressure gauges (range-0-5 kg/cm2)
Duly insulated with 40 kg/cum density close cell elatromeric Nitrile rubber
insulation. cladded with aluminium sheets of 0.5mm thickness and
properly clamped to pump in two semicircular sections as per
specifications.
Minimum Required Efficiency of Pump-70 %
M.O.C of Impeller- BRONZE
The pumps shall be provided with cast iron suction guides and Triple Duty
Valve (PN-16) factory fitted
1 No. -Vertical Inline split coupled type single stage pump with bronze
impellar, S.S Shaft, CI body and outside fitted balanced mechanical seal
and Pump casing should be PN 16 rated.
Chilled water 3557LPM at 12 M head (2 # Working 1 # Standby) 3 Nos. 259989.00 2599.89 262588.89
Secondary Chilled water pumps
Supply, Installation, Testing and Commissioning of vertical inline Split
coupled chilled water circulating pump set capable of delivering water
against a head of 25 meters complete with motor, VFD shall be motor
mounted with (IP-55) protection for Sensorless Control and VFD shows
flow and head on its display all the time and separate Pump Logic
controller etc.as per specifications and drawings.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Variable Pumps must be provided with a cloud-based subscription service
that enables Active Performance Management. It must proactively tracks
and manages pump performance and provides early diagnostic
messaging, web accessible trends and analysis along with automated
reports helping end customer to make performance-based decisions and
take immediate action to deliver the best possible HVAC pump
performance.The cloud based subscription should deliver real-time alerts,
1) Alarms & warnings on excessive vibration,
2) Pump in hand,
5) BrokenCoupling
6) VFDandMotorOverheating
The connectivity kit supplied by OEM/authorized representative should
have ability to connect and provide real time data for upto 8 pumps in a
single plant room.
The pumps shall be provided with cast iron suction guides and Triple Duty
Valve (PN-16) factory fitted
1 No. -Vertical Inline split coupled type single stage pump with bronze
impellar, S.S Shaft, CI body and outside fitted balanced mechanical seal
and Pump casing should be PN 16 rated.
Duly insulated with 40 kg/cum density close cell elatromeric Nitrile rubber
insulation. cladded with aluminium sheets of 0.5mm thickness and
properly clamped to pump in two semicircular sections as per
specifications.
Chilled water 3557 LPM at 25 M head (2 # Working 1 # Standby) 3 Nos. 542133.00 5421.33 547554.33
Condenser Water Pumps
Supply, Installation, Testing and Commissioning of vertical inline Split
coupled condenser water circulating pump set capable of delivering water
against a head of 30 meters complete with motor, VFD shall be motor
481 mounted with (IP-55) protection for Sensorless Control and VFD shows
flow and head on its display all the time and separate Pump Logic
controller etc.as per specifications and drawings.
Variable Pumps must be provided with a cloud-based subscription service
that enables Active Performance Management. It must proactively tracks
and manages pump performance and provides early diagnostic
messaging, web accessible trends and analysis along with automated
reports helping end customer to make performance-based decisions and
take immediate action to deliver the best possible HVAC pump
performance.The cloud based subscription should deliver real-time alerts,
1) Alarms & warnings on excessive vibration,
2) Pump in hand,
5) BrokenCoupling
6) VFDandMotorOverheating
The connectivity kit supplied by OEM/authorized representative should
have ability to connect and provide real time data for upto 8 pumps in a
single plant room.
The pumps shall be provided with cast iron suction guides and Triple Duty
Valve (PN-16) factory fitted
1 No. -Vertical Inline split coupled type single stage pump with bronze
impellar, S.S Shaft, CI body and outside fitted balanced mechanical seal
and Pump casing should be PN 16 rated.
Duly insulated with 40 kg/cum density close cell elatromeric Nitrile rubber
insulation. cladded with aluminium sheets of 0.5mm thickness and
properly clamped to pump in two semicircular sections as per
specifications.
The pump characteristic shall be as follows:
Chilled water 5632 LPM at 30 M head (1 standby) (2 # Working 1 #
FRP Cooling Tower
Supply, installation, testing and commissioning of CTI Approved FRP
cooling tower of 14,36,400 Kcal/hr heat rejection capacity with FRP water
basin, PVC fillings with integral louvers and drift eliminators complete with
hot water basin either fitted with spray nozzles or having self rotating
sprinklers, statically and dynamically balanced axial flow fan direct drivan
or driven through speed reduction gear box with TEFC induction motor,
suction screen, make up- quick fill arrangement, over flow and drain pipe
connections with valves and suitable inspection ladder, access
arangement for cooling tower interier, cement concrete foundation,
steel/masonary supporting structure, anti vibration mountings etc. as per
specifications and as required. 2 coats of coating STARCOAT FRP
475 TR capacity @ 25.6 Deg.C Wb (Ambient) (2 # Working)
Flow Rate : 5632 LPM
Motor (18 KW x 2 Fan)
Cooling Tower 'IN' Temp. : 36.4oC
Cooling Tower 'OUT' Temp.: 32.2oC 2 Nos. 1164161.86 11641.62 1175803.48
Air - Dirt Separator
Supply installation testing and commisioning of Deaerator-dirt separator.
Flanged connections, complete with Brass drain valve 1” F (from DN 50 to
DN 150), 2” F (from DN 200 to DN 300). complete with a set of concentric
metal mesh surfaces to create the swirling motion required to facilitate the
release of micro-bubbles and dirt to the surfaces. Epoxy resin coated steel
body. Brass automatic air vent valve body. Stainless steel internal
element. PP float. Brass float guide and stem. Stainless steel float lever
483 and spring. EPDM hydraulic seals. Medium water and non-hazardous
glycol solutions excluded from the guidelines of EC directive 67/548;
maximum percentage of glycol 50%. Maximum working pressure 10 bar.
Working temperature range 0–110°C. Particle separation rating down to
5µ. Working temperature range 0–100°C. Floor brackets as per site
requirement. Third Party test report is required to be submit by contractor
from manufacturer for 5µ Particle separation (TNO)
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Supplying, installing, testing, and commissioning Automatic Tube Cleaning
System for water-cooled chiller condenser/evaporator, complete with
cleaning balls, injection and collection units, control panel, piping, valves,
electrical works, BMS interface, accessories, and documentation, as per
specifications and directions of Engineer-in-Charge
Hot Water Generator (Winter heating)
Supply, installation, testing and commissioning of electrically operated Hot
Water Generator of efficiency more than 90% of capacity 150 KW in
multiple bank complete with PLC based microprocessor controls, electrical
panels, stainless steel braided pipe flexible connector etc. confirming to
tender specifications section. (1W+1S)
Hot water 'In' : 55 °C
Hot water 'Out' : 65 °C
Hot water pump for hot water generator (Winter heating)
Supply,erection, testing and commissioning of vertical Inline chilled water
pump for hot water recirculation, pump set capable of delivering
USGPM of water against 30 mtr head each comprising of the following
and complete as required
1 No. - Vertical Inline split coupled type pump with bronze impellar and
outside fitted mechanical seal.
Duly insulated with 32 kg/cum density close cell cross linked cladded with
aluminium sheets of 0.5mm thickness and properly clamped to pump in
two semicircular sections as per specifications.
Note: One set of pump shall be used as stand by.
1 No. Suitable HP, TEFC squirrel cage induction motor (IE2) with class 'F'
insulation, 3000 RPM synchronous speed, operating on 415 Volts ± 10 % , 3 Nos. 112550.00 1125.50 113675.50
3 phase , 50 Hz A.C. supply.
SUB HEAD 'B' - EQUIPMENTS
Air Handling Unit
Ceiling/Floor mounted suspended
Supplying, installing, testing and commissioning of factory built
Ceiling/Floor mounted double skin type air handling units Eurovent
Certified made of 40 mm thick panels consisting of pre plasticized G.I
casing made of thickness 0.6 mm outside layer and G.I sheet of thickness
0.6 mm inside layer with polyurethane foam (PUF) insulation of density
kg/m3 factory injected between them by injection moulding machine,
complete with Direct Driven Backward Curved Aerofoil Plug Type Fans
with VFD's with aluminium finned copper tubes (tubes thickness not less
than 0.5 mm),filter sections with 50 mm thick washable synthetic type pre
filter having efficiency 90% down to 10 micron, with AHU dampers (manual
control) for SA/RA/ FA in mixing box, Direct Drive package with TEFC
(EFF-1) suitable for VFD operation at 415 ± 10% volts, 50 Hz, 3 phase,
A.C supply, mixing box ,drain connections with drain valve, stainless steel
drain pan, necessary vibration isolation arrangement etc. TP isolator with
MS enclosure box should be Provided. etc, complete as per specifications
CS-AHU, 1000 CFM (2.5 TR), 2.0 Sqft. Coil Area, 35 mm static pressure.
4 row for summer cooling.
CS-AHU, 2000 CFM (5.0 TR), 4.0 Sqft. Coil Area, 35 mm static pressure.
4 row for summer cooling.
CS-AHU, 2500 CFM (6.25 TR), 5.0 Sqft. Coil Area, 35 mm static pressure.
4 row for summer cooling.
FM-AHU, 3000 CFM (7.5 TR), 6.0 Sqft. Coil Area, 35 mm static pressure.
4 row for summer cooling.
CS-AHU, 3000 CFM (7.5 TR), 6.0 Sqft. Coil Area, 35 mm static pressure.
4 row for summer cooling.
CS-AHU, 3500 CFM (8.75 TR), 7.0 Sqft. Coil Area, 35 mm static pressure.
4 row for summer cooling.
CS-AHU, 4000 CFM (8.75 TR), 7.0 Sqft. Coil Area, 35 mm static pressure.
4 row for summer cooling.
FM-AHU, 4000 CFM (8.75 TR), 7.0 Sqft. Coil Area, 35 mm static pressure.
4 row for summer cooling.
CS-AHU, 4500 CFM ( 11.25 TR), 9.0 Sqft. Coil Area, 35 mm static
pressure. 4 row for summer cooling.
FM-AHU, 5500 CFM (13.75 TR), 11.0 Sqft. Coil Area, 35 mm static
pressure. 4 row for summer cooling.
FM-AHU, 6000 CFM (15.0 TR), 12.0 Sqft. Coil Area, 35 mm static
pressure. 6 row for summer cooling.
FM-AHU, 7000 CFM (17.5 TR), 14.0 Sqft. Coil Area, 35 mm static
pressure. 6 row for summer cooling.
FM-AHU, 8000 CFM (20.0TR), 16.0 Sqft. Coil Area, 35 mm static
pressure. 6 row for summer cooling.
FM-AHU, 9000 CFM (22.5TR), 18.0 Sqft. Coil Area, 35 mm static
pressure. 6 row for summer cooling.
FM-AHU, 10500 CFM (26.25TR), 21.0 Sqft. Coil Area, 35 mm static
pressure. 6 row for summer cooling.
FM-AHU, 12000 CFM (30.0 TR), 24.0 Sqft. Coil Area, 35 mm static
pressure. 6 row for summer cooling.
FM-AHU, 13000 CFM (32.5TR), 26.0 Sqft. Coil Area, 35 mm static
pressure. 6 row for summer cooling.
25000 CFM (62.5 TR), 50 Sqft. Coil Area, 65 mm static pressure. 6 row for
summer cooling.
AHU's Controls/Dynamic Balancing Valves
Supply, Installation, Testing and Commissioning of following sizes
electronic, self-balancing, pressure independent type dynamic balancing
valve with integrated 2 way modualating control valve in a single body.
The actuator shall be capable of accepting upto 10V DC and upto 20mA
electric signal and shall provide similar transduced feedback output to
control system. Maximum close off pressure shall not be less than 6 Bar
for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have
pressure rating of 25 Bar minimum.
Water flow rate 3.8-7.2 USGPM, 25 MM
Water flow rate 7.4-14.4 USGPM, 32 MM
Water flow rate 14.6-21.6 USGPM, 40 MM
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Water flow rate 21.8-40.8 USGPM, 50 MM
Water flow rate 41.62.4 USGPM, 65 MM
Water flow rate 62.64-120 USGPM, 80 MM
Water flow rate 120.2-252 USGPM, 100 MM
Modulating Thermostats 71 Nos. 3115.00 31.15 3146.15
Chilled water Cassette Units.
Supply, installation, testing and commissioning of Chilled water Cassette
type indoor units with compact cooling coil, multispeed fan motor, the
blower shall be dynamicaly balanced and designed for silent operation,
the filters shall be washable synthetic media type arranged for convenient
cleaning and replacement and inbuilt drain pump.The units as specified in
Schedule of Quantities shall be factory fitted with valve package
comprising of 2 way pressure independent valve suitable for variable
CHW flow with modulating actuator, ball with Y strainer valve at inlet &
Ball valve at outlet and necessary piping connections. The actuator of
modulating valve shall be provided with interface cards to receive 0-10V or
4-20 mA signal from Minxon Digital Thermostat.The unit is supplied with
cordless remote controller of approved as per specifications
508 1.5 TR capacity (600 CFM)- Cassette Unit 13 Nos. 12212.71 122.13 12334.84
509 2.0 TR capacity (800 CFM)- Cassette Unit 11 Nos. 14274.58 142.75 14417.33
510 4.0 TR capacity (1600 CFM)- Cassette Unit 8 Nos. 39675.42 396.75 40072.17
511 1.0 TR capacity (400 CFM)- One way Cassette Unit 11 Nos. 29417.00 294.17 29711.17
512 1.5 TR capacity (600 CFM)- One way Cassette Unit 60 Nos. 33429.00 334.29 33763.29
513 2.0 TR capacity (800 CFM)- One way Cassette Unit 6 Nos. 36926.00 369.26 37295.26
Fan Coil Units.
Supply, installation, testing and commissioning of ceiling suspended
Normal static type FCU's each complete with 3 row deep cooling coil of
copper tubes aluminium fins construction, centrifugal fan, 3 speed motor,
with modulating thermostat, factorty fitted complete valve station (it
includes ball valve with Strainer, ball valve without strainer, 2 way
motorized valve, gauges etc.) ,filters insulated drain pan which covers the
valve station completely, coil piping connections, condensate drain
connection, complete as required complete with manual air vent valve, SP
isolator with MS enclosure box should be Provided etc. as required as per
specification & drawings with the following capacities:-
UVGI (Ultra Violet Germicidal Irradiation) SYSTEM
Supply, Installation , testing , commissioning and handing over of the
imported Ultra Violet Germicidial Irradiatons ( UVGI) (AHU Coil) System
for maintaining indoor Air Quality.The System can be UL listed for fire
safety. The components of the system must be in strict conformity with the
specifications.and shall be including freight from Delhi Airport to site
,Insurance,Lifting,Shifting etc.as required . The prices to include all inter
connected wiring between the UVGI Lamps.
Supply,Installation, testing & commissioning of Air Curtain for isolation of
Air conditioned area from air cooled area.
SUB HEAD 'C' - PIPING WORKS
Plumbing (Chilled Pipe)
Supplying, laying/ fixing, testing and commissioning of following nominal
sizes of chilled water piping inside the building (with necessary clamps,
vibration isolators and fittings but excluding valves, strainers, gauges etc.)
duly insulated with following closed cell elastomeric nitrile rubber of
minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better
at 20 deg mean temperature class 'O' insulation applied by suitable
adhesive complete including repairing of damage to building etc. as per
specifications and as required complete in all respect.
Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per
IS:1239 and pipes size above 150mm shall be welded black steel pipe
heavy class as per IS:3589, from minimum 6.35mm thick M.S. Sheet for
pipes upto 350mm dia. and from minimum 7mm thick MS sheet for pipes of
400mm dia and above.
Insulation Thickness Range
Supplying, fixing, testing and commissioning of following PN-10 Rating
valves, strainers, gauges in the chilled water plumbing duly insulated to
the same specification as the connected piping and adequetly supported
as per specifications.
Butterfly Valves
BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber
Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation
Motorized Butterfly Valves
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Supplying, fixing, testing and commissioning of following sizes Motorized
Butter fly Valve with CI Body, SS Disc,O - ring and minimum PN-16
pressure rating , conforming to BS 5155, IS 13095, with IP-55 actuator,
capable of accepting upto 10V DC , and upto 20mA electric signal and
providing similar transduced feedback output to control system as
Balancing Valves
BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I
body flanged construction with EPDM coated disc with long pitch with
protected out pipe insulation & PN 16 pressure rating for chilled / hot water
circulation as specified.
Non-Return Valves
NON - RETURN VALVE with duel plate of CI body SS plates vulcanized
NBR seal flanged end & PN 16 pressure rating for chilled / hot water
circulation including insulation as specified.
Providing and fixing of suction guide of following sizes in the inlet of
chilled water pumps as per specifications
Y - STRAINER of Ductile CI Body flanged ends with stainless steel
strainer for chilled / hot water circulation including insulation as specified.
Ball valve with strainer
Ball valve without strainer
Pressure Gauges
Providing and fixing pressure gauge with gauge cock, thermowell.
complete as per specifications and drawings.
Thermometers with thermowell
Providing and fixing thermometer Mercury filled V form type complete as
per speci-fications and drawings.
Providing and fixing water flow switch on chilled water outlet complete as
per specifications and drawings.
Automatic Air Vents
Providing and fixing auto airvent purging valve complete as per
specification and drawings.
Thermowell of 15 mm dia.(Test Point)
Providing and fixing thermowell on chilled water pipe complete as per
specifications and drawings.
Condenser Water Piping
Supplying, fixing, testing and commissioning of condenser water pipes of
following sizes of MS 'C' class along with necessary clamps, vibration
isolators and fittings such as bends,tees etc.but excluding valves,
strainers, gauges etc. adequately supported on rigid supports duly
painted/buried in ground excavation and refilling etc( Paracoat BPC
coating for Buried Pipeline). as per specification and as required complete
in all respect.
Note:-The Pipes size 150mm & below shall be M.S. 'C' class as per IS :
1239 and pipes size above 150mm shall be welded black steel pipe heavy
class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes
upto 350 mm dia. And from minimum 7mm thick MS sheet for pipes of
mm dia and above.
Butterfly Valves
BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O -
ring & PN 16 pressure rating as specified.
Motorized Butterfly Valves
Supplying, fixing, testing and commissioning of following sizes Motorized
Butter fly Valve with CI Body, SS Disc,O - ring and minimum PN-16
pressure rating , conforming to BS 5155, IS 13095, with IP-55 actuator,
capable of accepting upto 10V DC , and upto 20mA electric signal and
providing similar transduced feedback output to control system as
Balancing Valves
BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I
body flanged construction with EPDM coated disc with long pitch with
protected out pipe insulation & PN 16 pressure rating for chilled / hot water
circulation as specified.
Non-Return Valves
NON - RETURN VALVE with duel plate of CI body SS plates vulcanized
NBR seal flanged end & PN 16 pressure rating for chilled / hot water
circulation including insulation as specified.
Providing and fixing of suction guide of following sizes in the inlet of
condense water pumps as per specifications and drawings.
Providing and fixing of pot strainer in the condenser water pipe as per
specifications and drawings.
Pressure Gauges
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and fixing pressure gauge with gauge cock, thermowell.
complete as per specifications and drawings.
Thermometers with thermowell
Providing and fixing thermometer Mercury filled V form type complete as
per speci-fications and drawings.
Providing and fixing water flow switch on chilled water outlet complete as
per specifications and drawings.
Thermowell (Test Point)
Providing and fixing thermowell on chilled water pipe complete as per
specifications and drawings.
On-line non-chemical water treatment system
Supply, Installation, Testing and Commissioning of On line, Non-Chemical
568 Water Treatment Scale Preventor System : “Scale Guard / Caliphi” for 390 3 Nos. 551301.00 5513.01 556814.01
TR AC Chiller, having flow rate 3557 LPM
Supply, installation, testing, balancing and commissioning of
PRESSURISED CHILLED WATER EXPANSION TANK along with
necessary accessories such as air vents, Safety Valves, Pressurisation
pumps and its panel , with required Support & Foundation etc. in order to
keep chilled water system under pressure and to prevent entrapment of air
in the system. The tank shall be precharged M.S expansion tank with
replaceable heavy duty butyl rubber bladder. The tank shall have 20 mm
drain and charging valve connection to facilitate the onsite charging of the
tank to meet system requirement. The tank shall be fabricated as per
Indian standard code for “non-fired pressure vessels” and the flanges shall
be as per IS 6392-1971. For chilled/hot water application, it will be
insulated with 50mm thick insulation to the specifications and cladded with
STARBOND 30-36, Anti-Fungal, Fire retardant insulation protective
coating, tested as per ASTM D 4804, ASTM E 84, ASTM D-5035-11,
ASTM D 1777-64 and ASTM D 3776-09, finally finished with 2 layers of
Insulation protective coating to provide complete seal against air and
moisture/resistance against mechanical impact, scratch, weather
resistance with the properties of mold, fungus and bacterial resistance.
The coating surface flame spread should be 0 and smoke developed
should be also 0, coating should also comply with NFPA 90A & 90B-
25/50 for parameter and the VOC level of the coating should comply with
LEED IEQ 4.2 i.e. VOC level should be below than 50 gram/litter and it
should also comply the guidelines of MIA 3316C- Class 1 &. Grade A.
Supplying, fixing, testing and commissioning of condenser water pipes of
following sizes of MS 'C' class along with necessary clamps, vibration
isolators and fittings such as bends,tees etc.but excluding valves,
strainers, gauges etc. adequately supported on rigid supports duly
painted/buried in ground excavation and refilling etc( Paracoat BPC
coating for Buried Pipeline). as per specification and as required complete
in all respect.
Note:-The Pipes size 150mm & below shall be M.S. 'C' class as per IS :
1239 and pipes size above 150mm shall be welded black steel pipe heavy
class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes
upto 350 mm dia. And from minimum 7mm thick MS sheet for pipes of
mm dia and above.
G. I. drain piping of 'B' Class complete with fittings, supports, valves and
570 2 layers of 6 mm thick Polyethylene Foam (Kinney Foam) insulation as
per specifications and drawings.
Providng and fixing pipes with all necessary fittings, supports and
Supplying, installing, testing, and commissioning automatic water
softening plant for cooling tower make-up water, complete with softener
571 vessel, resin, control valve, brine tank, piping, bypass, electrical panel, 1 SET 1049845.00 10498.45 1060343.45
accessories, and documentation, as per specifications and Engineer-in-
Charge instructions.
SUB HEAD 'D' AIR DISTRIBUTION
Supplying, installation, balancing and commissioning of factory fabricated
GSS sheet metal rectangular/ round ducting complete with neoprene
rubber gaskets, elbows, splitter dampers, vanes, hangers, supports,
bends, transitions, reducers, end caps, collars etc as required complete in
all respect in confirmation to IS : 655 and approved drawings and
specifications of following sheet thickness complete as required.
G.I. Sheet Metal Ducting (Rectangular)- FACTORY FABRICATED
G.I. Sheet Metal Ducting (Rectangular)- SITE FABRICATED
Supplying, installation, balancing and commissioning of fabricated at site
GSS sheet metal rectangular/ round ducting complete with neoprene
rubber gaskets, elbows, splitter dampers, vanes, hangers,
supports, bends, transitions, reducers, end caps, collars etc as required
complete in all respect in confirmation with IS : 655 and approved
drawings and specifications of following sheet thickness complete as
G.I. Sheet Metal Ducting (Spiral/Oval)
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Supply, fabrication, installation and testing of G.S.S. factory fabricated
insulated spiral duct made in two layers with insulation sandwitched in
between two layers, finished with silver powder coat. The ducting shall
comply with the latest IS / SMACNA standard and complete with spliter,
damper, vanes etc as required complying with standard secifications and
as per approved shop drawings. The insulation used shall be of closed
cell, Fire retardant, self extinguishing type crossed linked polyethylene
insulation of 25 mm thick, density not less than 24 Kg/cu.m, 'K' value not
more than 0.028 Kcal/degC with adhesive tape etc. Duct shall be supplied
as per size given bellow.
Aluminium Sheet Metal Ducting
Supply, installation, balancing and commissioning of factory fabricated
Aluminium sheet metal rectangular/round ducting complete with
neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers,
supports etc. as specifications of following sheet thickness complete as
581 Thickness 1.00mm Sheet 50.00 Sqm 1845.00 18.45 1863.45
582 Thickness 0.80mm Sheet 200.00 Sqm 1422.00 14.22 1436.22
Providing, fabricating, supplying, and installing PPGL & FRP circular duct
system for fume hood and general laboratory exhaust air, complete as per
specification and drawings.
The ducting shall consist of an inner layer of Pre-Painted Galvanized Iron
(PPGL) and an outer layer of Fiberglass Reinforced Plastic (FRP) for
corrosion resistance and chemical protection.
Technical Specifications:
1) Type : Double-layer composite circular duct (PPGL + FRP)
2) Inner Layer: PPGL sheet of minimum 2.0 mm thickness (zinc coating
120 g/m² with epoxy-based paint finish)
3) Outer Layer: FRP coating of 3.0 mm thickness, UV-resistant, reinforced
with chopped strand mat (450 GSM) using polyester resin suitable for
laboratory exhaust application
583 4) Diameter: As per design and approved drawings 50.00 Sqm 3408.00 34.08 3442.08
5) Jointing: Flanged and gasketed joints using FRP-coated MS flanges,
neoprene gasket, and stainless steel bolts/nuts
6) Support System: Heavy-duty MS angle iron supports at intervals not
exceeding 2.4 m c/c, painted with epoxy primer and finish coat
7) Accessories: Elbows, reducers, tees, dampers, flexible connections,
and other fittings as required
8) Testing: Ducts shall be inspected for air leakage, proper alignment, and
coating uniformity before commissioning
9) Standard: Fabrication and installation shall comply with SMACNA / IS
655 / ASHRAE guidelines
All materials, labor, fabrication, transportation, erection, painting, jointing,
FRP coating, testing, and commissioning complete in all respects.
Duct Acoustic Lining
Supply and fixing of acoustic lining of supply air duct and plenum with
mm thick resin bonded glass wool having density of 32 kg/m3, with 25 mm
X 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered
584 with Reinforced Plastic tissue paper and 0.5 mm thick perforated
aluminum sheet fixed to inside surface of ducts with cadmium plated nuts,
bolts, stick pins, CPRX compound etc. complete as required and as per
specifications.
25 MM thick(for indoor ducts) 600.00 Sqm. 754.24 7.54 761.78
Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with
50mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction
fixed in 610mm x 610 mm frame work made of 25X50X50X50X25 mm
585 made out of 0.6mm thick GI sheet U shaped channel and covered with
reinforced fiber glass tissue and finished with 0.80 mm perforated
aluminium sheet etc. complete as required and as per specifications.
50 MM thick(for AHU ROOM) 550.00 Sqm. 895.76 8.96 904.72
Underdeck Insulation
Supply of Underdeck insulation of Crosslinked Closed cell Polyethylene
FR XPE Thermal insulation having density 0f 30± 3 Kg/ M³ ,having K
value 0.0314 W/m ° K at 23°C Deg temp and temp range of -40°C to
586 +115°C and fire rating Class O as per BS 476 Part 6 from Exova
Warringtonfire-UK and CBRI,Roorkee as per the approved specifications.
Material shall be HCFC/CFC free as per US EPA 5021 A (2014 )
25mm thick insulation FR XPE laminated with aluminium foil 900.00 Sqm. 1120.00 11.20 1131.20
Duct Insulation
Supply,Installation, testing & commissioning of Closed cell, Fire retardant
(Class "O") , self extinguishing type crossed linked polyethylene
insulation density not less than 24 Kg/sqM, 'K' value not more than
587 Kcal/degC with adhesive tape etc. on ducts complete as per specification
and drawings. All insulation is to be adhered to the duct surface uniformly
and no air bubbles are allowed anywhere.
Grilles/Diffusers
Supply,installation, testing and commissioning supply and return air
grilles/ diffusers as per specifications and drawings including fixing frame
of G.I./wooden in false ceiling/walls.
588 Aluminium supply air grilles with volume control 35.00 Sqm. 8155.08 81.55 8236.63
589 Aluminium Return air grilles without volume control 50.00 Sqm 5326.27 53.26 5379.53
590 Duct Volume Control dampers 20.00 Sqm 6423.73 64.24 6487.97
Aluminium S/A Square diffuser with volume control damper damper with
with anti smudge ring & removable core
Aluminium R/A square diffuser without volume control damper with anti
smudge ring & removable core
593 Aluminium Exhaust air diffuser with damper 15.00 Sqm 10882.20 108.82 10991.02
594 Fresh/Exhaust air Louvers with VCD,Bird screen/wire mesh etc. 20.00 Sqm 10183.00 101.83 10284.83
Flexible Duct Connection 0.00
Supply,installation,testing and commissioning of fire retardant nonporous
595 double layer flexible canvass connection between each indoor unit and 170 Nos. 2469.00 24.69 2493.69
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Supplying, Fixing, testing and commissioning of fire dampers in supply air
duct/main branch and return air path as and where required of required
sizes i/c control wiring,the damper shall be motorized and spring return so
as to close the damper in the event of power failure automatically and
open the same in case of power being restored. The spring return action
shall be inbuilt mechanism and not externally mounted. The damper shall
also be closed in the event of fire signal complete as required and as per
specifications.
596 Supply air fire damper 20.00 Sqm. 15573.73 155.74 15729.47
597 Return air fire damper 20.00 Sqm. 15573.73 155.74 15729.47
598 Spring return acturtor with panel of Motorised actuator for Dampers 20 Nos. 8299.15 82.99 8382.14
SUB HEAD 'E' VENTILATION WORKS
Supplying, Installing, Testing and Commissioning of Inline fans complete
with motor, supporting frame, gravity louvres,etc. as per drawings and
specifications.
Supplying, Installing, Testing and Commissioning of propeller fans
complete with motor, supporting frame, gravity louvres,etc. as per
drawings and specifications.
MEDICAL COLLEGE WING -
Ventilation Fans
Supplying, installation, testing and commissioning of supply air Tube
Axial flow fan with 20 mmWC Static Pressure of following capacity with
GSS casing and aluminium alloy impellers with high efficiency aero-foil
sections, blades, the impeller directly driven by TEFC induction motor
(motor should be of high efficiency (efficiency 1) suitable for 3 Phase
Hz 415 V ± 10 %,1400 RPM of class 'F' insulation etc. complete as
required and as per specifications. TP isolator with MS enclosure box
should be Provided.
Pressurization Fans
Supplying, installation, testing and commissioning of Tube Axial flow fan
suitable for outdoor application of following capacity with GSS casing and
aluminium alloy impellers with high efficiency (efficiency-2) aero-foil
sections, blades, the impeller directly driven by TEFC induction motor,
suitable for 3 Phase 50 Hz 415 V ± 10 %,1400 RPM of class 'F' insulation
etc. complete as required and as per specifications (20 mm Static
Pressure WC) (For Pressurization of lift lobby, lift well, stairwell). TP
isolator with MS enclosure box should be Provided.
608 11000 CFM @ 35 mm wg for pressurization of Lift Lobby 1 Nos. 98742.00 987.42 99729.42
609 14500 CFM @ 20 mm wg for pressurization of Lift Well 4 Nos. 116228.00 1162.28 117390.28
610 12000 CFM @ 20 mm wg for pressurization of stair case 2 Nos. 107999.00 1079.99 109078.99
611 11000 CFM @ 20 mm wg for pressurization of stair case 1 Nos. 98742.00 987.42 99729.42
Fire rated coating for Duct
All insulated chilled water duct insulation shall be coated with STARBOND
30-36 Anti-Fungal insulation protective coating in conjunction with 7mil
non-combustible certified Parafab GFC woven fiber glass cloth, tested as
per BS 476 part Ignitability 5,Fire Propagation 6, ASTM D 4804, ASTM E
84, ASTM D-5035-11, ASTM D 1777-64 and ASTM D 3776-09, finally
finished with 2 layers of Insulation protective coating to provide complete
seal against air and moisture/resistance against mechanical impact,
612 scratch, weather resistance with the properties of mold, fungus and 350.00 Kg 127.00 1.27 128.27
bacterial resistance, coating should also comply with NFPA 90A
&amp; 90B- 25/50 for parameter and the VOC level of the coating
should comply with LEED IEQ 4.2 i.e. VOC level should be below than
gram/litter and it should also comply the guidelines of BS standard- Class
(For Indoor & amp; Outdoor Duct Application of Airconditioning)
Fire Rated Paint : Supplying, Application & Commissioning for fire
rated paint (Starcoat CRC) CBRI approved and tested for 2 hours as per
BS 476 part 6, 7, 20 & 24 duct Vertical & Horizontal for Kitchen
613 Extraction Duct, Car Parking Duct, Duct Crossing Fire compartment, 1100.00 Kg 978.00 9.78 987.78
Ventilation Duct along with all the necessary accessories (Sealant-
Chemxseal 32-17 & Class O Gasket) etc. Details shall be as per
tender specifications.
SUB HEAD 'F' - ELECTRICAL WORKS
Electrical Control Panel
Plant Room AC PANEL- Main Panel
Supplying, assembling, erecting, connecting, testing and commissioning of
dust, damp and vermin proof free floor standing factory built sheet steel
enclosed non-drawout modular type Panel fabricated out of suitable sized
angle iron and flats, base channel and covered with 2.0mm thick PCRC
sheet, duly painted complete with earth bus, aluminium bus bar,
numbering & sign writing, interconnection & including the cost of
connection through bus bar / copper conductor flexible connection with all
accessories, rotary handles,phase barriers etc. complete as shown in
drawing & as per specifications and mounted with the followings etc.
complete as required. (All the starters should have NO/ NC contacts for
remote/ fire control facility etc. complete)
2 Nos 1000 A, 415V, 50 KA 4P, electrical draw out type, Micro-processor
based release (for over current and Earth fault protections) A.C.B. with
all indications, metering, protections, push buttons etc. complete in all
respects as mentioned in specifications and as required with following
Digital flush type class- I accuracy with power load manager, showing V,
A, KVA, KWH etc. with 3 Nos. current transformers of 2000/5A ratio, 10 VA
Class 1.0 metering.
1 Set of RYB phase indicating & ON/OFF/TRIP LED lamps with 2Amps.
SP MCB's backup.
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
1 set, 1500 A, 415V, 50 KA 4 Pole, electrical draw out type, A.C.B. with
all indications, push buttons etc. complete in all respects as mentioned in
specifications and as required with ON/OFF/TRIP indications.
Arrangement to be considered as required to couple with existing panel.
Interlocking to be considered as required.
Electrolytic high conductivity aluminium three phase and neutral busbars
rated at 415V, 50 Hz., 1500 amps. insulated with heat shrinkable coloured
PVC sleeves & clip on shrouds for joints.
All outgoing feeders shall be provided with On indicating lamp with 2 A SP
MCB protection & resin cast CT's class-1 suitable rating with digital Amps.
630A TPN MCCB '35 KA' with TM release etc. with MFM showing V,A,
KWH, KVA & ON/OFF/Trip indications, complete - 3 set (for chillers) (
WORKING,1 STAND BY)
40A TPN MCB '25 KA' with TM release etc. complete - 3 set (Primary
pumps) ( Spare for future)
63A TPN MCCB '25 KA' with TM release etc. complete - 4 set (Secondary
pumps) ( Spare for future)
100A TPN MCCB '25 KA' with TM release etc. complete - 3 set
(Condensor Pump) ( Spare for future)
80A TPN MCCB '25 KA' with TM release etc. complete - 2 set (cooling
tower) ( Spare for future)
63A TPN MCCB '25 KA' with TM release etc. complete - 3 set (hot water
pump) ( Spare for future)
150A TPN MCCB '25 KA' with TM release etc. complete - 2 set (hot water
generator) ( Spare for future)
Fully automatic Star Delta starter suitable for 1 nos. of 15.0 KW motor
including suitable MPCB type-2 selection, CT's, Ammeter, Push Buttons,
LED Indications, Auto/ Manual/ OFF selector switch, SPPR, FRLS copper
control wiring etc. Complete for each - 3 Set (PRIMARY Pumps)
Fully automatic star delta starter suitable for 22.0 KW motor including
suitable MPCB type-2 selection, CT's, Ammeter, Push Buttons, LED
Indications, Auto/ Manual/ OFF selector switch, SPPR, FRLS copper
control wiring etc. Complete - 3 Set (Secondary pumps)
Fully automatic star delta starter suitable for 45.0 KW motor including
suitable MPCB type-2 selection, CT's, Ammeter, Push Buttons, LED
Indications, Auto/ Manual/ OFF selector switch, SPPR, FRLS copper
control wiring etc. Complete - 3 Set (Condensory pumps)
Fully automatic star delta starter suitable for 9.3 KW motor including
suitable MPCB type-2 selection, CT's, Ammeter, Push Buttons, LED
Indications, Auto/ Manual/ OFF selector switch, SPPR, FRLS copper
control wiring etc. Complete - 3 Set (Hot water pumps)
Fully automatic star delta starter suitable for 2 nos. of 15 KW motor
including suitable MPCB type-2 selection, CT's, Ammeter, Push Buttons,
614 LED Indications, Auto/ Manual/ OFF selector switch, SPPR, FRLS copper 1 Lot 919891.00 9198.91 929089.91
control wiring etc. Complete for each - 2 Set (Cooling tower)
Supplying, installation, testing and commissioning of MV panel board of
cubical type, compartmentalised design fabricated from 2.0 mm thick
CRCA sheet having necessary cable alleys, powder coated through seven-
tank process facility for pricking and degreasing, including connections
and inter connections as per specifications complete with following
accessories as required( supply panels in each AHU room).
(Note: Power supply up to the each sub panel shall be in the scope of
client/other agencies)
615 Panel - P2 (AHU)
1 No. 16 Amps MCB 10 KA for 0.5-1.5 KW motor
1 No. DOL Starter
1 No. single phase preventer MPRD-2 type
2 Nos indicating lights
2 Nos. Push buttons 34 Sets 11020.00 110.20 11130.20
616 Panel - P3 (AHU)
1 No. 25 Amps MCB 10 KA for 2.0-5.5 KW motor
1 No. DOL Starter
1 No. single phase preventer MPRD-2 type
2 Nos indicating lights
2 Nos. Push buttons 34 Sets 17139.00 171.39 17310.39
617 Panel - P4 (AHU)
1 No. 32 Amps MCB 10 KA for 7.5-11.0 KW motor
1 No. Star Delta Starter
1 No. single phase preventer MPRD-2 type
2 Nos indicating lights
2 Nos. Push buttons 3 Sets 22989.00 229.89 23218.89
618 Panel - P5 (Axial Fan)
1 No. 25 Amps MCB 10 KA for 2.5 KW motor
1 No. Star Delta Starter
1 No. single phase preventer MPRD-2 type
2 Nos indicating lights
2 Nos. Push buttons 10 Sets 17918.00 179.18 18097.18
619 Panel - P6 (PRESS.)
1 No. 25 Amps MCB 10 KA for 3.7 KW motor
1 No. DOL Starter
1 No. single phase preventer MPRD-2 type
2 Nos indicating lights
2 Nos. Push buttons 8 Sets 17918.00 179.18 18097.18
Electrical cable
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
Providing and fixing PVC insulated armoured aluminium conductor cables
(3 1/2 Core) & COPPER CABLE (4 CORE) from main panel boards to
620 various equipments through walls/ceiling with appropriate clamps and
fixing arrangements, termination etc. as per specifications and drawings.
Fabricating and installing perforated MS cable trays including
horizontal and vertical bends, reducers, tees cross members and other
accessories as required and duly suspended from the ceiling with M.S.
suspenders and including painting etc. as required.
Providing and fixing 25 mm x 5 mm G.I. strip on surface or in recess for
earth connection etc. complete as required.
Providing and fixing 6 SWG dia GI wire on surgace or in recess for loop
623 earthing alongwith the existing surface/ recessed conduit/ submain wiring/ 800.00 Mtr. 185.00 1.85 186.85
cable as required.
Total HVAC Work Total
INTEGRATED BUILDING MANAGEMENT SYSTEM
CENTRAL CONTROL STATIONS
Supply, Installation, Testing & Commissioning of Building Management
System (BMS). BMS shall be complete as per point schedule suitable to
monitor, operate & control the total air conditioning system as well as other
systems from a central location Computer. The system shall be complete
624 with all accessories including Server Computer, System/ Network Controller,
DDC, Graphics Software, sensors, actuators, network & electronic
components, transformers, relays & associated cabling, conduiting, control
wiring, Enclosures etc. as required to make the system operative and
BMS Workstation - Supply, installation, testing and commissioning PC i7
Intel Processor, 2.93 Ghtz or better, 8GB RAM (Expandable), 1TB HDD,
a 2GB NVIDIA graphic card, CD/DVD R/RW Drive & 32" inch TFT colour 1 No 130000.00 1300.00 131300.00
monitor, laser printer, cordless key board, mouse, Windows 10 operating
system, etc. all complete
b UPS 6KV for DDC Panel 1 No 32500.00 325.00 32825.00
Web Based Graphical interface software. The system should be accessible
from anywhere on LAN or WAN or Ethernet without additional licenses. The
Communication protocol shall be one of the Industry Standard Open
Protocols such as BACNet, LON etc. System should be scalable and
software should be integrable with Access Control, CCTV VMS seamlessly
to generate a holistic view. Software shall have 3 simultaneous user license.
Third Party Integartion: UL & BTL listed Gateway / Open Protocol Software
for integrating the foll third party system communicating on one of the
Standard Open Protocols such as BACNet , MODBUS, M-Bus, J Bus etc -
Vendor to consider required No. of Integrators for qty's mentioned in IO
summary. Integrator/Gateway/supervisory controller shall be of the same
OEM as field controllers & software.
SITC of Standalone BTL & UL listed BACNet I/P field DDC controller
having universal input/ output ports. Controller shall have 2 10/100 ethernet
626 port & can communicate in Star, Daisy chain, RSTP topology & offer path
redundancy for communication. DDC controller shall be DHCP enabled to
ensure VPN network .
All DDC Controllers shall be provided with hinged doors with locking facility.
Apart from the controllers, the enclosers shall house the terminal blocks,
load relays and associaetd equipment. The internal wiring in the enclosure
shall be factory wired. The packaging shall be such that complete
installation of the field equipment and field wiring can be done prior to the
installation of the electronics.
The controller shall be independent in operation and the failure of any other
device / controller or the operator workstations, shall not cause any
disruption to the function of the rest of the system. The DDC controllers
shall have the facility to implement user modifiable time schedules as daily,
weekly, monthly annual temporary schedules.
DDC to meet data point summary requirement. 1 Lot 3500000.00 35000.00 3535000.00
SENSORS & FIELD DEVICES
SENSORS & FIELD DEVICES
627 Supply, installation, testing & commissioning of the following Sensors :
a Immersion type Temperature Sensor 142 Nos 2500.00 25.00 2525.00
b Differential Pressure switch AHU air filter 71 Nos 1209.00 12.09 1221.09
Rate excl GST Rate with LCess
S.No. Description Qty Unit 1% L Cess excl GST Amount
c DP Switch Air/Blower 134 Nos 975.00 9.75 984.75
d Pressure Sensor 4 Nos 3900.00 39.00 3939.00
e CO sensor 8 Nos 4550.00 45.50 4595.50
f 1 Point Level switch 6 Nos 1625.00 16.25 1641.25
g Temp. Sensor 80 Nos. 3500.00 35.00 3535.00
CABLING & CONDUTING
CABLING & CONDUTING
Supply, Installation, Testing & Commissioning of the following cables as per
the specifications:
a 2 Cr x 1 Sq.mm FRLS Shielded Cable for Field Devices 800.00 RM 48.75 0.49 49.24
b 3 Cr x 1.5 Sq.mm FRLS Cable 900.00 RM 61.75 0.62 62.37
c 4 Cr x 1 Sq.mm. FRLS Shielded. Cable for Field Devices 4000.00 RM 71.50 0.72 72.22
d CAT 6 FRLS Cable for Communication 1000.00 RM 58.50 0.59 59.09
e 25mm GI conduit 8000.00 RM 71.50 0.72 72.22
f 25 mm flexible conduit 6000.00 RM 65.00 0.65 65.65
Total BMS Work Total
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
00 NIT Tender Details.docx
DOCX
1. Volume - I.pdf
3. 202210-TS-Incite Building-Part 1(Civil) R1 13.01.26.pdf
4. 202210-TS-Electrical Part 2 TS2.pdf
5. 202210-TS-HVAC BMS.pdf
6. 202210 INCITE DBR Scope of work.pdf
7.1 202210-INC-S4-LOM-001 Civil 16.02.26.pdf
7.2 202210-INC-S4-LOM-001 ELECTRICAL_R1.pdf
7.3 202210-INC-S4-LOM-001 HVAC BMS.pdf
8. 202210-gbu-incite finishing schedule R2.pdf
9. 202210-BOQ- Incite Building Civil R5 dt 16.02.26a.pdf
Binder2_compressed.pdf
Binder3_compressed.pdf
Binder4_compressed.pdf
ilovepdf_merged (2)_compressed-1-9.pdf
ilovepdf_merged (2)_compressed (1)-10-18.pdf
ilovepdf_merged (3)_compressed.pdf
ilovepdf_merged (6)_compressed.pdf
ilovepdf_merged (7).pdf
ilovepdf_merged (8).pdf
ilovepdf_merged (9)_compressed.pdf
2. Volume - II.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .