GE (AF) Chandigarh
GE (AF) Chandigarh PIN-160003
Repair / Maint to lightning arresters with associated works, electrical wiring and fitting including geysers etc at AF Stn Highgrounds under GE AF Chandigarh
2020_MES_382308_1
GE (AF)/CHD/T-24/2020-2021
Open Tender
Civil Works
Item Rate
180 days
GE (AF) Chandigarh
All as per NIT and Tender Documents
9 documents required · 9 mandatory
₹500
GE (AF) Chandigarh
₹40,000
Yes
6 Feb 2021
30 Sept 2020
30 Oct 2020
30 Sept 2020
28 Oct 2020
15 Oct 2020
Amount
Material & labour in replacement of earthing complete with galvanized steel earth plate electrode 60 cms x 60 cms x6.00mm thick buried directly in ground vertically to a depth not less than 2.25 meter below ground level with top edge of the plate not less than 1.5 metre below normal ground level earth plate surrounded by 15 cm thick and packed alternate layers of charcoal dust and common salt, electrode connections using galvanised iron strip of size 32mmx6mm thick (upto body of equipment) by means of bolts ,nuts ,check nuts and GI washers connected to main switch board and protected by galvanized iron or steel pipe light grade 40 mm bore and water pipe 20 mm bore GI light grade (ISI marked ) with funnel and wire mesh ,including all necessary excavation and earth work PCC chamber in cement concrete 1:2:4 type B-1 and RCC cover and all as shown in electrical plate No 3 of MES Sch Part-1 (2009), complete all as specified and directed by Engineer-in-Charge.
Material & labour in replacement of Chemical earthing using mixture of copper sulphate (CuSo4) - 100 Kg, common salt-200 Kg and charcoal - 300 Kg complete with copper plate 90 cm x 60 cm x 5 mm thick buried directly in ground vertically at a depth not less than 3.50 metre below ground level with top edge of earth plate at a depth not less than 5 metre below normal ground level and the mixture should be filled 15 cm above top edge of earth plate to achieve result less than one ohm resistance including copper strip 32 x 6mm size (upto test point) by means of brass bolts, buts, check nuts and washers earth strip protected by galvanized steel pipe 40 mm bore (light grade) connected to test point all as shown in electrical plate No 3 of SSR - 2009 Part-I and including necessary excavation and earth work in any type of soil, 25 mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6). type C-1 chamber pit cover of precast RCC (1:2:4), type B-1 reinforced XPM of weight not less than 4 Kg/Sqm and MS frame etc, complete all as specified. Note :- (i) The unit rate includes copper earth strip and protection pipe upto (maximum 7.5 metre from earth plate) earth point/test point. (ii) The complete earth system shall be guaranted to give result less than 1 ohm resistance. (iii) Complete earthing will be redone at no extra cost to department, if result is found below 1 obm.
Material & labour in replacement for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required 25 x 4 mm galvanised iron strip, complete all as specified and directed by Engineer-in-Charge.
Material & labour in replacement Aluminium strip 25 x 3.15mm with saddles and fixing screws etc for roof conductors and down conductions above ground complete all as specified and directed by Engineer-in-Charge.
Material & labour in replacement for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required 20 x 3 mm copper strip , complete all as specified and directed by Engineer-in-Charge.
Material & labour in replacement for test point made out of GI strip 50x6mm, 200 mm long brass nut bolts - 2 Nos and 12mm dia GI nut bolts 40mm long- 03 Nos complete all as specified and directed by Engineer-in-Charge.
Material & labour in replacement for test point made out of copper strip 32x6mm, 200 mm long brass nut bolts - 2 Nos and 12mm dia GI nut bolts 40mm long- 03 Nos complete all as specified and directed by Engineer-in-Charge.
Material & labour in replacement for air termination, single pointed aluminium rod 12 mm dia and 300 mm long fixed to GI pipe bracket complete all as specified and directed by Engineer-in-Charge.
Material & labour in replacement for air termination, single pointed copper rod 12 mm dia and 300 mm long fixed to GI pipe bracket complete all as specified and directed by Engineer-in-Charge.
Suppy & Fixing/laying in repair galvanised, steel ( GI) , medium grade, ISI marked, 40mm bore with all fittings for fixing air termination rod complete all as specified and directed by Engineer-in-Charge.
Material & labour for PCC (1:3:6), type C-1 using 20mm graded crushed stone aggregate for casting PCC cubes of size as directed for mounting GI pipe 40mm dia including demolition of existing PCC complete all as specified and directed by Engineer-in-Charge.
Taking down carefully with battens/ PVC surface/ concealed conduit unserviceable copper/ aluminium point wiring (light, fan, socket) complete including fittings such as switches, ceiling roses, pendants, socket etc. and removing unserviceable material from site and making good disturbed surfaces of walls, floors etc. complete all as specified and directed by Engineer-in-Charge.
Material & labour for Point wiring PVC insulated unsheathed multistranded copper conductor FRLS cable using two single core 1.5 Sq.mm (nominal area) in and including 20mm dia nonmetallic rigid PVC concealled conduit medium grade including fittings and accessories, one run of continuous single core copper cable of 1.5 Sq. mm connecting to common earth dolly, using the existing pressed steel terminal box, provision of 3 mm thick plastic laminated sheet cover for mounting of switches sockets fan regulators etc. & making good to disturbed surface area for the one light/ fan point controlled by one single pole, one way switch complete all as specified and directed by Engineer-in-Charge. NOTE: (a).The quoted rates includes the cutting chasis for conduit and sunken boxes.
All as per item No.13 here-in-before but point wiring for one 5Amps socket outlet point on independent board controlled by one single pole, one way switch complete all as specified and directed by Engineer-in-Charge.
All as per item No. 13 here-in-before but point wiring for one 5Amps socket outlet point on d same board controlled by one single pole, one way switch complete all as specified and directed by Engineer-in-Charge.
All as per item No. 13 here-in-before but point wiring for one bell point controlled by one single pole, one way bell push complete all as specified and directed by Engineer-in-Charge.
All as per item No. 13 here-in-before but point wiring for one light point controlled by two single pole, two ways switch complete all as specified and directed by Engineer-in-Charge.
All as per item No. 13 here-in-before but point wiring using 2.5 sqmm as main wire & 1.5Sqmm as continous earth wire, for one 15Amps socket outlet point on independent board controlled by one single pole, one way switch complete all as specified and directed by Engineer-in-Charge.
All as per item No. 13 here-in-before but point wiring using 4sqmm as main wire & 2.5Sqmm as continous earth wire, for one 15Amps socket outlet point on independent board controlled by one single pole, one way switch complete all as specified and directed by Engineer-in-Charge.
Material & labour Point wiring PVC insulated unsheathed multistranded copper conductor FRLS cable using two single core 1.5 Sq.mm (nominal area) in the existing conduit medium grade including fittings and accessories, one run of continuous single core copper cable of 1.5 Sq. mm connecting to common earth dolly, using the existing pressed steel terminal box, provision of 3 mm thick plastic laminated sheet cover for mounting of switches sockets fan regulators etc. & making good to disturbed surface area for the one light/ fan point controlled by one single pole, one way switch complete all as specified and directed by Engineer-in-Charge.
All as per item No. 20 here-in-before but point wiring for one 5Amps socket outlet point on independent board controlled by one single pole, one way switch complete all as specified and directed by Engineer-in-Charge.
All as per item No. 20 here-in-before but point wiring for one 5Amps socket outlet point on the same board controlled by one single pole, one way switch complete all as specified and directed by Engineer-in-Charge.
All as per item No. 20 here-in-before but point wiring for one bell point controlled by one single pole, one way bell push complete all as specified and directed by Engineer-in-Charge.
All as per item No. 20 here-in-before but point wiring for one light point controlled by two single pole, two ways switch complete all as specified and directed by Engineer-in-Charge.
All as per item No.20 here-in-before but point wiring using 2.5 sqmm as main wire & 1.5Sqmm as continous earth wire, for one 15Amps socket outlet point on independent board controlled by one single pole, one way switch complete all as specified and directed by Engineer-in-Charge.
All as per item No. 20 here-in-before but point wiring using 4sqmm as main wire & 2.5Sqmm as continous earth wire, for one 15 Amps socket outlet point on independent board controlled by one single pole, one way switch complete all as specified and directed by Engineer-in-Charge.
Material & labour Point wiring PVC insulated unsheathed multistranded copper conductor FR cable using two single core 1.5 Sq.mm (nominal area) in PVC conduit wiring including fittings and accessories, one run of continuous single core copper cable of 1.5 Sq. mm connecting to common earth dolly, using suitable PVC box for mounting of switches sockets fan regulators etc. & making good to disturbed surface area for the one light/ fan point controlled by one single pole, one way switch complete all as specified and directed by Engineer-in-Charge.
All as per item No. 27 here-in-before but point wiring for1.5 sqmm copper conductor single core as earth continuity connected to common earth dolly for one 5 pin 5 Amp socket outlet on independent board complete all as specified and directed by Engineer-in-Charge.
All as per item No. 27 here-in-before but point wiring for one 5Amps socket outlet point on the same board controlled by one single pole, one way switch complete all as specified and directed by Engineer-in-Charge.
All as per item No. 27 here-in-before but point wiring for 2.5 sqmm as main wire & 1.5Sqmm as earth continuity connected to common earth dolly for one 5 pin 5 Amp socket outlet on indipendent board complete all as specified and directed by Engineer-in-Charge.
All as per item No. 27 here-in-before but point wiring for 4 sqmm as main wire & 2.5Sqmm as earth continuity connected to common earth dolly for one 5 pin 5 Amp socket outlet on independent board complete all as specified and directed by Engineer-in-Charge.
Supply & Fixing Switch piano, flush type, single pole, one way, 5 Amp, 230volts complete all as specified complete all as specified and directed by Engineer-in-Charge.
Supply & Fixing Switch Bell push, flush type, single pole, one way,, 230volts complete all as specified and directed by Engineer-in-Charge.
Supply & Fixing Switch piano, flush type, single pole, two way, 5 Amp 230volts complete all as specified and directed by Engineer-in-Charge.
Supply & Fixing Switch piano, flush type, single pole, one way, 15 Amp 230volts complete all as specified and directed by Engineer-in-Charge.
Supply & Fixing Socket outlet multipurpose 3 pin, 5 Amp and 2 pin 5 Amp, flush type, complete all as specified and directed by Engineer-in-Charge.
Supply & Fixing Socket outlet multipurpose 3 pin 5 Amp & 15 Amp, flush type, complete all as specified and directed by Engineer-in-Charge.
Supply & Fixing Ceiling rose, two to three terminals, PVC/ isolated body, complete all as specified and directed by Engineer-in-Charge.
Supply & Fixing Call bell, electric Ding - Dong type (Domestic pattern), 230 volt, single pole,complete all as specified and directed by Engineer-in-Charge.
Supply & Fixing Fan regulator electronic, socket type, suitable for 1200mm /1400mm sweep ceiling fan, fixed in repairs, with and including provision of PVC flexible cable of size 1sqmm copper conductor as required, complete all as specified and directed by Engineer-in-Charge.
Supply & Fixing PVC angualr holder suitable for 230V AC complete all as specified and directed by Engineer-in-Charge.
Supply and fixing Sheet metal enclosure single pole and neutral with a two pin socket and earth plug complete with one MCB single pole and 240V, 20 Amp ‘B’ curve, 10 kA, including taking out old unserviceable complete all as specified and directed by Engineer in Charge.
Supply and fixing Sheet metal enclosure (DB) single phase with neutral,2 way, 240 volt without bus bar & IP 54 protection, including taking out old unserviceable complete all as specified and directed by Engineer-in-Charge.
Supply and fixing Sheet metal enclosure (DB) single phase & neutral, double door 4 way, 240 volt with 200 Amps rated bus bar & IP 54 protection, including taking out old unserviceable complete all as specified and directed by Engineer-in-Charge.
All as per item No. 44 here-in-before but DB 8way complete all as specified.
All as per item No. 44 here-in-before but DB 12waycomplete all as specified.
Supply and fixing Sheet metal distribution board TPN, with double door,4 way, 415 volt with 200 Amps rated bus bar & IP 54 protection, including taking out old unserviceable complete all as specified and directed by Engineer-in-Charge.
All as per item No.47 here-in-before but DB 8way complete all as specified.
Supply and fixing in repair MCB DB, TP & N, vertical Loadline, 8 ways, double door, with provision for MCCB, having IP-43 protection complete all as specified and directed by Engineer-in-Charge.
Supply and fixing MCCB in repair , TP, 100 Amps, 415 Volt, having breaking capacity 10 kA, fixed thermal & fixed magnetic setting, Ics=100% of Icu including taking down old MCCB complete all as specified and directed by Engineer-in-Charge.
Supply and fixing MCB 63 Amp, 415 Volt, TPN, breaking capacity 10 KA, 'C' curve, fixed in repairs, complete all as specified and directed by Engineer-in-Charge.
Supply and fixing MCB 32/40 Amp, 415 Volt, TPN, breaking capacity 10 KA, 'C' curve, fixed in repairs, complete all as specified and directed by Engineer-in-Charge.
Supply and fixing MCB 32/ 40 Amp, 230 Volt, SPN, breaking capacity 10 KA, 'B' curve, fixed in repairs, complete all as specified and directed by Engineer-in-Charge.
Supply and fixing MCB 6 to 32 Amp, 240 Volt, SP, breaking capacity 10 KA, 'B' curve, fixed in repairs, complete all as specified and directed by Engineer-in-Charge.
Material & labour for sub main wiring with 2 runs of 2.5 sqmm PVC insulated unsheathed 1100 volt grade multistranded copper conductor including PVC casing & caping of suitable size and provision of one run 1.5 sqmm PVC insulated unsheathed single core copper conductor as earth continuity , connected to earth dolly inclusive of all accessories,as in repairs, complete all as specified and directed by Engineer-in-Charge. Note :- 2 Runs of 2.5 Sqmm wire and one run of 1.5 Sqmm with PVC casing & caping shall be measured as one unit .
Material & labour for sub main wiring with 2 runs of 4 sqmm PVC insulated unsheathed 1100 volt grade multistranded copper conductor including PVC casing & caping of suitable size and provision of one run 2.5 sqmm PVC insulated unsheathed single core copper conductor as earth continuity , connected to earth dolly inclusive of all accessories,as in repairs, complete all as specified and directed by Engineer-in-Charge. Note :- 2 Runs of 4 Sqmm wire and one run of 2.5 Sqmm with PVC casing & caping shall be measured as one unit .
Material & labour for Sub main wiring with two single core 10.0 Sq.mm (nominal area) PVC insulated and unsheathed cables with stranded copper FRLS conductor in existing conduit including one run of continuous PVC insulated FRLS copper stranded cable of wiring size 6.0 Sq.mm for earth continuity , connected to earth dolly inclusive of all accessories,as in repairs, complete all as specified and directed by Engineer-in-Charge. Notes :- (i) 2 runs of 10 Sq.mm main cable + 1 run of 6.0 Sq.mm earth cable considered as 1 Running Metre.
All as per item No. 57 here-in-before but using 2 single 6Sqmm as main & 1 single core 4Sqmm as earth wire complete all as specified.
All as per item No. 57 here-in-before but using 2 single 4Sqmm as main & 1 single core 2.5Sqmm as earth wire complete all as specified.
All as per item No. 57 here-in-before but using 2 single 2.5Sqmm as main & 1 single core 1.5Sqmm as earth wire complete all as specified.
Supply & Fixing PVC non metallic rigid concealed conduit 32mm, medium grade inclusive of junction, bends, elbows, tees, reducers, bell mouth tube ends fixing accessories such as couplers lock nuts, saddles, pipe hooks etc. including cutting chases for conduits and taking down existing batten/ conduit and making good to wall as per existing specifications complete all as specified and directed by Engineer-in-Charge.
All as per item No. 61 here-in-before but using 25mm dia conduit complete all as specified.
All as per item No. 61 here-in-before but using 19mm dia conduit complete all as specified.
Material & labour in replacement for earthing complete with galvanized steel earth plate electrode 60 cms x 60 cms x6.00mm thick buried directly in ground vertically to a depth not less than 2.25 meter below ground level with top edge of the plate not less than 1.5 metre below normal ground level earth plate surrounded by 15 cm thick and packed alternate layers of charcoal dust and common salt, earth lead wire 4.0 mm by means of bolts ,nuts ,check nuts and washers of galvanized iron or steel and thimbles and other end of the earth wire connected to main switch board and protected by galvanized iron or steel pipe light grade 15 mm bore and water pipe 20 mm bore GI light grade (ISI marked ) with funnel and wire mesh ,including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 5 of MES Sch Part-1 (2009), complete all as specified.
Taking up / down water heater (Geyser) of capacity 50/35/25 ltrs operating on 230 volts AC electric supply, in any position and of any make, after disconnecting all electric connection and hot and cold water connection, and including transportation to the contractor 's workshop for repair and vice - versa, , and painting / numbering ( if necessary) and vice - versa after repairing, general cleaning/overhauling, cleaning and discaling the tank and assembly with suitable detergent and making fully serviceable and fixing back in same location / position or new location all as directed. Note :- (a) Replacement of any un serviceable parts required for making the geyser serviceable will be measured and paid seperatelly under "supply only" and No extra payment will be allowed for replacing these items, as the same is deemed to be included in relevant item
Supply only stainless steel inner tank suitable for 25 ltrs Geyser of any make / shape to with stand a pressure not less than 4KG/sqcm all as specified and as directed.
All as per item No 66 herein before but for 35 ltrs capacity.
All as per item No 66 herein before but for 50 ltrs capacity.
Supply only base assembly complete with inlet,outlet,thermostat pipe with drain plug and screw for fixing the element inclusive of clamp for holding the element with nuts&bolts of any capacity and type as required at site of stianless steel suitable for 35/25 ltrs capacity geyser all as directed.
All as per item No 69 here-in- before but for 50 ltrs capacity geyser .
Supply only heating element including rubber gasket ISI marked ,1000/1500/2000 watts capacity, of any shape /type Make :- Ditz/Dass pass/ Theeta
Supply only thermostat ISI marked suitable to adjust the temperature from 0º C to 75º C all as directed.
Supply only Thermostat suitable to adjust the temperature from 0º C to 80º C all as directed. Make :- Ditz, Dass Pass
Supply only neon indicator lamp of any shape / size / colour all as directed.
Supply only PVC insulated and PVC sheathed 3 core flexible copper conductor cable of size 2.5 Sqmm all as directed.
Supply only high pressure safety plug / release valve of any type and size complete all as directed.
Supply only non return valve ISI marked 15mm bore cast copper alloy screwed down high pressure and screwed both ends suitble for geyser complete all as specified and as direceted
Supply only Rubber gasket of thickness 5 mm for geyser assembly of 08 holes / 09 holes all as specified.
Supply only bottom inspection cover plate in two pieces with suitable openings for indicator lamps, power cable entry with rubber washer etc, gauge of plate not less than 18 SWG for 25/35/50 Ltrs capacity geysers of any make/ shape and duly painted with spray paint all as directed.
Supply only 3 pin plug top 15 Amps, bakelite suitable for 230/240 volts AC supply all as directed.
Supply only Outer MS shell complete including top and bottom suitable for 25 Ltrs capacity geyser of any make, shape & size as per existing but gauge of sheet not less than 22 SWG all as directed.
Supply only CP connection 15mm bore 450mm long in any position with both end brass nut with inner thereading and washer suitable for cold water connection complete all as directed .
Material & labour for spray painting of geyser outer body of any make / size by applying one coat of synthetic enamel (white paint) over the existing paint after rubbing/cleaning existing body of geyser and writing of MES NO with synthetic enameled black paint in bold letters of size not less than10mm complete all as specified and directed by Engineer-in-Charge.
Disconnecting & taking down complete ceiling fan with blade of any make 1200 mm / 1400 mm sweep from fan hook/ fan box, transporting to local workshop , opening, cutting and taking out complete copper winding , cleaning with kerosene oil /diesel/ terpin oil and dried out, rewinding with new super enamelled copper wire of suitable size and gauge and number of turns as recommended by the respective manufactures, varnishing and heating the winding including replacing u/s providing paper insulation including (cuff / strip type) replacing u/s / missing spare (bush, bearing, capacitor shackle insulator, capacitor, nuts , bolts, earthing , screw, upper, socket, CI block , quarter /split pin (top & bottom) , lock nut etc) fixing the stator in rotor properly aligned and resembling ensuring right DOR, speedy and noiseless running and connecting cable and refixing the same complete all as directed by Engr in charge Note: Bush, bearing, capacitor, and canopy, Rubber real nuts, bolts and sockets shall be measured and paid for separately. No extra payment shall be allowed for replacing these items as the rate is deemed to be inclued in quoted rate of the item.
Supply only capacitor 2.50 MFD, 440 Volt AC, 50 Hz plastic body powder filled type complete all as directed.Make:Epcos/Unistar/Usha
Supply only capacitor 3.15 MFD, 440 Volt AC, 50 Hz plastic body powder filled type complete all as directed.Make:Epcos/Unistar/Usha
Supply only MS fan clamps with rubber real including nuts and bolts, split pin suitable for ceiling fan 1200 / 1400 mm sweep complete all as directed.
Supply only bearing suitable for 1200 / 1400 mm sweep ceiling fan complete all as specified and directed.Make :-SKF/NBC/TATA
Supply only bush suitable for 1200 / 1400 mm sweep ceiling fan complete all as specified and directed.
Supply only PVC Canopy suitable for ceiling fan of 1200 / 1400 mm sweep set of two complete all as directed.
Supply only PVC insulated and PVC sheathed flexible 3 core, 1sqmm size copper conductor cable including taking out the old unserviceable PVC flexible wire complete all as specified all as specified and directed by Engineer in Charge.
Supply & fixing for Mild Steel Down Rod of suitable dia , 45 Cms long white or coloured, compatible to existing ceiling fans of 1200mm or 1400 mm sweep including taking out old unserviceable down rod from the fan complete all as specified and as directed by the Engineer–in-charge. Down-Rod shall be of make of existing fan or as approved by the GE.
Disconnecting and taking down ceiling fan of any sweep for carrying out overhauling such as cleaning ,oiling, lubricating, greasing etc and replacement of minor parts such as washer, split pins/ blade screw etc and defective parts, if any, and refixing the ceiling fan fan on same location and connecting it properly and testing for noiseless running to the entire satisfaction of Engineer-in-charge. Note : (i). Defective parts required to be replaced shall be measured and paid for separately as supply only. (ii). Cost of the minor parts i.e. washer, split pins/ blade screw etc deemed to be included in unit rate & nothing shall be paid on this account.
Material & labour for Spray painting of ceiling fan 1200/1400 mm sweep and testing at site full load with super enamelled heat resistant synthetic white paint duly filling the cavities with filler and re-writing the MES number in black paint in appropriate size and shape complete all as directed by Engr-in-charge.
Disconnecting & taking down (burnt winding) exhaust fan of any make 300mm sweep transporting to local workshop, opening, cutting and taking out complete copper winding , cleaning with kerosene oil / diesel/ terpin oil and dried out, rewinding with new super enamelled copper wire of suitable size and gauge as recommended by the respective manufactures, varnishing and heating the winding including providing paper insulation (cuff /strip type) and replacing u/s / missing spare (bush, bearing , capacitor etc) fixing the stator in rotor properly aligned and reassembling ensuring right DOR , speedy and noiseless running and depositing in E/M yard Note :- (a) Repairing of any parts except the work mentioned in item No 103 will be maasured and paid seperatelly. (b) Replacement of any un serviceable parts required for making the exhaust fan serviceable will be measured and paid seperatelly under "supply only" and No extra payment will be allowed for replacing these items, as the same is deemed to be included in quoted rate of this item
All as per serial item No. 95 here-in-before but exhaust fan 450 mm sweep.
Taking down old and Supply and fix in repair capacitor 4 MFD, 230 Volt AC, 50 Hz plastic body powder filled type for exhaust fan of 300/400mm sweep complete all as directed.
Disconnecting and taking down exhaust fan of any sweep for carrying out overhauling such as cleaning ,oiling, lubricating, greasing etc and replacement of defective parts, if any, and refixing the exhaust fan at same location and connecting it properly and testing for noiseless running to the entire satisfaction of Engineer-in-charge. Note : (i). Defective parts required to be replaced shall be measured and paid for separately as supply only. (ii). Cost of the minor parts i.e. washer, split pins/ blade screw etc deemed to be included in unit rate & nothing shall be paid on this account. (iii) Replacement of any un serviceable parts required for making the exhaust fan serviceable will be measured and paid seperatelly under "supply only" and No extra payment will be allowed for replacing these items, as the same is deemed to be included in quoted rate of this item
Supply only bearing suitable for 300/ 400/450 mm sweep Exhaust fan complete all as specified and directed.Make:SKF/NBC/TATA
Material & labour for Spray painting of Exhaust fan and testing at site full load with super enamelled heat resistant synthetic white paint duly filling the cavities with filler and re-writing the MES number in black paint in appropriate size and shape complete all as directed by Engineer-in-charge. (Bush, bearing, capacitor, canopy, shackle insulator with nuts, bolts and sockets will be measured and paid separately).
Collecting unserviceable (burnt) table / cabin fan of any make and sweep up to 450 mm from Internal Elect Section, transporting to local workshop, opening, cutting and taking out complete copper winding, cleaning with kerosene oil / diesel / terpin oil and dried out, rewinding with new super enamelled copper wire of suitable size and gauge as recommended by the respective manufacturers, varnishing and heating the winding including providing paper insulation (cuff / strip type), replacing unserviceable / missing spares (bush, bearing, capacitor etc), fixing the stator in rotor properly aligned and reassembling ensuring right DOR, speedy and noiseless running and depositing in E/M Yard for further issue to the user.
Supply & Fix in replacement of electronic energy meter with LCD display 10-60A ,complete all as specified and directed by Engineer-in-Charge. Make L&T Cat no WM101BC7DLO or equivalent in performance in Secure Meters/GE/Legrand as approved by GE. Note : Old meter will be deposited to AGE E/M yard
Supply & Fix in replacement of electronic energy meter with LCD display 5-30A ,complete all as specified and directed by Engineer-in-Charge.Make L&T Cat no WM101BC5DL0 of L& T or equivalent in performance in Secure Meters/GE/Legrand as approved by GE. Note : Old meter will be deposited to AGE E/M yard
Supply only ionization smoke detector all as specified and directed by Engineer in charge .Make Siemens or equivalent in performance in Bosch/Schneider/ABB as approved by GE.
Supply only battery maintanence free 12V 7 AH all as specified and directed by Engineer in charge.Make Exide /Amron/Amco
Supply only battery maintanence free 12V 28 AH all as specified and directed by Engineer in charge. Make Exide /Amron/Amco
Supply only Zone cord for fire alarm system all as specified and directed by Engineer in charge. Make:Siemens/Bosch/Adward/Noti Fire
Periodical maintenance to Fire alarm systems installed in three technical buildings (two loop system ) of make Siemens including replacement of faulty service parts of fire alarm system ( Fire alarm controll pannel ) The alarm function of controlls of controll and indicating eqpt (controll Pannel) will be checked by operation of trigger of each zone.All fault indicator and their circuits shall be checked by stimulation of fault condition (SMOKE DETECTOR ) Smoke detector shall be cleaned periodically so as to remove dust or dirt that accumulates on them due to local ambiant condition at least each detectors is cleaned twise in a month, MANNUAL CALL POINTS HOOTERS: All mannual call points will be operated twice a month by removing glass cover or by actual braking the glass so as to ensuare that system is capable of operation under alarm conditions and all hooters give proper sound, RESPONSE INDICTORS All detctectors which are placed in side a cabin or room will be tested by indicating the particular detector So as to ensusure the proper working of response indicator . WIRING AND CABLES : A visual inspection will be made so that structure or occupancy changes do not damage cables and sitting of trigger divice (mannual call points ,smoke detectors and heat detectors Note: All major items will be paid and measured seperatily
Atternding comptaints of internal elect supply,including locating and rectification of fault and ensuring the compete serviceablity with replacement of defective/unserviceable components such as switches ,sockets,lamp,holder ,ceiling rose of any type ,DBs,MCB main switches service wires/cables etc and other accessories and per site requirement . the deffective items shall be measured and paid for separetly under respective items of supply only here-in-after and item 85 & 86 above. Note:-(a) Rate are inclusive of taking down and refixing of under related item only. (b) Any Nos of complaint attended at one place/one qtr under one job card will be considered as one job. (c) Emergent compaint will be attended in 02 Hour. (d) Contractor shall be employ one team consisting of one electrician ITI passed and one helper to attend the complaints. (e) Contractor or his representative will report to JE E/M daily at 0900 Hrs on all working days at the complaint cell and collect the compaints slip.After completion of job all complaints slip will be deposited back to complaint cell by 1700 Hrs. (f) Any T&P reqd for rectification of complaints will be provided by the contractor. the rate of T&P deemed to be included in quoted rate.
Supply only Switch piano, flush type, single pole, one way, 5 Amp, 230volts complete all as specified.
Supply only Switch Bell push, flush type, single pole, one way,, 230volts complete all as specified.
Supply only Switch piano, flush type, single pole, two way, 5 Amp 230voltscomplete all as specified.
Supply only Switch piano, flush type, single pole, one way, 15 Amp 230volts complete all as specified.
Supply only Socket outlet multipurpose 3 pin, 5 Amp and 2 pin 5 Amp, flush type, complete all as specified.
Supply only Socket outlet multipurpose 3 pin 5 Amp & 15 Amp, flush type, complete all as specified.
Supply only Ceiling rose, two to three terminals, PVC/ isolated body, complete all as specified.
Supply only Call bell, electric Ding - Dong type (Domestic pattern), 230 volt, single pole, complete all as specified.
Supply only Fan regulator electronic, socket type, suitable for 1200mm /1400mm sweep ceiling fan, fixed in repairs, with and including provision of PVC flexible cable of size 1sqmm copper conductor as required, complete all as specified.
Supply only PVC angualr holder suitable for 230V AC all as specified and directed
Supply only MCB 63 Amp, 415 Volt, TPN, breaking capacity 10 KA, 'C' curve, fixed in repairs, complete all as specified.
Supply only MCB 32/40 Amp, 415 Volt, TPN, breaking capacity 10 KA, 'C' curve, fixed in repairs, complete all as specified.
Supply only MCB 63 Amp, 415 Volt, TP, breaking capacity 10 KA, 'B' curve, fixed in repairs, complete all as specified.
Supply only MCB 40 Amp, 415 Volt, TP, breaking capacity 10 KA, 'B' curve, fixed in repairs, complete all as specified.
Supply only MCB 32 Amp, 415 Volt, TP, breaking capacity 10 KA, 'B' curve, fixed in repairs, complete all as specified.
Supply only MCB 32/ 40 Amp, 230 Volt, SPN, breaking capacity 10 KA, 'B' curve, fixed in repairs, complete all as specified.
Supply only MCB 6 to 32 Amp, 240 Volt, SP, breaking capacity 10 KA, 'B' curve, fixed in repairs, complete all as specified.
Supply only LED Decorative box type batten fitting 1x20W,including LED tube rod retrofit type 20W, prewired upto connection block and connecting with three core PVC copper flexible cable of size 1. Sq. mm from ceiling roseto connector block, complete all as specified and directed by Engineer-in-Charge. Make: Havells/WIPRO/PHILLIPS/CROMPTON
Supply only Basic all purpose surface and wall mounted LED batten with polycarbonate housing & integrated electronic driver 9W complete all as specified and directed by Engineer in Charge. Make :Havells/WIPRO/PHILLIPS/CROMPTON
Supply only wall mounted fittings with ABS housing and clear polycarbonate cover including LED bulb 15watts complete and provision of flexible copper 3core cable 0.5Sqmm from connector/ ceiling rose to fitting complete all as specified and directed by Engineer in Charge. Make : HPL code HPL81410(CW) /Bajaj/philip/Havell's
Supply only Ultra modern designed architectural LED luminaire 36W which provides soft-light and glare free symmetrical illumination suitable for Armstrong/Grid ceiling complete all as specified and directed by Engineer in Charge.Make Havells Cat no VENUSNEOHE2X2PLR36WLED865MOD or equivalent in performance in Cromptorn/ HPL as approved by GE.
Supply only Recess mounted downlighter LED 12W with pressure die-cast aluminium heat sink & PC diffuser in white powder coated finish with integrated driver complete all as specified and directed by Engineer in Charge.Make Havells Cat no INTEGRANEODLR12WLED857S or equivalent in performance in Cromptorn/ HPL as approved by GE.
Note:- Amount of credit of Rs. 64707.00 for retrieved materials is mentioned in Schedule of Credit Page No 115 (R) & 116 (R) of tender documents in pdf form which will be deducted offline while acceptance of tender.
P.K.MALL ENTERIPRSES
HARISH SALES CORPORATION
B N FRIENDS AND CO
Babu Ram Sud and Sons
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .