Executive Engineer TLMD-IV, Pampore
xecutive Engineer TLMD-IV, Pampore
Augmentation of Grid Sub Station Zainakote from 220/132 KV, 450 MVA to 220/132 KV, 780 MVA by replacing old aged 06 Nos 50 MVA ,220/132 KV Auto Transformers (CG Make) by 06 Nos 220/132/11KV , 105 MVA 01x105 MVA Spare Auto transformers including alli
2026_PDD_331457_1
TLMD-IV/e-NIT/08 of 2026-27
Open Tender
Electrical Works
Item Rate
608 days
Zainakote
Please refer Tender documents.
4 documents required · 4 mandatory
₹10,000
Chief Accounts Officer with Chief Engineer, JKPTCL
₹1.7 Cr
Office of Chief Engineer JKPTCL Bemina Srinagar
9 Dec 2026
17 Nov 2026
11 Dec 2026
18 Nov 2026
9 Dec 2026
19 Nov 2026
18 Nov 2026 - 25 Nov 2026
27 Nov 2026
180 days
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | (A) Design,Manufacture,Supply,Packing & Forwarding,Transportation,Delivery At Site of Equipments and Material
Main Equipments | - | - | - | - |
| 2 | 105 MVA (ONAN/ONAF/OFAF), 220/132/11KV Single phase Auto Transformer with OLTC, SCADA Compatible RTCC, HV and LV connectors and other required accessories and fittings, and maintenance free Automatic Breathers as per detailed technical specifications , inbuilt NCTs),common MB/indivdual MB, cables including special cables if any and other required accessories,control cables and fittings as per technical specifications .Current density for HV/IV/LV not more than 2.4 A/Sqmm and core flux density not more than 1.5 Tesla at rated voltage.The scope shall also include first filling of Transformer and 10% extra oil.Mandatory spares shall include following:
HV RIP bushing 02 No. IV OIP bushing 02No. , Neutral and Tertiary bushing 02 No. each ,OTI 04 No.,WTI 04 No. ,oil cooler pump with motor 04 No, cooler fans with motor 04 Nos, PRV 06 No, Bucholz 06 No, OSR 06 No., MOG 06 No., Bushing CTs for two transformers , Air cell for conservator 02 No and 16 Nos oil sampling bottles, Tap changer diverter switch contacts 02 No, Tap changer diverter switch contacts 02 No, Set of valves (complete set for one transformer) 02 set, Breather assembly (one of each type) for conservator and OLTC 03 set, Complete set of tools for installation and maintenance of Power Transformers | 7 | Nos | - | - |
| 3 | Online DG Monitoring kit 07 Gases, technical specifications as per SBD. | 7 | Nos | - | - |
| 4 | Online Dehydration Kit technical specifications as per SBD. | 7 | Nos | - | - |
| 5 | NIFPES for existing 50MVA, 220/132KV Single Phase Transformer with 05Kl capacity MS prefabricated cylindracal 6 mm thick tank including all civil works as per drawings | 1 | Nos | - | - |
| 6 | 3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (245KV, 3150 Amps of 3 phase, 50 c/s and 50KA for 1 second) along with supporting structure etc complete in all respects , universal spring charging motor and with breaker mandatory spares.Mandatory spares per breaker include following.
closing coil with resistor 04 No, Tripping coils 06 Nos, Relays, power contactors push buttons, Limit switches, Timers, MCBs and switch fuse units, closing coil assembly and trip coil assembly, 02 set Rubber gaskets, ‘O’ rings & seals (complete replacement for one CB/one pole), 01 set Rubber gaskets, ‘O’ rings & seals for operating | 3 | No | - | - |
| 7 | 3 pole SF6 gas filled, outdoor circuit breaker, including all accessories, auxillaries and marshalling boxes/kiosks (145KV,3150 Amp of 3 Phase 50c/s and 40KA for 1 sec) along with supporting structure etc complete in all respects, universal spring charging motor and with breaker mandatory spares. Mandatory spares per breaker include following.
closing coil with resistor 03 No, Tripping coils 06 Nos, Relays, power contactors push buttons, Limit switches, Timers, MCBs and switch fuse units, closing coil assembly and trip coil assembly, 02 set Rubber gaskets, ‘O’ rings & seals (complete replacement for one CB/one pole), 01 set Rubber gaskets, ‘O’ rings & seals for operating | 3 | No | - | - |
| 8 | Single phase, 50 c/s 245KV Current Transformers (2000-1500-1000/ 1-1-1-1-1A or as per site specifications), 50KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA, 3 No PS core , 1 No. 5P20, 1No. 0.2 S Class, 1 No. Galvanized Tank including first fill of transformer oil plus 20% extra and including all acessories and auxiliaries | 18 | No | - | - |
| 9 | Single phase, 50 c/s 145 KV Current Transformers (2500-2000-1600/ 1-1-1-1-1 A or as per site specifications), 40KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA, 3 No PS core , 1 No. 5P20, 1No. 0.2 S Class, Galvanized Tank including first fill of transformer oil plus 20% extra and including all acessories and auxiliaries | 6 | No | - | - |
| 10 | Single phase, 50 c/s 36 KV Neutral Current Transformers (1800-900/ 1-1-1 A or as per site specifications), 31.5 KA for one second, rated dynamic current 31.5 KA(peak), Class A insulation, Burden 20 VA, 3No PS core , , Galvanized Tank including first fill of transformer oil plus 20% extra and including all acessories and auxiliaries | 2 | No | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.07 MB
SBD_vol_Ist.pdf
Tender Documents • 1.65 MB
SBD_Vol_II.pdf
Other Document • 4.63 MB
Nameplate.pdf
Additional Documents • 0.71 MB
BOQ_1124945.xls
BOQ • 0.42 MB
Prebidmeeting.pdf
PDF • 0.02 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .