Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹102.6 CrAccepted-AOC MANATHA ENCLAVE 3RD FLOOR OLIMUGAL KAKKANAD P O KOCHI 682 030 KERALA | ERNAKULAM | KERALA | 682030 | ₹102.6 Cr Quoted ₹102.7 Cr | L1 | Accepted-AOC ACCEPTED BEING L1 |
| 2 | L2₹114.7 CrRejected-Finance PREMISES NO 5 30 5 N C SENGUPTA SARANI GROUND FLOOR MALL ROAD KOLKATA WEST BENGAL INDIA 700 080 | KOLKATA | KOLKATA | WEST BENGAL | 700080 | ₹114.7 Cr | L2 | Rejected-Finance REJECT BEING L2 |
| 3 | L3₹120.0 CrRejected-Finance 5TH FLOOR ALPHA PLAZA K P VALLON ROAD KADAVANTHRA KOCHI KERALA PIN 682020 | KOCHI | ERNAKULAM | KERALA | 682020 | ₹120.0 Cr | L3 | Rejected-Finance REJECT BEING L3 |
Tender Value
₹109.3 Cr
EMD Value
₹57.9 L
Closing Date
2 Mar 2024, 6:00 pmClosed
CE NW Kochi
CE(NW) Kochi
ENGINEERING, PROCUREMENT AND CONSTRUCTION OF DEFICIENT MARRIED ACCOMMODATION(200 Dus)FOR SAILORS(POs AND BELOW) AT NAVAL BASE KOCHI UNDER GE (P)NW KOCHI
2023_MES_599579_1
891039
Open Tender
Civil Works
1080 days
Kochi
As per NIT
8 documents required · 8 mandatory
₹3,000
Yes
₹57.9 L
21 Mar 2024
30 May 2023
5 Mar 2024
30 Nov 2023
2 Mar 2024
14 Feb 2024
14 Aug 2023 - 9 Sept 2023
Amount
Total amount of Sch 'A' Part-I (BUILDINGS/STRUCTURES)
Total amount of Sch 'A' Part-II (EXCAVATION, EARTHWORK, SITE CLEARANCE AND SITE DEVELOPMENT)
Total amount of Sch 'A' Part-III (INTERNAL ELECTRIFICATION/TELEPHONE/TV SOCKET)
Total amount of Sch 'A' Part-IV (INTERNAL WATER SUPPLY)
Total amount of Sch 'A' Part-V (EXTERNAL WATER SUPPLY)
Total amount of Sch 'A' Part-VI (EXTERNAL ELECTRIFICATION/STANDBY DG SET/LIFT)
Total amount of Sch 'A' Part-VII (LIGHTNING PROTECTION)
Total amount of Sch 'A' Part-VIII (FIRE FIGHTING)
Total amount of Sch 'A' Part-IX (ROAD/ PATH/ HARD STANDING)
Total amount of Sch 'A' Part-X (SEWAGE DISPOSAL)
Total amount of Sch 'A' Part-XI (AREA DRAINAGE)
Total amount of Sch 'A' Part-XII (DEMOLITION/DISMANTLING)
Sch 'A' Part- XIII (MISCELLANEOUS ITEMS) (Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.)
INTERNAL ELECTRIFICATION:
Material and Labour for point wiring with multi stranded copper conductor 1.5 Sqmm size nominal area PVC insulated unsheathed FRLS cable 1100 volts grade conforming to IS: 694 drawn in and including concealed PVC rigid conduit heavy duty and conduit acccessories concealed in wall/ floor/ roof etc. ISI marked making good the surfaces as per existing surfaces or as directed including modular GI flush box of suitable size with inner and outer white plastic plate including single core stranded copper conductor 1.5 Sqmm PVC insulated unsheathed FRLS cable as earth wire to common earth and connected to earth dolly complete all as specified and as directed. Note: Switch and socket shall be measured and paid seperately
One light/Bell point controlled by one 5/6 Amp one way switch
One ceiling fan point controlled by one 5/6 Amp one way switch
One exhaust fan point controlled by one 5/6 Amp one way switch
One socket outlet 3/5 pin, 5 Amps on independent board controlled by one 5/6 amps one way switch or switch socket combination 5 Amps 5 pin
One socket outlet 3/5 pin, 5 Amps on same board controlled by one 5/6 amps one way switch
One light point controlled by 2 Nos two way switches 5/6 Amps
Material and Labour for point wiring with multi stranded copper conductor 2.50 Sqmm size nominal area PVC insulated unsheathed FRLS cable 1100 volts grade conforming to IS: 694 drawn in and including concealed PVC rigid conduit heavy duty and conduit acccessories concealed in wall/ floor/ roof etc. ISI marked making good the surfaces as per existing surfaces or as directed including modular GI flush box of suitable size with inner and outer white plastic plate including single core stranded copper conductor 2.5 Sqmm PVC insulated unsheathed FRLS cable as earth wire to common earth and connected to earth dolly for one 3/5 pin 15/16A socket outlet on independent board complete all as specified and directed. Note: Switch and socket shall be measured and paid seperately
Material and Labour for point wiring with multi stranded copper conductor 4.0 Sqmm size nominal area PVC insulated unsheathed FRLS cable 1100 volts grade conforming to IS: 694 drawn in and including concealed PVC rigid conduit heavy duty and conduit acccessories concealed in wall/ floor/ roof etc. ISI marked making good the surfaces as per existing surfaces or as directed including modular GI flush box of suitable size with inner and outer white plastic plate including single core stranded copper conductor 4.0 Sqmm PVC insulated unsheathed FRLS cable as earth wire to common earth and connected to earth dolly for independent AC starter switch point 20A suitable for 4 module complete all as specified and directed. Note: Switch and socket shall be measured and paid seperately
Material and labour for starter switch of capacity 20A, including socket and plug top working on 240 Volts AC supply and suitable for air conditioners complete all as specified and directed. Make : Crabtree cat part No. ACAO202504 or equivalent as given in approved list of makes.
Supply and fixing lamp holder, PVC/ polycarbonate type with cord grip cap batten fitting suitable and fixing LED bulbs complete all as specified and as directed.
Supply and fixing ceiling fan 1400mm sweep copper wound BLDC service value not less than 4.5 rated with power consumption 26 to 35 watts with operating on remote control, minimum speed 320 RPM, min air delivery 245 cum/min with service value 6.00 BEE, with 2 years minimum manufactures warranty, including fixing of down rod and connecting up complete with and including three core flexible PVC insulated multistranded copper conductor connection cable of size 0.5Sqmm from ceiling rose to fan etc. complete all as specified and as directed.
Supply and fix exhaust fan made of sturdy engineering plastic complete with louvers shutter voltage 230V, 50 Hz, RPM 1200 of sweep 250mm complete including connecting up from ceiling rose with 3 core flexible copper cable PVC sheathed of size 1.5Sqmm, completed all as specified and directed.
Supply and fix exhaust fan made of sturdy engineering plastic complete with louvers shutter voltage 230V, 50 Hz, RPM 1200 of sweep 300mm complete including connecting up from ceiling rose with 3 core flexible copper cable PVC sheathed of size 1.5Sqmm, complete all as specified and as directed.
Supply and fixing electric water heater, storage type steel body with copper inner tank and heating element upto 2KW capacity 25 litre, BEE 5 star rated complete with all accessories such as safety valve, thermostat, NRV, connection piece etc. complete all as specified and as directed.
Supply and fixing LED Tube light 1 X 22 Watt 4' universal batten type with and including connecting 3 core 1 Sqmm PVC insulated multistranded copper conductor's sleeve color matching to fitting and connecting up complete all as specified and as directed.
Supply and fixing LED Tube light 1X20 Watt 4' inverter LED batten square profile and polycarbonate channel. Lithium Ion battery with charging time 8hours-10 hours and back up time upto 4 hours including 3 core 1 Sqmm PVC insulated multi stranded copper conductor's sleeve color matching to fitting and connecting up complete all as specified and as directed.
Supply and fixing LED Light fittings 1X10W bulkhead luminaries including LED light driver holder connecting up with 3 core 1 Sqmm PVC insulated multistranded copper conductor's sleeve color matching to fitting and connecting up complete all as specified and as directed.
Supply and fixing LED light 1X10 Watt 2' with and including connecting 3 core 1.0 Sqmm PVC insulated multistranded copper conductor color of sleeve matching to fitting and connecting up complete all as specified and as directed.
Supply and fixing building LED security light 1 x 35W new generation energy saving and environmental friendly long life made of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP OPENING separate driver compartment with IP 66 protection and impact resistance of IK 07 complete with and including wall mounted bracket fabricated out of 40mm GI pipe light grade bend to shape 1.5 mtr long and two nos wall mounting clamps using 25x4mm thick MS strip bend to shape and welded with pipe to form solid structure and one run of 1Sqmm PVC insulated multistranded copper conductor wire connecting PVC terminal to fitting complete all as specified and as directed.
Supply and fixing MCCB DB VTPN 4 way, double door, 415 Volts with provision for MCCB as incomer and SP/TP MCBs as out going with IP 43 protection, door earthing, isolated neutral bar, mechanical impact strength IK 09 including cement spill protector complete all as specified and directed.
Supply, installation, testing and commissioning indoor door type LT main distribution panel board/ Metering panel double door with front opening made of 2.00mm MS sheet powder coated fixing on wall/ floor complete with arrangement of fixing of VTPN 4 way-02 Nos as in comming, fixing of electronic energy Meter with LCD display-18 Nos complete all as specified and directed Engr -in- charge. Note: VTPN electronic energy meters will be measured and paid separately.
Supply and fixing sheet metal enclosure distribution board MCB DB SPN 4 way with metal double door 240 Volts with IP-43 protection including door earthing complete all as specified and directed.
Supply and fixing sheet metal enclosure distribution board MCB DB SPN 8 way with metal double door 240 Volts with IP-43 protection including door earthing complete all as specified and directed.
Supply and fixing RCBOs for earth leakage, overload and short circuit protection double pole 30mA 16A complete all as specified and as directed.
Supply and fixing MCB SP 06-32 Amps 10 kA with characteristic "C" curve conforming to IS/IEC 60898 complete all as specified and as directed.
Material and labour for sub main wiring using 2 runs of 6 Sqmm single core PVC insulated cable FRLS copper conductor multi stranded and one runs of 6 sqmm copper conductor insulated unsheathed cable FRLS using as earth continuity connected to earth dolly drawn through and including suitable size heavy duty PVC conduit and its accessories laid in concealed in wall/roof/floor etc complete all as specified and as directed. Note- One run of PVC conduit of suitable dia and 3 runs of 6 sqmm PVC copper wire shall be measured and paid as one unit.
Material and labour for sub main wiring using 2 runs of 10 Sqmm single core PVC insulated cable FRLS copper conductor multi stranded and one runs of 10 sqmm copper conductor insulated unsheathed cable FRLS using as earth continuity connected to earth dolly drawn through and including suitable size heavy duty PVC conduit and its accessories laid in concealed in wall/roof/floor etc complete all as specified and as directed. Note- One run of PVC conduit of suitable dia and 3 runs of 10 sqmm PVC copper wire shall be measured and paid as one unit.
Material and labour for sub main wiring using 4 runs of 10 Sqmm single core PVC insulated cable FRLS copper conductor multi stranded and one runs of 10 sqmm copper conductor insulated unsheathed cable FRLS using as earth continuity connected to earth dolly drawn through and including suitable size heavy duty PVC conduit and its accessories laid in concealed in wall/roof/floor etc complete all as specified and as directed. Note- One run of PVC conduit of suitable dia and 5 runs of 10 sqmm PVC copper wire shall be measured and paid as one unit.
Supply and laying UG cable XLPE insulated, screened, PVC bedded, galvanised steel wire/strip armoured electric power cables, heavy duty LT 1100 Volt grade, with aluminium conductor of size 10 Sqmm 4 core including cable glands, aluminium lugs, nuts, bolts, washers etc and connections laid in trenches/ fixing on wall/ poles/ passing through pipes complete all as specified and as directed. NOTE: Excavation and earth work shall be measured and paid separately
Supply and laying UG cable XLPE insulated, screened, PVC bedded, galvanised steel wire/strip armoured electric power cables, heavy duty LT 1100 Volt grade, with aluminium conductor of size 16 Sqmm 4 core including cable glands, aluminium lugs, nuts, bolts, washers etc and connections laid in trenches/ fixing on wall/ poles/ passing through pipes complete all as specified and as directed. NOTE: Excavation and earth work shall be measured and paid separately
Supply and laying LED bulb 7W, polycarbonate body 700 lumen complete all as specified and as directed.
Supply, installation, testing and commissioning of 1 phase, 2 wire digital energy metre, 10-60 Ams, 240V, 50 Hz accuracy class 1.0 single source of direct connected prepaid mode facility, BIS marked confirming IS 16444:2015 (re-affirmed 2020) with inbuilt 6 LOW PAN /-867 MHz, radio frequency communication facilities having LCD type display, calibration LED, optical communication port push button for scroll and having futures for load disconnection through internal latching relay complying as per QC 1 and data download port for las 200 tamper events and load survey of last 45 days with all standard anti tamper futures with ceiling facility with self healing mesh. with default and on demand display billing data generation facility, anti tamper features, microprocessor and LED /LCD based circuit complete with communication protocol DLMS as per category D1 including design software database, testing & commissioing of prepaid energy meter complete all as specified and as directed.
Meter should have following inbuilt capacity and should support the following: 30 min instantaneous data voltage, current power factor, power, cumulative energy and frequency, 30 load survey data for energy, monthly billing survey for cumulative energy and maximum demand. Meter should connect /disco net functionality operable from prepaid billing software. The meter should support open communication protocol DLMS with the software and cost is inclusive of audit of software/ data interface charges.
INTERNAL WATER SUPPLY:
Supply and fixing in angular stop cock 15 mm bore of cast copper alloy Chromium plated with wall flange screwed down high pressure with crutch or butter fly handle screwed both ends for CPVC pipe complete all as specified and as directed. Make: Jaguar Cat Part No. CQT-23059 or equivalent in approved list of makes.
Supply and fixing Bib taps, cast copper alloy, fancy type, chromium plated of size 15mm crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed complete all as specified and as directed. Make- Jaguar Cat No. CQT-23047 or equivalent in approved list of makes.
Supply and fixing pillar tap 15mm bore, cast copper alloy fancy type chromium plated, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed complete all as specified and as directed. Make: Cat No. CQT-23021B of Jaguar or equivalent in approved list of makes.
Supply and fix brass with chromium plated health faucet with 8 mm dia, 1.5mtr long flexible tube chrome finish & wall hook complete all as specified and directed. Make: Cat No. No ALD573 and SHA571 of Jaguar or equivalent in approved list of makes.
Supply and fix over head shower rose 100mm dia round shape single flow ABS body chrome plated wirh grey face plate and Rubi/ cleaning system alongwith shower arm casted 120mm long heavy body round shape for wall mounted shower with wall flange complete all as specified and directed. Make: Cat No. OHS1989 and SHA-487 of Jaguaror equivalent in approved list of makes
Supply and fix stop cock long body combination of exposed part kit of concealed stop cock with fitting sleeve, operating knob, adjustable wall flange and regular body concealed stop cock suitable for 15mm pipe line with protection cap complete all as specified and as directed. Make: Cat No.CQT-23082K and ALD083 of Jaguaror equivalent in approved list of makes
AVIATION OBSTRUCTION LIGHT/ TELEPHONE/ TV SOCKET:
Supply and fix aviation obstruction light LED type medium indensity type 'C' luminious of 2000 Cadla red obstruction light, Aluminium housing, covered by transparent glass/ polycarbonate enclosure with timer switch and one 10A MCB SP 230V, input voltage 150-240 VAC range with mounting brackets, foundation complete at height appx 40m building complete all as specified and as directed.
Supply and lay UG cable XLPE insulated, screened, PVC bedded, galvanised steel wire/ strip armoured electric power cables (heavy duty) LT 1100 Volt grade, with aluminium conductor of size 6 Sqmm 2 core in trenches/fixing on wall/poles/passing through pipes complete all as specified and as directed. NOTE: Excavation and earth work shall be measured and paid separately.
Supply and fix TV coaxial socket 1 module with cover plate complete all as specified and directed.
Supply and fix RJ 11 telephone socket with shutter 1 module complete all as specified and directed.
Supply and fixing GI metal flush boxes 2 module complete all as specified and directed.
EXTERNAL WATER SUPPLY:
Cutting the existing 150mm bore CI pipe line and inserting CI Tee of size 150x150x150mm for taking branch conncetion complete including specials and jointing materials complete all as specified and as directed.
Supply, laying, joint, testing and commissioning of DI pipes 100 mm bore Centrifugally cast, internal cement mortar lining, external zinc coating with finishing layer of bitumen, pressure pipe flanged both ends, confirming to IS 8329-2000 with ISI marked K-9 in standard length including necessary rubber gasket and jointing materials complete all as specified.
Material and labour for valve chamber of size 1200 x 1200 x 1200mm PCC solid block masonary 200mm thick over concrete foundation in PCC 1:4:8 type D2 150mm thick, 50mm thick PCC 1:2:4 type B1 in coping including 15mm thick plastering in cement mortar 1:4 for internal and external surfaces 15cm below normal ground level with MS sheet 3.15 thick hinged MS cover with two nos of hinges and one No. handle made out of MS round bar 10mm dia with necessary locking arrangements. Lifting handle fitted to 50 x 50 x 6 mm angle iron frame including painting with two coats of synthetic enamel paint over a coat of red oxide primer, excavation etc complete all as specified and as directed.
Supply, installation, testing and commissioning of electrically driven centrifugal pump set as per specification, motor TEFC type, 2900 rpm, 420 V, 50 Hz, 3 ph, class 'F' insulation, IP 55 protection, not less than 25HP, starting on suitable DOL/Star Delta starter. The pump shall be horizontal, end suction, top discharge. The pump shall have cast iron casing, cast iron/ bronze impeller (as per manufacturer), carbon steel shaft with common base frame (fabricated mild steel channel frame or cast iron type) placed on RCC (1:2:4) including foundation bolts, nuts etc. complete with anti-vibrator pad as required capable of discharging not less than 650 LPM at 60 mtr head inclusive of suitable rated 3 ph starter as recommented by the manufacturer, PVC insulated copper cable connection from starter to the motor terminals complete all as specified and as directed by the Engineer-in-charge.
Material and labour for CI foot valves flanged type of 100 mm bore, ISI marked (flange drilling) confirming to IS 4038 complete all as specified and as directed.
Supply, installation, testing and commissioning of outdoor type power coated PLC (Programmable Logic Controller) based PUMP AUTOMATION PANEL slave monitoring/ annunciating control panel made out of 1.6mm thick CRCA sheet for control 2 Nos of Pump and monitoring of 20 Nos of Magnetic Level Sensor, 08 Nos of motorised valves complete all as specified and as directed by the Engineer-in-charge. The panel shall consist of the following equipments; (i) PLC with suitable Digital and analog Inputs / outputs, expansion modules, RTC . (ii) 4" LCD HMI (iii) Transformer with regulated output voltage of 230V +/-5%, (iv) SMPS of Suitable rating
(v) Set of Control Relays and suitable MCB (vi) Audio visual generator (vii) Suitable No. of LED Indicators for easy visualisation (viii) Selecetor Swtiches (ix) Push Buttons / Illuminated Push Buttons (x) 0.5 sqmm multistrand internal wiring with ferruling and suitable lugs. (xi) Ethernet card (xii) Media Converter (xiii) Ethernet Switch (xiv) LIU (Light Interface Unit)box patch chord and mounting accessories with following specification. Communication: Primary- OFC, Stand by: GPRS
Up-gradation of the existing SCADA software to incorporate management and control of various OHTs at various area, developing and adding the additional features as described below by altering the existing SCADA software complete all as specified and as directed by the Engineer-in-charge. a) Development of libraries and screens for display of the schematic of the remote motorized valves. b) Creation of additional soft keys for remote/ manual operation of the motorized valves in the OHTs. c) Modification of the Main SCADA screen to create a link to easily navigate to the newly developed OHT schematic screen etc. as required at Kataribag main pump house SCADA room and CERT audit of SCADA system at the time of commissioing shall be carried out by the contractor with any extra cost
Supply, draw, connecting, testing and commissioning of 2 core 1.5 sqmm stranded copper conductor, PVC insulated PVC sheathed, aluminium myler tape shielded FRLS armoured cable fiited on surface/ in trenches etc complete all as specified and as directed. Note: Earth work shall be measured and paid seperately
Supply, draw, connecting, testing and commissioning of 4 core 1.5 sqmm stranded copper conductor, PVC insulated PVC sheathed, aluminium myler tape shielded FRLS armoured cable fiited on surface/ in trenches etc complete all as specified and as directed. Note: Earth work shall be measured and paid seperately
Supply, draw, connecting, testing and commissioning of 6 core 1.5 sqmm stranded copper conductor, PVC insulated PVC sheathed, aluminium myler tape shielded FRLS armoured cable fiited on surface/ in trenches etc complete all as specified and as directed. Note: Earth work shall be measured and paid seperately
Supply, draw, connecting, testing and commissioning of 5 pair 0.5 sqmm stranded copper conductor, PVC insulated PVC sheathed, aluminium myler tape shielded FRLS armoured cable fiited on surface/ in trenches etc complete all as specified and as directed. Note: Earth work shall be measured and paid seperately
Supply, installation, testing & commissioning of Magnetic Level Sensor with the following specifications complete all as specified and as directed by Engr-in-charge. Type: Magnetic
Supply, installation, testing & commissioning UPS/ Inverter along of capacity 1.0 KVA with suitable battery bank with weather proof enclosure with locking arrangement complete including electric connection from tapping and to PLC based control panel with armoured copper wire complete all as specified and as directed by Engr-in-charge. Note: The scope of work includes integrating the UPS with the PLC based Panel so as to ensure that the Motorised valves are functional even in case of a power failure for a minimum of 6 hours
Supply, installation, testing & commissioning of pressure Transmitter with following specification including necessary power pack for supply of DC complete all as specified and as directed by Engr-in-charge. Power supply: 10-36 V DC Process connection: G ½ “ Enclosure: Whether proof IP 65 Process temperature: -30 to 120 celcius Accuracy: 0.25 %
Supply, installation, testing & commissioning of solenoid valve suitable for 25 mm pipe for priming of pump including all necessary GI fittings with following specifications complete all as specified and as directed by Engr-in-charge. Size: 25 mm Pressure rating: 10 kg /Sqcm
Supply, installation, testing & commissioning of direct acting type release solenoid valve for air release during priming; with follwing specifications complete all as specified and as directed by Engr-in-charge. Size: 10 mm Pressure rating: 10 kg / sq. cm. Type: Normally closed
Supply, installation, testing & commissioning of motor actuated butterfly valve made of SS-304, stem material SS-410, EPDM seat in butterfly valve consisiting of quarter turn single phase actuator and wafer type butterfly valve of size 75/80 mm dia with appropriate bracket/mounting arrangement including two nos of limit switches for open and closed condition and splash proof enclosure. Specifications & Features: Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/sq cm. Operating Angle: 90 degrees Disc Material: CI with nylon coating Limit Switches : 02 Nos.For open and close status Mounting :In Direct on valve Note:The torque of actuator shall be atleast 25% higher than the valve
Supply, installation, testing & commissioning of Motor Actuated Butterfly Valve made of SS- 304, stem material SS-410, EPDM seat in butterfly valve consisiting of Quarter turn single phase Actuator and Wafer type butterfly valve of size 100 mm dia with appropriate bracket/ mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclosure complete all as specified and as directed by Engr-in-charge. Specifications & features: Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/Sqcm. Operating Angle: 90 degrees Disc Material: CI with nylon coating Limit Switches : 02 Nos. for open and close status Mounting: In direct on valve Note: The torque of actuator shall be atleast 25% higher than the valve.
Supply, installation, testing & commissioning of motor actuated butterfly valve made of SS-304, stem material SS-410, EPDM seat in butterfly valve consisiting of Quarter turn single phase actuator and wafer type butterfly valve of size 150 mm dia with appropriate bracket/mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclosure complete all as specified and as directed by Engr-in-charge. Specifications & Features: Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/sq cm. Operating Angle: 90 degrees Disc Material: CI with nylon coating Limit Switches : 02 Nos. for open and close status Mounting :In direct on valve Note: The torque of actuator shall be atleast 25% higher than the valve
EXTERNAL ELECTRIFICATION/STAND BY DG SET:
Supply, install, testing and commissioning of static silent Diesel Engine with accoustic enclosure, capable of delivering 160 KW (200 KVA), including (AMF panel) Automatic starting on main faiilure control panel water cooled, 415 volts (AC three phase, 4 wire system of supply), frequency 50 Hz, at power factor 0.80 minimum. The DG set shall consists of a diesel engine coupled to a matching the alternator through flexible coupling and mounted on a common based frame and complete with control panel standardized by the manufacturer, fuel tank with mounting arrangements and with standard fuel pipes for inlet, outlet and return inlet oil arrangements, exhaust pipe, silencer and asbestos rope protection complete all as specified and as directed by Engr-in-charge.
Note: (i) Designed capacity of Diesel engine and alternator shall be worked out by considering all derating factors prevailed at the area to be installed) (ii) The foundation of Gen Set shall be as specified by the manufacturer and shall be mounted on a suitable Channel frame structure with anti-vibration pads and including all technical features to comply with latest CPCB guidelines and comprising of followings:-
(i) DIESEL ENGINE (Prime Mover): Diesel Engine 1500 RPM, direct injection, six cylinders, four stroke, confirming to ISO3046/ BS5514, water cooled, natuarally turbo charged, capable of giving adequate BHP to drive alternator capable of delivering 160 KW (200 KVA) at outdoor atmospheric conditions at palluruthy, Kochi (Considering all derating factors prevailed in the area). Batteries 12/24 Volts and desired ampere hours (as per manufacturers recommendations), electric battery start, complete with fly wheel and all standard fittings and fixtures as per manufacturer and including suitable panel with tacho meter, lub oil temperature, pressure gauge and frequency meters. The engine shall have self starter, dynamo, FIP, oil pump, fuel electric control panel with mechanical governor (ECPG) and Engine protection system (Shut down, High water temperature, low lub oil, oil pressure, over speed etc., recommented capacity of fuel tank and first filling of fuel and lub oil and other consumables etc.
(ii) ALTERNATOR: Brushless AC alternator, 3 phase, 415 Volts, 4 wire rated for output of 160 KW (200 KVA) minimum power factort 0.80, 1500 RPM, IP 23 ptotection class enclosure, insulation class 'H', salient pole, revolving field, single bearing, automatic voltage regulator coupled through flexible coupling with and match the above engine. (iii) BASE PLATE: Made of structural steel as per manufacturers recommended design/ specifications.
(iv) ACOUSTIC ENCLOSURE: Sheet metal fabricated canopy type, silent enclosure, manufactured on CNC machines as per CPCB norms and shall be powder coated. The enclosure shall be designed for reducing the sound level to 75 DB at a distance of 1 mtr at 75% load under field condition and 70DB at 3 M from Gen Set when DG set is working at full load along with testing performance, labeling certification etc. as laid down in GSR No. 371(E) dt 17 May 2002. (i) Foundation/ Plinth/ Base shall be provided as per manufacturers recommendations, however minimum 0.50 M space should be available all around the set and height of plinth shall not be less than 0.50 M. (ii) Standard Diesel Engine tank of adequate capacity for running the Gen Set continuously for 12 hours including standard pvc pipes from tank to FIP, overflow pipe from FIP to tank.
(v) MISCELLANEOUS:- Tool kit, Operation and maintenance catalogue, spare parts list, overhauling manuals, guarantee cards, test certificate of Engine and alternator etc. shall be provided as per manufacturer standard practice.
Supply and lay UG cable XLPE insulated, screened, PVC bedded, galvanised steel wire/ strip armoured electric power cables (heavy duty) LT 1100 Volt grade, with aluminium conductor of size 185 Sqmm 3.5 core in trenches/ fixing on wall/ poles/ passing through pipes complete all as specified and as directed. NOTE: Excavation and earth work shall be measured and paid separately.
Supply and lay UG cable XLPE insulated, screened, PVC bedded, galvanised steel wire/ strip armoured electric power cables (heavy duty) LT 1100 Volt grade, with aluminium conductor of size 150 Sqmm 3.5 core in trenches/ fixing on wall/ poles/ passing through pipes complete all as specified and as directed. NOTE: Excavation and earth work shall be measured and paid separately.
Supply and lay UG cable XLPE insulated, screened, PVC bedded, galvanised steel wire/ strip armoured electric power cables (heavy duty) LT 1100 Volt grade, with aluminium conductor of size 95 Sqmm 3.5 core in trenches/ fixing on wall/ poles/ passing through pipes complete all as specified and as directed. NOTE: Excavation and earth work shall be measured and paid separately.
Supply and lay UG cable XLPE insulated, screened, PVC bedded, galvanised steel wire/ strip armoured electric power cables (heavy duty) HT 11000 Volt grade, with aluminium conductor of size 185 Sqmm 3.0 core in trenches/ fixing on wall/ poles/ passing through pipes complete all as specified and as directed. NOTE: Excavation and earth work shall be measured and paid separately.
Supply and fix sandwich type bus trunking system with copper bus trunking system with copper bus bar 1600 Amps 50KA breaking capacity IP 54 complete all as specified and as directed.
Supply, install, testing and commissioning of factory made and CPRI tested indoor type feeder pllar box suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating of suitable Amps for phases and suitable Amps for neutral fixed on porcelain insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2mm CRCA sheet duly powder coated after seven tank process and pedestal of size 50 x 50 x 6 mm thick MS angle iron frame work. The panel shall be both front and back openable type adequate space all around acessories such as LT switchgear and measuring instruments on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings accessories complete all as specified and as directed (Main LT Panel).
INCOMING: (a) ACB 1600 Amps, 50 KA -01 No (b) Digital volt meter 0-500 Volts- 01 No (c) Digital Ampere meter 0-300 Amps with and including CTs OUTGOING: (a) MCCB TPN 400 Amps, 25 KA- 05 Nos (b) MCCB TPN 320 Amps, 25 KA- 01 No (c) Internal wiring of panel with stranded copper cable of suitable size. (d) Neon phase indicating lamp (Set of three)- 01 No (e) Stencling of panel board including marking of distribuitions
Supply, install, testing and commissioning of factory made and CPRI tested indoor type pedestal mounted on PCC Plinth. LT panel board cubicle type panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating of suitable Amps for phases and suitable Amps for neutral fixed on porcelain insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2mm CRCA sheet duly powder coated after seven tank process and pedestal of size 50 x 50 x 6 mm thick MS angle iron frame work. The panel shall be both front and back openable type adequate space all around acessories such as LT switchgear and measuring instruments on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings accessories complete all as specified and as directed.
INCOMING: (a) MCCB 415 Volts, 400 Amps TPN ,25 KA- 1 No (b) Digital volt meter 0-500 Volts- 01 No (c) Digital Ampere meter 0-300 Amps with and including CTs- 01 No OUTGOING: (a) MCCB 415 Volts, 125 A TPN - 03 Nos (b) MCB 415 Volts 63 A TPN - 01 No (c) MCB 415 Volts 200 A TPN - 01 No (d) Internal wiring of panel with stranded copper cable of suitable size (e) Neon phase indicating lamp (Set of three)- 01 No (f) Stencling of panel board including marking of distribuitions
Supply, install, testing and commissioning of factory made and CPRI tested indoor type pedestal mounted on PCC Plinth. LT panel board cubicle type panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating 200 Amps for phases and 200 Amps for neutral fixed on porcelain insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2.0 mm CRCA sheet duly powder coated after seven tank process and pedestal of size 50 x 50 x 6 mm thick MS angle iron frame work. The panel shall be both front and back openable type adequate space all around accessories such as LT switchgear and measuring instruments on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings accessories complete all as specified and as directed.
INCOMING: (a) MCCB 415 volts TPN 125Amps 10 KA - 01 No (b) Digital volt meter 0-500 Volts- 01 No (c) Digital Ampere meter 0-100 Amps with and including CTs- 01 No OUTGOING: (a) MCB 63 Amps 4 pole , 415 Volts, 10KA - 04 Nos (b) MCB 40 Amps 4 pole , 415 Volts, 10KA - 03 Nos (c) MCB SPN 25 Amps - 02 Nos (d) Digital volt meter 0-500 Volts- 01 No (e) Digital Ampere meter 0-300 Amps with and including CTs (f) Neon phase indicating lamp (Set of three)- 01 No (g) Stencling of panel board including marking of distribuitions
Supply, install, testing and commissioning of factory made and CPRI tested indoor type pedestal mounted on PCC Plinth. LT panel board cubicle type panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating 500 Amps for phases and 500 Amps for neutral fixed on porcelain insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2 mm CRCA sheet duly powder coated after seven tank process and pedestal of size 50 x 50 x 6 mm thick MS angle iron frame work. The panel shall be both front and back openable type adequate space all around acessories such as LT switchgear and measuring instruments on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of following accessories complete all as specified and as directed (Building Panel G+9).
INCOMING: (a) MCCB 415 Volts, 400 Amps TPN , 65 Ka- 1 No (b) Digital volt meter 0-500 Volts-01 (c) Digital Ampere meter 0-100 Amps with and including CTs-01 No OUTGOING: (a) MCB, 415 volts, 10KA, TPN 63 Amps - 12 Nos (b) MCB SPN 32 Amps - 02 Nos (c) Digital volt meter 0-500 Volts-01 No (d) Digital Ampere meter 0-300 Amps with and including CTs (e) Neon phase indicating lamp (Set of three)- 01 No (f) Stencling of panel board including marking of distribuitions
Supply, install, testing and commissioning of factory made and CPRI tested indoor type pedestal mounted on PCC Plinth. LT panel board cubicle type panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating 500 Amps for phases and 500 Amps for neutral fixed on porcelain insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2 mm CRCA sheet duly powder coated after seven tank process and pedestal of size 50 x 50 x 6 mm thick MS angle iron frame work. The panel shall be both front and back openable type adequate space all around acessories such as LT switchgear and measuring instruments on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of following accessories complete all as specified and as directed (Building Panel G+7).
INCOMING (a) MCCB 415 Volts, 320 Amps TPN , 65 KA- 1 No (b) Digital volt meter 0-500 Volts- 01 No (c) Digital Ampere meter 0-100 Amps with and including CTs-01 No OUTGOING: (a) MCB, 415 volts, 10KA TPN 63 Amps - 09 Nos (b) MCB SPN 32 Amps - 02 Nos (c) Digital volt meter 0-500 Volts- 01 No (d) Digital Ampere meter 0-300 Amps with and including CTs (e) Neon phase indicating lamp (Set of three)- 01 No (f) Stencling of panel board including marking of distribuitions
Supply, install, testing and commissioning of factory made and CPRI tested indoor type pedestal mounted on PCC Plinth. LT panel board cubicle type panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on copper bus bar of rating 200 Amps for phases and 200 Amps for neutral fixed on porcelain insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2.0 mm CRCA sheet duly powder coated after seven tank process and pedestal of size 50 x 50 x 6 mm thick MS angle iron frame work. The panel shall be both front and back openable type adequate space all around acessories such as LT switchgear and measuring instruments on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of following accessories complete all as specified and as directed (Water Supply Panel).
INCOMING: (a) MCCB 415 Volts, TPN 63 Amps 18 kA - 01 No (b) Digital volt meter 0-500 Volts- 01 No (c) Digital Ampere meter 0-100 Amps with and including CTs- 01 No OUTGOING (a) MCB TP 40 Amps 15 kA - 02 Nos (b) MCB SPN 16 Amps 15 kA - 01 No (c) Star delta starter for 20 HP pump- 2 Nos (d) Digital volt meter 0-500 Volts-01 No (e) Digital Ampere meter 0-300 Amps with and including CTs (d) Neon phase indicating lamp (Set of three)- 01 No (e) Stencling of panel board including marking of distribuitions
INCOMING: (a) MCCB 415 Volts, TPN 63 Amps 18 kA - 01 No (b) Digital volt meter 0-500 Volts- 01 No (c) Digital Ampere meter 0-100 Amps with and including CTs- 01 No OUTGOING (a) MCB TP 32 Amps 15 kA - 02 Nos (b) MCB SPN 16 Amps 15 kA - 01 No (c) Provision for fixing 02 Nos star delta starters (d) Digital volt meter 0-500 Volts- 01 No (e) Digital Ampere meter 0-300 Amps with and including CTs (d) Neon phase indicating lamp (Set of three)- 01 No (e) Stencling of panel board including marking of distribuitions (f) Star Delta starters for 90 HP pump- 1 No (g) DOL starters for 7.5 HP pump- 1 No
Supply and install 175 KVAR with 6 steps (2x12.5+2x25 + 2x50) APFC panel with MPP-H Capacitor and MCCB as incoming complete all as specified and as directed by Engr-in-charge.
Supply and installation of HT 11 KV, 3 phase, 50 Hz totally enclosed metal clad switchgear complete with vacuum circuit breaker outdoor type having rupturing capacity 350 MVA, overload and earth fault protection, ammeter, voltmeter and of rating upto 11 KV 630 Amps, 21 KA Motor operated compact outdoor both side extensible, non drawout type (+C+) (01 No Load break Switch (OD) as incomer SAFEPLUS compact gas insulated Ring Main Unit (RMU), all live parts enclosed in a welded stainless steel tank of IP 67 class of protection including coupling accessories with battery and battery charger, foundation and transportation complete all as specified and as directed by Engr-in-charge
Supply and installation of HT 11 KV, 3 phase, 50 cycles totally enclosed metal clad switchgear complete with vacuum circuit breaker indoor type having rupturing capacity upto 350 MVA, overload and earth fault protection, ammeter, voltmeter and of rating upto 630 Amp, 21 KA Motor operated compact indoor both side extensible, non drawout type (CV+) (01 No Load break Switch OD incomer and 1 no fixed type motor operated Vaccum circuit breaker( VL) outgoing) safeplus compact gas insulated Ring Main Unit (RMU), all live parts enclosed in a welded stainless steel tank of IP 67 class of protection including coupling accessories with battery and battery charge, foundation and transporatation complete all as specified and as directed by Engr-in-charge.
Supply and installation of Transformer step down, indoor type, copper wound, oil cooled complete with standard fittings HT 11/0.433 KV, 3 phase, 4 wire with off load tappings on HT side to vary secondary voltage within limit +/- 5% in step of +/- 2.5%. ONAN all as per IS :1180,2026 of capacity 1000 KVA duly initial oil filled up to normal level with following accessories and functions alongwith foundation as per the manufacturer instruction complete all as specified and as directed by Engr-in-charge.
(i) No load loss as per standard (subject to IS tolerance) (ii) Full load loss as per standard (subject to IS tolerance) (iii) Impedance is 4.75% (subject to IS tolerance) (iv) Vector group is Dyn 11 (v) Silica gel breather (vi) Conservator with plain oil gauge and oil drain plug (vii) Top filter valve (viii) Bottom filter cum drain valve (ix) Shut off valve between buchholz relay and conservator (x) Off circult tap changer (xi) Rating and dilagramme plate (xii) Earthing terminals (xiii) Thermometer pockets
(ivx) Lifting lugs (xv) Air relief plug (xvi) Jacking pads (xvi) Bi-directional rollers (xviii) Explosion vent with single diaphragm (xix) Detachable radiators (xx) Inspection cover (xxi) Danger notice board (xxii) cable entry box. The secondary LT will be laid suitable ampere rating insulated GI srip for 1000KVA tranformer upto main LT panel board
Supply and fix cable jointing kit for 11 KV grade cable ( Earthed) for outdoor/indoor termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 185 Sq.mm complete all as specified and as directed by Engr-in-charge
Supply & erect 9 meter steel tubular swaged pole consisting of pole with cast iron base plate finial taper plugs type 410 SP-31 including necessary earth work excavation, PCC foundation, PCC coping & cross arms etc. complete all as specified and as directed by Engineer-in-charge.
Supply and fix street light fitting pressure die cast aluminium housing with heat resistant toughened glass IP 66 protection of 35 watt, 230 V, LED street light fitting complete with LED lights, in-built erlectronic driver, minimum 10 KV surge protection, number of LED 44 with clear acrylic cover accessories pre wired and fixing accessories i.e. nut bolt washers, Flat iron strips, Gi pipe etc. complete all as specified and as directed by Engineer-in-charge.
Supply and fixing poly carbonate street light junction boxes IP 66/67 weather proof suitable for outdoor installation having minimum size 225 x 295 x 122 mm including suitable cable connecting terminals, cable lugs, including provn of one No MCB SP 6 Amps for operating the street light fittings, suitable cable glands as per site requirement complete all as specified and as directed by the Engineer-in-Charge.
Supply and fix time switches astro type having longitude and latitude of indian cities in memory 250 V Single phase of 20 Amp rating with contactor fitted inside steel enclosure complete all as specified and as directed by the Engineer-in-Charge.
Supply & fix HT cable route marker of cast iron type circle 100 dia complete all as specified and as directed.
Supply & fix LT cable route marker of cast iron type circle 100 dia complete all as specified and as directed.
Supply & fix blue metal stones for Electric installations of size 20mm complete all as specified and as directed.
Supply & fix chain link fencing with angle iron bar type over perimeter of electric installation area 10 X 4 M by 0.5m PCC foundation all around inculding gate all necessary connections complete all as specified and as directed by Engineer-in-Charge.
FIRE FIGHTING:
Supply, connect, joint and lay MS pipe (ERW) heavy duty ISI marked with all fittings of size 100 mm dia with flanged ends and including flanges, leather gaskets, heavy duty bolts, nuts, washers etc, laid in trenches, floors, fixed on walls/ floors/ roof ete including fixing with clamps on wall for the wet riser including painting with approved synthetic enamel paint complete all as specified and as directed by Engr-in-charge.
Supply and fix Automatic air release valve 50 mm dia suitable for domestic water with 50 mm gun metal stop valve complete all as specified and as directed by the Engineer-in-Charge.
Supply and fix mild steel class 'C' diesel pump exhaust pipe 150 mm dia with one layer of 10 mm thick asbestos rope insulation and including all fitting clamp/ structural steel supports complete all as specified and as directed by the Engineer-in-Charge.
Material and labour for CI foot valves flanged type of 150 mm bore, ISI marked (flange drilling) confirming to IS 4038 complete all as specified and as directed by the Engineer-in-Charge.
Supply and fixing non-return (reflex) valve 150mm bore cast iron body complete ISI mark, including rubber flanges, nuts bolts, washers etc. complete all as specified and as directed by the Engineer-in-Charge.
Supply and fixing non-return (reflex) valve 100mm bore cast iron body complete ISI mark, including rubber flanges, nuts bolts, washers etc. complete all as specified and as directed by the Engineer-in-Charge.
Supply and fixing non-return (reflex) valve 80mm bore cast iron body complete ISI mark, including rubber flanges, nuts bolts, washers etc. complete all as specified and as directed by the Engineer-in-Charge.
Supply and fixing of Analog addressable type active loop repeater (Loop power/ external power) fire terminal with inbuilt turbo isolator, Backlit LCD Display 6 x 40 characters display, having controls for reset, mute,accept, silence alarms and self test, with programmable free keys and duly approved by EN54/ LPCB/ VDS/ FM complete all as specified and as directed by Engr-in-charge.
Supply and fixing of LED Emergency exit signage luminaire lit up using regular main supply comes with a unique rechargeable battery capable of emergency backup upto 05 hours complete all as specified and as directed by Engr-in-charge.
Supply and fixing of LED Emergency escape lighting luminaire lit up using regular main supply comes with a unique rechargeable battery capable of emergency backup upto 05 hours complete all as specified and as directed by Engr-in-charge.
Supply, installation testing and commissioning of XLPE insulated PVC sheathed FRLS galvanised steel strip or wire (Heavy duty) electric cable with copper coductor of size 1.5 sq.mm, 2 core suitable for working pressure 1100 Volts to IS: 7098 and drawn into PVC coduit pipe 20 mm complete all as specified and as directed by the Engineer-in-Charge.
Supply, installation, testing and commissioning of addressable isolator module for isolating short /dewired /loose circuits with automatic resetting arrangement. Isolator base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. The isolator module shall not occupy any address on loop. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. The module shall be UL listed and FM approved complete all as specified and as directed by the Engineer-in-Charge.
Supply, installation, testing and commissioning of addressable control module for sounders /strobes /sounder cum strobes. The control module shall provide DPDTcontact rated at 24V DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. The module shall be UL listed and FM approved complete all as specified and as directed by the Engineer-in-Charge.
Supply, installation, testing and commissioning of 2W multi-tap (0.25W; 0.5W; 1W; 2W), Ceiling Mount Speakers. The speakers shall be of same make as that of the Control Panel & Amplifiers. They shall be compatible with supplied Amplifiers and shall work on 70.7Vrms. The speaker shall be UL listed complete all as specified and as directed by the Engineer-in-Charge.
Supply, installation, testing and commissioning of Fire Alarm Sirens Electronic type horizontal single stage continous normal operation for atleast 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound output variation of +5 DB, range upto 1000m complete all as specified and as directed by the Engineer-in-Charge.
Note for item No. 141 to 144: a) The lift shall be provided with Fireman switch and shall be automated with emergency switch on ground level. It shall be equipped with suitable inter communication equipments for communicating with control room on the ground floor of the building. (b) The integral dimension of the lift car should be suitable size for the specified load and in accordance with the statutory requirements. (c) The inside car measurement shall be based on lift well dimensions shown on drawings forming part of the Contract. Each lift shall be complete with following accessories & fittings. (i) Double button with 7 segmental display at all floors. (ii) Car opening panel with micro stroke push button with 7 segment digital car position indicator, car direction indicator (iii) Fire exitingusher which provided at main lobby. (iv) Battery operated alarm bell and emergency lift with battery. (v) Voice Synthesizer
(vi) Car Chime (vii) Provision of cross flow rectangular (low noise/ mild air flow) fan-01 of approved make. (viii) Supply and fix Decorative LED spot light (ix) Provn of emergency intercom system (car machine room-control system) (x) Oveload function, constant indication/buzzer. (xi) 5/15 A power socket & light point at every floor level in the hoist way. (xii) MS Ladder (xiii) 3 Phase power supply & earthing from machine room to all equipment. (xiv) Multi beam full length infra red door sensor (minimum of 32) (xv) Emegency landing device ELD (ARD) (xvi) Extra cores in travelling cable for customer smoke detectors. (xvii) Back ground music speakers.
Supply and lay UG cable XLPE insulated, screened, PVC bedded, galvanised steel wire/ strip armoured electric power cables (heavy duty) LT 1100 Volt grade, with aluminium conductor of size 50 Sqmm 3.5 core in trenches/ fixing on wall/ poles/ passing through pipes complete all as specified and as directed. NOTE: Excavation and earth work shall be measured and paid separately.
EXTERNAL WATER SUPPLY/FIRE FIGHTING/EXTERNAL ELECTRIFICATION:
Riddled soil as earth cushioning to UG cable by using IS sieve to separate the composite particle/roots etc. and filling/spread in trenches as cushioning and punned to required thickness to form a solid bed complete all as specified and as directed. Note: 1. Punned thickness only will be measured and paid . 2. Excavated approved soil shall be riddled by using sieve to separate composite particles etc as per IS.
Supply, laying, joint, testing and commissioning of DI pipes 150 mm bore Centrifugally cast, internal cement mortar lining, external zinc coating with finishing layer of bitumen, pressure pipe flanged both ends, confirming to IS 8329-2000 with ISI marked K-9 in standard length including necessary rubber gasket and jointing materials complete all as specified.
Supply and fixing MCCB 4 pole of current rating capacity 63 Amps with breaking capacity Icu AC 16kA, 415V AC 50 Hz conforming to IS/IEC 60947-2 & EN 60947-2 of thermal magnetic release with ON-TRIP-OFF indication complete all as specified and directed.
DEMOILITION/DISMANTLING:
Taking down old Vitreous china wash basin of any description complete all as specified and as directed by Engr-in-charge.
Taking down old pillar taps/ bib taps/ stop cock of any description complete all as specified and as directed by Engr-in-charge.
Taking down old water closet of any description complete all as specified and as directed by Engr-in-charge.
Taking down old kitchen sink of any description complete all as specified and as directed by Engr-in-charge.
Taking down Sub main wiring Aluminium/ copper including of 2 x 4 Sqmm/ 6 Sqmm/ 10 Sqmm and deposited in stores complete all as specified and as directed by Engr-in-charge.
Taking down old main switches/ DBs and deposited in stores complete all as specified and as directed by Engr-in-charge.
Taking down ceiling fan/ exhaust fan of any capacity and depositing it MES for further disposal complete all as specified and as directed by Engr-in-charge.
Taking down old LT panel indoor/ outdoor of any specification complete all as specified and as directed by Engr-in-charge.
Taking down 3 phase energy meter carefully and hand over to MES departement complete all as specified and as directed by Engr-in-charge.
COMPREHENSIVE MAINTENANCE:
Annual Comprehensive Maintenance and petty repairs like repairs to joineries including Alu.windows, internal sanitary fittings, repairs to taps and other plumbing works, leakage, Switch and Socket, Tube lights, lamps holder, call bell, MCBs, DBs, Ceiling fan and Exhaust fan ,fittings, electric wiring, geysers for Married Accn for (200 DUs GF+9 of two blocks and GF+7 of one block) for Sailors (POs and below) at Naval Base Kochi for the First Year after defects liability period complete all as specified and as directed by the Engineer-in-charge.
Annual Comprehensive Maintenance and petty repairs like repairs to joineries including Alu.windows, internal sanitary fittings, repairs to taps and other plumbing works, leakage, Switch and Socket, Tube lights, lamps holder, call bell, MCBs, DBs, Ceiling fan and Exhaust fan ,fittings, electric wiring, geysers for Married Accn for (200 DUs GF+9 of two blocks and GF+7 of one block) for Sailors (POs and below) at Naval Base Kochi for the Second Year after defects liability period complete all as specified and as directed by the Engineer-in-charge.
Annual Comprehensive Maintenance and petty repairs like repairs to joineries including Alu.windows, internal sanitary fittings, repairs to taps and other plumbing works, leakage , Switch and Socket, Tube lights, lamps holder, call bell, MCBs, DBs, Ceiling fan and Exhaust fan ,fittings, electric wiring, geysers for Married Accn for (200 DUs GF+9 of two blocks and GF+7 of one block) for Sailors (POs and below) at Naval Base Kochi for the Third Year after defects liability period complete all as specified and as directed by the Engineer-in-charge.
Annual Comprehensive Maintenance and petty repairs to External Services like repairs to Area drainage, repairs to Road/ Path/ Hardstanding and Sewage Disposal etc for Married Accn for (200 DUs GF+9 of two blocks and GF+7 of one block) for Sailors (POs and below) at Naval Base Kochi for the First Year after defects liability period complete all as specified and as directed by the Engineer-in-charge.
Annual Comprehensive Maintenance and petty repairs to External Services like repairs to Area drainage, repairs to Road/ Path/ Hardstanding and Sewage Disposal etc for Married Accn for (200 DUs GF+9 of two blocks and GF+7 of one block) for Sailors (POs and below) at Naval Base Kochi for the Second Year after defects liability period complete all as specified and as directed by the Engineer-in-charge.
Annual Comprehensive Maintenance and petty repairs to External Services like repairs to Area drainage, repairs to Road/ Path/ Hardstanding and Sewage Disposal etc for Married Accn for (200 DUs GF+9 of two blocks and GF+7 of one block) for Sailors (POs and below) at Naval Base Kochi for the Third Year after defects liability period complete all as specified and as directed by the Engineer-in-charge.
Comprehensive maintenance and servicing of electrically operated gearless elevator not less than 544 Kg capacity 08 passenger with a speed of 1.5m/sec to serve ground floor and ten floor (G+9) (2 Blocks with 2 Nos of 08 passenger lift) as provided and repairs/ replacement of defective and unserviceable parts during maintenance period attending to break down as and when intimated including necessary periodical safety checking and testing of lift as mentioned in relevant code of practices/ IS for the safe and efficient performance of lifts for first year after expiry of defects liability period complete all as specified and directed by OEM.
All as per item No. 169 here-in-before, but for second year after expiry of defects liability period
All as per item No. 169 here-in-before, but for third year after expiry of defects liability period
Comprehensive maintenance and servicing of electrically operated gearless elevator not less than 884 Kg capacity 13 passenger with a speed of 1.5m/sec to serve ground floor and ten floor (G+9) (2 Blocks with 2 Nos of 13 passenger lift) as provided and repairs/ replacement of defective and unserviceable parts during maintenance period attending to break down as and when intimated including necessary periodical safety checking and testing of lift as mentioned in relevant code of practices /IS for the safe and efficient performance of lifts for first year after expiry of defects liability period complete all as specified and directed by OEM.
All as per item No. 172 here-in-before, but for second year after expiry of defects liability period
All as per item No. 172 here-in-before, but for third year after expiry of defects liability period
Comprehensive maintenance and servicing of electrically operated gearless elevator not less than 544 Kg capacity 08 passenger with a speed of 1.5m/sec to serve ground floor and eight floor (G+7) (2 Nos of 08 passenger lift) as provided and repairs/ replacement of defective and unserviceable parts during maintenance period attending to break down as and when intimated including necessary periodical safety checking and testing of lift as mentioned in relevant code of practices /IS for the safe and efficient performance of lifts for first year after expiry of defects liability period complete all as specified and directed by OEM.
All as per item No. 175 here-in-before, but for second year after expiry of defects liability period
All as per item No. 175 here-in-before, but for third year after expiry of defects liability period
Comprehensive maintenance and servicing of electrically operated gearless elevator not less than 884 Kg capacity 13 passenger with a speed of 1.5m/sec to serve ground floor and eight floor (G+7) (2 Nos of 13 passenger lift) as provided and repairs/ replacement of defective and unserviceable parts during maintenance period attending to break down as and when intimated including necessary periodical safety checking and testing of lift as mentioned in relevant code of practices /IS for the safe and efficient performance of lifts for first year after expiry of defects liability period complete all as specified and directed by OEM.
All as per item No. 178 here-in-before, but for second year after expiry of defects liability period
All as per item No. 178 here-in-before, but for third year after expiry of defects liability period
Note for item No. 169 to 180: a) No of spare parts will be supplied by the department b) The rate for maintenance, service and repair include all the materials and labour required for the satisfactory functioning of this lifts as stipulated on particular specifications.
PUSHKARRAJ CONSTRUCTION PRIVATE LIMITED
CHERIAN VARKEY CONSTRUCTION CO PVT LTD
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid