Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹8.0 LAccepted-AOC TAILOR MARKET MAIN BAZAAR MANDI ADAMPUR 125052 | HISAR | HARYANA | 125052 | L-1 | Accepted-AOC AOC | |
| 2 | L-2₹8.2 L+₹24,441 (3.07%)Rejected-Finance 315 INDUSTRIAL AREA II PANCHKULA 134113 | PANCHKULA | HARYANA | 134113 | L-2 | Rejected-Finance Highest | |
| 3 | L-3₹8.4 L+₹43,356 (5.45%)Rejected-Finance 209 210 AGGARWAL TOWER PLOT NO 2 SECTOR 5 ROHINI NORTH WEST DELHI DELHI 110085 | DELHI | NORTH WEST DELHI | DELHI | 110085 | L-3 | Rejected-Finance Highest | |
| 4 | Rejected-Technical HOUSE NO 2246 SECTOR 15 C CHANDIGARH | NA | NA | 160001 | - | Rejected-Technical Non Reosponsive | |
| 5 | Rejected-Technical | - | Rejected-Technical Non Reosponsive |
Tender Value
₹10.3 L
Closing Date
18 Jun 2019, 5:00 pmClosed
Ritesh Nandal
Executive Engineer, Elect. Division PWD B and R Br., Ambala Cantt
Construction of Govt. ITI at Village Nahoni in Distt Ambala (Pdg. Fire Alarm System).
2019_HRY_79700_1
PWD/Elect-KNL/Elect-AMB/10509
Open Tender
Construction Works
Works
60 days
Ambala
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,000
Executive Engineer, Elect. Division PWD BandR Br.
Exempted
19 Oct 2021
7 Jun 2019
20 Jun 2019
7 Jun 2019
18 Jun 2019
7 Jun 2019
Amount
Supply and erection of PVC unsheathed copper conductor cable single core 1100 volts grade in pipe of suitable size excluding cost and erection of pipe. (31. 40)
Size 1.5 sqmm (3 / 0.81mm). (31.40 (i))
Supply and erection of PVC conduit pipe ISI marked (Medium) recessed in wall /ceiling etc. including cost of PVC bends, inspection box and all other material requiredto complete the job in all respect to the entiresatisfaction of Engineer-in-Charge of work. (31.44(HSR Item) )
25 mm dia (31.44(b))
SITC of Micro processor based 2 wire fault tolerant, networkable type Fire Alarm / Detection Control Panel (having nos. of loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 characters LCD unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80 LED Indicators. The Panel shall have 3 Serial Ports. The pane\l shall have a built in power supply and battery charger along with maintenance free 24 AH,2 x 12 volt SMF lead acid batteries capable of running for a minimum 24 hours with battery charger complete as required. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS/ as per specifications complete in all respect up to the entire satisfaction of Engineer-in – charge of work. (1)
(Make: Bosch-FPA1000 series / Honeywell Morley -ZXE series / Siemens Cerberus / Edwards EST3 ()
SITC of Public Address System consisting of the following (2)
SITC of 6 watt speaker (Bosch / Morley / GST (3)
SITC of intelligent Analog Addressable type Smoke Detector that combine photo Electronic and fixed temp thermal with base complete with LED Hard Addressable Having rotary decade Address switches, with Mounting Base for each detector complete as required conforming to BS 5839 standards and duly approved by EN54/UL/VDS respect up to the entire satisfaction of Engineer – in Charge of work. ()
(Make: Bosch / Morley / Siemens / Edwards ()
SITC of intelligent Analog Addressable type Manual Call Point having Surface or flush mounting option fully compliant to EN 54 having Rotary Decade switches for addressing with Back Box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. (4)
(Make: Bosch / Morley / Siemens / Edwards ()
SITC of Addressable Loop powered hooter with strobe complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. (Make: Bosch / Morley / Siemens / Edwards (5)
SITC of Glow Type EXIT Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink sulphate as bare chemical class 1 material PSPA fixed on 3mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour & material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. (6)
(Make: PE / Glolite / Omex) ()
SITC of Intelligent Analog Addressable Type Monitor Modules having option of RAIL or Surface Mounting with Tri Color LED status indicator with Built in Short Circuit Isolators having Visible Rotary Decade Address Switch from 01-99 dully approved to GEA GEW1-082 conforming to BS5839 Standards and Duly approved by EN54/LPCB/VDS with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. (7)
(Make: Bosch / Morley / Siemens / Edwards ()
SITC of minimum 1000 Mtr. Range Kheraj/National make SIRON generator provided at the roof of the building with separate Power Supply, relay etc. complete the in all respect up to the entire satisfaction of Engineer-in-Charge of work. (8)
Supply & Erection of Fire extinguisher all as Per IS 15683 duly hanged on the wall with necessary hooks to complete the job in all respect upto entire satisfaction of engineer incharge of work (10)
Make: Safex / Minimax / cease fire) ()
ABC dry Powder extinguisher 6 Kg Cap (10.1)
Water/C2 type extinguisher 9 Ltr Cap (10.2)
CO2 4.5kg capacity (10.3)
SITC of 1KVA UPS with 2 hour backup on line ( Elnova / Microtek) (11)
SITC of fault isolator/base to check short circuit every 20 Deductors (12)
Insat Techno Services
Hytek Turnkey Projects Pvt. Ltd.
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .