| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance CC 1 BOOTH NO 8 JANTA BHAWAN ROAD SIRSA SIRSA HARYANA 125055 | SIRSA | HARYANA | 125055 | Admitted-Finance |
| 2 | Admitted-Finance WARD NO 01 PUNJABI COLONY GADARPUR U S NAGAR | LUDHIANA | PUNJAB | 141001 | Admitted-Finance |
| 3 | Admitted-Finance WARD NO 4 SUNHERI KICHHA RUDRAPUR | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹75,000
Closing Date
18 Apr 2022, 3:00 pmClosed
Superintending Engineer
Electricity Distribution Circle Rudrapur
Replacement of conductor ACSR Weasel to ACSR dog in 11 KV Fauzi Matkota Feeder from 33/11 KV S/s Danpur under EDD Rudrapur-II
2022_UPCL3_42352_1
EDC(USN)67/2021-22
Open Tender
Electrical Works
Item Rate
90 days
Rudrapur
Please refer tender documents
3 documents required · 3 mandatory
₹1,180
SE EDC Rudrapur
₹75,000
29 Apr 2022
26 Mar 2022
19 Apr 2022
26 Mar 2022
18 Apr 2022
26 Mar 2022
Amount
Annexure -A ( Works )
Cartage of the ST Pole SP-55, 11 Mtr. long by private truck from Store Centre Rudrapur to work site dump store, including loading and unloading.
Cartage of the P.C.C.Pole 8.5 Mtr. long by private truck from Store Centre Rudrapur to work site dump store, including loading and unloading.
Cartage of the Other small materail by private truck from Store Centre Rudrapur to work site dump store, including loading and unloading.
Errection of Single Pole Structure of ST Pole SP-55 support after digging of pit size 0.60x0.6x1/6 length of support on 300x300x75mm. Stoune pad including fixing of 11KV. Pin insulator & Grouting of pole in CC Ratio 1:4:8 in size ( Height 0.45& 0.45 round ) Above ground level including fixing of all accessories as per direction of Engineer In Charge.
Errection of Double Pole Structure of ST Pole SP-55 support after digging of pit size 0.60x0.6x1/6 length of support on 300x300x75mm. Stoune pad including fixing of 11KV. Pin insulator & Grouting of pole in CC Ratio 1:4:8 in size ( Height 0.45& 0.45 round ) Above ground level including fixing of all accessories as per direction of Engineer In Charge.
Errection of P.C,.C. Pole 8.5 Mtr. long inclding frixing of all accessories in 11KV. Line as per UPCL, norms as per direction of Engineer In Charge.
Dismantling of Old ACSR Weasel conductor from existing 11KV. Line is section wise including Re-Rolling of conductor shifting of material at one collection for cass cartage including unloading & maeking and back cartage scrap. From site work to JE Store.
Replacement of damage 11KV. X-arm as per direction of Engineer-In-Charge.
Laying and stringing of 11KV. Line 23Km. On ACSR Dog conductor and including fixing lf all accessories and providing proper straightning, sagging and binding on insulator & jumpering etgc complete work as per direction of Engineer- In-Charge.
Febrication of M.S. Channel/Angle.
Febrication and fixing of 11KV. X-arm.
Fixing of M.S. Earth Rod 20x2500mm. For Earthing of support as per RESPO drawing No. RES-12 including earth rod 2.5mm. Deep below ground level connected to support with Earth wire fixing of bolts and nuts.
Fixing of Stay Set complete as per RESPO drawing No. RES-16 with stay rod 16x1600mm. Stay wire 7/8SWG stay set, wire clamps, Nut & bolts abnd fixing of stay clamps of suitable including excavation of earth and grouting of stay in pit with CC 1:4:8 in bottom of pit size 0.60x0.60x0.60 Mtr. including cost of cement, sand stone ballast etc andback filling complete inall respect with all other item T&P etc. as per direction of Engineer In Charge.
Fixing the Guarding for protection of Road/Telephone lines/H.T. lines as per RESPO drawing No. RES-48 at crossing location consisting of guarding channel in size 100x50mm. And fixing of G.I. Wire including fixing with all accessories complete work.
Restreightening of tilted pole as per direction of Engineer -In-Charge.
Lopping and Chopping of Tree Branches near by line.
Annexure - B ( Supply )
Supply of M.S. Stay clamp for ST Pole,SP-55 & P.C.C. Pole made of M.S. Flat for size 50x6sq,mm. duly red oxide painted with suitable size with fitted Nuts and bolts and washer as per specification of UPCL.
Supply of M.S. X-arm holding clamp for ST Pole,SP-55 & P.C.C. Pole made of M.S. Flat for size 50x6sq,mm. duly red oxide painted with suitable size with fitted Nuts and bolts and washer as per specification of UPCL.
Supply of M.S. L.T. clamp for ST Pole,SP-55 & P.C.C. Pole made of M.S. Flat for size 50x6sq,mm. duly red oxide painted with suitable size with fitted Nuts and bolts and washer as per specification of UPCL. For 11KV. Top wire.
Supply of M.S. Earth clamp for ST Pole,SP-55 & P.C.C. Pole made of M.S. Flat for size 50x6sq,mm. duly red oxide painted with suitable size with fitted Nuts and bolts and washer as per specification of UPCL.
Supply of M.S.Double pole bracing clamps for ST Pole,SP-55 & P.C.C. Pole made of M.S. Flat for size 50x6sq,mm. duly red oxide painted with suitable size with fitted Nuts and bolts and washer as per specification of UPCL.
Supply of P.G.Clamps Dog to Dog conductor as per UPCL specification New double pole 15x12PG-180+Extra 240PG.
Supply of M.S. Nut& Bolts off size.
Supply of Eye Bolt size 100x16mm.
HIMALAYA BUILDCON
M/s JAY ELECTRCIALS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .