| Sl No | Description | Qty | Unit | BHATTACHARYYA ENTERPRISE L3 | SRIDAM MONDAL L2 | R.T.ELECTRICALS L1 |
|---|---|---|---|---|---|---|
| 1.00 | Technical Specification for 20 KVA UPS 3phase input
&
3 phase out put on line UPS systems [Make: Switching AVO,POWER ONE, NUMERIC] | 1 | Unit | 7,50,000 ₹7,50,000 | 6,75,000 ₹6,75,000 | 6,07,000 ₹6,07,000 Lowest |
| 1.01Topology, IGBT BASED DSP CONTROLED | ||||||
| 1.02Rating of UPS(KVA/KW): 20 KVA / 16 KW (Make: Switching AVO,Legrand,Emerson,Schneider,PowerOne) | ||||||
| 1.03Input Voltage: 310----400----415 VAC 165-288 Volt /Phase(selectble) | ||||||
| 1.04Input Frequency: 45 to 65 Hz | ||||||
| 1.05Isolation Transformer: Inbuilt Isolation Transformer with 1:1 ratio at UPS Input to be provided at output | ||||||
| 1.06Back feed Protection: UPS should have back feed protection | ||||||
| 1.07Charging: Autometic float cum Boots Charging Capability with setteble flote & boost charging voltages and current levels and boots charger timer | ||||||
| 1.08Output Voltage: 230 VAC | ||||||
| 1.09Output Voltage Regulation: Static Variation +/_ 1% and Dynamic variation +/-3% | ||||||
Tender Value
Refer Docs
EMD Value
₹12,150
Closing Date
24 Jan 2026, 12:00 pmClosed
Executive Engineer,PWD
O/o The Executive Engineer Murshidabad Electrical Division P.W.Dte. 184, C.R.Das Road, Berhampore, Murshidabad, PIN-742101
Electrical Installation work of proposed extended OT Complex of Murshidabad Medical College and Hospital, Murshidabad - SITC OF UPS.
2026_WBPWD_989190_1
WBPWD/EE/MsdED/46/e-Q of 25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
20 days
Murshidabad
Please refer Tender documents.
5 documents required · 5 mandatory
₹12,150
13 Mar 2026
15 Jan 2026
26 Jan 2026
15 Jan 2026
24 Jan 2026
17 Jan 2026
Technical Specification for 20 KVA UPS 3phase input & 3 phase out put on line UPS systems [Make: Switching AVO,POWER ONE, NUMERIC]
Topology, IGBT BASED DSP CONTROLED
Rating of UPS(KVA/KW): 20 KVA / 16 KW (Make: Switching AVO,Legrand,Emerson,Schneider,PowerOne)
Input Frequency: 45 to 65 Hz
Isolation Transformer: Inbuilt Isolation Transformer with 1:1 ratio at UPS Input to be provided at output
Back feed Protection: UPS should have back feed protection
Charging: Autometic float cum Boots Charging Capability with setteble flote & boost charging voltages and current levels and boots charger timer
Output Voltage: 230 VAC
Output Voltage Regulation: Static Variation +/_ 1% and Dynamic variation +/-3%
Output Frequency: 50 Hz +/- 0.1%
Output Power Factor: 0.8
Crest Factor: 3:1
THDu: < 2% (linear load), < 5%(non linear load)
Waveform: Pure Sine Wave
Birdge: Microprocessor based and IGBT Technology
Overload: 110% for 60 minutes, 125% for 10 minutes, 150% for 30 sec
Static By Pass: 100 % rated static switches with fuse protection overload on Bypass: 100% for 10 ms
Overall Efficiency: 92%
Battary Rack: With power coated MS angle with suiteble dimention and gadge.Useing Nyvin cable with proper rating for interlink cables and battery input and necessary acessiress.
Battery : 12 V, Mono Block batteries. SMF VRLA
DC Bus : Minimum 192V or above, 30 mim back up required () Battery. Capacity-042AH (Battery Make: Exide/Amar Raja(Quanta)
Protection: Multi Protection-Over Temperature Protection with 8 Sensors, Overload, Battery Under Voltage, Fan Failures ,Short Circuit. Four Circuit Breakers, Providing Full Protection When Fault, Strong Overload Capability. Surge Protector at Panel Input & EB Input. PV Reverse Polarity, Input Low & High Voltage, Output Low & High Voltage cut off. Glass cartridge Fuse on Control Circuits MCB at Input Panel,
Audio Alarm, Mains Fail, Battery Low Pre-alarm, Inverter Trip
Metering: Graphical LCD display for Input & Output - Voltage, Current & Frequency, Battery - Voltage & Current
Indications: Mains - On / Fail / High / Low / Single Phasing DC - On / High, Battery - Low Pre-alarm / Low Trip Inverter - On / Trip / High / Low / Over Current
Switchgear: MCB / MCCB for Input, Battery, Output & Manual Bypass Switch
Termination: Input, Battery, Output & Bypass
Enclosure: IP 20
Operating Temp: 0 to 40 Deg C
Humidity: Upto 95% Rh (non-condensing)
Cooling: Forced Air
Noise: < 55 dB
Cold Start : Provided
CE Certification:IEC/EN 62040-1-1,IEC/EN50091-1,IEC/EN 60950 (Safety) IEC/EN 50091-2, IEC/EN 62040-2(EMC Emmission),IEC/EN 62040-3(performance & Design)IEC/EN 61000-4(EMC Emmunity) & IEC/EN 60146 (Design & Manufacture)
ISO 9001: 2015, ISO 14001: 2015, ISO 45001:2018,ISO 50001;2018 , ISO:20000-1:2011,ISO:27001:2013, ROHS
Warranty:Two Year on UPS & two yers on batteries on site against any Manufacturing defects
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.42 MB
Tendernotice_2.pdf
PDF • 0.55 MB
BOQ_2416766.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .