Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹29.8 LAccepted-AOC NO 10 71 VELLALAR STREET PANCHATCHARAM NAGAR CHINNAPANICHERY BHARANIPUTHUR CHENNAI 600 122 | CHENNAI | KANCHIPURAM | TAMIL NADU | 600122 | ₹29.8 L | L1 | Accepted-AOC L1 Tenderer |
| 2 | L2₹33.0 LRejected-AOC NO 01 ARCOT ROAD REMI COMPOUND AZHWARTHIRUNAGAR CHENNAI 600087 | CHENNAI | CHENNAI | TAMIL NADU | 600087 | ₹33.0 L | L2 | Rejected-AOC Rejection due to L2 bidder |
| Sl No | Description | Qty | Unit | SHRI MEENATCHI ENGINEERING L2 | SAIBABA ENTERPRISES L1 |
|---|---|---|---|---|---|
| 1.00Labour charges for Dismantling with out using board crane the complete accessories of Power/Auto transformer such as header pipes,Cooler Bank radiators,H.V. & L.V. bushings, conservator tanks, bucholz relays, equalizing pipes, Cooler fans, Pumps etc. and Draining the oil to the required level as directed by Field Engineer. | |||||
| 1.01 | 10 MVA Power Transformer | 4 | each | 24,000 ₹96,000 | 18,000 ₹72,000 |
| 1.02 | 16 MVA Power Transformer | 1 | each | 26,352 ₹26,352 | 17,000 ₹17,000 |
| 2.00 | Labour charges for Pulling of Power/Auto transformer from plinth to safer side or vice versa as directed by the Field Engineer. | 2,100 | MT/Mtr | 31.2 ₹65,520 | 28 ₹58,800 |
| 3.00 | Labour charges for loading of Power /auto transformer with complete accessories including released oil, initial lead of 5 Metres as directed by the Field Engineer. | 260 | MT | 1,144 ₹3.0 L | 1,000 ₹2.6 L |
| 4.00Transporting of Power/Auto Transformer, main tank with core level oil/ N2 gas , wherever necessary including all accessories and released oil by Low bed trailer and lorry as directed by Field Engineer. | |||||
| 4.01 | From 31 Ton to 50 Ton, Upto 100 Kms | 4 | Flat rate | 99,360 ₹4.0 L | 95,000 ₹3.8 L |
| 4.02 | Beyond 100 Kms | 5,000 | Km/T | 4.8 ₹24,000 | 6 ₹30,000 |
| 5.00 | Labour charges for unloading of Power /auto transformer with complete accessories including released oil, initial lead of 5 Metres as directed by the Field Engineer. | 260 | MT | 1,144 ₹3.0 L | 1,000 ₹2.6 L |
| 6.00Labour charges for erection of Power/Auto Transformer with out using Board crane wherever applicable including gasket changing for H.V. & L.V. Bushings ,Radiator valve, Conservator Valve, equalizer Pipe Valve, Bucholz Valve, etc. as directed by Field Engineer (Gasket to be supplied by board) | |||||
Tender Value
Refer Docs
EMD Value
₹38,400
Closing Date
26 Feb 2026, 3:00 pmClosed
SE/GCC/TRICHY
O/O SE/GCC/Trichy, 110 KV Grid SS Campus, Trichy
Running contract for Dismantling, Pulling,Loading, Transporting, unloading, Erection, Cabling, termination, earthing, HOC, painting etc. of various Power Auto Transformers in respect of Trichy Division
2026_EB_655841_1
Spec No GCC077 MM061 2025-26
Open Tender
Electrical Works
365 days
Trichy
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
₹38,400
Yes
26 May 2026
12 Feb 2026
27 Feb 2026
12 Feb 2026
26 Feb 2026
12 Feb 2026
Labour charges for Dismantling with out using board crane the complete accessories of Power/Auto transformer such as header pipes,Cooler Bank radiators,H.V. & L.V. bushings, conservator tanks, bucholz relays, equalizing pipes, Cooler fans, Pumps etc. and Draining the oil to the required level as directed by Field Engineer.
10 MVA Power Transformer
16 MVA Power Transformer
Labour charges for Pulling of Power/Auto transformer from plinth to safer side or vice versa as directed by the Field Engineer.
Labour charges for loading of Power /auto transformer with complete accessories including released oil, initial lead of 5 Metres as directed by the Field Engineer.
Transporting of Power/Auto Transformer, main tank with core level oil/ N2 gas , wherever necessary including all accessories and released oil by Low bed trailer and lorry as directed by Field Engineer.
From 31 Ton to 50 Ton, Upto 100 Kms
Beyond 100 Kms
Labour charges for unloading of Power /auto transformer with complete accessories including released oil, initial lead of 5 Metres as directed by the Field Engineer.
Labour charges for erection of Power/Auto Transformer with out using Board crane wherever applicable including gasket changing for H.V. & L.V. Bushings ,Radiator valve, Conservator Valve, equalizer Pipe Valve, Bucholz Valve, etc. as directed by Field Engineer (Gasket to be supplied by board)
10 MVA Power Transformer
16 MVA Power Transformer
Labour charges for Hot oil Circulation of Transformer and OLTC under vacuum drying whenever applicable and maintain required level and circulation of oil till obtaining satisfactory results as directed by Field Engineer. The filter will be provided by contractor.
Charges for Hot Oil Circulation for New/Released used oil
Oil Filter Machine Rent, Maintenance, Transportation (To & Fro), Toll Charges and including all consumables.
Labour for the erection of required control cable ducts from power transformer to control room and in the transformer body as directed by the Field Engineer.
Upto 8 core cable
Above 8 core cable
Supply and glanding of all the control cable in transformer to RTCC, DM.Box, MBox, etc including removing of insulation of the control cable and providing suitable holes in the gland plate as directed by the field engineer.
Supply and Termination of cable core end dressed neatly including the cost of cable sockets , ferrules, sleeves, tags, ties,stropes etc. as per drawing directed by the field engineer. (No. of core ends in unit of 1000).
Supply of various steel materials confirming to ISS 2062 - Gr A including ,frieght,handling etc. at site for earthing with labour for fabrication and erection for earthing including labour, machinery consumables for the double earthing of neutral, main tank and other panel etc.as directed by the field engineer.
Labour charges for one finish coating of aluminium painting works with spray gun for transformer complete including T&P etc. and painting of valves, bushings with red, yellow, blue and black paint including cost of paint of reputed make company viz Asian, Berger etc., and Consumables as directed by the field engineer.
10 MVA to 25 MVA Power Transformer
Labour charges for Dismantling of busbar and Jumper connection of Power/Auto Transformer including disconnection of necessary wiring as directed by the Field Engineer.
75 MM (1 length)
Labour Charges for loading /unloading of power transformer oil barrel with new/ released oil from store to site or vice versa including crane hire charges as directed by the Field Engineer.
Labour Charges for loading /unloading of power transformer empty oil barrel from store to site or vice versa as directed by the Field Engineer.
Labour charges for draining of oil from main tank as directed by the Field Engineer.
Labour charges for Intial filling of oil under vacuum from spare tank / barrel to main tank as directed by the Field Engineer.
Labour for dismantling of Top Cover with gaskets including OLTC cover and Replacement of Top cover gaskets, OLTC gaskets, Radiator, Butterfly valve inner Gaskets and all other gaskets, which are not normally covered under dismantling and re-erection, gaskets changing and refitting of top cover and OLTC cover plate & all other dismantled accessories and complete tightening works as directed by the Field Engineer. All the required Gaskets of RC 70C grade and governed by IS 4253 to be supplied by Contractor.
10 MVA Power Transformer
16 MVA Power Transformer
Labour Charges for Overhauling of Power/Auto Transformer OLTC mechanism including Lifting of divertor switch, cleaning and replacing of defective spares and gaskets, consumables, crane hire charges etc. as directed by the Field Engineer. (Excluding the cost of replacement materials) The work can be carried out purely on the basis specially trained technician's service availed from the reputed companies.
10 MVA to 25 MVA ( 110 KV Class ) - Double Unit
Supply and erection of silica gel breather flange type including the cost of 4-6 mm blue mesh silica gel.
Labour charges for rewinding of cooling fan motors including cost of bearings, terminal blocks, terminal cover including testing of fan motors for healthiness and refixing the repaired motors in its place (ie) on radiators (if necessary) as directed by the Field Engineer.
25 MVA & above
Supply and erection of Neutral omega copper with copper M-42 Nut & washer of suitable length and diameter as per drawing and as directed by the field engineer.
Up to 16 MVA
Butterfly valve as per required size
Labour charges for Dismantling of RTCC, Cooler control panels including consumables of Power/Auto Transformer including disconnection of necessary wiring as directed by the Field Engineer.
Panel and wiring dismantling
Bushing CT's
HV CT's as per required ratio
LV CT's as per required ratio
GST (Mention percentage only)
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.03 MB
BOQ_786463.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid