Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.3 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹26.4 L+₹1.1 L (4.29%)Rejected-Finance | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹28.6 L+₹3.2 L (12.7%)Rejected-Finance FLAT NO 202 GANGOTRI PARADISE VINAYAKA NAGAR VUDA COLONY GAJUWAKA VISAKHAPATNAM 530 004 | VISAKHAPATANAM | ANDHRA PRADESH | 530004 | L3 | Rejected-Finance Not Being L1 | |
| 4 | L4₹29.6 L+₹4.3 L (16.9%)Rejected-Finance | L4 | Rejected-Finance Not Being L1 | |
| 5 | L5₹30.0 L+₹4.7 L (18.4%)Rejected-Finance | L5 | Rejected-Finance Not Being L1 |
Tender Value
₹32.2 L
EMD Value
₹64,400
Closing Date
12 Mar 2020, 6:00 pmClosed
GE I DM
GE I DM NAVAL DOCKYARD VISAKHAPATNAM 530014
REPAIR/ REPLACEMENT/MAINTENANCE OF LT CABLES , JOINTING KITS OF INTERCONNECTION DISTRIBUTION LT NETWORK, SWITCH GEARS AND LT CAPACITOR BANK AND ALLIED WORKS OF VARIOUS SUBSTATIONS AT NAVAL DOCKYARD VISAKHAPATNAM
2020_MES_327240_1
SSGE/8280/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
NAVAL DOCKYARD VISAKHAPATNAM
As per tender documents
7 documents required · 7 mandatory
₹500
GE I DM
₹64,400
Yes
6 May 2020
20 Feb 2020
16 Mar 2020
20 Feb 2020
12 Mar 2020
6 Mar 2020
Amount
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 M deep for taking out / laying cable and getting out in soft/loose soil complete all as specified and as directed.
All as per item No 1.00 above, but in hard /dense soil.
Returning, filling in soil including spreading, levelling, watering and well ramming in layers not exceeding 25 cm complete all as specified and as directed.
Removing excavated soil to a distance not exceeding 50M and depositing where directed at level not exceeding 1.5 m above starting point complete all as specified and as directed.
Material & labour for dry sand cushioning under ground cable provided in layer of 8 cm deep before laying the cable and 15cm after laying the cable complete all as specified and as directed. Note : Punned depth only shall be measured as per SSR provisions.
Supply and laying of sub class 'B' bricks, old size for cable protection complete all as specified and as directed.
Material & labour for filling the road / hard standings cut for laying cable with PCC 1:2:4, type B2, using 40 mm graded stone aggregate and finishing the surface even and smooth without using extra cement complete all as specified and as directed.
Taking out old unserviceable cable and supply, laying and connecting up through surface/wall/duct cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 400 sqmm 3.5 core complete all as specified and as directed.
All as per item No 8.00 above but size of 240 sqmm 3.5 core.
All as per item No 8.00 above but size of 185 sqmm 3.5 core.
All as per item No 8.00 above but size of 95 sqmm 3.5 core.
Taking down old unserviceable galvanised iron pipe and supply & lay new GI pipe of size 80 mm bore ISI marked light grade for cable protection in road crossing complete all as specified and as directed.
All as per Item No 12 above but 100 mm bore
Material & labour for jointing the heat shrinkable straight through joint for 1100 Volts grade aluminum conductor cables of 3 1/2 / 4 core 50-95 sq mm sizes after crimpling ferrules, testing and commissioning complete all as specified and as directed. Make : REPL / 3M
All as per item No 14.00 above but for 3 1/2 / 4 core 120-185 sq mm
All as per item No 14.00 above but for 3 1/2 / 4 core 225-300 sq mm
All as per item No 14.00 above but for 3 1/2 / 4 core 400-500 sq mm Note : Excavation and earth work wherever required shall be deemed to be included in the unit rate quoted.
Taking down unserviceable/burnt cable end termination by isolating power supply from transformer/LT panel disconnecting burnt/faulty cable from the bunch of cables in trenches/duct, removing cable loop and material and labour for making Re-rout, cable termination of 3 1/2 core armoured aluminium conductor cable of size 95 sqmm to 150 sqmm, 1100 volts with suitable size of cable glands, aluminium lugs duly crimpled and insulated with insulation tape (in different colours) duly replaced the rusted nuts, bolts and washers of nickel chromium plated with new ones and applying petroleum jelly, testing and commissioning complete all as specified and as directed.
Taking down unserviceable/burnt cable end termination by isolating power supply from transformer/LT panel disconnecting burnt/faulty cable from the bunch of cables in trenches/duct, removing cable loop and material and labour for making cable termination, Re-rout of 3 1/2 core armoured aluminium conductor cable of size 240 sqmm to 500 sqmm, 1100 volts with suitable size of cable glands, aluminium lugs duly crimpled and insulated with insulation tape (in different colours) duly replaced the rusted nuts, bolts and washers of nickel chromium plated with new ones and applying petroleum jelly, testing and commissioning complete all as specified and as directed.
Dismantling/taking out cable any size/grade from trenches for finding of fault/rerouting and relaying complete with sand and brick protection to the original trench or diverted trench complete all as specified and as directed. Note :- Excavation & earth work, bricks/GI pipe for cable, protection and sand cushioning shall be measured and paid for separately.
Supply & fix Air circuit Breaker (ACB) 4 pole 415 volt, with thermal magnetic release mannual draout type of capacity 1600 Amps 50, KA complete all as specified and as directed including taking out old one. Make- L&T Cat no MDO SL96044 / schneider/Indo Asian)
All as per item No 21.00 above but capacity of 1250 Amps. Make- L&T Cat no MDO SL96042 / Schneider/Indo Asian)
Supply, install, test and commissioning MCCB with fixed thermal maganetic relase for 415 V, 50 Hz AC supply of 400 Amp, 4 pole 36 KA rated capacity by taking out old unserviceable MCCB's complete all as specified and directed. Make : Make : Indo Asian /L&T/ABB
Supply, install, test and commissioning MCCB with fixed thermal maganetic relase for 415 V, 50 Hz AC supply of 250 Amp, 4 pole ,25 KA rated capacity by taking out old unserviceable MCCB's complete all as specified and as directed. Make : Indo Asian /L&T/ABB
Taking down old unserviceable battery charger from the battery bank, supply, fix and testing new DC battery charger of capacity 200 AH, 110 volts, 30 Amps FCBD with DCBD suitable for 110V , 200 AH, (VRLA) battery complete all as specified and as directed.
Disconnecting and taking down old damaged lead acid batteries from various sub-stations and supply & fix new maintenance free (VALA) 24 volts, 200AH batteris united/fixed together with copper strips by series connection to make a battry bank of 110 V with initial charging and commissioning complete all as specified and directed. Make Amara Raja only Note :- Unit rate quoted shall be deemed to be included for providing necessary battery connection links and contro wiring from charger to HT panels.
Servicing, repair, maintenance of Air circuit breaker 400 Amps to 1600 Amps capacity by drawing out movable unit, forced air cleaning of movable and fixed unit , decarbonize breaker contacts and checking for any defects due to any flush/ loose contact, cleaning of all fixed and moving contact point, terminal connection points with CTC, replacement of defective parts and re-fixing ACB, cables complete all as specified and as directed. Note: (a) Required male/female ACB contacts, trip coils, closing coils, electronic protection unit will be measured as supply only. (b) All cleaning agents are included in the quoted rate
Supply only fixed contact of ACB 630A to 150A complete all as specified and as directed.
Supply only moving contract of ACB 630A to 150A complete all as specified and as directed.
Supply only electronic protection unit of ACB 630A to 1250A complete all as specified and as directed.
Supply only shunt trip coil ACB 630A to 1250A complete all as specified and as directed.
Supply only closing coil ACB 630A to 1250A complete all as specified and as directed.
Supply only switch disconnector fuse unit, TPN, open execution, bolted fuse link, 415V, conforming to IS/IEC 60947-3, telescopic shaft for depth adjustment terminal shrouds on both side, door interlock facility of current rating 100 amps including bolted HRC fuse-03 Nos complete all as specified and as directed. Make:- L&T cat No FN 100 TPN SK95568 & hrc FUSE -ST30768
All as per item No 33.00 above but capacity of 200 Amps. Make:- L&T cat No FN 200 TPN SK95418 & hrc FUSE -ST30779
All as per item No 33.00 above but capacity of 250 Amps. Make:- L&T cat No FN 250 TPN SK95642 & hrc FUSE -ST30781
All as per item No 33.00 above but capacity of 400 Amps. Make:- L&T cat No FN 400 TPN SK95481 & hrc FUSE -ST30784
All as per item No 34.00 above but capacity of 630 Amps. Make:- L&T cat No FN 630 TPN SK95521 & hrc FUSE -ST30787
Supply & fix flood light fitting LED 150 watt including taking down unserviceable one complete all as specified and as directed. Make:- CG, Model-LSTP-150-CDL-M or equivalent in Havells/ Bajaj/ Philips/Wipro
Supply & fix flood light fitting LED 200 watt including dismantling taking down unserviceable one complete all as specified and as directed. Make :- Bajaj, model No BARFEG 200W LED or equivalent in Havells/ Philips/Wipro/CG
Supply & fix flood light fitting LED 250 watt including dismantling taking down unserviceable one complete all as specified and as directed. Make:- CG, model No LSFO-250-CDL-M or equivalent in Havells/ Bajaj/Philips/Wipro/CG
Material & labour for taking out cables 25 sqmm to 35 sqmm from trench, for making straight through joints at damaged portion and relaying to trench complete all as specified and as directed. Note: Earth work, sand & Brick protection shall be measured and paid separately. Heat shrink straight through cable joints is included in quoted rate.
Material & labour for taking out cables 70 sqmm to 150 sqmm from trench for making straight through joints at damaged portion and relaying to trench complete all as specified and as directed. Note: Earth work, sand & Brick protection shall be measured and paid separately. Heat shrink straight through cable joints is included in the quoted rate )
Material & labour for taking out cables 185 sqmm to 400 sqmm from trench for making straight through joints at damaged portion and relaying to trench complete all as specified and as directed. Note: Earth work, sand & Brick protection shall be measured and paid separately. Heat shrink straight through cable joints is included in the quoted rate )
Supply,lay and connecting up earth coninuity galvanised iron strip 25 X 4 mm complete all as specified and as directed including taking out old one.
Supply,lay and connecting up earth coninuity galvanised iron strip 32 X 6 mm complete all as specified and as directed including taking out old one.
Servicing, repair, maintinance of APFC panel of any capacity, checking the capacitor bank, cleaning, in out loose connection, contact, defective capacitor, control wiring, relays, indication meter and replace the defective capacitor/ contactor, APFC controller, Relays indicator lamps, meter and connect all connection in fuctional position complete all as specified and as directed. Note :- Spares shall be measured and paid separately
Supply only cylindrical type series LTCCU Ultra Heavy duty Capacitor 5 to 15 KVAR complete all as specified and as directed.
Supply only Box type series LTBCU Ultra Heavy duty Capacitor 5 to 15 KVAR complete all as specified and as directed.
Supply only capacitor heavy duty Contactor complete all as specified and as directed. Make:- L&T Cat No CS96127
Supply only APFC controller complete all as specified and as directed. Make:- L&T Cat No CS908840000)
CHINNI ELECTRICAL ENGINEERING WORKS
RAVITEJA ENGINEERING WORKS
sri sai ram constructions
CHAVA CONSTRUCTIONS AND ELECTRICAL PROJECTS
SRI VIJAYA LAKSHMI ENTERPRISES
M V R ENGINEERING WORKS
ANUJ INFRA
HARSHITHA INFRA
bhavani constructions
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .