Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.0 LAccepted-AOC | L1 | Accepted-AOC Lowest |
Tender Value
Refer Docs
EMD Value
₹5,282
Closing Date
9 Aug 2024, 3:00 pmClosed
Assistant Executive Engineer
Office of the Assistant Executive, Electrical wing irrigation Sub division Aluva
GENERAL AMC 2023 24 Maintenance of various LI Schemes in Parakkadavu Area area under Electrical L I Section Aluva. General Electrical Work
2024_Irrig_663492_25
PWD/BLDG/ALY/15261/2023-2024
Open Tender
Electrical Works
Item Rate
180 days
Parakkadav
Please refer Tender documents.
10 documents required · 10 mandatory
₹555
₹5,282
18 Nov 2024
30 Jul 2024
12 Aug 2024
30 Jul 2024
9 Aug 2024
30 Jul 2024
Amount
Lifting
OD204270/2023-2024: Lifting the 3HP motor after disconnecting the wire connection, decoupling the pump, detaching from the base plate, starters, TP switches etc. and placing them conveniently on the platform.
OD204272/2023-2024: Lifting the 5 HP motor after disconnecting the wire connection, decoupling the pump, detaching from the base plate, starters, TP switches etc. and placing them conveniently on the platform.
OD204264/2023-2024: Lifting the 15 HP motor after disconnecting the wire connection, decoupling the pump, detaching from the base plate, starters, TP switches etc. and placing them conveniently on the platform.
OD204265/2023-2024: Lifting the 20 HP motor after disconnecting the wire connection, decoupling the pump, detaching from the base plate, starters, TP switches etc. and placing them conveniently on the platform.
OD204271/2023-2024: Lifting the 30 HP motor after disconnecting the wire connection, decoupling the pump, detaching from the base plate, starters, TP switches etc. and placing them conveniently on the platform.
OD204269/2023-2024: Lifting the 40 HP motor after disconnecting the wire connection, decoupling the pump, detaching from the base plate, starters, TP switches etc. and placing them conveniently on the platform.
OD204268/2023-2024: Lifting the 60 HP motor after disconnecting the wire connection, decoupling the pump, detaching from the base plate, starters, TP switches etc. and placing them conveniently on the platform.
OD204267/2023-2024: Lifting the 75 HP motor after disconnecting the wire connection, decoupling the pump, detaching from the base plate, starters, TP switches etc. and placing them conveniently on the platform.
OD204266/2023-2024: Lifting the 100 HP motor after disconnecting the wire connection, decoupling the pump, detaching from the base plate, starters, TP switches etc. and placing them conveniently on the platform.
Lowering/Refitting
OD204315/2023-2024: Lowering down and erecting upto 3HP motor/vacuum motor pump set and erecting the motor on the base plate in position giving connections checking correct alignment and trial run on full load
OD204314/2023-2024: Lowering down and erecting 5HP motor and erecting the motor on the base plate coupling with pump in position giving connections checking correct alignment and trial run on full load
OD204313/2023-2024:Lowering down and erecting 15 HP motor, starter and other electrical accessories,( Accessories when necessary ) and erecting the motor on the base plate coupling with pump, erecting the starter regulator TP switch etc in position giving connections checking correct alignment and trial run on full load
OD204312/2023-2024:Lowering down and erecting 20 HP motor, starter and other electrical accessories,( Accessories when necessary ) and erecting the motor on the base plate coupling with pump, erecting the starter regulator TP switch etc in position giving connections checking correct alignment and trial run on full load
OD204311/2023-2024:Lowering down and erecting 30 HP motor, starter and other electrical accessories,( Accessories when necessary ) and erecting the motor on the base plate coupling with pump, erecting the starter regulator TP switch etc in position giving connections checking correct alignment and trial run on full load
OD204309/2023-2024:Lowering down and erecting 40 HP motor, starter and other electrical accessories,( Accessories when necessary ) and erecting the motor on the base plate coupling with pump, erecting the starter regulator TP switch etc in position giving connections checking correct alignment and trial run on full load
OD204308/2023-2024:Lowering down and erecting 60 HP motor, starter and other electrical accessories,( Accessories when necessary ) and erecting the motor on the base plate coupling with pump, erecting the starter regulator TP switch etc in position giving connections checking correct alignment and trial run on full load
OD204307/2023-2024:Lowering down and erecting 75 HP motor, starter and other electrical accessories,( Accessories when necessary ) and erecting the motor on the base plate coupling with pump, erecting the starter regulator TP switch etc in position giving connections checking correct alignment and trial run on full load
OD204306/2023-2024:Lowering down and erecting 100 HP motor, starter and other electrical accessories,( Accessories when necessary ) and erecting the motor on the base plate coupling with pump, erecting the starter regulator TP switch etc in position giving connections checking correct alignment and trial run on full load
other maintenance works
90.14.24.1:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.1 KVAr, 3 phase, 440 V, delta connected Metalised Poly Propylene Capacitor, Cylinderical Type, suitable for direct connection to motors.
2.2.2:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.125 Amp,16 KA,TPMCCB
90.14.11.14:MCCB AccessoriesSupply and fixing rotary handle, Direct type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
OD228551/2023-2024:Supply and fixing Spreader/Terminal adapter Kit Extended terminal for 4 pole MCCB of rating upto 200 A & 250 A (8 pcs)
OD215704/2023-2024:Supply and installation of dust and vermin proof wall mounting , sintex make meter box of size 700X480X210 mm GSMB 7450 ( IP65 ) or equivalent suitable for fixing KSEB meter,fuse units,CT etc hinged door construction ,double door,for the front side with compartments if necessary,providing vision panel for the meter compartment knock out for cable entry as required including fixing it ,making good the damages etc. as required.
OD215717/2023-2024:Supply and fitting Digital multifunction meter to read VA,PF,KW,KWh, accuracy class-1 LCD
OD228668/2023-2024:Supply,fixing and installation of CURRENT TRANSFORMER -100/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT
OD228669/2023-2024:CURRENT TRANSFORMER - 200/5 A, 5 VA, accuracy class 1, Resin cast Metering CT
90.14.24.2:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.2 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Capacitor, Cylinderical Type, suitable for direct connection to motors.
90.14.24.9:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.12.5 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Cylinderical Type Capacitor suitable for direct connection to motors.
90.14.24.10:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.15 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Cylinderical Type Capacitor, suitable for direct connection to motors.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
OD215794/2023-2024:Supply and providing 95 sq mm FRLS PVC insulated and sheathed single core flexible copper conductor cable
OD224349/2023-2024:supply, installation testing and commissioning of the coupling pulley suitable for 20 HP squirrel cage induction motor in the Erayankudy L I Scheme
90.12.5.23:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3 core 185 sq mm
90.12.7.23:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 185 sq mm
OD245783/2023-2024:Supply and providing 90/75mm DWC pipe as required
90.12.1.34:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 185 sq mm
9.1.27:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
9.2.24:Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 185 sq. mm
Bidder Name
FRANCIS PINHERO
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1062711.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .