Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.8 LAccepted-AOC 121004 | L1 | Accepted-AOC being L1 | |
| 2 | L2₹7.0 L+₹3,296.46 (0.47%)Rejected-AOC JJ BHAVAN TC 10 1378 2 GN 31 CHENCHERY ROAD NALACHIRA PO TRIVANDRUM 695 015 | TRIVANDRUM | THIRUVANANTHAPURAM | KERALA | 695015 | L2 | Rejected-AOC being L2 | |
| 3 | L3₹7.3 L+₹30,923 (4.45%)Rejected-AOC DOOR NO IV 400 NEAR RAMANTHALI GHSS RAMANTHALI PO KANNUR 670308 | KANNUR | KERALA | 670308 | L3 | Rejected-AOC being L3 |
Tender Value
Refer Docs
EMD Value
₹15,000
Closing Date
17 Jan 2022, 6:00 pmClosed
AGE (I) Cannanore
AGE (I) Cannanore HQ Hospital Kannur PO Kannur
Repairs/replacement of LT panels, MCCBs, LT UG cable and misc works at Mily Station Calicut under AGE (I) CANNANORE.
2021_MES_494614_1
8164
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Cannanore
Class E category b (i)
8 documents required · 8 mandatory
₹500
Yes
AGE (I) Cannanore
₹15,000
Yes
16 Feb 2022
14 Dec 2021
22 Jan 2022
15 Dec 2021
17 Jan 2022
28 Dec 2021
15 Dec 2021 - 21 Dec 2021
Amount
Excavating in trenches n.exc. 1.5m wide and n.exc. 1.5m in depth for laying of LT UG cable, pipe, pole, stay etc and n exc 10sqm on plan and getting out in any type of soil including taking out and removal of old bricks laid over for protection of cable all as specified and directed.
Excavating in trenches n.exc. 1.5m wide and exc 1.5m and n.exc. 3m in depth for laying of LT UG cable, pipe, pole, stay etc and n exc 10sqm on plan and getting out in soft disintegerated rock including taking out and removal of old bricks laid over for protection of cable all as specified and directed.
Returning and filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick with soil obtained from excavation all as directed
Removing excavated materials (soil) to a distance n exceeding 50m and depositing where directed at a level 1.5m above starting point all as specified and directed.
Supply and spreading in natuaral riddled soil as earth cushioning to cable by using IS sieve to separate the composite particle/roots etc and refilling in trenches and compacted in layers to form a solid bed covering to cable all as specified and directed.
Supply and laying in trenches burnt brick sub class B of old size for protection of UG cable laid flat and dry over the cable , perpendicular to the direction of cable all as specified and directed.
Laying only old bricks obtained from item No 1 here in before in trenches for protection of UG cable all as specified and directed.
M&L for GI tubing, 40mm bore light grade, galvanized, with all fittings required such as bends, Tees, elbows, sockets, fixing clamps etc for protection of cable/GI strip in road crossing/fixing on ploe, wall etc including removing old unserviceable pipe any size all as directed. Note : Excavation shall be measured and paid seperately.
All as above item No 8 but 80mm bore light grade, GI tubing etc all as directed. Note : Excavation shall be measured and paid seperately.
Taking out unserviceable UG PVC insulated cable, armoured or un armoured any size from trenches/GI tubing/on pole/on wall etc all as directed.
Supply and lay including fixing and connecting electrically and testing LT underground cable, XLPE insulated, , armoured heavy duty electric cable with aluminum conductor multi-stranded 1100 volts grade, laid in trench, fixed on wall/pole drawn through pipe etc including provision of lugs & testing of following sizes complete all as specified and directed. (a) 3.5 core 25 sqmm Note : Excavation shall be measured and paid seperately. Quoted rate include of making connection to LT panel/feeder pillar box/junction box through suitable size aluminium lugs and cable glands.
All as per item No 11 here in before but 3.5 core 50 sqmm all as specified and directed.
All as per item No 11 here in before but 3.5 core 70 sqmm all as specified and directed.
All as per item No 11 here in before but 3.5 core 95 sqmm all as specified and directed.
All as per item No 11 here in before but 3.5 core 150 sqmm all as specified and directed.
M & L for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate for concrete as in foundation for pole and stay including use and waste of form work all as specified and directed.
M & L for PCC 1:3:6 type C-1 using 20 mm graded stone aggregate for concrete as in pole coping including use and waste of form work all as specified and directed.
Dismantling old and unserviceable pre stressed concrete /Steel poles any type and height including breaking cement concrete complete, Material and erection of Prestressed concrete pole, 9.0 metres long, 102mm x 152mm at top and 102mm x 289mm at bottom, class 10 complete all as specified and directed by engr-in charge. Note - Excavation shall be measured and paid seperately.
Supply and fixing MCCB , 4 pole, 250 Amps, adjustable type, rupturing capacity 36 KA, 415 Volts with Thermal - Magnetic Release of Make L&T Cat No : CM92109OOP1OG, Type - DN2-250D or equivallent in Schneider/ABB/Havells elctrically connecting up including taking down/removing of U/s MCCB from existing LT panel after disconnecting electric connetion complete all as specified.
Supply and fixing MCCB , 4 pole, 160 Amps, adjustable type, rupturing capacity 25 KA, 415 Volts with Thermal - Magnetic of Release make L&T Cat No : CM90642OOMO, Type - DN1-250C or equivallent in Schneider/ABB/Havells electrically connecting up including taking down/removing of U/s MCCB from existing LT panel after disconnecting electric connetion complete all as specified.
Supply and fixing MCCB , 4 pole, 125 Amps, adjustable type, rupturing capacity 25 KA, 415 Volts with Thermal - Magnetic Release make L&T Cat No : CM90642OOMO, Type - DN1-250C or equivallent in Schneider/ABB/Havells connecting up including taking down/removing of U/s MCCB from existing LT panel after disconnecting electric connetion complete all as specified.
Supply and fixing MCCB , 4 pole, 100 Amps, adjustable type, rupturing capacity 25 KA, 415 Volts with Thermal - Magnetic Release make L&T Cat No : CM90642OOLO, Type - DN0-100C or equivallent in Schneider/ABB connecting up including taking down/removing of U/s MCCB from existing LT panel after disconnecting electric connetion complete all as specified.
Supply and fixing MCB, TPN, 415 volt, 63 amps, C curve, including taking down/removing of U/s MCB from existing LT panel after disconnecting electric connetion complete all as specified.
S & F of Integral LED street light luminaires complete comprising of epoxy powder coated housing, enclosed with glass cover in front 60 Watts mounted on MCPCB suitable for 50mm dia pipe in gress protection IP-66 make : Bajaj BRTFG 60W or equiavalent in Phiips/ Crompton including taking down old street light fittings from existing from pole after disconnecting electric connetion complete all as specified.
Supply and replacing of 1100 volts grade heavy duty cable PVC insulated aluminium conductor as service connections served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 01 metre apart including 4 mm dia GI suspension wire one twin core cable flat or circular stranded conductor of size 10 sqmm 2 core complete all as specified and directed.
M&L for PVC weather proof junction boxes of size 250x200x100 mm with PVC connector heavy duty connector 4 way 16 amps one No SP MCB 6 amps and making necessary cable connection all as specified and directed.
M & L for Painting of concrete pole, by applying one coat of white paint after scraping / brushing and cleaning the Algae on pole and cross arms and a coat of white synthetic enamel painting to pole upto 1.5 mtr from ground level shall be painted by alternate layer of black and white enamel paint ( 30 cms apart) Pole Number shall be written on pole by black paint in yellow circle of 150mm dia. A coat of aluminium painting shall be done on Cross arm and bracing, nut, bolts and washers etc after prep of surfaces all as directed by Engr in charge.
Excavating in trenches n.exc. 1.5m wide and n.exc. 1.5m in depth for laying of LT UG cable, pipe, pole, stay etc and n exc 10sqm on plan and getting out in soft disintegerated rock including taking out and removal of old bricks laid over for protection of cable all as specified and directed.
JEETH CONSTRUCTION
Sreekrupa Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .