Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.5 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹8.6 L+₹2,668.46 (0.31%)Rejected-AOC PARUVAYAD W VIILITAITHUNAD ALUVA SRM 600017 | ERNAKULAM | KERALA | 680667 | L2 | Rejected-AOC L2 |
Tender Value
₹8.6 L
EMD Value
₹21,581
Closing Date
26 Dec 2024, 6:00 pmClosed
Assistant Engineer
O/o the Assistant Engineer, LIDEW, Piravom
S0196/25 SITC of DG in Ayurveda Dispensary under Piravom Municipality (RETENDER)
2024_LSGD_711709_2
ET7/AE/LIDEW/PVM/24-25_8
Open Tender
Electrical Works
Item Rate
15 days
Piravom
Please refer Tender documents.
9 documents required · 9 mandatory
₹1,905
₹21,581
27 Feb 2025
17 Dec 2024
28 Dec 2024
17 Dec 2024
26 Dec 2024
17 Dec 2024
Amount
SITC of DG and allied work
OD245203/2024-2025:SITC of 30 KVA, Three Phase 415V, 50 Hz, 0.8 pf liquid cooled Leypower RTU diesel generator for producing electricity with a 4- cylinder ASHOK LEYLAND CPCB 4 engine (model PI5G4DE30) developing 37 HP complete in all respects and supplied with LEYPOWER alternator and CPCB-approved acoustic enclosure, Standard control panel, battery, leads and a integrated fuel tank g. Fuel filter. h. Lubricating oil filter. i. Exhaust silencer. j. Exhaust Muffler k. Battery Charger/Generator "Engine Instrument Panel a. Starting switch with key or button" b. Lubricating oil pressure gauge. c. Water temperature gauge. d. RPM Indicator with hour meter. e. Battery charging ammeter. "Safety Controls for Engine a. Trip for low lubricating oil pressure." b. Trip for high water temperature. "Brushless Alternator a. Make - LS/KEL/Stamford/ LEYPOWER" b. Type - Self exited and self regulated. c. Capacity 30 KVA @ 0.8 PF d. System of Voltage -Three Phase, 415 V,50Hz e. Speed - 1500 rpm. f. Voltage regulation band - +/- 5% of rated voltage g. Frequency : 50 Hz h. Insulation - Class F / H The alternator should confirm to IS 4722 and warranteed for 3 years.Operation and service manual , spares and tools shall be provided. "Fuel Tank Suitable size built in type integrated with the acoustic enclosure with full tank Diesel" Fuel connection shall be done as per standards "Battery Suitable capacity fully charged battery with leads and terminals of appropriate AH capacity as per Manufactures requirement." 10. Supplying and providing Automatic Battery charger suitable for the 30 KVA DG set 11.Tools Kit Standard control panel including all necessary accessories and meters Accoustic enclosure: As per CPCB norms The DG set should have warranty of 3 years from the date of installation.
OD245118/2024-2025:Supply and provide wall mounting 125A 4pole ATS made out of 1.6 mm CRCA sheet , powder coted, 100A MCCB in both DG & EB side, 25x6mm Al. bus bar and 125A ATS commo out going metering and line indication both DG & EB side including internal wiring auto and manual options, etc as required.
OD368925/2023-2024:Unloading 30 KVA DG from the vehicle using mobile suitable size crane including fuel and crew, and kept in suitable safe position as directed by the officials.
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
OD368933/2023-2024:Supply and providing high speed diesel for trial run and the load test of 30kvA DG
90.12.5.1:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 4 sq mm
90.12.7.1:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 4 sq mm with factory made clamp
90.12.5.28:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 35 sq mm
90.12.7.28:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp
9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
90.12.10.4:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation77/63 mm or nearest size
OD368920/2023-2024:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required -2.50 cm, 4 cm or 5 cm height
OD368921/2023-2024:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
OD368922/2023-2024:Enameled Danger Notice Board of size 250 x 200 mm. with inscriptions ( both in English and Malayalam) and conventional Skull and Bone in Red colour.
OD368934/2023-2024:Supply and providing 5 Kg. Dry Chemical Powder type Fire Extinguisher with hose and clamps including fixing it to wall as required.
OD368935/2023-2024:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level. Thermo - Mechanically Treated bars of grade Fe-500D or more
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
14.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
OD368936/2023-2024:Copying charge of Electrical schematic diagram in A3 sheet
OD368937/2023-2024:Preparation of Electrical schematic diagram in A3 sheet and submitted at Electrical inspectorate.
OD368938/2023-2024:Supply and providing 2mm thick Elastomeric Fire retardent insulating mat as per IS.15652/2006 to with stand 3.3 KV die Electric strength
5.1:Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required.
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.1.5:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.16.5.5:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.75 mm (6 SWG)
OD369242/2023-2024:Supply and provide 25 x 6 mm brass nut 7bolt with washer
90.17.7.5:Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :65 mm dia
90.17.7.6:Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :80 mm dia
OD369270/2023-2024:Fabrication, supply & installation of dust and vermin proof, wall mounting, Sintex meter box of following size suitable for fixing KSEB meter, fuse units, CT etc, hinged door construction for the front side with compartments if necessary, providing vision panel for the meter compartment, knock out for cable entry and exit.- Sintex make GS MB 6535
OD369271/2023-2024:Supply and fixing the following accessories in the existing meter board and giving connections etc. 100 A, 415 V, 2 way neutral link mounted on DMC/ SMC base.
OD369272/2023-2024:Supply and fixing the following accessories in the existing meter board and giving connections etc. 100 A fuse unit with suitable rated & type fuse link
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
Rich Engineers (BID ID -2031953)
Bidder Name
K AND K ASSOCIATES
Rich Engineers
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1131527.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .