ARC work of Attend the cable fault at site within 03 HRS from receiving the message from D.E OF concern S/DN AND Locating the Fault underground Cable for ALL scheme in the jurisdiction of Sayan S/dn of KIM Division. Through outsourced agency for existing DGVCL Network for SDN under Kim Division.
320428
KIM/O&M/TECH/N-PROCURE/26-27/01/SR-46 DT:03-07-2026
Open
Electrical and Maintenance Works
Surat
5 documents required · 5 mandatory
3 Jul 2026
3 Jul 2026
3 Jul 2026
13 Jul 2026
3 Jul 2026
ARC work of Attend the cable fault at site within 03 HRS from receiving the message from D.E OF concern S/DN
AND Locating the Fault underground Cable for ALL scheme in the jurisdiction of Sayan S/dn of KIM Division.
Item Code No. Description Unit Rate Amount
Labour charge for excavation of cable trench of 400mm width x Meter
1200mm depth, in any type of soil for laying of cable of size up to
1 9925000001 240 mm2 (For additional cable 200 mm additional width shall be
considered i.e. half trench length is to be considered
Labour charge for excavation of cable trench of 600mm width x Meter
1200mm depth, in any type of soil for laying of cable of size up to
2 9925000002 240 mm2 (For additional cable 200 mm additional width shall be
considered i.e. half trench length is to be considered
Labour charge for excavation of cable trench of 400mm width x Meter
1500mm depth, in any type of soil for laying of cable of size up to
3 9925000003 240 mm2 (For additional cable 200 mm additional width shall be
considered i.e. half trench leng th is to be considered
Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to Meter
240 mm2 & preparation of sand layer 100mm thick, in the cable
trench & covering the cable with 150 mm dia (Outer), thickness
mm, 1.0 meter long RCC half round muffs and providing and fixing of
4inch width yellow colour polyethylene tape with printing"CAUTION
ELECTRIC CABLE BELOW' at 0.75 m depth from ground surface
after laying cable in trench. This will provide indication that electric
cable is passing underground so as to protect cable from mechanical
injuries, refilling the same, as per Instruction of E gineer in Charge
Labour charge for horizontal drilling using Auger machine without Meter
damage to surface road at max 2.0 mtrs depth & putting of
kg/cm2 , class-4,Green color, 110mm 0.D. 8.5mm thickness
H.D.P.E. pipe confirms to IS 4984-1987(3rd revision) and BIS
certification and laying of 11KV/22KV XLPE cable of size up to
5 9925000005 mm2 in HDPE pipe, as per Site Condition (excluding cost of pipe).
The detail map obtained from HDD machine and excel sheet hard
and soft copy) indicating the respective depth and distance from
adjacent landmark for each segment for HDD is must require to be
submitted. HDD to be carried out at depth 1.5 mtrs to 2.0 mtrs as per
site conditions and as er instruction of EIC.
File No: DGVCLDOKI/TND/e-file/6817/2026/3418/Technical
Approved By: Executive Engineer,Technical,DGVCLDOKI
Letter No: DGVCLDOKI/0062/07/2026 Approved Date: 03-07-2026 01:57
Labour charge for horizontal drilling manually without damage to Meter
surface road at max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-
4,Green color, 110mm O.D. , 8.5mm thickness H.D.P.E. pipe
confirms to IS 4984-1987(3rd revision) and BIS certification and
laying of 11KV/22KV XLPE cable of size up to 240 mm2 size, as per
Site Condition (excluding cost of pipe). The detail map and excel
sheet (hard and soft copy) indicating the respective depth and
distance from adjacent landmark for each segment of cable to be
submitted. Drilling to be carried out at depth Minimum 1.2 mtrs to
mtrs as per site conditions as per instruction of EIC.
Supply of 6.11kg/cm2 , class-4,Green color, 110mm O.D. , 8.5 mm Meter
7 9925000007 thickness H.D.P.E. pipe confirms to IS 4984 and BIS certification for
laying of underground 11KV/ 22KV XLPE cable up to 240 mm 2 size.
Labour work for RCC concreting on disputed location and repairing CMT
of damage portion of road crossing for the work carried out for roads
crossing as well as concreting & muffing of poles including all
Providing & fixing concrete stone route marker of 300 mm width x No
150 mm thick x 650 mm height embedded in earth at least 300 mm
below & 350 mm above ground level respectively at distance approx.
50 meters along the length of cable. The RCC concreting (1:2:4)(all
necessary materials will be in bidder's scope) of route marker is to
be carried out 300 mm width x 150 mm thick x 300 mm below
ground level as per instruction of EIC. The route marker should be
with name of company with approved yellow colour-DGVCL. The
distance from marker to cable and cable depth with feeder name
etc., marked with arrow sign is to be painted on it. The route marker
is to be fixed at location near to any fixed permanent location (not
necessary to fix exact on top of cable) as per instruction of EIC.
Labour charge for erecting of 11kV / 22 kV XLPE cable of size up to perJob
240 mm 2 on DP Structure with fixing of 02 Nos polymer cleats on
10 9925000014 top and middle part. Polymer cleats, nut bolts etc. fixing material to
be provided by contractor.
Providing & fixing of 6.11kg/cm2 , class4,Green color, 110mm O.D. perJob
8.5mm thickness H.D.P.E. pipe confirms to IS 4984 and BIS
certification on the erected DP structure for the mechanical
protection of cable by inserting the cable inside HDPE pipe. The
HDPE pipe shall be erected in such a way that 300mm shall be
below the ground level and the rest 2700 mm shall be supported on
the DP Structure with 01 No Polymer cleat. All materials including
polymer cleat and Nut bolt to be provided by contractor.
Providing and fixing of pipe type earthing from 80 mm dia class-B GI No
pipe with pit to be filled with salt & coke and construction of chamber
12 9925000016 as per DGVCL Drg. No. dg /100 for DP and cable. The earthing pit
should be joined with cable by G.I. strip of size 1" width & 2 mm
thick. All material GI pipe, Coke Salt etc will be supplied by bidder.
Supply & fixing of heat shrink type end terminations (outdoor) for up No
13 9925000017 to 11kV 3C x 185 mm2 size XLPE cable as per DGVCL technical
Supply & fixing of heat & shrinkable end terminations (outdoor) for up No
14 9925000018 to 22 kV 3C x 185 mm 2 size XLPE cable ( as per DGVCL technical
Supply & fixing of heat shrinkable type end terminations (indoor) for No
15 9925000019 up to 11kV 3C x 185 mm 2 size XLPE cable as per DGVCL technical
Supply & fixing of heat & shrinkable end terminations (indoor) for up No
16 9925000020 to 22 kV 3C x 185 mm 2 size XLPE cable as per DGVCL technical
File No: DGVCLDOKI/TND/e-file/6817/2026/3418/Technical
Approved By: Executive Engineer,Technical,DGVCLDOKI
Letter No: DGVCLDOKI/0062/07/2026 Approved Date: 03-07-2026 01:57
Supply & fixing of heat shrinkable straight through joint for up to No
17 9925000021 11kV 3C x 185 mm 2 size XLPE cables as per DGVCL technical
Supply & fixing of heat shrinkable straight through joint type for up to No
18 9925000022 22kV 3C x 185 mm 2 size XLPE cable as per DGVCL technical
Labour charge for excavation of 2100mm long x 1200mm wide x No
1200 mm deep joint pits for installation of 11kV / 22kV Straight
19 9925000023 through joints as per instruction of engineer-in-charge & covering the
cable with 150 mm dia (Outer), thickness 25 mm, 1.0 meter long
RCC half round muffs & refilling same as per instruction of EIC .
Providing and fixing of insulating bus bar, made from 11KV/22KV No
XLPE cable after removal of semi conducting layer and applying of
PVC heat shrinkable antitracking core insulating tubing (1.1KV), on
both end terminal using Aluminium long barrel heavy duty up to
20 9925000024 sq mm lugs, Aluminium bus connector. Taping with PGclamp for bus
conductor as per drawing and as per instruction of EIC. The
Allurninium lugs and PG clamp shall be covered with 11KV/22KV HT
insulating tapes.(11KV/22KV XLPE cable will be in scope of DGVCL
while all other materials will be in bidder's scope.
Testing of cable at various points and commissioning the feeder as No
21 9925000025 per instruction of engineer-in-charge.Test result shall be submitted
by contractor with bill.
Preparation and submission of 6 (six) copies, of complete layout Set
22 9925000026 drawings with GIS mapping as per actual cable routing showing road
crossing, HDPE pipe sleeving, jointing locations, markers etc.
To Attend the cable fault at site within 03 hrs from receiving the No
23 9925000047 message from D.E of concern S/dn and locating the fault under
TOTAL AMOUNT :-Twenty Four Lacs Only 24,00,000/-
TOTAL AMOUNT :-Twenty Four Lacs Only 24,00,000/-
Executive Engineer (O&M)
DGVCL, KIM IND DIVISION.
File No: DGVCLDOKI/TND/e-file/6817/2026/3418/Technical
Approved By: Executive Engineer,Technical,DGVCLDOKI
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
2.1 Sayan.pdf
2.2 N-procure.pdf
2.3 Sayan.pdf
2.4 Sayan.pdf
Schedule-B Sayan.pdf
Download all tender documents and submit your bid