| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.2 LAccepted-AOC HIMACHAL PRADESH HP | ₹9.2 L | L1 | Accepted-AOC L1 |
| 2 | L2₹10.0 L+₹72,936 (7.89%)Rejected-AOC | ₹10.0 L+₹72,936 (7.89%) | L2 | Rejected-AOC L2 |
| Sl No | Description | Qty | Unit | Kalap Engineers and Builders L1 | M/S SUKHMANI ENGINEERS L2 |
|---|---|---|---|---|---|
| 1.00Supply and laying XLPE insulated armoured cable (heavy duty) electric cable with aluminium stranded conductor 1100 volts grade of following size after taking down complete all as specified and directed by Engr-in-charge :- | |||||
| 1.10 | 10 Sqmm x 2 Core | 300 | RM | 165 ₹49,500 | 160 ₹48,000 Lowest |
| 1.20 | 16 Sqmm x 4 Core | 100 | RM | 291 ₹29,100 | 260 ₹26,000 Lowest |
| 1.30 | 35 sqmm x 3.5 core | 200 | RM | 485 ₹97,000 Lowest | 514 ₹1,02,800 |
| 1.40 | 50 Sqmm x 3.5 Core | 50 | RM | 667 ₹33,350 | 478 ₹23,900 Lowest |
| 1.50 | 70 Sqmm x 3.5 Core | 25 | RM | 880 ₹22,000 | 650 ₹16,250 Lowest |
| 1.60 | 95 Sqmm x 3.5 Core | 150 | RM | 1,158 ₹1,73,700 | 825 ₹1,23,750 Lowest |
| 2.00 | Supply, installing, testing and commissioning factory made LT panel ( 415 Volts, 50 Hz , 3-phase, 4 wire supply ) CPRI approved manufacturer, factory assembled Outdoor Feeder Pillar type, weather proof, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated Aluminium bus bars of 100 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, ingress protection class ( IP-65 ) and made of 3.15 mm thick CRCA mild steel sheet and mild steel, Angle iron frame work made out of 40 X 40 X 6 mm ), front and rear opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR wire of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035 embedded in ground with and including masonry in 1:4 CM of blocks of PCC 1:2:4 type B1 of block size 30x30x30 cm and rendering in CM 1:4 with comprising of the following:- | 1 | Each | 80,000 ₹80,000 | 66,786 ₹66,786 Lowest |
| 2.01BUS BAR CHAMBER :- (a) 100 Amps 3 Strips & Neutral Strip 50 Amps, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INCOMING SUPPLY :- (i) MCCB 63 Amps 16 KA 3 Pole with Fixed thermal & magnetic release 415 volts , 50Hz,=01 No., Make of MCCB:-L&T/ Schneider / HPL/ Havells. INSTRUMENT FEEDER :- (a) Digital Volt Meter, 96X96mm, flush type rated 0-500 V, with Volt meter selector switch- 01 Set. (b) Digital Amp Meter, 96X96mm, flush type rated 0-100 A, with Amp meter Selector switch- 01 Set. (c) C.T's 100/5 A CL 1.0 Tape Wound- 01 Set. (Set of three) (d) Red, Yellow, Green Phase indicating Lights LED type 220 V AC- 1 Set. (Set of three). (e) Protection MCB 6 A SP C Series- 1 Set. (Set of three). Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. | |||||
| 2.02OUTGOING SUPPLY :- (i) MCB SPN 32 Amps, 230 volts, 50Hz, rupturing capacity 10 KA C Curve = 3 Nos. Make of MCB:- L&T/ Schneider / HPL/ Havells. (ii) MCB TPN 32 Amps, 230 volts, 50Hz, rupturing capacity 10 KA C Curve = 3 Nos. Make of MCB:- L&T/ Schneider / HPL/ Havells. The panel manufacturer should have following Govt. Approved Certificates: 1. Panel should be according to IEC-61439. CPRI Certification Degree of Protection IP-54 (IS/IEC : 61439 (Part-1), 2011 & IS/IEC : 61439 (Part-2) 2011) 2. Tempreature Rise (IS/IEC : 61439-1, 2011 & IS/IEC : 61439-2 2011) 3. CPRI Short Circuit IEC-61439-1 & 2 withstand strenght should be 70kArms for 1.0 Sec with intial peak of 154kApk 4. CPRI Certification IEC-61439-1 & 2 Rated current for short circuit not less than 6300 A with rated insulation voltage 660V 5. ISO 9001 CERTIFIED Contractor will get the copy of above certificates from manufacturer and submit to Engineer-in-charge/AGE(I) before erection of panel on ground. | |||||
Tender Value
₹9.6 L
EMD Value
₹19,100
Closing Date
16 Jul 2026, 6:00 pmClosed
Sh K K Soni AE (Civ) AGE I R and D Manali
AGE I R AND D MANALI PIN 175103 PH 01902255014
REPAIR/MAINTENANCE OF LT PANELS, CABLE AND CONNECTED ITEMS AT HELIPAD AREA DGRE RDC MANALI AT AGE(I) RnD MANALI.
2026_MES_772005_1
AGE(I)/MNL-43/2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Manali
As per NIT and tender documents
5 documents required · 5 mandatory
₹500
AGE I R AND D MANALI
₹19,100
Yes
28 Aug 2026
13 Jun 2026
23 Jul 2026
13 Jun 2026
16 Jul 2026
27 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply and laying XLPE insulated armoured cable (heavy duty) electric cable with aluminium stranded conductor 1100 volts grade of following size after taking down complete all as specified and directed by Engr-in-charge :- | |||||
| 1.1 | 10 Sqmm x 2 Core | 300 | RM | - | - |
| 1.2 | 16 Sqmm x 4 Core | 100 | RM | - | - |
| 1.3 | 35 sqmm x 3.5 core | 200 | RM | - | - |
| 1.4 | 50 Sqmm x 3.5 Core | 50 | RM | - | - |
| 1.5 | 70 Sqmm x 3.5 Core | 25 | RM | - | - |
| 1.6 | 95 Sqmm x 3.5 Core | 150 | RM | - | - |
| 2 | Supply, installing, testing and commissioning factory made LT panel ( 415 Volts, 50 Hz , 3-phase, 4 wire supply ) CPRI approved manufacturer, factory assembled Outdoor Feeder Pillar type, weather proof, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated Aluminium bus bars of 100 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, ingress protection class ( IP-65 ) and made of 3.15 mm thick CRCA mild steel sheet and mild steel, Angle iron frame work made out of 40 X 40 X 6 mm ), front and rear opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR wire of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035 embedded in ground with and including masonry in 1:4 CM of blocks of PCC 1:2:4 type B1 of block size 30x30x30 cm and rendering in CM 1:4 with comprising of the following:- | 1 | Each | - | - |
| 2.01 | BUS BAR CHAMBER :-
(a) 100 Amps 3 Strips & Neutral Strip 50 Amps, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings.
INCOMING SUPPLY :-
(i) MCCB 63 Amps 16 KA 3 Pole with Fixed thermal & magnetic release 415 volts , 50Hz,=01 No., Make of MCCB:-L&T/ Schneider / HPL/ Havells.
INSTRUMENT FEEDER :-
(a) Digital Volt Meter, 96X96mm, flush type rated 0-500 V, with Volt meter selector switch- 01 Set.
(b) Digital Amp Meter, 96X96mm, flush type rated 0-100 A, with Amp meter Selector switch- 01 Set.
(c) C.T's 100/5 A CL 1.0 Tape Wound- 01 Set. (Set of three)
(d) Red, Yellow, Green Phase indicating Lights LED type 220 V AC- 1 Set. (Set of three).
(e) Protection MCB 6 A SP C Series- 1 Set. (Set of three).
Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider. | - | - | - | - |
| 2.02 | OUTGOING SUPPLY :-
(i) MCB SPN 32 Amps, 230 volts, 50Hz, rupturing capacity 10 KA C Curve = 3 Nos. Make of MCB:- L&T/ Schneider / HPL/ Havells.
(ii) MCB TPN 32 Amps, 230 volts, 50Hz, rupturing capacity 10 KA C Curve = 3 Nos. Make of MCB:- L&T/ Schneider / HPL/ Havells.
The panel manufacturer should have following Govt. Approved Certificates:
1. Panel should be according to IEC-61439. CPRI Certification Degree of Protection IP-54 (IS/IEC : 61439 (Part-1), 2011 & IS/IEC : 61439 (Part-2) 2011)
2. Tempreature Rise (IS/IEC : 61439-1, 2011 & IS/IEC : 61439-2 2011)
3. CPRI Short Circuit IEC-61439-1 & 2 withstand strenght should be 70kArms for 1.0 Sec with intial peak of 154kApk
4. CPRI Certification IEC-61439-1 & 2 Rated current for short circuit not less than 6300 A with rated insulation voltage 660V
5. ISO 9001 CERTIFIED
Contractor will get the copy of above certificates from manufacturer and submit to Engineer-in-charge/AGE(I) before erection of panel on ground. | - | - | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.24 MB
BOQ_864471.xls
BOQ • 14.31 MB
TenderDocuments432627EM.pdf
Tender Documents • 0.95 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .