The Executive Engineer Electrical HEED
O/o The chief Engineer, Harbour Engineering Electrical Division, Kamaleswaram, TVPM
GENERAL-Electrical works-2025-2026 Upgradation and Capital repairs of electrical installations- Thottapally Fishing Harbour General Electrical Work
2026_HED_825325_1
HED/CEHED/TR/98/2025_6_1_1/1
Open Tender
Electrical Works
Item Rate
60 days
Thottapally Fishing Harbour
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,760
₹39,482
27 Jan 2026
3 Jan 2026
14 Jan 2026
3 Jan 2026
12 Jan 2026
3 Jan 2026
OLD AUCTION HALL 1 and 2 and high mast maintenance
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.3:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
2.10.3:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole
2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
5.3:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required.
5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
5.17:Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required.
5.13:Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required.
7.5.1:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm
90.3.2:Conveyance installation testing and commissioning of pre-wired fluorescent fittings of all types complete with all accessories and fluorescent lamps etc. directly on wall or ceiling with Suitable size PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connections as required.
90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.4.11:Supply Conveyance, installation, testing and commissioning of 200W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.4.6:Supply Conveyance, installation, testing and commissioning of 70W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.3.18.3:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.40 mm dia with clamps made from 20 x 3 mm MS flat
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.14.10.3:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm
90.6.6.1:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.1.50 sq mm
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
OD6079/2025-2026:Supply of 2 core 1.5 Sqmm pvc insulated and pvc sheathed armored copper control cable operating voltage of 600V complete as required make as per approved list
OD6080/2025-2026: Supply and making end termination nickel plated single compression brass cable gland for 2 core 1.5 Sqmm pvc insulated and pvc sheathed armored copper control cable including providing earth clip and superior quality copper cable socket
OD6519/2025-2026:Supply and installation of wall mounting cubicle type dust and vermin proof Hensel 300X600 X170 Mi 0401 IP66,IK 10 Glass fibre reinforced polyester enclosure including providing earthstrip 20 x 3mm 0.20m and Din rail for accommodating MCBs with all fixing accessories complete as required
OD6492/2025-2026:Labour charges for dismantling the old wiring ,cables, damaged fittings and distribution boards etc as directed by the Engineer in charge at site
OD6074/2025-2026:Fabricating supplying and fixing special clamping arrangement for fixing LED bay light and cable junction box to the beam using 500 mm long 50x6mm MS flat, 12mm dia MS round bar with U shape open hook fixed vertically to hang the luminaire welded to the 50x6 mm MS flat and 2 pieces of 1.1m 32 x 6mm MS flat welded to the rod for fixing the cable junction box . The entire arrangement is to be fixed to the beam using 6 x 25 mm SS bolt and nut 2 Nos on each. All the items are to be painted with two coats of epoxy based industrial primer of approved quality and two coats of best quality epoxy paint of approved colour as per drawing.
OD6076/2025-2026:Scaffolding charges for dismounting the light fittings/maintenance of high mast light in the existing pole height up to 15 meters complete as required
OD6077/2025-2026:Supply and installation of IP65 rated, LED 70 W, 270V, 50Hz, 5700K High bay light, System efficiency is 150 Lumens/watt, with driver. Designed for operations under diverse environments ranging from 10 C to 50 C, IK08 polycarbonate cover provides strong protection under harsh conditions, Aluminum die cast ADC 1 alloy grade (ENAC - 47100) Pressure die - cast housing offers excellent corrosion resistance and robustness have mounting device like Eye - Bolt with all accessories complete as required. Preferred make Philips Green Perform Prime or equivalent.
OD7079/2025-2026:Scrapping and cleaning the surface and painting two coats of best quality synthetic enamel paint of approved color over two coat of epoxy based industrial primer on electrical panel /street light pole etc including all cost of labour and materials complete as required
OD7078/2025-2026: Supply and providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required.
OD6078/2025-2026:Supplying and fixing surface /recess mounting Vertical TPN distribution board with Double door , dust and water proof IP 66 Hensel make FP VN 0402 opaque or equivalent , 4 way DB of poly carbonate inclusive of tinned copper 250 A busbar, common neutral link, earth bar, din bar for mounting MCB with provision for MCCB as incomer.
OD6500/2025-2026:Supplying and fixing HENSEL make KV -thermoplastic circuit breker boxes IP65 with metrick knock out for cable entry, 1 row 18 module size 400 x 333 x 129 KV 9118 M with PE+N terminals
OD6522/2025-2026:Supply of surface mounting corrosion-resistant industrial lighting IP65 ratted luminaire WT 150C LED 40S 6500PSUL120 (Philips) or equivalent 40 W LED lamp
OD6491/2025-2026:Fabricating and supplying special clamping arrangement for fixing an asymmetrical beam integral LED flood light on 50 mm dia GI pipe ring with two clamps each made out of 50 x6mm MS flat and 8x40mm SS nuts and bolts for one luminaire. The clamps are to be linked with 40x6mm MS flat with suitable holes 8mm,10mm, or 12mm size with suitable size SS Bolt& Nut to fix the luminaire. All the items are to be painted with two coats of epoxy-based industrial primer of approved quality and two coats of epoxy paint of approved color as per drawing.
OD6502/2025-2026:Supply and fixing Cable Junction Boxes IP 67 for outdoor applications (with knock outs for cable entry - Black Colour) suitable for cable sizes 2.5 sq.mm ,88 X 88X 53 mm Hensel model No KF 5025 B or equivalent and accessories for Cable Junction Boxes such as Copper Terminal Set 2.5 sq.mm 5 Pole 1 No,Support for Terminal 1No including fixing the accessories using suitable size Stainless steel Bolt and nut, giving necessary connections, making good the damages etc. as required.
AUCTION HALL 3
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.3:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.3:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
5.13:Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required.
5.3:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required.
5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
5.17:Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required.
90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.4.3:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.3.18.3:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.40 mm dia with clamps made from 20 x 3 mm MS flat
90.3.2:Conveyance installation testing and commissioning of pre-wired fluorescent fittings of all types complete with all accessories and fluorescent lamps etc. directly on wall or ceiling with Suitable size PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connections as required.
90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm
90.14.10.3:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
OD6389/2025-2026:Supplying and fixing HENSEL make KV -thermoplastic circuit breker boxes IP65 with metrick knock out for cable entry, 1 row 18 module size 400 x 333 x 129 KV 9118 M with PE+N terminals
OD6098/2025-2026:Supply and installation of IP65 rated, LED 70 W, 270V, 50Hz, 5700K High bay light, System efficiency is 150 Lumens/watt, with driver. Designed for operations under diverse environments ranging from 10 C to 50 C, IK08 polycarbonate cover provides strong protection under harsh conditions, Aluminum die cast ADC 1 alloy grade (ENAC - 47100) Pressure die - cast housing offers excellent corrosion resistance and robustness have mounting device like Eye - Bolt with all accessories complete as required. Preferred make Philips Green Perform Prime or equivalent.
OD6094/2025-2026:Fabricating supplying and fixing special clamping arrangement for fixing LED bay light and cable junction box to the beam using 500 mm long 50x6mm MS flat, 12mm dia MS round bar with U shape open hook fixed vertically to hang the luminaire welded to the 50x6 mm MS flat and 2 pieces of 1.1m 32 x 6mm MS flat welded to the rod for fixing the cable junction box . The entire arrangement is to be fixed to the beam using 6 x 25 mm SS bolt and nut 2 Nos on each. All the items are to be painted with two coats of epoxy based industrial primer of approved quality and two coats of best quality epoxy paint of approved colour as per drawing.
OD6306/2025-2026:Supply and installation of wall mounting cubicle type CAPE make BRES 64 or equivalent Glass Fibre Reinforced Polyester energy meter enclosure IP66 ,1K 10 with hinged door 600 X400 X 230 mm with supply and fixing of with Base Plate for fixing 3Phase KSEB meter, cut out and neutral link with sufficient holes for fixing KSEB electronic energy meter, cut outs and neutral link supply and provide 3 no 32 amp HRC fuse unit with link and 1 no 32 amp 2 way neutral link in the meter portion necessary holes are to be provide in the box for entry and exit of wire. inter connection should be done using 10 sq mm copper wire. Necessary holes are to be provided in the box for entry and exit of wire and sealed the joint with suitable sealing agent etc and all fixing accessories complete as required.
OD6445/2025-2026:Supply and installation of wall mounting cubicle type dust and vermin proof size 4 , 600x300x214 mm, Mi0411 high lid thermoplastic box or equivalent including 16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL with BUC rotory drive kit , including giving connection using 10.0 sq.mm pvc insulated copper wire, and 2A SPMCB with RYB indication lamp and wiring the circuit with 2.5 sqmm copper wire complete
OD6390/2025-2026:Providing and fixing 12 SWG insulated GI wire for service wire binding along with service line complete with all accesaries complete as required.
OD6494/2025-2026:Labour charges for dismantling the old wirings ,cables, damaged fittings and distribution boards etc.as directed by the engineer in charge
OD7077/2025-2026: Supply and providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required.
OD6609/2025-2026:Supply and fixing Cable Junction Boxes IP 67 for outdoor applications (with knock outs for cable entry - Black Colour) suitable for cable sizes 2.5 sq.mm ,88 X 88X 53 mm Hensel model No KF 5025 B or equivalent and accessories for Cable Junction Boxes such as Copper Terminal Set 2.5 sq.mm 5 Pole 1 No,Support for Terminal 1No including fixing the accessories using suitable size Stainless steel Bolt and nut, giving necessary connections, making good the damages etc. as required.
OD6449/2025-2026:Supply of surface mounting corrosion-resistant industrial lighting IP65 ratted luminaire WT 150C LED 40S 6500PSUL120 (Philips) or equivalent 40 W LED lamp
OD6095/2025-2026:Supplying and fixing surface /recess mounting Vertical TPN distribution board with Double door , dust and water proof IP 66 Hensel make FP VN 0402 opaque or equivalent , 4 way DB of poly carbonate inclusive of tinned copper 250 A busbar, common neutral link, earth bar,din bar for mounting MCB with provision for MCCB as incomer.
OD6235/2025-2026:Documentation charge for taking connection from KSEB including all file work preparation of drawing etc complete as required.
HIGH MAST
2.10.3:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
5.13:Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required.
5.3:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required.
5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
7.10:Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
7.5.1:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm
5.17:Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required.
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.2:Excavation for cable trenches of depth upto 1.2 m in soft soil including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 metres.
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
14.13.1:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required50 mm dia
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.12.5.40:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm
90.6.6.1:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.1.50 sq mm
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
90.15.4.11:Supply Conveyance, installation, testing and commissioning of 200W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
90.15.1.3:Supply installation testing and commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70mm top diameter. 175 mm bottom diameter thickness 3mm base plate dimensions of 275x275x16 mm suitable for wind speed as per IS 875 Part III fixed head frame including round arm luminary carriage suitable to install 4/6 nos luminaries in symmetrical arrangement including connector foundation bolt 4 nos fixed in existing RCC foundation and junction box etc, complete 10 Meters
OD6367/2025-2026:Supply and installing RCC precast well steining of size 900mm dia and 300m height complete with all expense at site as required.
OD6376/2025-2026:Supply and installation of extra length of foundation bolt of size 24 mm diameter 275mm pitch circle diameter manufactured from special steel ( suitable for 10 M octogonal pole) in existing cement concrete complete as required.
OD6381/2025-2026:Supply and installation of wall mounting cubicle type dust and vermin proof Hensel 300X600 X170 Mi 0401 IP66,IK 10 Glass fibre reinforced polyester enclosure including providing earthstrip 20 x 3mm 0.20m and Din rail for accommodating MCBs with all fixing accessories complete as required
OD6484/2025-2026:Fabricating and supplying special clamping arrangement for fixing an asymmetrical beam integral LED flood light on 50 mm dia GI pipe ring with two clamps each made out of 50 x6mm MS flat and 8x40mm SS nuts and bolts for one luminaire. The clamps are to be linked with 40x6mm MS flat with suitable holes 8mm,10mm, or 12mm size with suitable size SS Bolt& Nut to fix the luminaire. All the items are to be painted with two coats of epoxy-based industrial primer of approved quality and two coats of epoxy paint of approved color as per drawing.
OD6082/2025-2026:Supply of 2 core 1.5 Sqmm pvc insulated and pvc sheathed armored copper control cable operating voltage of 600V complete as required
OD6218/2025-2026:Supply and fixing Cable Junction Boxes IP 65 for outdoor applications (Thermoplastic Polycarbonate ) suitable for cable sizes 2.5 sq.mm ,80 X 80X 52 mm Cape model Abox i025 or equivalent and accessories for Cable Junction Boxes such as Copper Terminal Set 2.5 sq.mm 5 Pole 1 No,Support for Terminal 1No including fixing the accessories using suitable size Stainless steel Bolt and nut, giving necessary connections, making good the damages etc. as required
OD7074/2025-2026:Scaffolding charges for mounting the flood light fittings/maintenance of high mast light in the existing pole height up to 15 meters complete as required
OD7075/2025-2026: Supply and providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required.
OD6323/2025-2026:Supplying and making end termination nickel plated single compression brass cable gland for 2 core 1.5 sq mm PVC insulated and PVC sheathed armored copper conductor cable 1.1 KV grade, including providing earth clip and superior quality copper cable socket.
Civil items
15.2.2:Demolishing cement concrete manually / by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in-Charge.Nominal concrete 1:4:8 or leaner mix ( including equivalent design mix)
5.22.1:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelMild steel and Medium Tensile steel bars
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.61 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.04 MB
BOQ_1383980.xls
BOQ • 0.39 MB
viewsbd.pdf
Tender Documents • 1.67 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .