Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.7 LAccepted-AOC | L1 | Accepted-AOC SM Sales Corporation Accepted L1 bidder | |
| 2 | L2₹25.7 L+₹80,675 (3.24%)Rejected-Finance 24 25 MANGAL ARCADE TELCO ROAD OPP HOTEL DOUBLE TREE MOHAN NAGAR CHINCHWAD PUNE 411019 | PUNE | MAHARASHTRA | 411019 | L2 | Rejected-Finance Rejected | |
| 3 | L3₹28.3 L+₹3.4 L (13.6%)Rejected-Finance | L3 | Rejected-Finance Rejected | |
| 4 | L4₹28.9 L+₹4.0 L (16.0%)Rejected-Finance | L4 | Rejected-Finance Rejected | |
| 5 | L5₹30.9 L+₹6.0 L (24.1%)Rejected-Finance | L5 | Rejected-Finance Rejected |
Tender Value
₹43 L
EMD Value
₹86,000
Closing Date
23 Feb 2023, 6:00 pmClosed
GE Dehu Road, Pune
GE Dehu Road, Pune
SPECIAL REPAIR OF UNDER GROUND CABLE FOR DSC GUARD POSTS NO 30 TO 41 AT PERIMETER AND ELECTRIC SUPPLY TO PERIMETER LIGHTING OF 29 FAD AND CERTAIN MINOR WORKS UNDER GE DEHU ROAD
2023_MES_578676_1
8726
Open Tender
Civil Works
Item Rate
180 days
GE Dehu Road, Pune
please refer tender documents
8 documents required · 8 mandatory
₹500
GE Dehu Road, Pune
₹86,000
Yes
27 Jan 2024
2 Feb 2023
28 Feb 2023
2 Feb 2023
23 Feb 2023
16 Feb 2023
Amount
Taking out of LT cable of any size & Supply,laying,jointing , testing and commisioning XLPE cable 1100 volts grade PVC insulated armoured & PVC sheathed with stranded aluminium conductor heavy duty ISI marked incl cable glands lugs bolts nuts washers etc to suit the cable size to be laid in trenches fixed along pole, LT pannel floor bore or through GI pipe laid under floors, Fixed, concealed in wall encased in GI pipe etc complete of following sizes including taking down old unserviceable over head conductors and insulators channels carefully as directeed by engineer in charge.
35 Sq mm x 3.5 core
25 Sq mm x 3.5 core
10 Sq mm x 4.0 core
6 Sqmm x 4 Core
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5 m in depth and getting out all as specified and directed :-
Soft / loose soil
(b) Hard / dense soil
Returning, filling in soil, including spreading, leveling watering and well ramming in layers not exceeding 25 cm all as specified and directed.
Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point of any type of excavation all as specified and directed by Engineer -in-Charge.
Supply, laying HDPE DWC flexible type of size 50 mm dia for protection of LT cable laid in trenches including insertion of the cable complete all as specified and directed by Engr-in -Charge.
Ditto as above item but 40 mm dia
Supply, laying HDPE DWC flexible type of size 25 mm dia for protection of LT cable laid in trenches including insertion of the cable complete all as specified and directed by Engr-in -Charge.
Material & labour for cable route indicator made out of Aluminium plate 80 MM dia, 6 mm thick & fixed over M.S angle iron of size 30 x 30 x 6 mm, 60 cm in length duly painted with Synthetic enamel BLUE paint suitable for LT cable all as specified & including embedded in PCC (1:3:6) type C1 of size 30 x 30 x 20 cm in ground complete all as specified.
Supply and fix Bus bar chamber of size 250X300X150 mm, outdoor type pedelstal mounted dust proof, weather proof, vermin proof front side single door hinge type with locking arrangement rear side single door hinge type with locking arangement, sheet steel cubical type with slanting roof made out of 3mm thick CRCA sheet with powder coated finished suitable length and size and suitable size stand made with MS angles to keep bus bar chamber . High conductivity 3 phase and neutral aluminium bus bar of 100 Amps capacity duly mounted on pre cast insulators and 6 way all as specified and directed by Engr in charge.
M & L in repairs for earthing with galvanised steel earth plate electrode 60cmx60cmx6.3mm burried directly in ground earth pit not less than 2.25 m deep below normal ground level with top edge of the plate vertically to depth of not less than 1.2m below ground level connected to and including GI strip of size 25 x 4 mm as earthing lead welded with earth electrode (excluding GI protection pipe) and connecting to equipments by means of earthing lead connecting to equipments by means of GI bolts & nuts etc. with provision of char-coal and salt etc. all as per electrical plate No. 3 of SSR Part I, 2009 including RCC cover and MS angle iron frame watering arrangement with GI pipe 20mm dia (medium grade) & MS funnel, concrete pit including excavation and earthwork and testing on completion etc complete all as specified and directed by Engr-in-Charge. Note: Rate quoted deemed to be including excavation by compressor M/C for Soft disintegrated rock to required depth.
S&F SMC Junction box ,pole mounted for street lighting for 3 Phase/4 core system of size 240 X130X110mm top hinged,door fixed to base with hinges on top including aluminium bus bars for connection all as specified and directed. MAKE:- Cat no-GS-JB-2817-T of Sintex or Equivalent.
supply and fix in repair MCB DB SPN sheet metal enclosure double door suitable for mounting MCB 240 volts with 200 Amps rated busbar 08 way all as specified and directed by Engr-in-Charge.
supply and fix in repair MCB TPN 40 Amps 415 volts all as specified and directed by Engr-in-Charge.
M& L for GI tubing 50 mm dia medium grade for cable protection all as specified and directed by Engr-in-Charge.
M&L for steel tubular swaged pole complete with MS base plate final taper plug.bolts,nuts& screwes as specified type 410 SP-37,(8.5 mtr) and applying one coat of aluminum coat over a coat of primer including necessary preparations of surfaces complete all as specified and as directed.
M & L for plain cement concrete 1:4:8 type D2 (using 40mm graded stone aggregate) as in plinth, platforms, pole coping etc., all as specified and as directed.
M & L for plain cement concrete 1:3:6 type C2 (using 40mm graded stone aggregate) as in plinth, platforms, pole coping etc., all as specified and as directed.
M & L PCC type B2 1:2:4 (40 mm graded aggregate) as the coping including form work of pole all as specified.
M & L for earthing complete with galvanised steel earth plate electrode 60cm ×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel,earth wire protected by GI pipe 15 mm dia 'light grade' including charcoal dust, common salt, excavation & earth work, PCC Pit with 1:3:6 type C-1, 40 mm thick RCC cover in 1:2:4 type B-1 reinforced with 8 mm dia TMT bars @ 75 mm c/c both ways with MS handles 12 mm dia, PGI funnel & GI watering pipe 'light grade' 20 mm bore all as shown in electrical plate No. 3 connected to earthing test point all as specified .
Supply and fix in LED street light 60 W ENDURA CITYLITE PLATINUM PLUS new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover with IP66 protection and resistance of IK07 and directed by Engr-in-Charge. Cat No : ENDURACITYLITEPLATPLUSSL35WLED757SASYBOPC of havells and equavalant of Bajaj/HPL/phillips
S&F in repairs street light mounting bracket made out of GI pipe of thickness 2.0 mm not less than with 1.5 m.long ,in round shape at one end to fix on the top of the poleand to fix street light on another end and including nuts and bolts all as direced by Engineer-in-charge.
Supply & fixing in replacement of automatic street light switch using Nature Switch for automatic switching of street lights based on LUX level of natural light the sensor (nature switch) along with suitable power contactors and MCBs (Input-output) should be enclosed Sheet steel enclosure made of rust proof, Electric shock proof, termite proof and FR grade conforming to IP 54.the contactor,MCBs and copper circuit wiring (min.16sqmm) should enough to take: three-phase load of 05KW;contactor Rating 20Amps; MCB(TPN) Rating 20 Amps including making all connection all as specified and directed by engineer in Charge..MAKE:-Nature switch :Kakatiya energy systems pvt.ltd. hyderabad/bajaj/healer. Contactor:- BCH/L&T/Schneider or equivalent (as per IEC-60947-4-1/IS-13947-4-1), MCBs(Input-output):Hager/schneider/L&T/BCH or equivalent (as per IEC-60898/IS-8828),Circuit wiring : Finolex/polycab/RR Kable or equivalent. Model no SWADEEP-02EC5KW3P.
Supply and install hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 3 star rating and EER 3.2 of capacity 1.5 TR all as specified and directed by Engr in charge.
S&F Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 amp complete all as specified .
Supply and fixing wall mounted voltage stablizer 4 KVA for automatic voltage correction single phase naturally air cooled indoor type designed for input voltage 170V to 270V with output voltage stabilized at 230V with accuaccy of + 2.5% with high/low voltage cut off with facility of incl instant start and time delay complete all as specified and directed model no VG 400 of Vguard or Equivalent.
S & F in repair submain wiring with cable insulated single core multistranded copper conductor FRLS cable 1100 volts 2x 4 sqmm drawn through & incl PVC casing caping suitable size alongwith 2.5 sqmm copper conductor cable for earth continuity. (Note : 2 runs of 4 sqmm cable, one run of 4.0 sqmm cable and one run of PVC casing capping will be measured as one RM).
metro electrical services
H S TAKHI
N D ELECTRICAL
SHREE VAIBHAV ELECTRICALS
M/S SVOJAS ELECTROMECH ENTERPRISES
Shivganga Enterprises
NANGIA AND CO
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .