OSD M
YAMUNA EXPRESSWAY INDUSTRIAL DEVELOPMENT AUTHORITY
Construction of Double Circuit 11Kv Ungerground HT Line from 33/11kv Substation in Pocket-A Sector-20 to Sector-22E (WC-EM-02)
2025_YEIDA_1096042_12
YEA/OSD(M)/2025/345 DT-01/12/2025
Open Tender
Electrical Works
Fixed-rate
270 days
YAMUNA EXPRESSWAY INDUSTRIAL DEVELOPMENT AUTHORITY
REFER TENDER DOC
5 documents required · 5 mandatory
₹2,270
₹2.2 L
5 Dec 2025
5 Dec 2025
31 Dec 2025
5 Dec 2025
30 Dec 2025
5 Dec 2025
S/E of Section Double pole structure on ST pole 410 SP-62 with 1/6 over length of poles grounted with cement concrete in 1:3:6 (one cement:3 coarse sand :6 Stone balleast) including plingthing of pole 30 cm above grade level, plastering of plinth including excavation & back filling etc. The double pole structure consist of 100X50X6mm 2.50 mtr. & 75X40X6mm 2.50 mtr. M.S. channel with M.S. clamp packing piece Nuts Bolts etc. The rates includes all materials labour T&P etc. required for proper completion of work as per direction of E/I. YEIDA SOR-51.
S/F of cross arm made of 100X50X6 mm M.S. channel 2.5 mtr. long on poles with packing, piece, M.S. clamp, Nut bolts etc. Complete in all respects as per direction of the Engineer-in-charge. Analysis of rates YEIDA SOR -30
Painting of the electric pole with two coat of Al-paint over red oxide primer Complete in all respects as per direction of the Engineer-in-charge. PWD-2018/PS No-634
Supply & fixing of MS rod for earthing with 2.5 m long, solid, 20 mm dia hot dipped galvanised MS rod buried till the top reaches 1.7 mts. Below the GL complete with bolts & nuts & GI earth wire 7/14. Complete in all respects as per direction of the Engineer-in-charge. Analysis of rates YEIDA SOR -52
S/F of G.I Pipe 15OMM dia "B"class Zindal/tata make including required material T&P etc. Complete in all respect, as directed by Engineer in charge. as per the directions of the Engineer-in charge. YEIDA SOR-65
S/L of 160mm dia. H.D.P.E pipe for drawing of power cable across the road by drilling of 200mm dia. at 1mtr. below the road level thereby doing the work of providing H.D.P.E pipe by Trenchless method PE-63/PN-6.Complete in all respects as per direction of the Engineer-in-charge. Analysis of rates YEIDA SOR -22
S/F of 11 KV Polymer pin insulator with pin on poles or anywhere specified including bolts to fasten on pole cap/cross arm with the poles.(Jaishree, BHEL,RR, Hindustan, Yamuna, AD,Make) Complete in all respect, as directed by Engineer in charge. YEIDA SOR-78
Supply, delivery, laying testing & commissioning of 11KV (E), XLPE cable having compacted circular staranded aluminium conductor, conductor screening of extruded semi conducting compound, cross linked polythylane (XLPE), insulation screening of the extruded semi conducting compound followed by copper tape, cores laid up, taped PVC inner sheath, single layer of steel strip armouring, overall PVC outer sheath conforming to IS: 7098 (Part-amendments) for following mentioned sizes. It should be operational at 11 KV, 50 Hz. AC system in ground at a depth of 1200 mm below ground level over a cushion of 75 mm thick sand alround and protected with bricks on sides and top on surface the cable run shall be fixed on M.S. clamps etc of suitable size or as directed by the E/I. Complete in all respect. The price are inclusive of all earth work such as digging, back filling, supply & spreading of good earth all around the cable, supply & providing cable identification markers. The installation should be complete in all respects and as per requirement of the job. (CCI (Bombay/Nashik), Fort Gloster (Calcutta / Baripara), Asian (Thane / Silvasha), Universal (Satna), Nicco (Calcutta), ICL (Rajpura), Diamond, Havells make &KEI. Analysis of rates OF yeida sor -2, (a) 3CX300 Sqmm.
Supply, Delivery, Installation, Testing & Commissioning of 11 KV Out door type cable termination kit of 3 core cable for cable termination at the panel & transformer complete in all respects as required for proper completion of work. (650mm length). Analysis of rates (make Raychem/C.C.I./Frontec) (a).3CX240/300 Sq.mm. YEIDA SOR-5
Supply, Delivery, Installation, Testing & Commissioning of 11 KV Straight through cable jointing kit of 3 core cable for cable jointing. Complete in all respects as required for proper completion of work. Analysis of rates. (make Raychem/C.C.I./ Frontec ) 3CX300 Sq.mm.YEIDA SOR-6
Supply & fixing of Cable route marker including Painting & Writing Analysis of rates Complete in all respects as per direction of the Engineer-in-charge. Analysis of rates YEIDA SOR -55
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.88 MB
12.pdf
Tender Documents • 1.50 MB
BOQ_2018887.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .