Executive Engineer
Office of the Executive Engineer Mechanical_Electrical Division Berhampore PH Engineering Dte Netaji Subhas Road P H E River Side Complex Berhampore Murshidabad PIN_742101
Operation and guarding of 250 KVA substation andother electrical accessories at Beldanga-Mahyampur W/S Scheme under MEDB PHE DteDist_Murshidabad
2024_PHED_761998_3
WBPHED/EE/MEDB/NIeQ-28 of 2024-25
Open Tender
MECHANICAL
Item Rate
365 days
Berhampore
Operation and guarding of 250 KVA substation andother electrical accessories at Beldanga-Mahyampur W/S Scheme under MEDB PHE DteDist_Murshidabad
7 documents required · 7 mandatory
₹42,000
19 Feb 2025
4 Oct 2024
11 Nov 2024
4 Oct 2024
5 Nov 2024
4 Oct 2024
Amount
Operation and guarding of 11 KV/ 0.433 KV , 3 Nos. 250KVA transformer, H.T.L.T. Panel boards, VCB, HTAVR including operation of all accessories and ancillaries for 24 hours a day, sweeping of the sub- station complex daily by engaging skilled, semi skilled, unskilled personnel including watch & word personnel.
Periodical inspection, 2 times in a month (5 days in each visit) by Electrical Supervisor having valid Supervisors’ Certificate of competency from Directorate of Electricity (Licensing Board) Govt. of W.B. under any other state Govt. of India. Each visit should be recorded in the Log Book (with date and time) to be supplied by the Agency and kept in the sub-station building. The Supervisor requires to have thorough / in- depth inspection of all the electrical appliances to ascertain the healthy/ fault- free operational condition of each equipment i.e. VCB, VLE transformers,HT AVR, L.T Panel. PDB Panel, capacitors, along with in- house lighting system etc. All other necessary requirement to execute the maintenance work along with Log book, cotton Waste, Broom, Torch, Detergents, Liquid soaps, Gloves, Apron, Tools-Tackles, Terminals, Sockets, Fuses, Indicating Lamp, Gland Packing , Silica gel to be supplied by the Agency as & when required.
Upkeepment of healthy condition of all feeders cleaning of all contactors, terminal sockets, coil etc. ones in a month with the help of CRC-226 spray, grease , Lub oil etc. checking of all internal connection of all feeders panels , LT Panel /H.T Panel , wiring of starters , external wiring of the Sub Station. All the illumination , fixtures including timers & contactors etc. by engaging electrician having valid and appropriate Licence ( Work mans permit) issued by Directorate of Electricity , Govt. of West Bengal or any other State Govt. of India or personnel having ITI (Electrician) Certificate and all the parameters to be recorded in the Log Book with Date & Signature.
Calibration & testing of various electrical equipments ,relays ,meters,instruments etc. to ensure all equipment are in troblefree including testing and filtration ,dehydration of 03nos 250KVA transformer ,01no.AVR & controller oil by suitable method as per direction of E.I.C.
MAHADEV ENTERPRISE (BID ID -5735799)
WEST BENGAL ENGINEERING CO. (BID ID -5733966)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .