| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.9 LAccepted-AOC | L1 | Accepted-AOC Accepted being reasonable and lowest | |
| 2 | L2₹47.5 L+₹6.4 L (15.5%)Rejected-Finance | L2 | Rejected-Finance NOT LOWEST | |
| 3 | L3₹47.6 L+₹6.5 L (15.9%)Rejected-Finance 30 INDUSTRIAL AREA KOKAR RANCHI 834004 JHARKHAND | RANCHI | JHARKHAND | 834004 | L3 | Rejected-Finance NOT LOWEST | |
| 4 | Rejected-Technical | - | Rejected-Technical Not enlisted in appropriate category | |
| 5 | Rejected-Technical GALI NO 4 GAUSHALA ROAD VIKASH NAGAR RAMGARH CANTT RAMGARH JHARKHAND 829122 | RAMGARH CANTT | RAMGARH | JHARKHAND | 829122 | - | Rejected-Technical Not enlisted in appropriate category |
Tender Value
Refer Docs
EMD Value
₹80,000
Closing Date
28 Jun 2021, 6:00 pmClosed
CWE RANCHI
HQ CWE Ranchi MES Dipatoli Cantt PO RMCH Ranchi-834009
REPAIR OF 33 KV SUB STATION, VCB, RELAY, EARTHING, UG CABLES ETC AND REPAIR/MAINT OF TRANSFORMERS AT RAMGARH CANTT.
2021_MES_445331_1
80599/1358/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Ramgarh
Class D Category b(iii)
7 documents required · 7 mandatory
₹500
Yes
GE RAMGARH
₹80,000
Yes
18 Sept 2021
25 May 2021
30 Jun 2021
25 May 2021
28 Jun 2021
21 Jun 2021
Amount
Dismantling and taking down existing old unserviceable/worn out isolators verticle/horizontal mounted including operating mechanism and Supply, installation, commissioning and testing of Air brake, off load Isolator switch, rotating type, manually operated, horizontal operational type, highest system voltage 36 KV rated current 800 Amps triple pole, each pole consists of insulating pedestals – 03 Nos. on galvanized steel base as per BSS/IS including rotating blade of HDE copper and fixed contacts of same material, spring loaded, arcing horns of adequate cross section to brake magnetizing current of transformer including earthing device with adequate size of G.I. operating pipe for operation from ground level and operating handle etc complete with both “OFF” and “ON” positions including provision of mechanical locking arrangement complete all as specified and as directed.
Dismantling and disconnecting old ACSR conductor from existing steel structure and S&F new ACSR conductor of (Panther) 6/7 X 3.96 mm, stringing and fixing in position and binding to insulators etc at HT 33 KV grid station complete all as specified and as directed by Engineer-in-charge
S&F announciation facia 8 window suitable for 24 V DC with Degree of Protection IP-54 including taking down old relay by disconnecting all electrical connection from panel complete all as specified and as directed.
S&F PLA auxillary relays for 24 V DC complete all as specified and as directed.
S&F 24 V DC LED indication lamps accessories of different colours including taking down old one complete all as specified and as directed.
S&F 24 V DC Hooter suitable for 33 KV relay panel complete all as specified and as directed.
S&F 'T' Clamp for droppers complete all as specified and as directed.
S&F PG Clamps complete all as specified and as directed.
M&L for repairs to 11 KV VCBs by replacement of tripping coils, DC shunt Motors 230 Volt, Bridge mechanical gear wheels with all moving parts, latches and releasing parts, over driven stopping and restarting mechanism, including greasing, servicing etc complete all as specified and as directed..
Dismantling and taking out old existing unserviceable or broken incsulators of any discription or any size complete all as specified and as directed.
S & F single Pin type insulator, porcelain, vitreous 145 mm high and 225 mm dia ball and socket type, brown, assembly for tension with tension clamps for conductors, 33000 volts complete all as specified and as directed
S & F single Disc type insulator, porcelain, vitreous 145 mm high and 225 mm dia ball and socket type, brown, assembly for tension with tension clamps for conductors, 33000 volts complete all as specified and as directed
M&L for 33 KV post insulator with the following technical specification :- (a) Nominal system voltage - 33 KV (b) Highest equipment voltage - 36 KV (c) Type - porceline solid core post insulator (d) One minute power frequency dry and wet withstand voltage - 70 KV (rms), (e) Impulse withstand voltage - 170 kvp (Peak), (f) Frequency - 50 Hz, (g) Porceline insulator petticoats should be alternate shape design and suitable for heavily poluted area, (h) Colour of glaze - Brown, (i) Cantiliver strengh - 4 Kn, (j) Torsional strength - 2.54 KN, (k) Tension strength - 80 KN, (l) Power factor withstand voltage Dry - 95 KV and Wet - 80 KV, PF flash over voltage - Dry 125 KV & Wet 100 KV, Impulse withstand Volt - 170 KVP, Impulse flash over voltage - +VE 225 KVP, - VE 240 KVP, Tem erature - as per IS - 3156 and altitude above sea level is 1700 Mtr, Atmosperic condition - Humidity varying between 50% to 98%, Type of installation - Out door electrically exposed, Creapage distance of porceline insulator - 1065mm, for metallic parts - Galvanised complete with fittings all as specified and as directed.
Supply, installation, commissioning and testing of lightening arrestor station type conforming to IEC 60099 of 2006 IS 3070 ( up to date) complete with all fittings, transmission class 36 KV 10 KA 50 Hz suitable for system voltage 33/36 KV (using extra porcelain base to increase the distance between live portion and earth). including taking down old one complete all as specified and as specified. Note:- Gap between live portion to earth should not be less than 600 mm
Supply, laying, jointing, testing and commissioning LT control panel cable, 1100 volts grade, PVC insulated and PVC sheathed, heavy duty armoured, with multistranded copper conductors Cables of the following sizes, IS-1554 marked, laid in trenches/ ducts/ fixed on poles/ walls/ laid under roads / paths/ or passing through GI pipe complete all as specified and directed.
1.5 Sqmm 7 core
2.5 Sqmm 10 core
1.5 Sqmm 3 core
Supply & laying of HT UG cable XLPE insulated armoured heavy duty electric cable with stranded aluminium conductor 11000 volts grade cross section area 95 Sqmm 3 core laid in trenches or fixing on panels/walls/poles or passing through pipe including connecting with suitable lugs, glands, nuts and bolts and testing including taking down complete all as specified and directed.
S&F XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor, 33000 volts, grade cross sectional area 185 sq. mm, 3 core including taking down old cable complete all as specified and as specified.
S&FCable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including taking out old one complete all as specified and as specified.
S&F Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm including taking out old one complete all as specified and as specified.
S&F cable jointing kit for 33 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 Sqmm including taking out old one complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 6 sq mm 4 core complete all as specified and as directed.
Supply and fixing cable PVC insulated unsheathed of size 2.5 Sqmm 3 core copper conductor for connections from junction box to security light complete all as specified and as directed (for juction box to flood lights). Make : KEY/Havells/Polycab
S&F winding temperature meter mercury type complete all as specified and as directed
S&F oil temperature meter mercury type complete all as specified and as directed
S&F DC spring charge control motor of capactiy 0.1 KW, current rating 1.3 A, 230 V for totally enclosed of 33 KV VCB control panel complete all as specified and as directed
S&F shunt trip 30 V DC coils for 33 KV VCB complete all as specified and as directed
S&F shunt trip 30 V DC coils for 11 KV VCB complete all as specified and as directed
S&F digital frequency meter complete all as specified and as directed
S&F digital ampere meter, 0-100 Amp sequence shape complete all as specified and as directed
M&L for Earthing complete with copper earth plate electrode of size 60cms x 60cms x 10.0 mm thick buried directly in to the ground (earth pit not less than 2.25 m deep below the ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to the copper earth strip 50 x 6 mm by means of bolts , nuts, bolts, thimbles check nuts and washers using copper including concrete chamber shall be PCC 1:3:6 Type C-1 using 20 mm graded stone aggregate, with fair finish internal surface concrete 15 mm thick plaster in CM 1:4, funnel, with wire gage of (0.68 mm) 8 mesh per inner inch, 80mm thick RCC Pit cover 320mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregated reinforced with XPM and charcole dust and comman salt all as shown in electrical plate No-3 of MES SSR Part -I including provision of earthing test point /transformer neutral/ body etc and testing on completion, complete all as specified and directed Note :- The Quoted rate of earthing is deemed to be inclusive of cost of 7.5 M long copper strip of size 50x6 mm and protection pipe of 80mm bore light grade, GI light grade 20mm bore watering pipe, funnel etc.
M&L for earth continuity conductor or main earthing lead buried in ground for loop earthing/making grid earthing mat by the distance of 1.5 Mtr on each earthing grid and inter connected to main earthing lead etc. as per site requirement of size 50 x 6mm thick galvanised iron strip including taking of all existing gravels and relaying of the same after making earthing mat complete all as specified and as directed by Engr-in-Charge.
Decarbonising / cleaning complete of HT 11KV and 33 KV 3 phase bus bar & bus bar chamber, all electrical connections complete HT VCBs/OCBs/Bus coupler arrangment after removing the bus bar spout, cleaning with petrol and CRC 226 spray solution and ensure proper de-carbonisation, refixing the same after completion complete all as specified and as directed by Engr-in-Charge.
Disconnecting HT/LT cables and earthing connections of burnt/defective station transformer of capacity 25 KVA, 33KV/433 volts 3 phase from pole/floor mounted, taking out the transformer from its original position carefully with the help of Crane and transportation of the same to the workshop for repairs, draining out the transformer oil, dismantling complete and taking out the core assembly and removing burnt out windings, dehydrating the core assembly, reassembling transformer after repair/rewinding, replacement of complete gasket set, refilling the oil duly filtered / dehydrated, topping up with new oil, carrying out routine tests, including transportation back to site, testing and commissioning of the repaired transformer at site on full load after making cable and earthing connections complete all as specified & as directed. Note :- (i) New transformer oil and Dehydration of Transformer oil, winding of coild shall be measured and paid separately. (ii) The vender should submit the guarentee certificate for the work done after rapair.
Material & labour for rewinding of station transformer (after dismantling and segregation of HT/LT legs coil in the presence of Engineer-in-Charge or GE) with and including of insulated copper wire of appropriate guage and quantities (as per existing size) duly insulated with and including insulating materials i.e., cotton tape, craft paper and insulating sleeves or other suitable insulating materials required to complete the job etc strictly according to the manufecturer's instructions and engineering pratice complete all as specified and directed by Engr-in-Charge.
For HT 33 KV leg coil with insulated copper wire/strip
For LT leg coil with insulated copper wire/strip
Material and Labour for heating, filtration and dehydration of transformer oil as per IS : 10028 (Part-III) 1981, Para 5.2 with dehydration/ filtration plant to achieve dielectric strength of 60KV at 4 mm air gap, complete all as specified and as directed. Note:- Any damage occurred to transformer during the process of dehydration, shall be made good by the contractor to the entire satisfaction of the Eng-in-charge at his own expenses and submit test report after dehydration.
Cleaning and servicing of HT 33/11 KV Structure by greasing, cleaning, servicing of jumpers and tightening of nut & Bolts etc. and rejumpering wherever required and painting with two coats of aluminium paint over a coat of zinc chrome primer from main recieving point to distribution bus bar bay structures up to transformers inside MRS Ramgarh Cantt (Note:- 1. Quoted rate is inclusive of all requirement accessories i.e. Nut & Bolts, Connecting rod type ACSR & Jumpering materials etc)
S&F LED flood light luminaire of 150 W with ultra sleek, light weight and with secondary optics, made of pressure die-cast housings with IP66 ingress protection and impact resistance of IK07. 4kV inbuilt and 10kV external surge protection complete including fixing arrangement on pole at cross arms complete all as specified and as directed by Engr-in-Charge. Make : Bajaj/Crompton/Havells/Philips
S & F in repair cross arms bracing supports, clamps and back plate fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat of red oxide zinc chrome, one under coat and one finishing coat of aluminum paint all as specified.
M&L for preparation of old painted surface, cleaning of surface portion complete for HT pole above PCC coping and applying a coat of red oxide and two coats of aluminium paint including brackets, clamps, etc including writing the pole No with black enameled paint of size 70 mm wide and 100 mm height complete all as directed by Engineer-in-Charge.
M&L for cable junction box of size 155 x 210 x 92 GFS polycarbonate, weather proof, UV resistant rainwater proof, halogen free glow wire test in accordance with IEC 60695-2-II 960 C flame retardant self extinguishing suitable for loop in/out cable size upto 10 Sq mm IP 66/67, alonwith one MCB SP 6-32A for controlling of flood lighs complete with all accessories all as specified and as directed . Make HENSEL Cat No.KF 1610 B or other equilant as approved by the GE
Supply and fix MCCB 4 Pole, 415 V, adjustabgle type, 32 Amps with breaking capacity 16 KA duly ISI marked complete including connection for flood lights controlled at power house complete all as specified and as directed. Make : Indo Asian or its equivalent make in Havells/Standard/L&T as approved by the GE
Disconnecting HT/LT cable and earthing connections of burnt/defective transformer of capacity 25 KVA to 500 KVA , 11 KV/433 volts 3 phase from pole/floor mounted, taking from site of installation carefully with the help of Crane and transportation of the same to workshop for repairs, draining out the transformer oil, dismantling complete and taking out the core assembly and removing burnt out windings, dehydrating the core assembly, reassembling transformer after repair, replacement of complete gasket set, refilling the oil duly filtered / dehydrated, topping up with new oil, carrying out routine tests, including transportation back to site, testing and commissioning of the repaired transformer at site on full load after making cable and earthing connections complete all as specified & as directed. Note :- (i) New transformer oil and Dehydration of Transformer oil shall be measured and paid separately. (ii) The vender should submit the guarentee certificate for the work done after rapair.
Material & labour for rewinding of HT side winding with copper strip of suitable size/gauge, fixing the coil in position in core assembly and making connection as per existing pattern including providing insulation, varnish etc complete all as specified and directed by Engr-in-Charge.
Material & labour for rewinding of LT side winding with copper strip of suitable size/gauge, fixing the coil in position in core assembly and making connection as per existing pattern including providing insulation, varnish etc complete all as specified and directed by Engr-in-Charge.
Disconnecting HT/LT cable/bus bar and Earthing connections complete of transformer capacity up to 125 KVA, 11 KV/433 Volts 3 phase from pole/floor/transformer shed with the help of Crane to carry out complete maint of transformer comprising of the following:- (i) Draining out oil from chamber. (ii) Opening top cover, disconnecting winding connection from bushings and taking out carefully core assembly complete with winding. (iii) Checking compactness of core & tightening the same where required. (iv) Chemical washing of winding to remove dirt,dust & carbon particles (v) Cleaning of oil tank to remove oil sludge followed by painting of inner surface of tank with zinc chromate base paint (vi) Refixing of core & winding assembly and making connection with HT/LT bushing . (vii Replacement of worn out gaskets & nut/bolts. (viii) Refilling of oil duly filtered/dehydrated/fresh oil (to be measured & paid separately under respective item). (Note: Overhauling of transformer should be done on existing installation place on same days)
All as per item No.45 here in before but transformer capacity from 160 KVA to 200 KVA.
All as per item No.45 here in before but suitable for transformer capacity 250 KVA to 500 KVA.
Material and Labour for preparing the surfaces of transformer of capacity up to 63 to 125 KVA by rubbing old paint and applying two coats of spray painting with grey deco paint from outside complete all as specified and as directed. Note. Painting of transformer will be carried out for plinth mounted and pole mounted transformer. Necessary tools and plants shall be arranged by the contractor. Shut down schedule for painting of transformer will be submitted in advance to plan shut down in the station. including writing MES / SM No with enamelled paint complete all as specified and as directed for transformer of rating upto 125 KVA (Indoor/outdoor type).
All as per item No.48 here in before but transformer capacity from 160 KVA to 200 KVA.
All as per item No.48 here in before but suitable for transformer capacity 250 KVA to 500 KVA.
Supply and pouring new transformer oil as per IS : 335 (1993) for transformers installed at various site as well as transformers under repair for topping up after dehydration to achieve the di electric strength 60 KV at 4 mm gap, complete all as specified and as directed. Make: Power link, Savita (Transol), Power Oil Note : Transformer oil shall be brought at site in sealed container from the original manufacturer and shall be opened in front of Engr-in-charge. Make: Power link, Savita, Power Oil as approved by the GE
Testing of transformer oil as per IS : 335 and IS 12463 for dielectric strength of transformer installed in various site, plinth mounted/pole mounted including submission of test report complete all as specified and as directed.
Supply and fixing in replacement of silica gel breather assembly with vent piipe complete with fresh blue coloured, for transformer of capacity upto 200 KVA complete all as specified & as directed.
All as per item No.53 here in before but suitable for transformer capacity 250 KVA to 500 KVA.
Supply and replacement of Silica gel only with fresh blue coloured complete all as specified and as directed.
Supply and replacing HT/LT side cable box cover plate made out of MS sheet of 16 SWG complete with nuts, bolts, washers suitable for indoor/outdoor type transformer of capacity upto 500 KVA.complete all as specified and as directed.
Supply and fixing in replacement HT bush assembly brass complete with brass spindle, nuts, bolts, washers etc without bushing insulators suitable for transformer of capacity upto 125 KVA complete all as specified & as directed.
All as per item No. 57 here in before but transformer capacity from 160 KVA to 500 KVA.
Supply and fixing in replacement LT bush assembly brass complete with brass spindle, nuts, bolts, washers etc without bushing insulators suitable for transformer of capacity upto 125 KVA complete all as specified & as directed.
All as per item No. 59 here in before but transformer capacity from 125 KVA to 500 KVA.
Supply and fixing in replacement 11KV porcelain bushing insulators for HT side of out door/indoor type transformer complete all as specified & as directed.
Supply and fixing in replacement 11KV porcelain bushing insulators for LT side of out door/indoor type transformer complete all as specified & as directed.
Supply and fixing in replacement drain plug of suitable size, complete all as specified and as directed.
Supply and replacing of gun metal gate valve with iron wheel head, screwed both ends suitable for iron pipe upto 25mm bore, ISI Marked one side fitted with cast iron plug (Drain-out valve of transformer)
Supply and fixing in replacement of rubberized cork sheet gasket 6mm thick for top cover and HT/LT bushes complete all as specified and directed for transformer upto 500 KVA capacity including replacement of Nuts & Bolts where required complete all as Specified and directed by Enge-in-Charge.
Supply and fix Lightning arresters expulsion type complete with all fittings, transmission class, 11000 Volts discharge capacity 65 kilo amp complete all as specified and directed..
M&L for Switch air break, gang operated triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 200 amps 11000 volts complete all as specified and directed.
Excavation in trenches n exc 1.5 m wide & n exc 1.5 mtr in depth for foundation, etc or for shafts, wells, cesspits, manholes, pier holesetc not exc 10 sqm on plan and getting out of soft/lose soil for laying of pipe & cable etc complete all as directed.
Returning, filling in including spreading, levelling,watering and well ramming excavated soil in layers not exceeding 25 cm thick, filling back in trenches after cables have been laid and tested, poles,stays,struts have been erected and tested complete all as specified.
Removal of excavated surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified.
M & L clean and dry sand free from sharp material in trenches around the cable for cushioning complete (depth 23 Cm and after punning down to 18 Cm) complete all as specified and as directed.
Material and labour for laying in trenches burnt brick sub class 'B' for cable protection laid adjacent to each other length wise perpendicular to the central axis of cable complete all as specified.
Supply & laying of UG cable LT 1100 volts grade XLPE insulated armoured heavy duty elect cable with stranded aluminium conductor cross section area 120 Sqmm 3 ½ core, laid in trenches or passing through pipe including connecting with suitable lugs, glands, nuts and bolts and testing complete all as specified and directed.
Supply & laying of UG cable LT 1100 volts grade XLPE insulated armoured heavy duty elect cable with stranded aluminium conductor cross section area 150 Sqmm 3 ½ core, laid in trenches or passing through pipe including connecting with suitable lugs, glands, nuts and bolts and testing complete all as specified and directed.
Supply & laying of UG cable LT 1100 volts grade XLPE insulated armoured heavy duty elect cable with stranded aluminium conductor cross section area 240 Sqmm 3 ½ core, laid in trenches or passing through pipe including connecting with suitable lugs, glands, nuts and bolts and testing complete all as specified and directed.
Supply & laying of UG cable LT 1100 volts grade XLPE insulated armoured heavy duty elect cable with stranded aluminium conductor cross section area 95 Sqmm 3 ½ core, laid in trenches or passing through pipe including connecting with suitable lugs, glands, nuts and bolts and testing complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV earthed grade cable for outdoor termination cold shrink type joint complete with jointing mterial and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sq mm complete all as specified and as directed.
Supply and fix cable jointing kit for 11 KV earthed grade cable for outdoor termination cold shrink type joint complete with jointing mterial and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sq mm complete all as specified and as directed.
Supply and fix drop out insulator with fuse wire, including necessary bracket of capacity 11000 Volts, 400 Amp complete all as specified and as directed. Note: Quoted rate is includive of jumpering from cable to drop out insulator including necessary bolts etc.
Supply and fixing in repair epoxy resin coat post insulator for air break switch for 11000 Volt grade, porcelain, brown colour insulators including taking down of old one complete all as specified and as directed.
Supplying and fixing light grade Galvanised mild steel water tubing, 80mm nominal bore, complete with all fittings and laid in trenches under roads/ drains,fixed to poles/ walls with Mild steel clamps , bolts , nuts and washers complete all as specified and directed.
Material and labour for earthing complete with galvanised steel earth plate electrode 60cmX60cmX6.0mm thick, buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5mtr below normal ground level connected to GI earth strip of size 32x6 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron complete earth pit of PCC M-10(Nominal mix) using 20mm graded stone aggregate, 50mm thick earth pit cover of RCC M-15 (Nominal mix) using 20mm graded stone aggregate with MS TMT reinforcement bar of 8mm dia @ 150mm centre to centre both ways, MS handle 10mm dia made to shape, GI funnel, wire mesh and 20mm bore GI water pipe medium grade and 40mm bore medium grade GI pipe for protection of earth strip from plate to main switch board, common salt, charcoal dust including testing on completion complete all as specified and as directed all as shown in electrical plate No. 3 including testing on completion and making good the disturbed surfaces of wall floors etc without claiming extra cost all as directed by Engr-in-Charge. (Note: GI strip & GI pipe beyond 7.5Mtr length from earth electrode shall be measured and paid separately). Note:- Earth wire up to 7.5 meter connected to earth point shall be deemed to be included in unit rate.
Supply and fixing Danger notice plate for HT poles made out of 1.6 mm thick mild steel sheet vitreous enemelled white letter , figurers and converntionl skull and bones marked in red colour with MS clamp of flat iron 25x3mm size bolts , nuts size of plate 25x20cm complete all as directed.
M & Laying cement concrete for coping of HT poles on two pole/four pole structure using B1 1:2:4, 20 mm graded stone aggregate, smooth finishing without using extra cement complete all as specified and directed. .
Scraping, cleaning and preparation of surface of complete four pole on steel structure including cross arms installed at varioius location under GE Ramgarh for painting with the help of sand paper, wire bursh and cotton cloth and applying externally with two coats of synthetic enamelled paint (aluminium) over a coat of red oxide primer and zebra strip type from ground level to 1.5mtr height of pole by black and red coloured strip and painting of cement pole by weather coating complete all as specified and directed by the Engr-in-Charge
Scraping, cleaning and preparation of surface of complete two pole on steel structure including cross arms installed at varioius location under GE Ramgarh for painting with the help of sand paper, wire bursh and cotton cloth and applying externally with two coats of synthetic enamelled paint (aluminium) over a coat of red oxide primer and zebra strip type from ground level to 1.5mtr height of pole by black and red coloured strip and painting of cement pole by weather coating complete all as specified and directed by the Engr-in-Charge
Mateial and labour for FRP board of size 60 cm x 60 cm duly printed with radium based letters with the following details as directed by Engr-in-Charge :- (a) Unit (b) Capacity of transformer (c) Location (d) Transformer serial number (e) Year of manufacturing (f) SM/MES No Note : Colour and design of board will be decided by Engr-in-Charge as directed.
Dismentling the exitsing transformer up to 500 KVA capacity from the plinth and keeping aside in working condition , necessary repair to plinth with PCC / brick work as directed with smooth and even surface , re mounting the transformer on the same plinth, all as specified and directed.
Associated Engineers
Raj Construction
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .