Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹58.8 LAccepted-AOC R N COLONY PO BIRPARA DIST ALIPURDUAR W B PIN 735204 | ALIPURDUAR | WEST BENGAL | 735204 | L1 | Accepted-AOC RATES ARE FOUND REASONABLE AND BEING L1 BIDDER | |
| 2 | L2₹61.3 L+₹1.3 L (2.12%)Rejected-Finance PO PS BANARHAT DIST JALPAIGURI PIN 735202 W B | JALPAIGURI | WEST BENGAL | 735202 | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 3 | L3₹67.0 L+₹7.0 L (11.7%)Rejected-Finance NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 4 | L4₹68.5 L+₹8.5 L (14.1%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 5 | L5₹69.6 L+₹9.6 L (16.0%)Rejected-Finance | L5 | Rejected-Finance OTHER THAN LOWEST BIDDER |
Tender Value
₹65 L
EMD Value
₹1.2 L
Closing Date
5 Jun 2023, 6:00 pmClosed
CWE BINNAGURI
HQ CWE BINNAGURI, BINNAGURI CANTT, JALPAIGURI, WEST BENGAL, PIN-735232
REPAIR / REPLACEMENT AND MAINTENANCE OF 66/11KV SWITCH YARD, TRANSFORMER, VCB, RMU, CENTRAL POWER HOUSE, CABLES AND ALLIED HT WORKS AT BINNAGURI MIL STN UNDER GE (N) BINNAGURI
2023_MES_593657_1
8071/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
BINNAGURI MIL STATION
AS PER NIT
8 documents required · 8 mandatory
₹1,000
GE (N) BINNAGURI
₹1.2 L
Yes
30 Jun 2023
6 May 2023
6 Jun 2023
6 May 2023
5 Jun 2023
28 May 2023
Amount
Dehydration, hot filtration de sludging of transformer oil of any type / capacity of transformer at site including all arrangement of tools plants etc to achieve dielectric strength not less than 60 KV(rms) with 2.5 mm testing gap, Complete all as specifed and directed by Engineer-in-Charge.
Dehydration, hot filtration de sludging of transformer oil of any type / capacity of transformer at site including all arrangement of tools plants etc to achieve dielectric strength not less than 50 KV(rms) with 2.5 mm testing gap, Complete all as specifed and directed by Engineer-in-Charge.
Supplying, filling dehydration and filtration of new transformer oil for toping up / replacement of transformer oil having dielectric strength not less than 50 KV (rms) with gap of 2.5 mm all as conforming to IS 335 of 1993, Complete all as specifed and directed by Engineer-in-Charge.
Disconnecting transformer outdoor / indoor type 11 KV /433 Volt supply system ellectrically both side, earth terminal and taking down carefully from pole / platform mounted on PCC foundation etc and carrying to work shop for repair of following capacities:-
(a) 63 KVA to 250 KVA
(b) 300 KVA to 750 KVA
Supply and replacing Surge counter Monitor suitable Lightning Arrestor (Surge Arrestor) for a rated voltage of 72.5 KV, Model No SC-07-1, Complete all as specifed and directed by Engineer-in-Charge.
M & L for repair/rewinding of transformer HT coil with super enamelled / paper coated copper wire of existing gauge including all associated insulating material such as separator etc complete varnishing, heating including dismantling of top cover, decanting transformer oil, storing the same in suitable container,disconnection live part, dismantling of bushing, lifting of core Assey, checking the windings, cleaning of cooling tube, conservator and all internal connection after all necessary repair work and rewinding, assemble the complete transformer and refilling after necessary filtration including all internal connection etc of any type / capacity transformer. Note : (i) Filtration of oil shall be measured and paid separately. (ii) New Transformer oil shall be measured and paid separately (if Reqd). (iii) New super enamelled / paper coated copper wire shall be measured and paid separately (if Reqd). (iv) Major spares/parts for repair shall be measured and paid separately as supply only under relevant items of this schedule.
M & L for rewinding of transformer HT coil with super enamelled / paper coated copper wire of existing gauge, Complete all as specifed and directed by Engineer-in-Charge.
All as per Serial item No 7.00 as above but LT winding.
M & L for painting of transformer with two coats of synthetic enamel paints including surface preparation and painting / making SM MES No Capacity etc all as directed of the following sizes :-
(a) 200 KVA to 300 KVA
(b) 400 KVA to 750 KVA
(c) 5000 KVA (5 MVA)
Supply & fixing in replacement of Silica gel breather assembly complete unit including Silica gel and taking out the old unserviceable one and providing proper gasket including replacement of corroded pipe connections to breather assembly suitable for transformer of capacity 100 - 200 KVA, Complete all as specifed and directed by Engineer-in-Charge.
All as per Serial item No 10.00 as above but for transformer of capacity 250-300 KVA.
All as per Serial item No 10.00 as above but for transformer of capacity 315-500 KVA
All as per Serial item No 10.00 as above but for transformer of capacity 750 KVA.
All as per Serial item No 10.00 as above but for transformer of capacity 5MVA.
M & L for repairing to Outdoor/Indoor transformer HT / LT bushing assembly including all worn out / damaged parts by replacing the following parts without disturbing the other parts as under :-
Brass spindle with 05 Nos nuts, check nuts and washer of dia 12 mm.
Brass spindle with 05 Nos nuts, check nuts and washer of dia 16 mm.
Brass spindle with 05 Nos nuts, check nuts and washer of dia 20 mm.
Rubber bush round type of any size.
Porcelain insulator for LT bushing of any size.
Porcelain insulator for HT bushing of any size.
M & L for transformer gasket for top cover 4mm thick rubber seal cork sheet, Complete all as specifed and directed by Engineer-in-Charge.
Shifting of transformer of any capacity from 2 pole structure / PCC foundation / sub station after disconnecting HT / LT connections, earthing leads etc and reinstallation the same at new location, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing and testing of externally operated tap changer switch off load type after dismantling of transformer conservation / top cover and reassembling the same after replacing complete suitable for 63 to 200 KVA Transformer, Complete all as specifed and directed by Engineer-in-Charge.
Supply fixing and testing of externally operated tap changer switch off load type after dismantling of transformer conservation / top cover and reassembling the same after repairs complete suitable for 250 to 750 KVA Transformer, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing of new temprature guage ( 0º C to 120º C ) range dial temprature as directed including taking down old unserviceable guage, Complete all as specifed and directed by Engineer-in-Charge.
M & L for transformer oil level indicator assembly complete with iron frame, glass, rubber packing sheet, nuts, bolts and washers etc as per existing, Complete all as specifed and directed by Engineer-in-Charge.
Tranporting, lifting and positioning repaired transformer from workshop to the desired place.
Capacity of Transformer 63 KVA to 250 KVA
Capacity of Transformer 300 KVA to 750 KVA
M & L for PCC work providing, type B-2 (1:2:4) with 20 mm graded aggregate in foundation for panel and finishing the surface even and smooth without using extra cement including breaking of old PCC, Complete all as specifed and directed by Engineer-in-Charge.
M & L for rough excavation not excading 1.5m deep and getting out hard/dense soil for 66 KV/11KV switch yard/Sub Station, Complete all as specifed and directed by Engineer-in-Charge.
M & L for screening metal, chipping etc on the site of the work, when specially order including removing screened material clear screen and stacking in separate heaps for measuring( Material from both sides of screen measured) complete all as specied and directed.
M&L for loose filling with stone aggregate of gauge 80mm to 150mm deposited, spread and levelled in layers n.exc 30 cm thick, Complete all as specifed and directed by Engineer-in-Charge.
All as per serial item No 26 here in before but with stone aggregate of gauge 40mm to 80mm deposited , spreas and levelled in layer n.exc 15 cm rthick, Complete all as specifed and directed by Engineer-in-Charge.
Supply & fixing in replacement of fabricated Duct covers made out of MS Sheet with carring handle complete of size 60cmx45cmx10mm thick, Complete all as specifed and directed by Engineer-in-Charge.
M&L for opening the cover of RMU 11 KV servicing of fixed and moving contacts, repair and replacement of fixed copper terminal/contacts (Male/Female), insulation tubes including other connected items for function of RMU, lamp indicators, meters triping coil etc. Cleaning the fixed and moving contact inside the RMUs properly, checking of spring changing mechanism, servicing and greasing all movable mechanism, replacement of defective fuse, wiring, spares and resembling and testing and service capability check from remote operation upto satisfaction, Complete all as specifed and directed by Engineer-in-Charge and the manufacture instruction. Note:- (i) The quoted rate of the contractor includes for fixing the serviceable parts in position and replacement of minor unserviceable parts with new parts. (ii) Servicing may be done by autharize person.
M&L for opening the cover of VCBs/Bus coupler 11 KV ,630 Amp and servicing of fixed and moving contacts, repair and replacement of fixed copper terminal/contact (Male/Female), insulation tubes including other connected items to functional of pannel board, lamp indicators, meters triping coil etc.Cleaning the fixed and moving contact inside the VCB properly, checking of spring changing mechanism, servicing and greasing all movable mechanism, replacement of defective fuse, wiring, spares and resembling and testing and service capability check from remote operation upto satisfaction, Complete all as specifed and directed by Engineer-in-Charge and the manufacture instruction. Note:- (i) The quoted rate of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts . The new replaced parts shall be measured and paid separately under appropriate item of Sch 'A' (ii) For Sl No 32 to 49 : The make of spare parts, vaccum interrupter, switches, LED indicators should be of existing make of VCB's installed at Main Recieving Station. (iii) Servicing may be done by autharize person.
Supply only spring charging motor & gear assembly 110V AC/DC, Complete all as specifed and directed by Engineer-in-Charge.
Supply only push button bracket assembly, Complete all as specifed and directed by Engineer-in-Charge.
Supply only gear assembly with motor shaft ,11 KV breaker, Complete all as specifed and directed by Engineer-in-Charge.
Supply only closing coil assembly 24 Volt, Complete all as specifed and directed by Engineer-in-Charge.
Supply only tripping coil assembly, 24 volt, Complete all as specifed and directed by Engineer-in-Charge.
Supply only closing coil assembly, 110 Volt, Complete all as specifed and directed by Engineer-in-Charge.
Supply only tripping coil assembly, 110 volt, Complete all as specifed and directed by Engineer-in-Charge.
Supply only TNC Switch, Complete all as specifed and directed by Engineer-in-Charge.
Supply only lower connector, Complete all as specifed and directed by Engineer-in-Charge.
Supply only isolating contacts, Complete all as specifed and directed by Engineer-in-Charge.
Supply only auxiliary switch (7 NO + 7NC) model 33 PO24, Complete all as specifed and directed by Engineer-in-Charge.
Supply only vacuum interputer for HT11 KV VCBs, 630 Amps, type- B-21-M4 (M-500), breaking capacity 13.1 KA, Complete all as specifed and directed by Engineer-in-Charge.
Supply only Indicating lamps LED,24V,2 Watt with holder, any type ( Red/ Green/ White/ Amber /blue), Complete all as specifed and directed by Engineer-in-Charge.
Supply only phase indicating lamps 110V AC with holder (Red/ Yellow / Blue), Complete all as specifed and directed by Engineer-in-Charge.
Supply only push button actuator 1 No element, 22.5mm dia (TCH), Complete all as specifed and directed by Engineer-in-Charge.
Supply only thermostat range 30-90 deg Celsius, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing Heater 230 volts AC 60 watt for 11 KV HT VCB complete all as specifed and as directed. Make :Heatco/Vileco Electrical, Complete all as specifed and directed by Engineer-in-Charge.
Supply only High insulating varnish of superior quality ISI Marked , Complete all as specifed and directed by Engineer-in-Charge.
M&L for servicing/testing /callibration of HT 11 KV relays ensuring of breaker tripping through relay by simulation CDG CDD completed for one VCB panel such as Mster trip relay,auxilary relay etc complete all as specified and as per WBSEB setting parameters, Complete all as specifed and directed by Engineer-in-Charge. Note:- (i) Callibration may be done by autharize person.
M & L for repair of HT 11 KV vaccum circuit breaker complete set including replacement of complete internal AC/DC circuit wiring with existing size of wire, internal and external painting as per exsting colour, reinsulation of HT busbar and calibration of relays and tripping mechanism and installation of VCB with existing system after coupling with VCB panel by suitable size copper busbar and testing, Complete all as specifed and directed by Engineer-in-Charge.
M & L for paint of HT VCB 11 KV Panel consisting of 14 Nos VCB at common busbar with two coats of hammer tone paint after preparation of existing surface without damaging any part of VCB, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing high speed master trip relay (3 element) of operating limits 50 to 120% if rated coil voltage, operational time 10-15ms normal rated voltage, coil rating 24V/30V/110V/220V DC or AC, burden @ 30VDC/24VDC:7VA, 110 VDC : 10 Va, 220 VDC:7 VA, mechanical flag (red to alarm and white for normal) in window HR type operational indicator 3No+1NC contacts, as per IS 3232-1981 including setting of relay and testing, Complete all as specifed and directed by Engineer-in-Charge.
M&L for Earthing complete with Copper earth plate electrode 600x600x3.15 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below the ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level, connected to Copper earth strip 20x3 mm by means of bolts, nuts, check nuts and washers of brass/copper all as shown in electrical plate No 3 of SSR part-I 2009 connected to lightening conductor all as specified and testing on completion including. Necessary excavation, earthwork, PCC works and CI earth pit cover with watering pipe 20mm dia GI pipe medium grade, funnel with wire mesh and lugs and GI pipe 40 mm dia of light grade, for protection of earth strip , Complete all as specifed and directed by Engineer-in-Charge. Note:- Excavation/PCC/Earth work/Charcoal/ Salt shall be deemed to be include in this unit rate.
M&L for Earthing complete with GI earth plate electrode 600x600x6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below the ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level, connected to GI earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of brass/copper all as shown in electrical plate No 3 of SSR part-I 2009 connected to lightening conductor all as specified and testing on completion including. Necessary excavation, earthwork, PCC works and CI earth pit cover with watering pipe 20mm dia GI pipe medium grade, funnel with wire mesh and lugs and GI pipe 40 mm dia of light grade, for protection of earth strip, Complete all as specifed and directed by Engineer-in-Charge. Note: Excavation/PCC/Earth work/Charcoal/ Salt shall be deemed to be include in this unit rate.
M&L inreplacement for GI pipe 40 mm bore steel tubing light grade ISI marked for protection of cable including necessary joints, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing aluminium strip of size 25x3.15 mm for earth continuity conductor fixed on PCC block, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing of Copper strip of size 20x3.15 mm for earth continuity conductor fixed on PCC block, Complete all as specifed and directed by Engineer-in-Charge.
Dismantling of existing unsv loose/disturbed Aluminum strip/GI Strip/Termination rod of any sizes on roof/down conductor fixed on wooden guities /directly on roof including screws etc., Complete all as specifed and directed by Engineer-in-Charge.
Supply & fixing in repairs of 32 x 6 mm galvanised iron strip,earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or burried in ground or fixed to poles or roof with saddel and screw current, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing of porcelain insulator of size 65x31 mm and height 30mm with three nos hole including GI bolts and nuts of required size and two nos washer on incl PCC block, fixing strip, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing of air termination single pointed aluminium rod 12mm dia and 300 mm dia, Complete all as specifed and directed by Engineer-in-Charge.
M&L for taking out old unserviceable cable of any size from trenches , GI pipe protection, with and including separating serviceable bricks & set aside and removing un-serviceable bricks from site, Complete all as specifed and directed by Engineer-in-Charge. Note : (i) The Excavation and earth work shall be mesured and paid separately under relevant items.
Supplying, laying, jointing, testing and commissioning HT XLPE insulated, screened , PVC bended galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor screening with extruded semi conditioning layers insulation screening with copper tape cover laid upto with PVC (ST-2) extruded, inner sheathing galvanized steel strip armoured PVC (ST-2) outer sheathed cable confirming to IS-7098 (Pt-II) 11 KV grade suitable for earthed system cross sectional area 120 sqmm 3 core H.T.U.G cable laid in trenches/through GI pipe/fixed along with pole complete all as specified & as directed including taking out of old unserviceable cable, Complete all as specifed and directed by Engineer-in-Charge.
Supplying, laying, jointing, testing and commissioning HT XLPE insulated, screened , PVC bended galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor screening with extruded semi conditioning layers insulation screening with copper tape cover laid upto with PVC (ST-2) extruded, inner sheathing galvanized steel strip armoured PVC (ST-2) outer sheathed cable confirming to IS-7098 (Pt-II) 11 KV grade suitable for earthed system cross sectional area 95 sqmm 3 core H.T.U.G cable laid in trenches/through GI pipe/fixed along with pole complete all as specified & as directed including taking out of old unserviceable cable, Complete all as specifed and directed by Engineer-in-Charge.
Relaying only cable of sizes 70-185sq mm 3 core retreived from item No- 63 , after rectifing defects, Complete all as specifed and directed by Engineer-in-Charge. NOTE: (i) Earth work & Excavation, GI pipe brick protection etc shall be measured and paid separately under relevant items.
Excavation in trenches in soft/loose soil not exc. 1.5 metre wide and not exc. 1.5 metre in depth and getting out for taking up / laying under ground electric cable/errection of pole, Complete all as specifed and directed by Engineer-in-Charge.
Returning, filling in, including spreading levelling watering and well rammming in layers not exceeding 25 cms in depth, Complete all as specifed and directed by Engineer-in-Charge.
Removing surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point, Complete all as specifed and directed by Engineer-in-Charge.
Laying only serviceable bricks obtained from item No 63.00 here in before, Complete all as specifed and directed by Engineer-in-Charge.
Supply and lay dry river sand filling for under ground cable protection with a layer of 8cm deep before laying and 15cm covering above the top edge of cable after laying, Complete all as specifed and directed by Engineer-in-Charge.
Supplying and Laying Reinforced Precast Concrete Cable Cover, class HVP, type – 1, flat size 300 mm x 180 mm x 40 mm, Complete all as specifed and directed by Engineer-in-Charge.
M&L 100 mm bore steel tubing light grade ISI marked for protection of cable including necessary joints, Complete all as specifed and directed by Engineer-in-Charge.
M & L for horizontal boring across the existing road without disturbing the road surface for inserting 100 mm bore GI pipe, Complete all as specifed and directed by Engineer-in-Charge. Note :- GI pipe will be measured and paid respective item..
Supply and installtion (above ground) including testing HT joint box 2 way outdoor type of size 1500 x 1000 x 900 mm (overall) made out of 3.15 mm thick CRCA sheet with support of angle iron frame of size 40 x 40 x 6 mm with KIOSK BOX and comprising of 03 Nos HT porcelain bushing and copper round bus bar 12 mm dia rigidly mounted on bakelite sheet 12 mm thick to support insulators of suitable size and shape including providing necessary electric connection and applied two coats of synthetic enamel paint over a coat of red oxide primer to steel surfaces (internally & externally) including PCC foundation base of size 1700 mm x 400 mm x 1400 mm height (700 mm above GL & 500 mm below GL) with PCC 1:3:6 type C1 usisng 20 mm graded aggregate complete including necessary excavation and earth work for foundation and necessary electric connection complete and including dismantling of unserviceable joint box, Complete all as specifed and directed by Engineer-in-Charge.
Supply and installtion (above ground) including testing HT joint box 3 way outdoor type of size 1700 x 1200 x 1000 mm (overall) made out of 3.15 mm thick CRCA sheet with support of angle iron frame of size 40 x 40 x 6 mm with KIOSK BOX and comprising of 06 Nos HT porcelain bushing and copper round bus bar 12 mm dia rigidly mounted on bakelite sheet 12 mm thick to support insulators of suitable size and shape including providing necessary electric connection and applied two coats of synthetic enamel paint over a coat of red oxide primer to steel surfaces (internally & externally) including PCC foundation base of size 1900 mm x 400 mm x 1400 mm height (700 mm above GL & 500 mm below GL) with PCC 1:3:6 type C1 usisng 20 mm graded aggregate complete including necessary excavation and earth work for foundation and necessary electric connection complete and including dismantling of unserviceable joint box, Complete all as specifed and directed by Engineer-in-Charge.
M & L for repairs to 66 KV SF-6 Breaker Switch auto charging electical system by replacing damaged spares,suitable for Outdoor SF6 Circuit Braker type 70-SFM-32B, 72.5 KV rated Amps 1250 A, Complete all as specifed and directed by Engineer-in-Charge. NOTE : -Replacement of unserviceable spares/accessories shall be measured & paid separately under relevant items.
Supply and fixing Closing coil 110 volts DC, 52C for 66 KV SF-6 circuit breaker for remote/manual operation, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing trip coil 110 volts DC, 52 T1 T2 for 66 KV SF-6 circuit breaker for remote/manual operation, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing Heater 230 volts AC 100 watt for 66 KV SF-6 circuit breaker for remote/manual operation, Complete all as specifed and directed by Engineer-in-Charge.
M& L for filling of Gas in SF-6 Circuit breaker 66 KV/RMU upto required level, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing Analogue Amp-meter CT operated of size 144 mm x 144mm, suitable for HV panel board 11000 V ranging 0 to 60/30 Amp, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing Analogue Amp-meter CT operated of size 144 mm x 144mm, suitable for HV panel board 11000 V ranging 0 to 100/50 Amp, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing Analogue Amp-meter CT operated of size 144 mm x 144mm, suitable for HV panel board 11000 V ranging 0 to 150/75 Amp, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing Analogue Volt meter of size 144 mm x 144 mm, suitable for HV panel board 11000 V, ranging 0 to 15 KV (excluding PT), Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing replacement of dry type epoxy resin cost totaly enclosed Single Phase PT (Potential Transformer) 11000 /110 V range, 50 Hz, voltage factor 1.2/1.9, Burden-100 VA insulation level 12/28/75 KVas per IS-3156/1992, Complete all as specifed and directed by Engineer-in-Charge.
Supply and replacement of Fuse Links of PT (Potential Transfoemer) 11000/110 V range with HRC fuse, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing Epoxy resin cost totaly enclosed dual core type Current transfomer (CT) for potection of system having ratio of 150/75 : 5 A ,Burden-10 VA, Class-I insulation level 12/28/75 KVas per ISS-2705 and IEC-60044, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing Epoxy resin cost totaly enclosed dual core type Current transfomer (CT) for potection of system having ratio of 100/50 : 5 A , Burden-15VA, class-I, insulation level 12/28/75 KV as per ISS-2705 and IEC-60044, Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing Epoxy resin cost totaly enclosed dual core type Current transfomer (CT) for potection of system having ratio of 60/30 : 5 A ,Burden-10VA, Class-I insulation level 12/28/75 KVas per ISS-2705 and IEC-60044, Complete all as specifed and directed by Engineer-in-Charge.
Material & labour of Indoor Red Polyethylene Heat Shrinkable Bus Bar Tubes/slives of thikness 3 mm suitable for 11000 Volts, Complete all as specifed and directed by Engineer-in-Charge.
Material & labour of Indoor cable termination protection Boot make right angle connection for RMU of size 95 to 185 sqmm, heavy duty insulating barrier device ,provide phase to phase insulation to the power cable terminals suitable for 11000 volts grade XLPE cable, Complete all as specifed and directed by Engineer-in-Charge.
Material & labour for straight through joints, outdoor, heat shrinkable type (Earthed) suitable for 3 core 70/95 Sqmm 11000 Volts grade XLPE cable with jointing materials and accessories complete including testing after jointing, Complete all as specifed and directed by Engineer-in-Charge.
Material & labour for straight through joints, outdoor, heat shrinkable type (Earthed) suitable for 3 core 120 Sqmm to 185 sq mm 11000 Volts grade XLPE cable with jointing materials and accessories complete including testing after jointing, Complete all as specifed and directed by Engineer-in-Charge.
Material & labour outdoor cable end termination joint cold shrinkable type suitable for 3 core 70/95 Sqmm 11000 Volts grade XLPE cable complete including testing after jointing, Complete all as specifed and directed by Engineer-in-Charge.
Material & labour Indoor cable end termination joint cold shrinkable type suitable for 3 core 70/95 Sqmm 11000 Volts grade XLPE cable complete including testing after jointing, Complete all as specifed and directed by Engineer-in-Charge.
Material & labour outdoor cable end termination joint cold shrinkable type suitable for 3 core 120/185 Sqmm 11000 Volts grade XLPE cable complete including testing after jointing, Complete all as specifed and directed by Engineer-in-Charge.
Material & labour of Indoor cable end termination joint cold shrinkable type suitable for 3 core 120/185 Sqmm 11000 Volts grade XLPE cable complete including testing after jointing, Complete all as specifed and directed by Engineer-in-Charge.
M&L for Servicing to outdoor type Potential Transformer suitable 72.5 KV oil immersed including replacing of old transformer insulation oil and all gaskets,Painting the metallic part and providing greasing/lubrication to other jointing/rusting components, reconditioning electric connections, Complete all as specifed and directed by Engineer-in-Charge.
M&L for Servicing to outdoor type Current Transformer suitable 72.5 KV oil immersed including replacing of old transformer insulation oil and all gaskets,Painting the metallic part and providing greasing/lubrication to other jointing/rusting components, reconditioning electric connections, Complete all as specifed and directed by Engineer-in-Charge.
Supply and replacing of metallic clamps/connections inclusive of fixing accessories for 66 KV expansion joint connection between tubular bus to equipment insulators flexible conductor to equipment/insulators tabular bus to other tubular bus for vertical connection/horizontal extension or connection all as required, Complete all as specifed and directed by Engineer-in-Charge.
Supply, fixing and testing post top insulator in 3 series including necessary connection with 66 KV distribution system complete all as specified and as directed. Note : Each insulator of the 3 series shall be of 66 KV rating, Complete all as specifed and directed by Engineer-in-Charge.
M & L for switch air break gang operated tripplle pole out door type with V type insulator drop out switch fuze unit on HT 11 KV 50 cycle AC suitable for current rating upto 200 amps mechanically operated mounted on insulators and frame with operating mechanism worked from ground level with and including locking arrangement and dismantling of old unserviceable one, Complete all as specifed and directed by Engineer-in-Charge.
M & L for HT lightening arrester expulsion type complete with all fittings discharging capacity 65 KA 11000 volts grade including taking down of old unservicable one., Complete all as specifed and directed by Engineer-in-Charge.
Supply and fixing HT rubber matting up to 66 KV of superior quality as per IS-15652/2006 of size 2Mx1Mx3 mm thick, Complete all as specifed and directed by Engineer-in-Charge.
M&L for preparation of the old decorated existing external steel surface of feeder HT JBs of any size and description in any position including removal of disintegrated & deteriorated paint either by hand scrapping or by blow lamps, applying necessary filler coat and stopponf required and applying two coats of Asian aspa paint (Mahindra Grade) by using spray painting machine on old prepared surface including marking of Feeder No and feeding area with applying synthetic enamel paint (1st grade), Complete all as specifed and directed by Engineer-in-Charge.
Material and labour for applying two coats of aluminium paint to GI structure of dirrerent size channel/angle/flat strip/pipe/Busbar etc at 66 KV distribution structure after preparation of existing surface, Complete all as specifed and directed by Engineer-in-Charge.
Material and labour for applying two coats of aluminium paint to steel tubular HT pole 9.0 mtr long including cross arms after preparation of existing surface, Complete all as specifed and directed by Engineer-in-Charge.
Material and labour for applying two coats of aluminium paint to steel tubular HT pole 11 mtr long including cross arms after preparation of existing surface, Complete all as specifed and directed by Engineer-in-Charge.
Material and labour for applying two coats of aluminium paint to steel tubular HT pole 16 mtr long including cross arms after preparation of existing surface, Complete all as specifed and directed by Engineer-in-Charge.
S & F wall mounted flex sign board size not less than 2 x1 x.15 mtr made out of high quality GI sheet thickness not less lthan 2 mm and suitable size of Aluminium bedding with flex for marking of schematic diagram of external electric supply scheme/Name of sub station with suitable fixing arrangement as directed by Engr-in-Charge and incl 4 x 18W batten type LED fitting and wiring inside the board with suitable size of cables and the board fixed on wall with suitable size of cables and the board fixed onwall with suitable size of GI nut bolts complete including taking down of old unservicable one, Complete all as specifed and directed by Engineer-in-Charge.
M&L for LED decorative gate light made up of high grade unbreakable polycarbonate material suitable for retrofit 10 W LED bulb with 22 B base including dismantling of old unserviceable light, Complete all as specifed and directed by Engineer-in-Charge.
M&L for PVC insulated unarmoured aluminium conductor cable 6 sq mm 2 core including dismantling of old unserviceable cable, Complete all as specifed and directed by Engineer-in-Charge.
M&L GI pipe light grade 40 mm dia for med grade installation of light as per reqd size inscuding bends or other fitting reqd at site , welding works ,etc including dismantling of old unserviceable pipe, Complete all as specifed and directed by Engineer-in-Charge.
M&L for PVC conduit pipe heavy duty 25 mm dia incl exdcavation work for laying cable in conduit, Complete all as specifed and directed by Engineer-in-Charge.
S&F Sheet metal enclosure for 4 way Distribution Boards (DB’s), double door, single pole and neutral with 200 amps rated bus bar, IP-20 protection suitable for fixing MCB"S/lsolators including taking down old existing, Complete all as specifed and directed by Engineer-in-Charge.
S&F of MCB, Single pole & Nuteral,32 amps, 240 volts, ‘C’ curve, 10 KA, Complete all as specifed and directed by Engineer-in-Charge.
M&L for PCC 1;3;6 of 20 mm graded type C1 aggregate, Complete all as specifed and directed by Engineer-in-Charge.
M&L for precast cable route indicator of size 100x30x10 Cms by using 20 mm graded aggregate type B1 1;2;4 for cable indicator and engraving as "HT CABLE" slightly round from one side incl Red painting with two coat of synthetci enamel paint of a coat of primer, Complete all as specifed and directed by Engineer-in-Charge.
Material and labour for earthing result testing for any type of earthing such as GI plate/copper plate/chemical/bore earthing connected with and for HT panel , LT panel,Equipments, Lightening arrestor, DG sets,Transformer etc in any position and any place under GE (N) Binnaguri Mil station using Digital Earth meter in 3M method and E-N voltage at main DBs and register the result as per performa provided in earth test register duly signed by JE and Engr in charge, Complete all as specifed and directed by Engineer-in-Charge.
M&L for mild Barrel slide door Bolt, Plate type stove enamalled black, with bright bolt not less than 12 mm dia 375 mm long with and including a minimum of 6 Bolts and nuts ,Four on bolt and two on staple plate including dismantling of old unserviceable sliding door bolt, Complete all as specifed and directed by Engineer-in-Charge.
M & L for detecting carefully the fault of RMU/VCB/Four & Two Pole Structure & HT UG Cable of size 95 Sqmm to 185 Sqmm 3 Core either HT cable fault locater machine or any other method and taking out the/remove the faulty portion of cable from under ground/over all length respectively including maggering/connecting/testing on Complete all as specifed and directed by Engineer-in-Charge. Note: (i) Exc and earth work shall be deemed to be included in the unit rate of this item of work. (ii) Straight through joint of HT Cable shall be measured and paid separately under respective item of this work. (iii) Actual detected fault shall be paid under this item, dummy location trial shall included in the unit rate of this item. (iv) Contractor shall provide Electrician and helper along with tools. (v) Major Spares/Parts for reapir will be measured and paid saperatly as supply only under relevent item of this schedule.
Cutting unaxious green growth and wild grass by manual labour or by machine at Electrical Installation Permises around pole, around panel board along boundaries fencing, removing runnish material from work site and depositing where directed not exc. 100 meter from the starting point, Complete all as specifed and directed by Engineer-in-Charge. Note 01 : The item shall be operated maximum 2 (Two) times in the entire period of the Contract period and measurement will be taken every time independently for payment. Note 02:- The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender, from total amount of Schedule 'A'/BOQ.
M/s Om Prakash Agarwala
PURBANCHAL BUILDERS
S.N. GHOSH AND CO.
CHAKRABORTY AND SONS
KD SAHA and CO.INDIA
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .