| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.2 LAccepted-AOC | L1 | Accepted-AOC Accepted. | |
| 2 | L2₹4.5 L+₹24,608 (5.80%)Rejected-Finance 14 BEPIN BEHARI GANGUALY STREET KOLKATA 700 012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | L2 | Rejected-Finance HIGHER BID VALUE. | |
| 3 | L3₹6.0 L+₹1.8 L (41.3%)Rejected-Finance GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | L3 | Rejected-Finance HIGHER BID VALUE. | |
| 4 | Rejected-Technical 12 1 FERRIGHAT ROAD P O BHATPARA DIST NORTH 24 PGS WEST BENGAL PIN 743123 | BHATPARA | NORTH 24 PARGANAS | WEST BENGAL | 743123 | - | Rejected-Technical Not Submitted all papers. |
Tender Value
Refer Docs
EMD Value
₹9,564
Closing Date
24 Jun 2022, 2:00 pmClosed
Executive Engineer, PWD.
Office of the Executive Engineer, PWD, Jalpaiguri Electrical Division, Purta Bhavan, Hakimpara, Post and District - Jalpaiguri, PIN - 753101.
Urgent Internal Electrical Installation Work for setting up of Hybrid CCU at District Hospital, Jalpaiguri - SITC of Fire Detection System.
2022_WBPWD_383821_1
WBPWD/EE/JED/NIQ 02e/Q of 2022-23.
Open Tender
ELECTRICAL WORKS ORG
Item Rate
15 days
Hybrid CCU at District Hospital
Please refer Tender documents.
2 documents required · 2 mandatory
₹9,564
31 Aug 2022
9 Jun 2022
27 Jun 2022
9 Jun 2022
24 Jun 2022
9 Jun 2022
Amount
Supply, Installation,Testing & Commisioning of Main Fire Alarm Control Panel: Microprocessor based Intelligent Addressable Fire Alarm Panel. Minimum 2 loop panel with loop card having capacity of minimum 125 detectors. Addressability of the Intelligent Panel shall be soft addressed so as to consume minimum time of addressing the system with Detectors and Devices . The Intelligent panel shall be able to give pin point location of all fire/fault conditions. All the multicriteria Detectors as applicable for various areas based on application and design considerations shall be fitted on Loop along with Loop powered Alarm Devices; MCPs and Input /output Modules . The panel shall have in built rectifier, Loop cards,provision for external, LCD unit to indicate Fire/Fault Signal with address. 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. The panel should be capable of taking minimum 1000 addressable detector and devices. (Approval standards:EN54 / Vds Certification) ( Approved Make: Honeywell-Esser/ Siemens make Cerberus Pro modular system model/Secutron/ Bosch ).
Supply, Installation,Testing & Commisioning of Analog Addressable Intelligent multisensor detector complete with all accessories like base plate etc.( VDS approved ) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard. ( Approved Make: Honeywell-Esser/ Siemens make Cerberus Pro modular system model/Secutron/ Bosch ).
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point complete with all accessories like base plate etc.( VDS approved ) addressable type with in built fault isolator as per NFPA style 7 wiring complete as required.( Approved Make: Honeywell-Esser/ Siemens make Cerberus Pro modular system model/Secutron/ Bosch ).
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter complete with all accessories like base plate etc.( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS approved) approved. (Approved Make: Honeywell-Esser/ Siemens make Cerberus Pro modular system model/Secutron/ Bosch ).
Supply, Installation, Testing & Commissioning of Addressable transponder/ Monitor Modules complete with all accessories like base plate etc. ( VDS approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. (Approved Make: Honeywell-Esser/ Siemens make Cerberus Pro modular system model/Secutron/ Bosch )
Supply, Installation, Testing & Commissioning of Addressable Relay (24V DC/AC, 220V DC/AC)Modules complete with all accessories like base plate etc.(VDS approved) for switching / integration of Lift / AHU etc complete as required. (Approved Make: Honeywell-Esser/ Siemens make Cerberus Pro modular system model/Secutron/ Bosch )
SITC of Power adapter suitable for 24V DC/AC, 220V DC/AC as per requirement. Make: Approved by EIC
Supplying, installation, testing and commissioning of LED type Response Indicator having 2 Nos. red coloured LED lamps including connections etc. (Approved Make: Agni/Ravel/System Sensor )
Supply, Installation, Testing & Commissioning of 120 Watt Power Amplifier with 2 zone and S/F gooseneck Microphone (Make:Honeywell /Bose/Bosch/Ahuja)
Supply, Installation, Testing & Commissioning of 6 Watt Celing Mounted Speaker along with necessary Accessories (Make: Honeywell /Bose/Bosch/Ahuja)
Supply and laying of Speaker cable (0.5 sqmm Cu) in PVC rigid conduit [Precision/ similar Make] on wall or ceiling, incl. S/F PVC rigid conduit, necy. fittings etc. and mending good damages to building works (Make:- KRAMMER/ FINOLEX/ EXTRON/ similar) as per direction of EIC.
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded Copper Cable (For Loop) (Make. KEI/Havells/RR Kabel /Polycab) in prelaid PVC rigid conduit on the surface of the wall as per direction of EIC.
Supplying and fixing of 19 mm dia & 3 mm thick PVC rigid conduit with discrete Red tape covering (Precision/ similar type) complete with fittings as necy. under ceiling/beam, bound with 22 SWG GI binding wire incl. supplying and drawing 1x18 SWG GI Wire as fish wire inside the pipes as per GS.
Supply, Installation, Testing & Commissioning of 40 mm width Danger Radium Self glowing self adhesive tape BOPP. Red/Green Zebra colouring. (1Coil=10 mtr) (Make: Supreme/ Creation/Polite or equivalent) as per EIC.
Supply, Installation, Testing & Commissioning of 1KVA offline ups, pure sine wavw output on UPS (inverter)mode with 15 mins battery backup at rated load (Make APC/Microtek/Numeric)
S& Delivery of Infrared type Thermal Scanner (Make:Fluke 59 Max Digital Infrared Thermometer -30°C to 350°C)
S& D of Thermal Imaging Camera having LCD display ,rotating screen for easy navigation cover.( Make: Fluke TIS-20)
SITC of Emergency hand Light with High quality rechargeable lithium battery,Power Requirements: 240V, 50Hz,Built in battery,White light watt: 6-8 watt (Make: Philips,Wipro or equivalent)
TESTS:1. The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.The system should not be PASSWORD protected.
Terms and Condition:
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules
The Defect Liablity Period of this work is 3 years from the date of Installation, Testing & Commissioning. Agency has to maintain the installation for 3 years with their own staff. OEM has to provide equipment support for 3 years.
ASSOCIATED ELECTRICAL CONST CO. 1963 PVT.LTD
GLYPTIC
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .